Electromagnetic Flowmeter
Field Hand Held Communicator
USER’S GUIDE
2006.11.231
2
CATALOGUE1. Brief Introduction
2. Field Connection
3. Definition of Key
4. Power on and off
5. Watch Primary Variables
6. Parameters Setting
6.1 PV Unit
6.2 Flow Range Setting
6.3 FLOW RSPNS Setting
6.4 FLOW CUT OFF Setting
6.5 FREQUEN MAX Setting
6.6 ALARM OVER L Setting
6.7 ALARM VALUE Setting
7. Attention
3
1. Brief IntroductionThe Field Hand Held Communicator of electromagnetic flowmeter is
employed to set parameters and watch primary variables. The user’s guide introduces you how to use the Field Hand Held Communicator to set and display Electromagnetic Flowmeter’s parameters.
2. Field ConnectionThe Field Hand Held Communicator should be connected with
Electromagnetic Flowmeter shown as the Fig2.1:
Fig2.1 Field ConnectionNotes:
1).The two signal line of the Field Hand Held Communicator should be connected in parallel with Electromagnetic Flowmeter’s IGND and Iout without polarity.
2).The load resistance of current circuit should be more than 200Ωand less than 500Ω.
3).The Field Hand Held Communicator couldn’t be connected in series with the current.
4
3. Definition of Key
4. Power On and Off On the power-off state, The Field Hand Held Communicator can be
turned on by pressing key five seconds later or more, and display
“MAG Field Hand Held Unit” and menu on the LCD shown as Fig 4.1: AM
Fige 4.1 Key-words Input MenuFirst, you should input the key word as “19818” by pressing figure
key or cursor key , and then pressing key to enter next
menu shown as Fig 4.3. Though this menu we could select primary variables displaying or parameter setting to operate.
51 Pro variables2 Detailed setup
Enter
MAG FieldHand Held Unit
00000OK
Fig4.3 Main Menu If you don’t input key-words or input wrong key-words, it could only
display primary variables and parameters of electromagnetic flowmeter. you couldn’t modify and set parameters of electromagnetic fowmeter.
When Field Hand Held Communicator is on, pressing the key
on more than five seconds, The Field Hand Held Communicator will be turned off automatically.
If there isn’t any key operation in three minute, The Field Hand Held Communicator will also be turned off automatically.
5. Watch the Primary Variables
Pressing figure key or pressing key to move light stick
to “1. Flowmeter Measure”, and then pressing key , you could
enter next menu and watch primary variables shown as Fig5.1:
Fig 5.1 Watch Primary Variables The primary variables of electromagnetic flowmeter is displayed in
this screen.The item PV means flow rate value, item AO means output current value, and item PV% means percentage of current
output. Pressing key you could be back to upper menu.
6. Parameters setting
Pressing figurer key or pressing key 、 to move the
light stick to “2. setting meter parameter” ,and then pressing key
and you could enter parameter setting menu shown as Fig6.1:
6
COMMUNICATE
1PV *** **2PV% **** %3AO **** mA
1 PV Unit 2 FLOW RANGE 3 FLOW RSPNS
Enter
Fig 6.1 Parameter Setting Menu In this menu, you could set parameters of the Electromagnetic
Flowmeter, and pressing key back to upper menu shown as Fig
4.2.
6.1 PV Unit
Fig 6.2 PV Unit Setting Menu
Pressing key 、 to move the light stick to “PV
Unit”(shown in Fig . 6.1) and press key to enter flow unit setting
menu ,select flow rate unit and press key to begin setting
parameter .
Figure 6.3 Confirm PV Unit Setting menus If the parameter is set successfully, the Field Hand Held
Communicator could return to the upper menu; and if the parameter is set unsuccessfully, and there will be “ERROR” on the menu.
7
1 PV Unitm3/h
m3/mExit Setup
Current value of instrument setting
Input unit
1 PV Unitm3/h
m3/mAbort OK
Current value of instrument setting
Input unit
The flow rate unit of electromagnetic flowmeter is as follwer:m3/h m3/m m3/s L/h L/m L/s (UKG USG) 6.2 Flow Range Setting
On the parameter setting menu (figure 6.1) , pressing figure key
or pressing key 、 to move the light stike to item “Flow
Range”, and pressing key to enter flow range setting menu
shown as Fig 6.4.
Fig 6.4Flow Range Setting Menu
In this menu, you could input parameter of flow range though
figure key and cursor key , and press key one time to set.
Screen will display hint “Enter” and “Cancel” to confirm whether this
operation is carried out. If press key one more time. Field Hand
Held Communicator begins to communicate parameter to
Electromagnetic Flowmeter. If you want to cancel, press key to
exit.If there isn’t any operation in five seconds, the input value is invalid ,
and Field Hand Held Communicator will return the upper menu.
Figure 6.5 Measurement Setting Menu If the parameter is set successfully, and Field Hand Held
Communicator would return to the upper level of menu; if the parameter is set unsuccessfully and there will be “ERROR” on the menu. After 5 seconds, you should enter "Flow Range" menu to check the parameter of electromagnetic flowmeter whether is set correctly.
8
2 FLOW RANGE 282.75m3/h
000.00
Exit Setup
Current value of instrument setting
Input value
2、Flow Range282.75m3/h
200.00
Abort OK
Current value of instrument setting
Input value
6.3 FLOW RSPNS SettingSetting steps and method of the FLOW RSPNS is the same as
PV Unit.6.4 FLOW CUT OFF Setting
Setting steps and method of the FLOW CUT OFF is the same as FLOW RANGE.6.5 FREQUEN MAX Setting
Setting steps and method is the same as the FLOW RANGE.6.6 ALARM OVER L Setting
Setting steps and method of the ALARM OVER L is the same as PV Unit.6.7 ALARM VALUE Setting
Setting steps and method is the same as the FLOW RANGE.
7.Attention
1). After the parameter of electromagnetic flowmeter is set, you must return to the setting item a moment ago, and check the parameter is set correctly. The parameter of electromagnetic flowmeter is needed several seconds to change. If you enter this operation item many times, and display incorrect parameter, then the setting parameter is invalid. The parameter needs to be set again, or inspects whether there are other reasons.
2).After power-up, if Field Hand Held Communicator appears the mistake information, you should check the device wiring with electromagnetic flowmeter and parameters of electromagnetic flowmeter whether are set correctly.
3).The communication parameter of electromagnetic flowmeter should be set as follow:the communication mode it is 2, the communication address is not 0, and the value of baud rate is 4800. If the communication mode, address and the baud rate setting are not
9
set correctly, the Field Hand Held Communicator will not be able to set the parameter and display primary variables.
4).If there is any operation in 3 minutes; the device will turn off automatically.
5).If the Field Hand Held Communicator couldn’t modify the parameter; you should confirm whether the password of the device is set correctly.
6).If you do not input any figure, and press key "→"to set the parameter, the value to be set to electromagnetic flowmeter is zero.
7).If the device is unable to turn on, you should open the device rear cap, and push”reset” button. Moreover, when the battery voltage of the device is lower than 5V, you should need to replace the new battery. Before operation of the first time, you should push “reset” button.