id3000 2 to 8 loop intelligent fire alarm panel
Post on 05-Feb-2016
48 Views
Preview:
DESCRIPTION
TRANSCRIPT
ID3000 2 to 8 Loop Intelligent Fire Alarm Panel
Applications
• Medium To Large Single/Multiple Building Systems
• Retrofit And New Construction
• Standalone Systems
• Networked Systems
Hardware Overview
BasicEquipment Kit Cover(s)
Backbox(es)Extension Chassis
(if required)
Optional ExpansionModules (if required) Power Supply
Modular Design
Key Components
Backbox Power Supply Basic Equipment Kit Covers & Batteries & Extension Chassis
ProcessorPCB
Display PCB
Base Card
Main Chassis
Expansion CardsBasic Equipment Kit
Basic Equipment Kit
Extension Options• Up to 3 Standard Loop
Cards (LIB)
• Up to 3 Enhanced Loop Cards (E-LIB)
• One RS-232 Card
• One RS-485 Card• One ID-Net Card
BEK - Inputs & Outputs• Outputs
• A/B/C/D - Sounder or Relay programmable• Sounder - rated @ 1A/30V each
• Dry contact relay - rated @ 1A/30V
• Fault and Fire Relays VF rated @ 1A/30V each• Auxiliary 26-28Vdc outputs 1 and 2 both rated @ 1A• Battery charger max 8.6A (130Ah batteries) when used
remotely.
BEK - Inputs & Outputs• Inputs
• Mains - 230Vac ± 15% 50/60 Hz
• Two addressable loops - 500mA/Loop
• Tamper switch input (VF dry contact)
• Communications• RS232 Port 1
• PC Programming, internal printer option
• RS232 Port 2 (optional module)
• RS485 Port (optional module)
Double Extension Chassis with 255 Zone Display
Module Kit
Extension Chassis with PRN2000
Printer Module Kit
Extension Chassis with 64 Zone Display
Module Kit (with or without Printer)
Extension Cover Blanking Plate
Extension Chassis Options
Dual LoopModule Kit
Isolated RS232Module Kit
Isolated RS485Module Kit
Printer Module Kit
ID-Net Network Card
Enhanced Dual Loop Module Kit
Optional Expansion Modules
Communication Modules• RS232 Card Option
• Isolated port• Third party interface• External printer • UniNet (NION) connection• Pager interface• VDU for terminal emulation
• RS485 Card Option• Isolated• Master/Slave network• Repeaters• Mimics
Standard LIB Vs E-LIB• LIB
• Handles communication only
• System CPU scans loops• In case of main CPU
failure all detection is lost
• Max. 512 devices per panel (EN54)
• E-LIB• Powerful microprocessor• Degrade mode
• In case of main CPU failure the E-LIB will still activate sounder circuits 1-4 and the Fire Relay when an alarm is received from the loop
• Full 1584 device count on the panel (EN54)
Power Supply Unit Kit2.5 Amp
Universal PSU Kit4.5A or 7.0A
(External enclosure or deep boxes only)
PSU DTPBooster Kit
(4.5 or 7.0A PSU only)
Remote Battery/Charger Enclosure Kit
+
Power Supply Selection
2.5A PSU mounts on the side of
the BEK
DTP Booster
mounts on the side of
the BEK
4.5A PSU mounts into the deep (extended) back box
7A PSU mounts into
the external charger/ battery enclosure
Power Supply Options
Standard Back Box Kit
Extended Back Box Kit(available in ‘standard’ and ‘deep’)
Double Extended Backbox Kit(available in ‘standard’ and ‘deep’)
Backbox Extension Kit (available in ‘standard’ and ‘deep’)
Flush Mounting Bezels
Back box Options
17Ah 17 Ah
38Ah
12Ah
Standard Extended Double Extended External Box
78Ah38Ah
Standarddepth
Deep Boxes
Backbox Options
Extension Cover Blanking Plate
Double Extension Cover Kit
Extension Cover Kit(High Security option)
Main Cover Kit(High Security option)
Security Door Kits(available for main &
extension covers)
Cover/Door Kits
19” Rack Mounting Option• 19” Rack Mounting Assembly for Basic Equipment Kit
• 6U x 19” Rack Mounting Assembly for 7A PSU
• 6U x 19” Rack Mounting Assembly for 64 Zone LED Extension Chassis & Printer Kit
• 6U x 19” Rack Mounting Assembly for 256 Zone LED Extension Chassis Kit
• 6U x 19” Rack Mounting Assembly for Printer
• 3U x 19” Rack Blank Cover with Mains Termination Kit
• 6U x 19” Rack Blank Cover with Mains Termination Kit
• 3U x 19” Rack Mounting Assembly for Mimic Driver Kit
• 6U x 19” Rack Blank Cover
• 3U x 19” Rack Blank Cover
6 Line x 40 Character
Graphic LCD
Main Control
Switches
System Status
Indicators
Navigation Keypad
Numeric Data Entry
&
Enter/Cancel
Key switchAccess Level 2
Main User Interface
Main User Interface• Fully EN54 compliant• Simple tabbed menu navigation• Prioritised event display
(Automatically displays highest priority event)• User in control… has choice
of what is displayed• Simple lights and switches for
common controls• Top level info displayed
Graphic Display
• Large 240 x 64 pixel LCD 6 lines x40 characters
• Short-cuts for test & disablement
• Selection by direct addressing
• Displays:• Time and Date• Active Point Count for each event• Event type, index and actions • Panel, Zone and Device descriptors
System Information on Windows Style Tabbed Screens
Graphic Display
Panel and Zone Text up to 32 Characters via Keyboard
to Navigate and to Select
Virtual Keyboard
Example - 3 Zones in Alarm: 2 Devices Alarmed in Zone 2 1 Device Alarmed in Zone 1
1 other zone in Alarm - Press “Zones in Alarm” to view others
Use Navigation keys to scroll through zones and display other devices, date/time of event and device % value, etc.
Short-cut key selects either device or zone disablement.
Fire Alarm Display
3 Zones are in FAULT with 4 events in the system.
Use to scroll through zones and to display device, type, value, etc.
Fault Display
142 Devices Disabled in 3 input zones. 12 devices are disabled in Zone 2 (all input devices).
No outputs are disabled. Use to scroll through zone list and to see device details.
Disablement Display
Main Features
• Meets EN54 Parts 2 and 4• Degraded mode of operation
• Enhanced LIB (parallel CPUs)
• Menu driven point/data access• Multi-level operator password control• Multiple language options
Key Functions
• 9 sensitivity levels for Fire & Pre-alarm• Adjustable alarm & fault verification delay• Two-stage alarm operation• Alarm silence/re-sound• Sound general alarm (Evacuate)• Day and Night modes• Fire output(s) inhibit • Internal and external printer options
Key Functions
• Powerful Control-by-Event (CBE) • Auto-Learn or PC programming• Duplicate address detection• One-man Walk Test with counter• Output device test• Daily high test• 2 pulse rates for outputs• Time of day functions
System CapacityStand-Alone• Up to 8 loops• 198 (99+99) devices per loop• Up to 1584 devices • Up to 255 zones• Up to 7A PSU• Up to 31 repeaters or mimics
• Up to 512 LEDs per controller
• 600 event history log
System CapacityStand-Alone• Four sounder circuits (NACs)
• Rated @ 1A each• Two programmable as VF relays
rated @ 30Vdc/1A• Two 24Vdc auxiliary outputs
• Rated at 1A each• Two programmable inputs • Fault and Fire relays
• VF rated @ 30Vdc/1A• Two loops as standard• One isolated RS232 port (optional)• One isolated RS485 port (optional)
System CapacityInterlinked• Master/Slave interlink
• Up to 32 network nodes• Maximum 8 panels• Remainder repeaters and mimics• Up to 64 loops in total• Up to 12,672 devices in total• Up to 2040 zones in total• Up to 56A PSU in total• Max. RS485 bus length of 3000m
Configuration Tool• Windows Operating Systems
• Standard Windows features (cut, copy, paste, etc)
• On-line error checking
• Software protection
• EN54 Network functions
• Easy report printouts
• Multi-lingual operation
On-Site Configuration• Multi-level password/key-switch access
• Level 2: Code 1/Keyswitch - Panel controls & menus• Level 3: Code 2 - Level 2 + Configuration menus• Level 3A: Code 3 - Level 3 + Advanced Configuration
• Panel settings
• Auto-learn facility
• Loop/Device configuration
• Text Editor (Virtual keyboard)
• Control matrix editor (512 lines)
• Network configuration
top related