  • When the reset period is initiated, the time for which START has been active issaved. If the fault reoccurs, that is, the negative-sequence current rises above theset value during the reset period, the operate calculations are continued using thesaved values. If the reset period elapses without a fault being detected, the operatetimer is reset and the saved values of start time and integration are cleared.

    Inv. curve BThe inverse time equation for curve type B is:

    t sk

    I

    I

    I

    Ir

    S

    r

    [ ] =

    2

    2 2

    GUID-805DCB50-71D2-4721-830B-3343E1A5500B V1 EN (Equation 68)

    t[s] Operate time in seconds

    k Machine time Mult

    I2 Negative-sequence current

    IS Set Start value

    Ir Set Rated current

    1MRS757644 B Section 4Protection functions

    620 series 441Technical Manual