Flatpack2 |Cabinetized48VDC/96kW DC Power Rack System
Product Description
The Flatpack2 48 VDC/ 96kW system proves that Flatpack2 isthe ultimate building block in any telecom application. Thesystem includes a complete power system with up to 2000Arectifier capacity, controller and flexible distribution options, allin a single cabinet.
Key features
Basic configuration is with six power shelves with the possibilityto expand up to 12 (in steps of three). Standard distributionmodules are available with the variety of knife fuses and MCBs.A high degree of flexibility makes it easy to meet most customerrequirements fast and cost efficient.
Applications
The Flatpack2 Cabinetized 2000A system is ideal for theapplication needing a higher power requirement. It has a wideapplication range in both mobile and fixed networks.
http://www.eltekenergy.com/http://www.eltekenergy.com/ -
7/23/2019 DS FP2 2x6U PRCabinatized 96kw
2/2
Location Company Telephone Fax
Europe Eltek Energy AS +47 32 20 32 00 +47 32 20 32 10
Americas Eltek Energy, LLC +1 815 459 9100 +1 815 459 9118
Asia/Pacific Eltek Energy Pte Ltd. +65 6 7732326 +65 6 7753602
China Eltek Energy Ltd. +867 692651108 +867 692296797
Middle East Eltek Middle East +971 4 887 1176 +971 4 887 1175
Flatpack2 |48V/ 96kW DC Power Rack SystemTechnical Specifications
AC Input
Voltage230 VAC, single phase
230 VAC, 3-phase IT network
230/400 VAC, 3-phase TN networkFrequency 45 to 66Hz
Maximum Current See Flatpack2 48VDC datasheet(241115.100.DS3)
MonitoringMonitoring unit See Smartpack (242100.100.DS3)
datasheet
Local operation Menu driven software viakeypads and LCD or PC (PowerSuite)
Remote operation PowerSuite via modem or Web NMS via
SNMP-agent
Alarm relays 6 relays are standard
Visual indications Green LED System ON
Yellow LED Minor alarm(s)Red LED Major alarm(s)
LCD system status
Digital inputs 6 (for monitoring of externalequipment)
Currentmeasurements
Battery currentRectifier current
Alarms Load fuse alarm
Battery fuse alarmLVD operated
Low output voltage alarms(2 individual alarm levels)
High output voltage alarms(2 individual alarm levels)Battery capacity
Temperature alarmSymmetry alarm
DC OutputVoltage 48 VDC
Current From 1U PR (150A) up to 12U PR
(2000A)
DC Distribution Options
MCB loaddistribution unit
30 x MCBs (DIN rail mounted, 2-
63A)
Options:- LVLD (300A)
Connection: Directly in MCB, max16mm2
Bulk loaddistribution unit(Isolated knife fuse
holders)
4 outputs, max 630A eachOptions- Additional 4 outputs, max.630A
- LVLD (1200A)Connection: M10 bolt
Battery distributionunit(Isolated knife fuse
holders)
Alt 1: 4 outputs, max.630A eachAlt 2: 2 outputs, max 1600A eachOptions
- LVBD contactor, 1200A or 1800AConnection: M10 bolt
Other Specifications
Isolation
3.0 KVAC input and output
1.5 KVAC input earth0.5 KVDC output earth
Operating temp. -40 to +60C (-40 to +140F)
Storage temp. -40 to +85C (-40 to +185F)
Dimensions 600 x 2000x600mm (wxhxd)
(23.6 x 59 x 23.6)
Weight Approx. 150kg (330.7lbs) excl.rectifiers
Applicable StandardsElectrical safety IEC 60950, UL 60950
EMC ETSI EN 300 386 V.1.3.1(telecommunication network)
EN 61000-6-3(emission, light industry)
EN 61000-6-2(immunity, industry)
Environment ETSI EN 300 019-2ETSI EN 300 132-2
Environment Storage: ETS 300 019-2-1Transport: ETS 300 019-2-2Operation: ETS 300 019-2-3
ORDERING INFORMATION
Part no. Description
241115.100 Flatpack2 48VDC/2000
211977.xxxxx Flatpack2 48VDC/ 96kW Power Rack Sales configured system (CTO)