fsss
Post on 15-Nov-2014
13 Views
Preview:
TRANSCRIPT
Furnace Safeguard Supervisory System
K.C. Yadav, AVP,
Noida Technical Training Centre
2 of 27confidentia
l
Learning Agenda» Objective of FSSS» Inter facing of field equipments and
instrumentation » Operational features of FSSS » Role of FSSS in starting/shutdown» Role of FSSS in maintaining the
design prescribed values of the parameters
3 of 27confidentia
l
It must be recognized that no amount of written instruction can replace intelligent thinking and reasoning on the part of boiler operators, especially when coping with unforeseen operating conditions. It is operators’ responsibility to become thoroughly familiar, not only with immediate steam generating equipment but also with all pertinent control equipment. Satisfactory performance and safety depend to a great extent on proper functioning of controls and auxiliary equipment.
4 of 27confidentia
l
Purpose
The FSSS is designed to ensure the execution of safe, orderly operating sequence in the start up and shutdown of fuel firing equipment and to prevent errors of omission and commission in following such a safe operating procedure.
5 of 27confidentia
l
Purpose Furnace purge supervision. Secondary air damper modulation, on/off control
and supervision. Light oil on-off control and supervision. Heavy oil on-off control and supervision. Pulveriser and feeder on-off control and
supervision. Flame scanner intelligence and checking. Overall boiler flame failure protection. Boiler trip protection.
6 of 27confidentia
l
Purpose Prevent any fuel firing unless a satisfactory furnace
purge sequence has first been completed. Prevent start-up of individual fuel firing equipment
unless certain permissive, interlocks have been satisfied.
Monitor and control proper component sequencing during start-up and shut-down of fuel firing equipment.
Subject continued operation of fuel firing equipment to ascertain safety interlocks remaining satisfied.
7 of 27confidentia
l
Purpose Provide component status feedback to the
operator and, in some cases, to the unit control system and / or to the data logger.
Provide flame supervision when fuel firing equipment is in service and effect an Elevation Fuel Trip or Master Fuel Trip upon certain condition of unacceptable firing / load combination.
Effect a Master Fuel Trip upon certain adverse Unit operating conditions.
8 of 27confidentia
l
Subsystem of FSSS
Purge Permissive (s)
HOTV Open/Close Interlocks
HORV Open/Close Interlocks
Oil Guns Start/Stop Cycle
Boiler Protection Logics
9 of 27confidentia
l
Subsystem of FSSS (Cont.)
PA Fan Interlocks
Coal Mill Start/Stop Interlocks
Coal Feeder Start/Stop Interlocks
Scanner Air Fans
Seal Air Fans
Secondary Air Damper Interlocks
10 of 27confidentia
l
Purge Permissives All HFO Nozzle Valves Closed
HFO Trip Valve closed
No Boiler Trip From MFR A & B
All Pulverizers Off.
All Feeders Off
All Flame Scanners Sense No Flame
Both PA fans Off
11 of 27confidentia
l
Purge Permissives (Cont.) All Auxiliary Air Dampers Modulating and
furnace to wind box P OK
All Hot Air Gates Closed
Air Flow > 30 %
Mode Permit Proven (Air Flow < 40%
Burner Tilt Horizontal)
Drum Level Satisfactory FSSS AC / DC Power Available.
12 of 27confidentia
l
HOTV InterlocksTo Open HOTV : Permissives
SET I No. Boiler Trip persisting HFO Header temperature satisfactory >950 C HFO supply pressure > 15 Kg / cm2
All HONV’s closed No close / Trip command Open PB depressed
13 of 27confidentia
l
HOTV InterlocksTo Open HOTV : Permissives
SET II All HONV’s closed MFT acted HORV open Open PB depressed
14 of 27confidentia
l
HOTV Interlocks
1. HOTV closes automatically under the following conditions:
Any HONV not closed AND
a) HFO pressure low < 3 Kg/cm2 OR
b) Atomizing steam pressure low < 3.5 Kg/cm2 OR
c) HFO Header Temperature Lo-Lo for > 2 secs. < 95 0C
2. Any HONV not closed and MFT acted
3. Loss of critical power > 2 Seconds
4. HOTV can be closed manually
15 of 27confidentia
l
HORV Interlocks
HORV can be opened by pressing the OPEN Push
button (PB) from Console if All the HONV s are
closed.
HORV closes automatically when any HONV is not
closed OR by pressing close PB.
16 of 27confidentia
l
s
s
ss
s
s
HFO PUMP-1
HFO PUMP-2
HFO PUMP-3
HFO HTR-1
HFO HTR-2
HFO HTR-3
FROM HFO DAY TANK
FROM AUXILIARY STEAM HEADERHFO Supply SchemeHFO Supply Scheme
TO BOILERFRONT
TO HFO DAY TANK
17 of 27confidentia
l
M
FT
FT
AB ELEVATION
CD ELEVATION
EF ELEVATION
HOFCVHOTV
HORV
SHORTRECIRCULATION
HFO SUPPLY
LINE
HFO RETURN
LINE
HFO Scheme At Boiler FrontHFO Scheme At Boiler Front
18 of 27confidentia
l
OIL GUN
ATOMISINGSTEAM VALVE
HFO NOZZLEVALVE SCAVENGE
VALVE
AB ELEVATION
CD ELEVATION
EF ELEVATION
Oil Gun ConnectionOil Gun Connection
Atomizing Steam Scheme
19 of 27confidentia
l
Pair Firing Mode (Start Up) Pair firing mode is selected when no feeder is in
service. Pairs are made for the opposite corners. (Pair 1-3 and Pair 2-4)
When pair 1-3 start push button is pressed;
A 30 second counting period is started
A 70 second counting period is started Oil Gun No-1 advances from retracted position if, it
is engaged, corresponding scavenge valve is closed, atomizing steam and HFO isolation valves are open.
20 of 27confidentia
l
Pair Firing Mode (Start Up) HEA igniter advances. Atomizing steam valve opens. Igniter starts sparking. HFO Nozzle valve for corner 1 opens HFO catches fire and flame indication comes. After 25 seconds igniter retracts. When the 30 second counting period expires
command will go to corner 3 and same events will take place.
Corner 2-4 can also be placed exactly in the same manner.
21 of 27confidentia
l
Elevation Firing Mode (Start Up) Elevation firing mode is selected when any feeder is
proven.
Oil elevation is placed in service when Pair 1-3 or Pair 2-4
start Push Button is pressed. In elevation firing mode also
the oil guns are proven on pair basis.
First command goes for placing Pair 1-3 into service and
Pair 1-3 is placed into service exactly in the same way as
in the pair mode.
22 of 27confidentia
l
Elevation Firing Mode (Start Up) First start command goes to corner-1 then after 30 second
start command goes to corner-3.
After the start command has gone to corner 3, a 30 second
counting period is started. When 30 seconds counting
period expires then start command goes for corner 2-4 and
corner 2-4 are placed into service exactly in the same
manner as in the pair mode.
23 of 27confidentia
l
PAIR FIRING MODE (SHUT DOWN) Pair firing mode is selected when no feeder
is in service. Pairs are made for the opposite corners. (Pair 1-3 and Pair 2-4)
When pair 1-3 stop push button is pressed the following events take placeA 30 second counting period is startedA 340 second counting period is started
Oil Gun No-1 HFO nozzle valve closes. Scavenge and atomizing steam valve opens. HEA igniter advances and spark remains for
15 seconds.
24 of 27confidentia
l
Pair Firing Mode (Shut Down) When atomizing steam valve is proven fully open,
a 5 minutes counting period starts. When 5 minutes counting period expires scavenge
valve and atomizing steam valve closes and further closing command goes HFO nozzle valves to reinsure that they are fully closed.
Oil Gun corner no-1 retracts to its home position. When the 30 second counting period expires stop
command will go to corner 3 and same events will take place.
Corner 2-4 can be shut-down exactly in the same manner.
25 of 27confidentia
l
Elevation Firing Mode (Shutdown) Elevation firing mode is selected when any feeder is proven.
By pressing stop push-button of Pair 1-3 or Pair 2-4 the
following events will take place.
Corner 1-3 will be shut-down in the similar way as in the pair
mode.
When stop command has gone to corner 3, a 30 second
counting period is started. When 30 seconds counting period expires then stop
command goes for corner 2-4 and corner 2-4 are shut-down
exactly in the same manner as in the pair mod
26 of 27confidentia
l
Boiler Trip Conditions Both FD Fans Off All ID Fans Off Inadequate Water Wall Circulation Loss Of Reheater Protection Deaerator level Lo-Lo ( -2134 mm 2 / 3 logic) All Boiler Feed Pumps Off Drum Level High-High (> + 250 mm, delay of 10 seconds) Drum Level Lo-Lo (< - 375 mm, delay 10 seconds) Elevation Power Failure For > 2 seconds. Furnace Pressure High-High (> + 325 mmWCl, 2 / 3 logic)
27 of 27confidentia
l
Boiler Trip Conditions Furnace Pressure Lo-Lo (< -250 mmWC, 2 / 3 logic) Loss Of All Fuel Unit Flame Failure Loss Of Critical Power For > 2 seconds Loss Of 220 V DC For > 2 seconds Loss Of ACS Power > 2 seconds Simulated Trip Air Flow < 30 % Both Emergency Push Buttons Pressed.
28 of 27confidentia
l
Boiler TripWhen the boiler trips the following events takes place
Boiler trip red lamp comes on. MFT A & B trip lamp comes on and reset lamp goes off. Cause of trip memory can not be reset till the furnace
purge is completed. F D Fans Control is transferred to manual. I D fans vane position is transferred to manual. Pulverizers are tripped. Coal feeders are tripped. P A fans are tripped.
29 of 27confidentia
l
Boiler Trip (Cont.)When the boiler trips …….
Cold air dampers opens 100 %. HFO trip valve closes. All HFO Nozzle valves closes. Upper and Lower Fuel air damper opens. Auxiliary air damper opens and control is transferred to
manual. Loss of all fuel trip protection disarms. S/H and R/H spray block valves S-82 & R-31 closes and
can not be opened unless furnace purge is completed. Turbine Trips
30 of 27confidentia
l
Inadequate Water Wall Circulation
1.Boiler load > 60 % and less than two pumps or
pump on and differential pressure < 10 psi.
2.Boiler load < 60 % and no BCW pump on or
pump on and differential pressure < 10 psi.
31 of 27confidentia
l
Reheat Protection
1. Turbine trip or generator circuit breaker open and hp/lp
bypass opening < 2 %.
2. Turbine working (hp & ip cvs opening > 2 % and load
shedding relay operated and hp/lp bypass opening < 2 %.
3. Turbine not working and boiler working and hp/lp bypass
opening < 2 %.
32 of 27confidentia
l
Loss of all fuel armingSET
RESETMFT 5 SEC
Any elevation¾ Nozzle valve proven
All feeders off 2 SEC
All HFO Nozzle valve closed
All feeders off
HOTV NOT OPEN
2 SEC
All HFO Elevation Trip
Loss of all fuel trip
Loss of All Fuel Trip
33 of 27confidentia
l
Flame Failure Trip
Elevation AB No Flame Vote
Elevation BC No Flame Vote
Elevation DE No Flame Vote
Elevation FG No Flame Vote
Elevation GH No Flame Vote
Any Feeder Proven 2 Sec
Flame Failure
Trip
34 of 27confidentia
l
Flame Failure Vote Logics
Feeder A Off2 Sec
Feeder B Off
Elevation AB Any HFO Nozzle Valve Not Closed
Elevation AB 2/4 Nozzle Valve Not Proven
Elevation AB Scanners No Flame
Feeder C Off
2 Sec
2 Sec
Elevation BC Scanners No Flame
Elevation AB No Flame Vote
Elevation BC No Flame Vote
Elevation DE No Flame VoteFeeder D Off
Feeder E Off
Elevation DE Scanners No Flame
35 of 27confidentia
l
FEEDER H OFF
ELEVATION GH ANY HFO NOZZLE VALVE NOT CLOSED
ELEVATION GH 2/4 NOZZLE VALVE NOT PROVEN
2 SEC
ELEVATION GH NO FLAME VOTE
ELEVATION FG NO FLAME VOTE
Flame Failure Vote Logics
FEEDER F OFF
FEEDER G OFF
ELEVATION FG SCANNERS NO FLAME
ELEVATION GH SCANNERS NO FLAME
36 of 27confidentia
l
Mill Interlocks Start Permissive (s):
Mill starts after the ‘ON’ push button is pressed if
following
conditions are fulfilled.
Pulveriser Ready available signal will be available if
following conditions are fulfilled M.D.V. is open (all four)
Mill outlet temp < 93 0 C Feeder local switch in Remote
37 of 27confidentia
l
Mill Interlocks
Pulverizer start permit (if Nozzle tilt Horizontal & air
flow < 40 %) OR
Any feeder proven & NO MFT Tramp iron valve open Cold air gate open Feeder inlet gate open Lub oil level & temp. adequate Lub oil pressure not low for more than 300 sec No Mill trip existing
38 of 27confidentia
l
Mill InterlocksP.A. permit available.
(i) Hot P.A. duct Pressure. not low (< 625 mmWCl)
(ii) P.A. duct pr. not lo-lo ( > 500 mmWCl AND
(iii) Both FD s ON and both PA fans ‘ON’ or (Any PA fan
ON and any FD Fan ‘ON’ and > 4 mills not ON)
No Auto pulverizer unsuccessful start
Seal air Header to mill under bowl DP satisfactory > 8" WCl
Mill not ‘ON’
Pulverizer Ignition permit available.
39 of 27confidentia
l
Mill Interlocks
FOR Mill A
AB elevation 3/4 HONV’s open
OR
Boiler load > 30 % and Feeder - B speed > 50 % ( > 30 T/hr.)
For Mill B
AB elevation proven 3/4 HONV’s open
OR
Boiler load > 30 % and Feeder A or Feeder C proven.
40 of 27confidentia
l
Mill InterlocksFor Mill C
CD elevation proven OR
AB oil elevation and feeder B proven OR
Boiler load > 30 % & either feeder B or Feeder D proven
For Mill D
CD elevation proven OR
Boiler load > 30 % and either feeder C or feeder E proven.
For Mill E,F,G & H identical logic
41 of 27confidentia
l
Pulveriser Trip Conditions Auto / manual mode selected to manual & stop PB
depressed.
Pulv. start command given & not ‘ON’ for > 2 Secs.
Loss of Elevation OR Unit Power for > 2 Secs
Pulv ‘ON’ & seal air / under DP Low > 1 min < 5”wc
Pulv ‘ON’ and lub oil pump OFF > 10 sec.
Pulv ‘ON’ and lub oil pr. low > 10 secs. < 1.76 Kg/cm2
Ignition permit required (> 180 secs) & ignition permit
lost (i.e. within 180 sec of feeder start)
42 of 27confidentia
l
Pulveriser Trip Conditions Any of the MDV is not fully open
Hot PA duct. pr. Lo < 625 mm of WCL (delay 5 sec)
Hot PA duct. pr. Lo - Lo = < 525mm WC (instantaneous)
MFT
PA / FD Fan trip
a) If both PA Fans & both FD fans running & any PA or any FD
Fan trips then mills start tripping from top elevations with 2 secs
time delay till 4 mills are available.
b) If both PA / FD fans trip then all mills will trip.
43 of 27confidentia
l
Pulverizer Seal Air Valves Interlocks Valve opens when Pulverizer start command is given
OR Mill is ON
Valve closes when Pulverizer is OFF
Hot Air Gate Interlocks Hot air gate (HAG) opens when Pulverizer is ‘ON’ AND
Hot air gate open
P.B. depressed or auto HAG open command is there
AND NO HAG close command.
44 of 27confidentia
l
Hot air gate closes when
1. Loss of power > 2 secs
2. Pulverizer off
3. Pulverizer outlet temp > 93 0 C
4. Close P.B. depressed
5. Feeder Trips.(Delay 40 sec)
6. Auto pulverizer unsuccessful start
7. Auto pulverizer run feeder speed to minimum
45 of 27confidentia
l
Feeder Start Permissive (s) Pulveriser Ready is available
Feeder speed demand at minimum
Pulveriser manual mode
Pulveriser ignition permit available
No feeder stop command
No MFT
Pulveriser ‘ON’
46 of 27confidentia
l
Feeder Trip Condition Ignition energy removed within 180 seconds of
feeder start
Feeder in manual mode & stop PB depressed
Auto Pulverizer Feeder stop command
Pulverizer OFF
MFT
No coal on belt Discharge plugged
47 of 27confidentia
l
SADCThe secondary air dampers located in wind box apportions the total secondary air between various elevations. How this air is proportioned, depends on which fuel is being burnt, the number of elevations in service and the firing rate at each elevation.The function of Secondary Air Damper Control System (SADC) is to proportion the total secondary air around the firing elevation as per the criteria spelt above. In fact the SADC system is a combination of both analog and digital system, as the amount of fuel fired and the no. of firing elevations decide the damper position.
48 of 27confidentia
l
The auxiliary air dampers are positioned to maintain the required wind box to furnace differential pressure according to the boiler load. In the initial periods of operation, the flame condition with reference to ignition stability, ignition point relative to fuel nozzles, overall combustion conditions in the furnace are to be studied for various wind box to furnace differential pressures and the values are to be optimized at site (the values are adjustable). Based on this, the final curve showing the relationship between the wind box to furnace differential pressure versus the boiler load is to be decided for the type of coal used.
49 of 27confidentia
l
The auxiliary elevation dampers act as fuel (oil) air dampers when oil firing is taking place and is open to a preset position. The fuel (oil) elevation dampers are selected to be closed if there is a back up trip in that elevation and adjacent pulverizers are off and “No Boiler Trip” signal is present. When a HFO Elevation is started (i.e. when the associated “elevation back-up” trip is removed) the associated auxiliary air dampers in that elevation are set to preset position for HFO firing.
50 of 27confidentia
l
Above 30% MCR boiler load, the auxiliary air elevation associated with the main fuel elevation in service modulate to maintain the varying DP. Those not associated with any elevation in service are closed from top to bottom. The closing signal comes from FSSS. When the unit load is increased above 30% MCR, the Aux. air dampers of elev. AA,AB, BC, CD, DE, EF & FF are closed in a timed sequence (10 sec. interval) provided the associated coal elevations are not in service and the associated oil elevations are not in service. The auxiliary air dampers are closed, starting from the top elevation, progressing towards the lowest elevation.
51 of 27confidentia
l
All elevations of the aux. air dampers will be automatically switched to “Manual” control and then commanded to open 100%, if any one of the following conditions exist.
Both FD fans are OFF. Both ID fans are OFF. Master fuel trip occurs. Loss of unit critical power . (+24V DC)
Also the auxiliary air control loop is tripped to manual if any of the following conditions exist.
DP transmitter deviation high. Failure of selected DP transmitter Furnace to Windbox DP very high (> 240mm WCL).
52 of 27confidentia
l
The fuel air damper control system positions the fuel air damper in proportion to the fuel firing rate. In the initial periods of operation, the flame condition with reference to ignition stability, ignition point relative to fuel nozzles, overall combustion conditions in the furnace are to be studied for various fuel air damper positions and the values are to be optimized at site.
Based on this the final curve showing the relationship between the fuel air damper positions versus the fuel feed rate is to be decided for the type of coal used.
53 of 27confidentia
l
All elevations of fuel air dampers are commanded to open 100% when any one of the following conditions exist.
Both FD fans are OFF. Both ID fans are OFF. Master fuel trip occurs. Loss of unit Critical Power.(+24 VDC)
54 of 27confidentia
l
On coal fired boilers the characteristics of fuel like, Fixed Carbon, Volatile Matter and Ash composition will determine the optimum wind box to furnace differential pressures and the fuel air damper positions. Accordingly the optimized settings are to be decided as above for the coal used.
55 of 27confidentia
l
Later, if the coal quality changes or the coal source itself is changed, it shall be necessary to once again carryout optimization studies for the new coal and revised settings are to be finalized.
56 of 27confidentia
l
57 of 27confidentia
l
Modulation of Auxiliary Air Dampers
58 of 27confidentia
l
Modulation of Fuel Air Dampers
59 of 27confidentia
l
Modulation of Over Firing Air Dampers
60 of 27confidentia
l
The two elevations of the over fire air dampers will be automatically switched to “Manual” control and then commanded to open 100%, if any one of the following conditions exist
Master fuel trip occurs. Loss of unit critical power .(+24 VDC) Both FD fans are OFF. Both ID fans are OFF. WB To Furnace DP exceeds 240mm WCL.
61 of 27confidentia
l
62 of 27confidentia
l
Thank you
12th July, 2008
top related