re_620_tech_757644_enb 447

1
When the reset period is initiated, the time for which START has been active is saved. If the fault reoccurs, that is, the negative-sequence current rises above the set value during the reset period, the operate calculations are continued using the saved values. If the reset period elapses without a fault being detected, the operate timer is reset and the saved values of start time and integration are cleared. Inv. curve B The inverse time equation for curve type B is: ts k I I I I r S r [] = - 2 2 2 GUID-805DCB50-71D2-4721-830B-3343E1A5500B V1 EN (Equation 68) t[s] Operate time in seconds k Machine time Mult I 2 Negative-sequence current I S Set Start value I r Set Rated current 1MRS757644 B Section 4 Protection functions 620 series 441 Technical Manual

Upload: abhijitwce

Post on 30-Sep-2015

217 views

Category:

Documents


3 download

DESCRIPTION

re_620_tech_757644_enb 447

TRANSCRIPT

  • When the reset period is initiated, the time for which START has been active issaved. If the fault reoccurs, that is, the negative-sequence current rises above theset value during the reset period, the operate calculations are continued using thesaved values. If the reset period elapses without a fault being detected, the operatetimer is reset and the saved values of start time and integration are cleared.

    Inv. curve BThe inverse time equation for curve type B is:

    t sk

    I

    I

    I

    Ir

    S

    r

    [ ] =

    2

    2 2

    GUID-805DCB50-71D2-4721-830B-3343E1A5500B V1 EN (Equation 68)

    t[s] Operate time in seconds

    k Machine time Mult

    I2 Negative-sequence current

    IS Set Start value

    Ir Set Rated current

    1MRS757644 B Section 4Protection functions

    620 series 441Technical Manual