compounding pharmacy cleanroom design for usp/fda compliance chris munoz, pharmd

Post on 18-Jan-2016

225 Views

Category:

Documents

3 Downloads

Preview:

Click to see full reader

TRANSCRIPT

Compounding Pharmacy Cleanroom Design for USP/FDA

ComplianceChris Munoz, PharmD

Why Are We Here Today?

1

New England Compounding Center

2

Our Goal:Demystify the

Regulations

3

The Hard Facts About the DQSA

4

5

2014 FDA/State Meeting

6

2014 FDA/State Meeting

7

Current Good Manufacturing Practice

(cGMP)

8

9

cGMP Guidance (Draft)

10

11

cGMP Guidance (Draft)

12

Today’s Regulatory Environment

13

14

2015 FDA/State Meeting

15

2015 FDA/State Meeting

16

Section 503A: Traditional

Compounding Pharmacies

17

18

ASHP Guidelines

19

20

503A Final Guidance

21

503A Final Guidance

22

Quick RecapBefore We Move On to

USP

23

State Oversight:USP <797>

(Under Revision)

24

USP <797> Draft

25

State Oversight:USP <800>

(Draft)

26

USP <800> Draft

27

USP <800> Draft

28

USP <800> Draft

29

Compounding Cleanroom Design

Mike Buckwalter Terra Universal, Inc.

Regulations & agencies that provide guidelines on cleanroom standards & practices:

Regulators: Who says what’s clean?

32

Regulation/Agency Industries Served Background

Fed-Std-209E/US General Service Administration

Fed-Std-209 initially regulated aerospace and semiconductor industries, but assumed international scope

Specified the familiar classifications: “Class 10, “ Class 100,” etc. Each classification referred to the number of permissible particles per cu. ft. Officially canceled in 2001, but still widely used

ISO 14644/International Standards Organization

All. Metric measurement adhere to international conventions.

Superseded Fed-Std-209E starting in 2001. Correlates roughly as follows:Fed-Std-209E ISO 14644Class 1 ISO 3Class 10 ISO 4Class 100 ISO 5Class 1000 ISO 6Class 10,000 ISO 7Class 100,000 ISO 8

EU GMP* ClassificationPharmaceutical Manufacturing in both the European Union and US

Uses the designations Class A, B, C and D. Classes “A” and “B” correspond to ISO 5, but “A” specifies a stricter “in operation” air change rate.

British Standard (BS) 5295

Great Britain Uses the designations Class 1, Class 2, Class 3, Class 4; superseded by ISO 14644

ISO I, 2 and 9 have no direct 209E equivalent

*European Union Good Manufacturing Practices

Allowable airborne particulates, by cubic meter*:*For ISO 1 through 6, this list refers to quantities of 0.3 micron-sized particles allowed in a controlled environment, and for ISO 7 through 9, it refers to 0.5 micron-sized particles. Source: ISO 14644-1

Particles: ISO level limits

ISO Level Particle Count

1 Less than 10

2 10

3 103

4 1,020

5 10,200

6 102,000

7 352,000

8 3,520,000

9 35,200,000

FYI:A cubic meter of typical room air contains ± 52 million 0.3-0.5 micron particles.

33

Particle Counter

• Uni-directional air flow controls contaminants more effectively than uncontrolled, multi-directional air flow• Turbulence stirs-up particles• Fan/filter units force air through filters in a laminar fashion• FFUs also provide uniform air speed with proper control system• Presence of furnishings, equipment and personnel interrupts laminarity; air hits surfaces and bounces• Rapid movements create turbulence

Laminar vs Turbulent Air Flow

34

Air movement promotes cleanliness. Filtered air sweeps particles toward the floor and exhaust vents. Air exchange rates shown here are IEST* recommendations but are occasionally revised downward: high ACR velocity can create unwanted turbulence. USP specifies 30 ACPH for ISO7.

Air Changes Per Hour (ACPH)

ISO Level Recommended ACR Ceiling FFU Coverage

1-2 360 – 600/hr 80 – 100%

3 360 – 540/hr 60 – 100%

4 300 – 640/hr 50 – 90%

5 240 – 480/hr 35 – 70%

6 150 – 240/hr 25 – 40%

7 60 – 90/hr 15 – 20%

8 5 – 48/hr 5 – 15%

9 less than 5 – 48/hr Less than 5%

ISO recommendations:

Range dependent upon variables like room design and access frequency.

35

FYI:Air change rates in an air-conditioned house average about one(1) per hour.

*Institute of Environmental Sciences and Technology

Calculate with this formula:

No. of FFUs = (Air Changes per Hour ⁄ 60) × (Cubic feet in room ⁄ 650*)

*Refers to the cubic feet/minute (CFM) of a typical 2 x 4 loaded FFU at medium speed.′ ′

Example of a 10’ x 10’ x 10’ ISO 7 room:60 – 90 ACH is required, therefore, you need 2-3 FFUs.

Calculations: • (60/60) x (1000/650) = 1.54 • (90/60) x (1000/650) = 2.31

Discussion: An ISO 7 room is more forgiving than (for example) ISO 5, however the 10-foot ceiling warrants a rounding up of the calculation fractions.

Air Change Rate: FFU coverage

36

• Moving (vs. stagnant) air = a cleaner environment• Too forceful = unnecessary turbulence• Consider room design: choose the higher end of the range to account for a higher ceiling (greater travel distance), for example

Airflow Design Basics

ISO Level Air Speed*

1-2 0.305 – 0.508 (60 – 100)

3 0.305 – 0.457 (60 – 90)

4 0.254 – 0.457 (50 – 90)

5 0.203 – 0.406 (40 – 80)

6 0.127 – 0.203 (25 – 40)

7 0.051 – 0.076 (10 – 15)

8 0.005 – 0.041 (1 – 8)

9 < 0.005 – 0.041 (1 – 8)

*Expressed as meters/second (m/s). Within parentheses are feet/minute (f/m). (Source: IEST)

37

Factors that can influence air speed (velocity), air changes rates, fan/filter coverage, turbulence and air balancing:

• Personnel: quantity, speed and movement patterns• Equipment: quantity, energy consumption and exhaust• Vents and Plenums: location, quantity• Ceiling height• Entryways: types, quantity• Ducting: type, size, direction• Floor plan/number of rooms• Air handling systems/HVAC

Room Variables

38

• Forces air out of a room• Referred to as an “isolation” enclosure• Control systems and/or adjustable air vents control positive pressure• Protects samples, not external environment (leaks are relatively unimportant)• Softwall cleanrooms won’t maintain pressure• Air can be recirculated to extend filter life• Pressure requirement: typically 0.025 - 0.05” water column (WC) differential between rated and unrated space or between rooms of differing ISO ratings• Measure & log room pressure and differentials

Pressure: Positive (USP-797)

39

®Dwyer Instruments, Inc.

Pressure: Negative (USP-800)

40

• Exhaust system removes more air than enters room (min. 0.01” WC negative pressure)• Referred to as a “containment” enclosure• Exhaust air fed to dedicated in-house removal system; may require “scrubbing” to remove biohazards• Leaks allow particle ingress; walls must be sealed• Protects people outside the room from bio-hazards• Air enters through HEPA floor louvers or ceiling HEPA filters; recirculation generally not permitted• Requires appropriate ducting system tied to in-house exhaust system• 0.025” - 0.05” water column (WC) pressure difference between rooms of differing ISO ratings

Laminar-flow cleanroom

Sterile-to-Sterile HD Compounding

41

Sterile-to-Sterile HD Compounding

42

Non-Sterile-to-Sterile HD Compounding

43

Non-Sterile-to-Sterile HD Compounding

44

Temperature & Humidity

45

Temperature: usually 5 - 10°F below ambient level to offset heat-generating equipment and provide comfort for garbed technicians

Relative Humidity (RH): Usually 40 - 60%, but is dependent upon application/industry. Low RH invites static electricity (ESD); high RH provides environment for micro-organisms to flourish

Automated Control Systems

46

Summary: Cost Considerations

47

Modular Cleanrooms: Reduce cost and installation schedule compared to brick-and-mortar rooms – USP 797 designs begin around $15,000. FFUs can be added for nominal cost if requirements change.

Exhaust Air (503B and non-sterile-to-sterile compounding): Requires additional expense of air exhaust ducting and ceiling centrifugal exhaust fan, typically installed by a local contractor

Air Conditioning: To keep control costs, use existing facility HVAC system. Supplemental A/C modules add cost and potentially fresh make-up air supply

Certification: Automated control system adds up-front cost (but typically only 10-20% of room cost) but simplifies and speeds up certification, saving in long-term expenses, as well as controlled operation expenses

Energy: Upgrade to ECM fan/filter units to increase energy efficiency and comply with local energy requirements (e.g., California’s Title 24)

Pre-submitted Questions

48

49

50

• Enclosed, controlled space; may serve as the ISO 5 primary engineering control (PEC) inside an ISO 7 secondary engineering control (SEC) cleanroom• Filtered, laminar airflow• Material compatibility• Controls: Particle filtration, pressure, sterilization, temperature, static neutralization• USP designs: - Compounding Aseptic Isolator (CAI): protects sample (no containment) - Compounding Aseptic Containment Isolator (CACI): protects sample and operator (for hazardous drug compounding)

Isolators (Glove Boxes)

51

• AKA “clean bench” or “laminar-flow cabinet”• Horizontal or vertical laminar flow• Positive pressure• Compatible materials:

- Acrylic: economical; damaged by IPA- Static-dissipative PVC eliminates ESD*- Polypropylene: resists damage from chemicals- Powder-coated steel: strong, damage-resistant- Stainless steel: strong, resists cleaner & solvent damage

• Controls: ionizing bars (neutralizes static), UV sterilization (disinfects), differential pressure gauges, air-speed gauge• Specialty designs: PCR, IV rods, explosion-proof, perforated surfaces

Laminar Flow Hoods

52

*Electro-static discharge

Negative-pressure containment hoods; filtered exhaust removes pathogens (but not vapors). CDC/NSF classifications:Class I: partial containment protects personnel but not the productClass II: protects personnel and the product

Class III: Maximum containment for highest-risk pathogens; small amounts of volatile toxic chemicals or radionuclides. Filtered exhaust and make-up air. This cabinet is a glovebox, not a hood

Biological Safety Cabinets

53

Class II Type Characteristics

A1 min. air velocity of 75 fpm; low to moderate risk; 30% exhausted air into lab

A2 min. air velocity of 100 fpm; low to moderate risk; exhaust into lab; some negative pressure

B1 min. air velocity of 100 fpm; hard-ducted, moderate risk with some volatile chemicals or radionuclides; 70% exhausted air out of lab

B2 min. air velocity of 100 fpm; low to moderate risk with some volatile chemicals or radionuclides; 100% exhausted air out of lab

Class II A2 BSC

• Purpose: exhausts fumes to ducting system• Negative pressure• Baffling system ensures no air escape (“second-pass air”) at the operator interface• Not ISO rated• Ductless designs incorporate carbon filters to allow in-door air release

Fume Hood

54

• Interlocked doors prevent cross-contamination• Smooth, chemical-resistant internal surfaces (electropolished SS)• Isolated electronic interlock• Optional Air Shower minimizes particle ingress• Security features include biometric readers, logged access, wireless remote access control

Transfer Options: Pass-Throughs

55

Open Q&A Session

• During the webinar, please submit questions to us through the Q&A chat box within your interface

• After the webinar has ended, please direct all questions to evan@TerraUniversal.com

• Each participant will receive an email in the coming days containing a link to the video recording of this webinar and a PDF copy of Terra Universal’s white paper on the impact of shifting USP/FDA regulations on pharmacy cleanroom design

• To contact Terra Universal directly, call 714-578-6000

56

top related