    Flatpack2 |Cabinetized48VDC/96kW DC Power Rack System

    Product Description

    The Flatpack2 48 VDC/ 96kW system proves that Flatpack2 isthe ultimate building block in any telecom application. Thesystem includes a complete power system with up to 2000Arectifier capacity, controller and flexible distribution options, allin a single cabinet.

    Key features

    Basic configuration is with six power shelves with the possibilityto expand up to 12 (in steps of three). Standard distributionmodules are available with the variety of knife fuses and MCBs.A high degree of flexibility makes it easy to meet most customerrequirements fast and cost efficient.

    Applications

    The Flatpack2 Cabinetized 2000A system is ideal for theapplication needing a higher power requirement. It has a wideapplication range in both mobile and fixed networks.

    http://www.eltekenergy.com/http://www.eltekenergy.com/
  • 7/23/2019 DS FP2 2x6U PRCabinatized 96kw

    2/2

    Location Company Telephone Fax

    Europe Eltek Energy AS +47 32 20 32 00 +47 32 20 32 10

    Americas Eltek Energy, LLC +1 815 459 9100 +1 815 459 9118

    Asia/Pacific Eltek Energy Pte Ltd. +65 6 7732326 +65 6 7753602

    China Eltek Energy Ltd. +867 692651108 +867 692296797

    Middle East Eltek Middle East +971 4 887 1176 +971 4 887 1175

    Flatpack2 |48V/ 96kW DC Power Rack SystemTechnical Specifications

    AC Input

    Voltage230 VAC, single phase

    230 VAC, 3-phase IT network

    230/400 VAC, 3-phase TN networkFrequency 45 to 66Hz

    Maximum Current See Flatpack2 48VDC datasheet(241115.100.DS3)

    MonitoringMonitoring unit See Smartpack (242100.100.DS3)

    datasheet

    Local operation Menu driven software viakeypads and LCD or PC (PowerSuite)

    Remote operation PowerSuite via modem or Web NMS via

    SNMP-agent

    Alarm relays 6 relays are standard

    Visual indications Green LED System ON

    Yellow LED Minor alarm(s)Red LED Major alarm(s)

    LCD system status

    Digital inputs 6 (for monitoring of externalequipment)

    Currentmeasurements

    Battery currentRectifier current

    Alarms Load fuse alarm

    Battery fuse alarmLVD operated

    Low output voltage alarms(2 individual alarm levels)

    High output voltage alarms(2 individual alarm levels)Battery capacity

    Temperature alarmSymmetry alarm

    DC OutputVoltage 48 VDC

    Current From 1U PR (150A) up to 12U PR

    (2000A)

    DC Distribution Options

    MCB loaddistribution unit

    30 x MCBs (DIN rail mounted, 2-

    63A)

    Options:- LVLD (300A)

    Connection: Directly in MCB, max16mm2

    Bulk loaddistribution unit(Isolated knife fuse

    holders)

    4 outputs, max 630A eachOptions- Additional 4 outputs, max.630A

    - LVLD (1200A)Connection: M10 bolt

    Battery distributionunit(Isolated knife fuse

    holders)

    Alt 1: 4 outputs, max.630A eachAlt 2: 2 outputs, max 1600A eachOptions

    - LVBD contactor, 1200A or 1800AConnection: M10 bolt

    Other Specifications

    Isolation

    3.0 KVAC input and output

    1.5 KVAC input earth0.5 KVDC output earth

    Operating temp. -40 to +60C (-40 to +140F)

    Storage temp. -40 to +85C (-40 to +185F)

    Dimensions 600 x 2000x600mm (wxhxd)

    (23.6 x 59 x 23.6)

    Weight Approx. 150kg (330.7lbs) excl.rectifiers

    Applicable StandardsElectrical safety IEC 60950, UL 60950

    EMC ETSI EN 300 386 V.1.3.1(telecommunication network)

    EN 61000-6-3(emission, light industry)

    EN 61000-6-2(immunity, industry)

    Environment ETSI EN 300 019-2ETSI EN 300 132-2

    Environment Storage: ETS 300 019-2-1Transport: ETS 300 019-2-2Operation: ETS 300 019-2-3

    ORDERING INFORMATION

    Part no. Description

    241115.100 Flatpack2 48VDC/2000

    211977.xxxxx Flatpack2 48VDC/ 96kW Power Rack Sales configured system (CTO)