Why Are We Here Today?

1

Page 3: Compounding Pharmacy Cleanroom Design for USP/FDA Compliance Chris Munoz, PharmD

New England Compounding Center

2

Page 4: Compounding Pharmacy Cleanroom Design for USP/FDA Compliance Chris Munoz, PharmD

Our Goal:Demystify the

Regulations

3

Page 5: Compounding Pharmacy Cleanroom Design for USP/FDA Compliance Chris Munoz, PharmD

The Hard Facts About the DQSA

4

Page 6: Compounding Pharmacy Cleanroom Design for USP/FDA Compliance Chris Munoz, PharmD

5

Page 7: Compounding Pharmacy Cleanroom Design for USP/FDA Compliance Chris Munoz, PharmD

2014 FDA/State Meeting

6

Page 8: Compounding Pharmacy Cleanroom Design for USP/FDA Compliance Chris Munoz, PharmD

2014 FDA/State Meeting

7

Page 9: Compounding Pharmacy Cleanroom Design for USP/FDA Compliance Chris Munoz, PharmD

Current Good Manufacturing Practice

(cGMP)

8

Page 10: Compounding Pharmacy Cleanroom Design for USP/FDA Compliance Chris Munoz, PharmD

9

Page 11: Compounding Pharmacy Cleanroom Design for USP/FDA Compliance Chris Munoz, PharmD

cGMP Guidance (Draft)

10

Page 12: Compounding Pharmacy Cleanroom Design for USP/FDA Compliance Chris Munoz, PharmD

11

Page 13: Compounding Pharmacy Cleanroom Design for USP/FDA Compliance Chris Munoz, PharmD

cGMP Guidance (Draft)

12

Page 14: Compounding Pharmacy Cleanroom Design for USP/FDA Compliance Chris Munoz, PharmD

Today’s Regulatory Environment

13

Page 15: Compounding Pharmacy Cleanroom Design for USP/FDA Compliance Chris Munoz, PharmD

14

Page 16: Compounding Pharmacy Cleanroom Design for USP/FDA Compliance Chris Munoz, PharmD

2015 FDA/State Meeting

15

Page 17: Compounding Pharmacy Cleanroom Design for USP/FDA Compliance Chris Munoz, PharmD

2015 FDA/State Meeting

16

Page 18: Compounding Pharmacy Cleanroom Design for USP/FDA Compliance Chris Munoz, PharmD

Section 503A: Traditional

Compounding Pharmacies

17

Page 19: Compounding Pharmacy Cleanroom Design for USP/FDA Compliance Chris Munoz, PharmD

18

Page 20: Compounding Pharmacy Cleanroom Design for USP/FDA Compliance Chris Munoz, PharmD

ASHP Guidelines

19

Page 21: Compounding Pharmacy Cleanroom Design for USP/FDA Compliance Chris Munoz, PharmD

20

Page 22: Compounding Pharmacy Cleanroom Design for USP/FDA Compliance Chris Munoz, PharmD

503A Final Guidance

21

Page 23: Compounding Pharmacy Cleanroom Design for USP/FDA Compliance Chris Munoz, PharmD

503A Final Guidance

22

Page 24: Compounding Pharmacy Cleanroom Design for USP/FDA Compliance Chris Munoz, PharmD

Quick RecapBefore We Move On to

USP

23

Page 25: Compounding Pharmacy Cleanroom Design for USP/FDA Compliance Chris Munoz, PharmD

State Oversight:USP <797>

(Under Revision)

24

Page 26: Compounding Pharmacy Cleanroom Design for USP/FDA Compliance Chris Munoz, PharmD

USP <797> Draft

25

Page 27: Compounding Pharmacy Cleanroom Design for USP/FDA Compliance Chris Munoz, PharmD

State Oversight:USP <800>

(Draft)

26

Page 28: Compounding Pharmacy Cleanroom Design for USP/FDA Compliance Chris Munoz, PharmD

USP <800> Draft

27

Page 29: Compounding Pharmacy Cleanroom Design for USP/FDA Compliance Chris Munoz, PharmD

USP <800> Draft

28

Page 30: Compounding Pharmacy Cleanroom Design for USP/FDA Compliance Chris Munoz, PharmD

USP <800> Draft

29

Page 31: Compounding Pharmacy Cleanroom Design for USP/FDA Compliance Chris Munoz, PharmD

Compounding Cleanroom Design

Mike Buckwalter Terra Universal, Inc.

Page 32: Compounding Pharmacy Cleanroom Design for USP/FDA Compliance Chris Munoz, PharmD

Regulations & agencies that provide guidelines on cleanroom standards & practices:

Regulators: Who says what’s clean?

32

Regulation/Agency Industries Served Background

Fed-Std-209E/US General Service Administration

Fed-Std-209 initially regulated aerospace and semiconductor industries, but assumed international scope

Specified the familiar classifications: “Class 10, “ Class 100,” etc. Each classification referred to the number of permissible particles per cu. ft. Officially canceled in 2001, but still widely used

ISO 14644/International Standards Organization

All. Metric measurement adhere to international conventions.

Superseded Fed-Std-209E starting in 2001. Correlates roughly as follows:Fed-Std-209E ISO 14644Class 1 ISO 3Class 10 ISO 4Class 100 ISO 5Class 1000 ISO 6Class 10,000 ISO 7Class 100,000 ISO 8

EU GMP* ClassificationPharmaceutical Manufacturing in both the European Union and US

Uses the designations Class A, B, C and D. Classes “A” and “B” correspond to ISO 5, but “A” specifies a stricter “in operation” air change rate.

British Standard (BS) 5295

Great Britain Uses the designations Class 1, Class 2, Class 3, Class 4; superseded by ISO 14644

ISO I, 2 and 9 have no direct 209E equivalent

*European Union Good Manufacturing Practices

Page 33: Compounding Pharmacy Cleanroom Design for USP/FDA Compliance Chris Munoz, PharmD

Allowable airborne particulates, by cubic meter*:*For ISO 1 through 6, this list refers to quantities of 0.3 micron-sized particles allowed in a controlled environment, and for ISO 7 through 9, it refers to 0.5 micron-sized particles. Source: ISO 14644-1

Particles: ISO level limits

ISO Level Particle Count

1 Less than 10

2 10

3 103

4 1,020

5 10,200

6 102,000

7 352,000

8 3,520,000

9 35,200,000

FYI:A cubic meter of typical room air contains ± 52 million 0.3-0.5 micron particles.

33

Particle Counter

Page 34: Compounding Pharmacy Cleanroom Design for USP/FDA Compliance Chris Munoz, PharmD

• Uni-directional air flow controls contaminants more effectively than uncontrolled, multi-directional air flow• Turbulence stirs-up particles• Fan/filter units force air through filters in a laminar fashion• FFUs also provide uniform air speed with proper control system• Presence of furnishings, equipment and personnel interrupts laminarity; air hits surfaces and bounces• Rapid movements create turbulence

Laminar vs Turbulent Air Flow

34

Page 35: Compounding Pharmacy Cleanroom Design for USP/FDA Compliance Chris Munoz, PharmD

Air movement promotes cleanliness. Filtered air sweeps particles toward the floor and exhaust vents. Air exchange rates shown here are IEST* recommendations but are occasionally revised downward: high ACR velocity can create unwanted turbulence. USP specifies 30 ACPH for ISO7.

Air Changes Per Hour (ACPH)

ISO Level Recommended ACR Ceiling FFU Coverage

1-2 360 – 600/hr 80 – 100%

3 360 – 540/hr 60 – 100%

4 300 – 640/hr 50 – 90%

5 240 – 480/hr 35 – 70%

6 150 – 240/hr 25 – 40%

7 60 – 90/hr 15 – 20%

8 5 – 48/hr 5 – 15%

9 less than 5 – 48/hr Less than 5%

ISO recommendations:

Range dependent upon variables like room design and access frequency.

35

FYI:Air change rates in an air-conditioned house average about one(1) per hour.

*Institute of Environmental Sciences and Technology

Page 36: Compounding Pharmacy Cleanroom Design for USP/FDA Compliance Chris Munoz, PharmD

Calculate with this formula:

No. of FFUs = (Air Changes per Hour ⁄ 60) × (Cubic feet in room ⁄ 650*)

*Refers to the cubic feet/minute (CFM) of a typical 2 x 4 loaded FFU at medium speed.′ ′

Example of a 10’ x 10’ x 10’ ISO 7 room:60 – 90 ACH is required, therefore, you need 2-3 FFUs.

Calculations: • (60/60) x (1000/650) = 1.54 • (90/60) x (1000/650) = 2.31

Discussion: An ISO 7 room is more forgiving than (for example) ISO 5, however the 10-foot ceiling warrants a rounding up of the calculation fractions.

Air Change Rate: FFU coverage

36

Page 37: Compounding Pharmacy Cleanroom Design for USP/FDA Compliance Chris Munoz, PharmD

• Moving (vs. stagnant) air = a cleaner environment• Too forceful = unnecessary turbulence• Consider room design: choose the higher end of the range to account for a higher ceiling (greater travel distance), for example

Airflow Design Basics

ISO Level Air Speed*

1-2 0.305 – 0.508 (60 – 100)

3 0.305 – 0.457 (60 – 90)

4 0.254 – 0.457 (50 – 90)

5 0.203 – 0.406 (40 – 80)

6 0.127 – 0.203 (25 – 40)

7 0.051 – 0.076 (10 – 15)

8 0.005 – 0.041 (1 – 8)

9 < 0.005 – 0.041 (1 – 8)

*Expressed as meters/second (m/s). Within parentheses are feet/minute (f/m). (Source: IEST)

37

Page 38: Compounding Pharmacy Cleanroom Design for USP/FDA Compliance Chris Munoz, PharmD

Factors that can influence air speed (velocity), air changes rates, fan/filter coverage, turbulence and air balancing:

• Personnel: quantity, speed and movement patterns• Equipment: quantity, energy consumption and exhaust• Vents and Plenums: location, quantity• Ceiling height• Entryways: types, quantity• Ducting: type, size, direction• Floor plan/number of rooms• Air handling systems/HVAC

Room Variables

38

Page 39: Compounding Pharmacy Cleanroom Design for USP/FDA Compliance Chris Munoz, PharmD

• Forces air out of a room• Referred to as an “isolation” enclosure• Control systems and/or adjustable air vents control positive pressure• Protects samples, not external environment (leaks are relatively unimportant)• Softwall cleanrooms won’t maintain pressure• Air can be recirculated to extend filter life• Pressure requirement: typically 0.025 - 0.05” water column (WC) differential between rated and unrated space or between rooms of differing ISO ratings• Measure & log room pressure and differentials

Pressure: Positive (USP-797)

39

®Dwyer Instruments, Inc.

Page 40: Compounding Pharmacy Cleanroom Design for USP/FDA Compliance Chris Munoz, PharmD

Pressure: Negative (USP-800)

40

• Exhaust system removes more air than enters room (min. 0.01” WC negative pressure)• Referred to as a “containment” enclosure• Exhaust air fed to dedicated in-house removal system; may require “scrubbing” to remove biohazards• Leaks allow particle ingress; walls must be sealed• Protects people outside the room from bio-hazards• Air enters through HEPA floor louvers or ceiling HEPA filters; recirculation generally not permitted• Requires appropriate ducting system tied to in-house exhaust system• 0.025” - 0.05” water column (WC) pressure difference between rooms of differing ISO ratings

Laminar-flow cleanroom

Page 41: Compounding Pharmacy Cleanroom Design for USP/FDA Compliance Chris Munoz, PharmD

Sterile-to-Sterile HD Compounding

41

Page 42: Compounding Pharmacy Cleanroom Design for USP/FDA Compliance Chris Munoz, PharmD

Sterile-to-Sterile HD Compounding

42

Page 43: Compounding Pharmacy Cleanroom Design for USP/FDA Compliance Chris Munoz, PharmD

Non-Sterile-to-Sterile HD Compounding

43

Page 44: Compounding Pharmacy Cleanroom Design for USP/FDA Compliance Chris Munoz, PharmD

Non-Sterile-to-Sterile HD Compounding

44

Page 45: Compounding Pharmacy Cleanroom Design for USP/FDA Compliance Chris Munoz, PharmD

Temperature & Humidity

45

Temperature: usually 5 - 10°F below ambient level to offset heat-generating equipment and provide comfort for garbed technicians

Relative Humidity (RH): Usually 40 - 60%, but is dependent upon application/industry. Low RH invites static electricity (ESD); high RH provides environment for micro-organisms to flourish

Page 46: Compounding Pharmacy Cleanroom Design for USP/FDA Compliance Chris Munoz, PharmD

Automated Control Systems

46

Page 47: Compounding Pharmacy Cleanroom Design for USP/FDA Compliance Chris Munoz, PharmD

Summary: Cost Considerations

47

Modular Cleanrooms: Reduce cost and installation schedule compared to brick-and-mortar rooms – USP 797 designs begin around $15,000. FFUs can be added for nominal cost if requirements change.

Exhaust Air (503B and non-sterile-to-sterile compounding): Requires additional expense of air exhaust ducting and ceiling centrifugal exhaust fan, typically installed by a local contractor

Air Conditioning: To keep control costs, use existing facility HVAC system. Supplemental A/C modules add cost and potentially fresh make-up air supply

Certification: Automated control system adds up-front cost (but typically only 10-20% of room cost) but simplifies and speeds up certification, saving in long-term expenses, as well as controlled operation expenses

Energy: Upgrade to ECM fan/filter units to increase energy efficiency and comply with local energy requirements (e.g., California’s Title 24)

Page 48: Compounding Pharmacy Cleanroom Design for USP/FDA Compliance Chris Munoz, PharmD

Pre-submitted Questions

48

Page 49: Compounding Pharmacy Cleanroom Design for USP/FDA Compliance Chris Munoz, PharmD

49

Page 50: Compounding Pharmacy Cleanroom Design for USP/FDA Compliance Chris Munoz, PharmD

50

Page 51: Compounding Pharmacy Cleanroom Design for USP/FDA Compliance Chris Munoz, PharmD

• Enclosed, controlled space; may serve as the ISO 5 primary engineering control (PEC) inside an ISO 7 secondary engineering control (SEC) cleanroom• Filtered, laminar airflow• Material compatibility• Controls: Particle filtration, pressure, sterilization, temperature, static neutralization• USP designs: - Compounding Aseptic Isolator (CAI): protects sample (no containment) - Compounding Aseptic Containment Isolator (CACI): protects sample and operator (for hazardous drug compounding)

Isolators (Glove Boxes)

51

Page 52: Compounding Pharmacy Cleanroom Design for USP/FDA Compliance Chris Munoz, PharmD

• AKA “clean bench” or “laminar-flow cabinet”• Horizontal or vertical laminar flow• Positive pressure• Compatible materials:

- Acrylic: economical; damaged by IPA- Static-dissipative PVC eliminates ESD*- Polypropylene: resists damage from chemicals- Powder-coated steel: strong, damage-resistant- Stainless steel: strong, resists cleaner & solvent damage

• Controls: ionizing bars (neutralizes static), UV sterilization (disinfects), differential pressure gauges, air-speed gauge• Specialty designs: PCR, IV rods, explosion-proof, perforated surfaces

Laminar Flow Hoods

52

*Electro-static discharge

Page 53: Compounding Pharmacy Cleanroom Design for USP/FDA Compliance Chris Munoz, PharmD

Negative-pressure containment hoods; filtered exhaust removes pathogens (but not vapors). CDC/NSF classifications:Class I: partial containment protects personnel but not the productClass II: protects personnel and the product

Class III: Maximum containment for highest-risk pathogens; small amounts of volatile toxic chemicals or radionuclides. Filtered exhaust and make-up air. This cabinet is a glovebox, not a hood

Biological Safety Cabinets

53

Class II Type Characteristics

A1 min. air velocity of 75 fpm; low to moderate risk; 30% exhausted air into lab

A2 min. air velocity of 100 fpm; low to moderate risk; exhaust into lab; some negative pressure

B1 min. air velocity of 100 fpm; hard-ducted, moderate risk with some volatile chemicals or radionuclides; 70% exhausted air out of lab

B2 min. air velocity of 100 fpm; low to moderate risk with some volatile chemicals or radionuclides; 100% exhausted air out of lab

Class II A2 BSC

Page 54: Compounding Pharmacy Cleanroom Design for USP/FDA Compliance Chris Munoz, PharmD

• Purpose: exhausts fumes to ducting system• Negative pressure• Baffling system ensures no air escape (“second-pass air”) at the operator interface• Not ISO rated• Ductless designs incorporate carbon filters to allow in-door air release

Fume Hood

54

Page 55: Compounding Pharmacy Cleanroom Design for USP/FDA Compliance Chris Munoz, PharmD

• Interlocked doors prevent cross-contamination• Smooth, chemical-resistant internal surfaces (electropolished SS)• Isolated electronic interlock• Optional Air Shower minimizes particle ingress• Security features include biometric readers, logged access, wireless remote access control

Transfer Options: Pass-Throughs

55

Page 56: Compounding Pharmacy Cleanroom Design for USP/FDA Compliance Chris Munoz, PharmD

Open Q&A Session