central battery system type cps 220/sv - inotec cps 220 series covers various load requirements and...
Post on 19-Mar-2018
224 Views
Preview:
TRANSCRIPT
Copyright: INOTEC Sicherheitstechnik GmbH, EnsePublications and copies, even partial, only with manufacturers permission.
Subject to technical changes.
INOTEC Sicherheitstechnik GmbH is a company with the target to create innovative and customer oriented solutions for the Emergency Lighting market.
A dynamic team of highly professional and flexible employees covers all aspects regarding products, engineering and standards.
Modern, technical advanced products set new standards world wide, i.e. JOKER technology for Emergency Lighting Systems or the Dynamic Escape Routing concept realised in the D.E.R.-System.
This catalogue contains the INOTEC Standard Central Battery Emergency Lighting Systems (CPS) and some complementing products. Should you require additional functions or special features please do not hesitate to ask our regional technical sales team for support.
Function, design and features 3-4
Advantages and function of Joker-technology 5
Installation sample 6-7
System components and options 8-12Control moduleChargerCircuit change-over devicesStairwell light switch module TLSRelay interface RIF 5Light switch monitors LSA8.1Phase monitors
Luminaire monitoring and supply modules 13-15
Low voltage halogenLED - Power LedElectronic ballastsMonitoring modules
External supervision and display 16-17Mimic panel, wall MTB/APMimic panel, recessed MTB/UPInoWeb / InoLan / InoWeb-ControlRTG interface
Technical data, systems overview 18-20
Designs sample, system engineering and tables 21-23
CPS 220/SVThe modular emergency lighting system
Page
ContentCPS 220 The modular emergency lighting system
CPS 220/SVFunction, design and features
220 V-central battery system with fully automatic function monitoring including individual lamp- and circuit failure detectionwithout additional data line
Internal and external system-bus
Automatic system configuration
Individual monitoring- and change-over devicesfor maintained- /non- maintained light
Simple design and engineering due to free selectable luminaire operation modes
Patented "Joker-Technology" function for mixed operation of maintained, non-main- tained and switched luminaires on one line
Included logbook for all relevant data within a minimum 2 year period
Centronics printer interface
Lead acid gas recombination OGi-battery with >10 years design life
Function principle: With functional mains all connected consumers are supplied with mains and the battery is charged / monitored. If mains fails or a partial light sub.-distribution or circuit failure is detected the supply is triggered by the emergency lighting system.
Emergency and safety luminaires
Emergency and safety luminaires
Battery 220V
3
Charger
Chargemonitoring
Mainsmonitoring
Mains CPS 220/SV
Controller with display
Change-over modules
Netz
Netz
Ein
Batterie
10AT
Betrieb
SV-ZENTRALE01.07.95 12:00
Funktionstest 2.7.95 8:30
Betrieb
Batt.-Betrieb
Störung
Ladestörung
Key-board
Drucker Cetronics
INOTEC
The CPS 220 series covers various load requirements and housing sizes. Joker-Technology, individual lamp- and circuit monitoring are our standard
System features
Modular design, various enclosure sizes for main-, sub-stations, battery-racks and battery enclosures
19" inch - rack modules
Isolation terminals for easy connection and insulation resistance measurement of luminaire circuits
Load for standard systems: from 1,5 KVA to 22 KVA
Compact design: Up to 48 circuits 3A (max. 576 monitored luminaires at 12 luminaires per circuit) or 24 circuits 6A on one system controller
Low maintenance and service costs due to central monitoring of stations and all connected luminaires
Automated or manually releaseing function test facility with logbook for status and failure information
Earth failure measurement and test facility
Control module for the program-ming, data processing and information storage, with:
4 line liquid crystal text display
free programmable via incorporatedbuttons or external key-board
various languages available
luminaire failure display with location info
luminaire function test and battery duration test cycles free programmable
manual reset on mains return selectable
delay on mains return (0 - 15 min) selectable
deep discharge protection with info
Connection possibilities to building management systems or in-house central monitoring systems
Technical data:Mains supply: 1~/N/PE, 230V AC, ± 10% or 3~/N/PE, 400V AC, ± 10%
Emergency supply: 220V DC, +10/-20%
EMC protection to EN 55081/EN 55082
Protection class : I
Protection category : IP20
Permissible ambient temperature: for system: -5 C to +35 C for battery: see datasheet
CPS 220/SVFunction, design and features
4
CPS Funk t i ons tes t Be tr i eb
U=247V I= 0 . 0A6-03 1 4 : 59 Menue
Advantages of the Joker - technology
Simple design and engineering
Reduced installation material content
Cut down on installation time Higher load level for final end circuits
Switching mode settable on each luminaire
Joker-technology - a cost saving innovation
Each INOTEC CPS emergency lighting system can be built-up to three different supply luminaire switching modes on the same output at the same time. Luminaires with Joker high frequency electronic ballast (common standard on INOTEC-SV luminaires) or Joker switch modules, for third party electronic ballast, must be used. These components allow an easy setting of the monitoring address and luminaire mode.
The patented JOKER-technology of INOTEC reduces the design- and installation time and cuts down on material cost.
The sample pictured shows the kind of installation savings which can be achieved.
Conventional systems and installations with the switching modes maintained-, non-maintained- and switched maintained mode, require 6 final end circuits to feed 9 luminaires in a part of the building shown.
The Joker-technology reduces the number of circuits required. Our sample needs only 2 final end circuits to feed the same number of luminaires due to the fact that the operation of all switching modes on one circuit is possible.
The maintained and switched maintained luminaires are active during mains presence. During mains failure, however, all luminaries, regardless of their operation mode, will be switched on and supplied by the central battery system.
German Patentnumber:DE 19807844
European Patentnumber:EP 0939476
CPS 220/SVAdvantages and function of Joker-technology
5
Maintained Non-maintained Switched maintained
Joker technology with 2 final end circuits
Circuit 1 Circuit 2
Conventional installationrequires 6 final end circuits
Circuit 3 Circuit4Circuit 1
Circuit 5
Circuit 6
Circuit 2
orInoLan
CPS 220/SVInstallation sample
MainsMonitoring
General lighting
General lighting
6
Em-light SystemsOperation Button
Button
Button
StatusData line
Safe manutautom
Functiontest:Durationtest:
Seminar room
System address Systemtype
Location
Luminaire locationWorkshop, mid-section
Toile
Work
Sale
Kitchen Toilett-men, gf
Status
Luminaire statusBattery status
Zurück
Selection
512 04.04.01 13:13 1 1 Operation
513 04.04.01 13:13 1 1 Operation
514 04.04.01 13:14 1 1 Sub.-dist. failure
515 04.04.01 16:25 1 1 Operation
516 04.04.01 16:26 1 1 Sub.-dist. failure
517 04.04.01 16:28 1 1 Funktiontest o.k.
518 04.04.01 09:16 1 1 DT interrupted
FunktiontestDurationtestCharge failureTransmission failureManual resetDischarge protection
Einträge insgesamt 520 Einträg
No. Date Time Address System Event
OpFailFailBloISOSys
Em-light SystemsButtonLog book
Button
Button
StatusData line
Functiontest:Durationtest:
Selection
Lager
Em-light Systems
Workshop
Women
Men
Seminar room
Engineering Sekrt. MD
Sales dept.
Kitchen
OfficeButton
Button
Button
Button
StatusData line
Functiontest:Durationtest:
Back
Help
Selection
Layout
Em-light Systems
Operation
Operation
Operation
Button
Button
Button
Button
StatusData line
Seminar room
Seminar room
System 3
Functiontest:Durationtest:
Functions
Select
Data line
SVPC - Softwaremax. 8x32 systems
RTGinterface
230V 50/60HZ
Com-Port
Fai lureSystemfai l . : Luminaire fa i lure
Ubatt=246,0 Vol t , Ibatt=+0,0 Amp.
INOTEC StandardSVPC- Software
INOWEBEthernet- or Internet connection
Other monitoring options (i.e. TCP/IP, LON, KOM-module) on request
Complex installations with a multiple of systems should be supervised from a cen-tral location. Wether the INOTEC own RTG-BUS, an existing network or the internet is used for this purpose depends on the specific individual project requirements.
DB
U<DPÜ
S+ S-
L1
L2
L3
N
PE
DB
U<DPÜ
S+ S-
L1
L2
L3
N
PE
InoLan
T
INOTECTxD
RS
232
GND
+24V
990 063RxD
R
rese
tR
TG
G/
InoLan
T
INOTECTxD
RS
232
GND
+24V
990 063RxD
R
rese
tR
TG
G/
or
192.100.100.103 First floor Failure Systemfail.inoweb.ense.inotec-licht.de First floor Functiontest Systemfail.192.100.100.39 Main Hotel bui ld ing Operation Systemfail.
Netz
Netz
Ladeteil 220V / 7,5A
Ein
Batterie
10AT
CPS 220
TEST
+
-UH
5AT
SU / SV - J 2x3A
Si 5AT
Si 5AT
Störung
BLEin
DLEin
Störung
BLEin
DLEin
SU / SV - 2x3A
Si 5AT
Si 5AT
Si 5AT
Si 5AT
Ein
Störung
Ein
Störung
SU / SKÜ - 2x3A
Si 5AT
Si 5AT
Si 5AT
Si 5AT
Ein
Störung
Ein
Störung
SU / SKÜ- J 2x3A
Si 5AT
Si 5AT
Störung
BLEin
DLEin
Störung
BLEin
DLEin
SU / SV - 2x3A
Si 5AT
Si 5AT
Si 5AT
Si 5AT
Ein
Störung
Ein
Störung
SU / SKÜ- J 2x3A
Si 5AT
Si 5AT
Störung
BLEin
DLEin
Störung
BLEin
DLEin
SU / SV - 1x6A
Si 10AT
Si 10AT
Ein
Störung
SU / SKÜ - 1x6A
Si 10AT
Si 10AT
Ein
Störung
SU / SV - J 2x3A
Si 5AT
Si 5AT
Störung
BLEin
DLEin
Störung
BLEin
DLEin
SU / SV - 2x3A
Si 5AT
Si 5AT
Si 5AT
Si 5AT
Ein
Störung
Ein
Störung
SU / SKÜ - 2x3A
Si 5AT
Si 5AT
Si 5AT
Si 5AT
Ein
Störung
Ein
Störung
SU / SKÜ- J 2x3A
Si 5AT
Si 5AT
Störung
BLEin
DLEin
Störung
BLEin
DLEin
SU / SV - 2x3A
Si 5AT
Si 5AT
Si 5AT
Si 5AT
Ein
Störung
Ein
Störung
SU / SKÜ- J 2x3A
Si 5AT
Si 5AT
Störung
BLEin
DLEin
Störung
BLEin
DLEin
SU / SV - 1x6A
Si 10AT
Si 10AT
Ein
Störung
SU / SKÜ - 1x6A
Si 10AT
Si 10AT
Ein
Störung
098
1
3456
72
CPS 220
TEST
+
-UH
5AT
SU / SV - J 2x3A
Si 5AT
Si 5AT
Störung
BLEin
DLEin
Störung
BLEin
DLEin
SU / SV - 2x3A
Si 5AT
Si 5AT
Si 5AT
Si 5AT
Ein
Störung
Ein
Störung
SU / SKÜ - 2x3A
Si 5AT
Si 5AT
Si 5AT
Si 5AT
Ein
Störung
Ein
Störung
SU / SKÜ- J 2x3A
Si 5AT
Si 5AT
Störung
BLEin
DLEin
Störung
BLEin
DLEin
SU / SV - 2x3A
Si 5AT
Si 5AT
Si 5AT
Si 5AT
Ein
Störung
Ein
Störung
SU / SKÜ- J 2x3A
Si 5AT
Si 5AT
Störung
BLEin
DLEin
Störung
BLEin
DLEin
SU / SV - 1x6A
Si 10AT
Si 10AT
Ein
Störung
SU / SKÜ - 1x6A
Si 10AT
Si 10AT
Ein
Störung
098
1
3456
72
Betrieb
SV-ZENTRALE01.07.95 12:00
Funktionstest 2.7.95 8:30
Betrieb
Batt.-Betrieb
Störung
Ladestörung
Key-board
Drucker Cetronics
INOTEC
Betrieb
SV-ZENTRALE01.07.95 12:00
Funktionstest 2.7.95 8:30
Betrieb
Batt.-Betrieb
Störung
Ladestörung
R T
Key-board
Drucker Cetronics
INOTEC
R T
General lighting
General lighting
General lighting
Netz Batt.
Ein Ein EinStörung Störung Störung
Stromkreis 1 Stromkreis 2 Stromkreis 6
BUS
5AT 5AT 5AT 5AT 5AT 5AT 5AT 5AT 5AT 5AT 5AT 5AT+ -N L
INOTEC CPUSB220/6
Netz NetzS1
Adresse
INOTECUS6B
L LNSt.-Kreis1
L+N–St.-Kreis2
L+N–St.-Kreis3
L+N–St.-Kreis4
L+N–St.-Kreis5
L+N–St.-Kreis6
L+N–BUS Batt. Batt.
B B +24VN0
3
456
7
StörungEin
Stromkreis 3
Ein Störung
Stromkreis 4
Ein Störung
Stromkreis 5
Netz NetzL LN
St.-Kreis1L+N–
St.-Kreis2L+N–
St.-Kreis3L+N–
St.-Kreis4L+N–
St.-Kreis5L+N–
St.-Kreis6L+N–
IBBatt. Batt.B BN
0 1
23
456
78
9
Safety lighting Safety lightingMains
Safety luminaire (non-maintained)
Safety luminaire (switched maintained)
Emergency luminaire (maintained)
Under voltage monitoring
Battery line
Data lineMains
7
CPS 220/SVInstallation sample
Each CPS system operates with its integrated controller as a complete independent unit. This allows to link different emergency lighting panels/sub-stations together (see below). One integrated controller can handle up to 48 circuits and, in addition, stores the systems logbook.
0 1.1 / 1.2 2.1 / 2.2 3.1 / 3.21 4.1 / 4.2 5.1 / 5.2 6.1 / 6.22 7.1 / 7.2 8.1 / 8.2 9.1 / 9.23 10.1 / 10.1 11.1 / 11.2 12.1 / 12.24 13.1 / 13.2 14.1 / 14.2 15.1 / 15.25 16.1 / 16.2 17.1 / 17.2 18.1 / 18.26 19.1 / 19.2 20.1 / 20.2 21.1 / 21.27 22.1 / 22.2 23.1 / 23.2 24.1 / 24.28 keine Funktion9 keine Funktion
Adresse Stromkreis Stromkreis Stromkreis Platz 1 Platz 2 Platz 3 links mitte rechts
Adresseinstellung INOTEC Sicherheitstechnik GmbH
DB
U<DPÜ
DB
U<DPÜ
S+ S-
L1
L2
L3
N
PE
DB
U<DPÜ
S+ S-
L1
L2
L3
N
PE
S+ S-
L1
L2
L3
N
PE
DB
U<DPÜ
S+ S-
L1
L2
L3
N
PE
U<DPÜ
Monitoringlighting circuits sub db
Netz
Netz
Ladeteil 220V / 7,5A
Ein
Batterie
10AT
CPS 220
TEST
+
-UH
5AT
SU / SV - J 2x3A
Si 5AT
Si 5AT
Störung
BLEin
DLEin
Störung
BLEin
DLEin
SU / SV - 2x3A
Si 5AT
Si 5AT
Si 5AT
Si 5AT
Ein
Störung
Ein
Störung
SU / SKÜ - 2x3A
Si 5AT
Si 5AT
Si 5AT
Si 5AT
Ein
Störung
Ein
Störung
SU / SKÜ- J 2x3A
Si 5AT
Si 5AT
Störung
BLEin
DLEin
Störung
BLEin
DLEin
SU / SV - 2x3A
Si 5AT
Si 5AT
Si 5AT
Si 5AT
Ein
Störung
Ein
Störung
SU / SKÜ- J 2x3A
Si 5AT
Si 5AT
Störung
BLEin
DLEin
Störung
BLEin
DLEin
SU / SV - 1x6A
Si 10AT
Si 10AT
Ein
Störung
SU / SKÜ - 1x6A
Si 10AT
Si 10AT
Ein
Störung
098
1
3456
72
098
1
3456
72
SU / SV - J 2x3A
Si 5AT
Si 5AT
Störung
BLEin
DLEin
Störung
BLEin
DLEin
SU / SV - 2x3A
Si 5AT
Si 5AT
Si 5AT
Si 5AT
Ein
Störung
Ein
Störung
SU / SKÜ - 2x3A
Si 5AT
Si 5AT
Si 5AT
Si 5AT
Ein
Störung
Ein
Störung
SU / SKÜ- J 2x3A
Si 5AT
Si 5AT
Störung
BLEin
DLEin
Störung
BLEin
DLEin
SU / SV - 2x3A
Si 5AT
Si 5AT
Si 5AT
Si 5AT
Ein
Störung
Ein
Störung
SU / SKÜ- J 2x3A
Si 5AT
Si 5AT
Störung
BLEin
DLEin
Störung
BLEin
DLEin
SU / SV - 1x6A
Si 10AT
Si 10AT
Ein
Störung
SU / SKÜ - 1x6A
Si 10AT
Si 10AT
Ein
Störung
SU / SV - J 2x3A
Si 5AT
Si 5AT
Störung
BLEin
DLEin
Störung
BLEin
DLEin
SU / SV - 2x3A
Si 5AT
Si 5AT
Si 5AT
Si 5AT
Ein
Störung
Ein
Störung
SU / SKÜ - 2x3A
Si 5AT
Si 5AT
Si 5AT
Si 5AT
Ein
Störung
Ein
Störung
SU / SKÜ- J 2x3A
Si 5AT
Si 5AT
Störung
BLEin
DLEin
Störung
BLEin
DLEin
SU / SV - 2x3A
Si 5AT
Si 5AT
Si 5AT
Si 5AT
Ein
Störung
Ein
Störung
SU / SKÜ- J 2x3A
Si 5AT
Si 5AT
Störung
BLEin
DLEin
Störung
BLEin
DLEin
SU / SV - 1x6A
Si 10AT
Si 10AT
Ein
Störung
SU / SKÜ - 1x6A
Si 10AT
Si 10AT
Ein
Störung
SU / SV - J 2x3A
Si 5AT
Si 5AT
Störung
BLEin
DLEin
Störung
BLEin
DLEin
SU / SV - 2x3A
Si 5AT
Si 5AT
Si 5AT
Si 5AT
Ein
Störung
Ein
Störung
SU / SKÜ - 2x3A
Si 5AT
Si 5AT
Si 5AT
Si 5AT
Ein
Störung
Ein
Störung
SU / SKÜ- J 2x3A
Si 5AT
Si 5AT
Störung
BLEin
DLEin
Störung
BLEin
DLEin
SU / SV - 2x3A
Si 5AT
Si 5AT
Si 5AT
Si 5AT
Ein
Störung
Ein
Störung
SU / SKÜ- J 2x3A
Si 5AT
Si 5AT
Störung
BLEin
DLEin
Störung
BLEin
DLEin
SU / SV - 1x6A
Si 10AT
Si 10AT
Ein
Störung
SU / SKÜ - 1x6A
Si 10AT
Si 10AT
Ein
Störung
Betrieb
SV-ZENTRALE01.07.95 12:00
Funktionstest 2.7.95 8:30
Betrieb
Batt.-Betrieb
Störung
Ladestörung
Key-board
Drucker Cetronics
INOTEC
Betrieb
SV-ZENTRALE01.07.95 12:00
Funktionstest 2.7.95 8:30
Betrieb
Batt.-Betrieb
Störung
Ladestörung
Key-board
Drucker Cetronics
INOTEC 990013
BIF
+
+
+ +
+
+24V
24V
24V BUS
BUS
BUS
extern
R T R T
8
CPS 220/SVSystem components and options
CPS control module
Microprocessor controlled free programmable module with internal/external BUS, 4 line liquid crystal display, CENTRONICS interface for external printer connection, keyboard connection port, logbook, LED status indicators, push buttons for programming and detailed status-/failure interrogation, blocking function for the complete system or the mains lighting.Electronically monitored 24V loop for voltage monitoring of any number of lighting sub-distribution boards.
Accessible display information:
· All available status information for the completeCPS-System
· Fault information for every circuit or individualluminaire with location text-info
· Achieved battery duration (in minutes) during the last endurance test
· Available battery capacity· Logbook entries
Programming possibilities:
· SV-monitoring functions- Single luminaire / lamp monitoring- Circuit monitoring
· Panel address· Date / time for function test· Date / time for duration test· Manual reset· Stairwell light switching· Time delay on mains return 1-15 min· Earth leakage monitor with test facility· Deep discharge protection · Log-book
LED-display for:
· Operation (mains healthy - green)· Battery operation (mains failed or test during
mains healthy - yellow)· General failure (red)· Charge failure (red)
Circuit module max. load Joker technology Fuse Order numberJ-SU/SKÜ 2x3A 2x 3A yes 5AT/250V, 6,3x32 919011SU/SKÜ 2x3A 2x 3A no 5AT/250V, 6,3x32 919001SU/SKÜ 1x6A 1x 6A no 10AT/250V, 6,3x32 919000
Circuit module max. load Joker technology Fuse Order numberJ-SU/SV 2x3A 2x 3A yes 5AT/250V, 6,3x32 929006SU/SV 2x3A 2x 3A no 5AT/250V, 6,3x32 929001SU/SV 1x6A 1x 6A no 10AT/250V, 6,3x32 929000
Individual lamp monitoring
Circuit monitoring
Change-over devices
· 19"-slide-in modules, double pole fused,for individual circuit(s)
· Circuit- (SKÜ) or individual lamp monitoring (SV)
· JOKER function optional
· No data line required for monitoring
· LEDs in the front plate to indicate fault / healthystatus and circuit switching mode
· completely wired to 3-tier terminals 4mm²,with isolating neutral
Charger 220 V/3,0 A and 220 V/7,5 A
For all available 216V lead-acid accumulators
· Service-friendly 19'' - housing
· Modern, microprocessor controlled design - high efficiency- low weight
· Battery charge- and discharge current informationis permanently available at the CPS controller
· Constant charger- and battery circuitmonitoring with fault display at the CPS controller in case of
- blown battery fuse- missing or defect battery block- faulty charger - open battery circuit- battery voltage to high / low
· Temperature controlled charging to ensure longer battery life
9
CPS 220/SVSystem components and options
TLS 1Staircase light switching module, 1 channel
· 19''- slide-in module · each CPS rack can accommodate one TLS 1
Details see TLS 5
TLS 5 Staircase light switching module, 5 channels
The TLS 5 module allows to utilise the same push button for the control of mains- and safety-/exit luminaires. The emergency function of a certain circuit or circuits is only given, for a preset time, after pushing a button. The modules 5 channels are galvanic separated and have terminals for the push button connection and the volt free contact.
Via the TLS 5 all glow-wire indication lamps with the push buttons are energised. Max. 20 (each 0,8mA) or 10 (each with 1,5mA) push buttons-indicator lamps can be connected to the respective terminals (1/1 - 5/5). Maximum cable length for the push-button line is 500m. Each potential free contact for mains lighting can be used up to 3A, 230V, 50/60 Hz.
The emergency luminaires are supplied via the allocated change-over devices of the CPS-system. This is programmable in the control module of the CPS.
· Free programmable push-button / emergencycircuit(s) allocation
· 1-15 min. run time for emergency
· Illuminated push buttons during all material times
Battery 220V
Internal wiring
each channelmax. 20 illuminatedpush buttons,0,8mA glow lampormax. 10 illuminatedpush buttons,1,5mA glow lamp
Lengh of the cable to the push buttonsmax. 500m
Each contact- max. switching load 3A at 230V 50/60Hz
BUS-connection
further pushbuttons
further luminaires
L N
further push buttons
L N N L
10
CPS 220/SVSystem components and options
System status Operation Sum- Battery failure operationFailure 1-2 close open closeOperation 3-4 close open openBattery open open closeoperation 5-6Option 1 selectableOption 2 selectable
Rel
ay c
on
tact
s
RIF 5
Function:Interface for remote status indication and system blocking function.· Free programmable, in connection to a switch, for
- maintained and non maintained emergencylight ON/OFF
- maintained emergency light ON/OFF
· With or without loop monitoring· 5 voltfree contacts for
- operation- battery operation- failure (general)- failure (battery-/ charge circuit))- free programmable
· Battery sensor for temperature controlledcharging, if required
· With phase monitor (sub-db or main-db), single phase
Contacts: 24V / 1AEMC protected to EN 55015Dimension: H = 59, W = 71.5, D = 90 (mm)
internal wiring
Temp. sensor
24VMonitoring loop
24V DCmax.100mA
single phase supply monitor
battery voltage
Remote switch
Volt free contacts
INOPRINT
available at the parallel port of a CPS-system can
be stored as a text file on INOPRINT.
Via PC / USB-interface the information can be
stored and printed.
850 009
11
CPS 220/SVSystem components and options
LSA 8.1 INV with DPÜ/BUSLight switch monitor, 8 channels, inverted
For the switching (on/off ) of safety luminaires along with the mains lighting and for the selective activation of emergency light circuits at partial mains failures.Each channel is galvanic separated.Up to two channels can be allocated by software to every individual, or a number of, CPS-change-over-device (output circuit). This switch/channel allocation happens during the set-up/ commissioning and is programmable on the CPS control module.
Three-phase-monitor, DPÜ/BUS- free selectable phase connections- 1 change-over contact- monitoring low voltage and mains failure- for single-phase monitoring too- voltage 230V AC, 400V AC- threshold 0,85 x UN- deactivation switch
Failure info at the CPS-controller with location
Supply voltage:Available in 230V AC 50/60 Hz or 24V DCEMC protected to EN 55015Dimension: H = 59, W = 71,5, D = 90(mm)
LSA 8.1 with DPÜ/BUSLight switch monitor, 8 channels
For the common switching (on/off ) of safety luminaires along with the mains lighting and for phase monitoring.
Each channel is galvanic separated. Up to two channels can be allocated by software to every individual, or a number of CPS-change-over-device (output circuit). This switch/channel allocation happens during the set-up/ commissioning and is programmable on the CPS control module.
Three-phase-monitor, DPÜ/BUS- free selectable phase connections- 1 change-over contact- monitoring low voltage and mains failure- for single-phase monitoring too- voltage 230V AC, 400V AC- threshold 0,85 x UN- deactivation switch
Failure info at the CPS-controller with location
Supply voltage:Available in 230V AC 50/60 Hz or 24V DCEMC protected to EN 55015Dimension: H = 59, W = 71,5, D = 90(mm)
A failing general lighting circuit or lighting sub-db triggers only the necessary safety lighting circuit for this area.
L1L2L3NPE
Sub-db 2
U<
L1NPE
Sub-db
General lighting
General lighting
850 008
LSA 8.1 INV
12
CPS 220/SVSystem components and options
01
23
45 6
78
9
01
23
45 6
78
9
gem. VDE 0108
EMC: gem. EN 55015ta: -15 bis 40°C
INOTEC
DPÜ / B.1890 414
L3L2L1
N L1 L2 L3
Kontakte (1 / 2) + (3 / 4)öffnen bei Netzausfall
Adresse1 bis 31
Ein
erZe
hner
+24V43
BUS1 2 T T
01
23
45 6
78
9
01
23
45 6
78
9
gem. VDE 0108
EMC: gem. EN 55015ta: -15 bis 40°C
INOTEC
DPÜ / B.1890 414
L3L2L1
N L1 L2 L3
Kontakte (1 / 2) + (3 / 4)öffnen bei Netzausfall
Adresse1 bis 31
Ein
erZe
hner
+24V43
BUS1 2 T T
01
23
45 6
78
9
01
23
45 6
78
9
gem. VDE 0108
EMC: gem. EN 55015ta: -15 bis 40°C
INOTEC
DPÜ / B.1890 414
L3L2L1
N L1 L2 L3
Kontakte (1 / 2) + (3 / 4)öffnen bei Netzausfall
Adresse1 bis 31
Ein
erZe
hner
+24V43
BUS1 2 T T
L1L2L3NPE
L1L2L3NPE
Address setting is mandatoryfor full functionality
Wire link on last DPÜ/B.1mandatory
L1L2L3NPE
DB 1 DB 2 DB ...
DPÜ Three Phase Monitor
To detect phase- or circuit failures in general lighting sub-distribution panelsWith volt-free failure indication contact
· LED-indication for L1, L2, L3· free selectable phase connections· 1 change-over contact· monitoring low voltage and mains failure in three-phase networks· for single-phase monitoring too acc. to IEC 255· for DIN rail mounting
For the connection to INOTEC central- and group supply battery systems.
Voltage: 230V/400V AC 50/60 Hz
Threshold 0,85 x UN
Perm. temp.: -20°C ... +60°C
EMC protected to 55015
Dimension: H =58, W = 17,5, D = 90(mm)
DPÜ/B.1Three Phase Monitor with BUS, addressable
To detect phase- or circuit failures in general lighting sub-distribution panels. With location info at CPS-controller of monitored sub-distribution panel in case of phase failure.With volt-free failure indication contact.
· LED-indication for L1, L2, L3· free selectable phase connections· 2 x n/o contacts· monitoring low voltage and mains failure in three -phase networks· for single-phase monitoring too acc. to IEC 255· for DIN rail mounting· Detailed phase failure with location info of the sub db at CPS controller
For the connection to INOTEC central- and group supply battery systems.
Voltage: 230V/400V AC 50/60 Hz
Threshold 0,85 x UN
Perm. temp.: -15°C ... +40°C
EMC protected to 55015
Dimension: H = 58, W = 36, D = 90(mm)
FS+SL+SL -
L
FS -
+-
SL
N
HV
Stromschleife
FS
Hauptverteiler
Fernschalter
Batt.
SLÜINOTEC
890 415
HV
SL+
RIF5 oder SLÜ KlemmleisteRIF5 or SLÜ terminal rail
+24V IB
850 009
13
CPS 220/SVLuminaire monitoring and supply modules
N-ET 20-70W
Luminaire module for he supply of low-voltage halogen lamps 20 - 70W.
For the connection to INOTEC central- and group supply battery systems.
Input voltage:230V AC 50/60 Hz220V DC ±20 %Output voltage: 11,5V DC
Output current: 150-490 mA
Perm. temp.: 0°C ... +65°C
EMC protected to EN 55015
Dimension: H = 31, W = 42, D = 102(mm)
J-ET 9/24 SV
Constant current luminaire module for the supply and monitoring of LEDs.
Light output in mains adjustable.
With easy accessible address-switch and JOKER function, switch to select maintained or non-maintained mode and individual light source failure detection
For the connection to INOTEC central- and group supply battery systems.
Input voltage:230V AC 50/60 Hz220V DC ±20 %
Output voltage: 24V DC
Output current: 320 mA constant
Perm. temp.: -15°C ... +50°C
EMC protected to EN 55015
Dimension: H = 28, W = 40, D = 90(mm)
102
3142
86
14
CPS 220/SVLuminaire monitoring and supply modules
EVG 4-6EVG 4-13.1EVG 18
J-EVG 4-6/SV-SJ-EVG 4-13/SV-SJ-EVG 18/SV-S
J-EVG 4-6/SVJ-EVG 4-13/SVJ-EVG 18/SVJ-Modul/SJ-SV Modul/SJ-ET 9/24 SV
J-SV-Modul.L/S
404
9080
330
404
9080
328
40
4
9080
320
4,2
235,4 4,2
17,9 7240,4
26,4
249,4
EVG 4-6 EVG 4-13.1 EVG 18 Compensated high frequency electronic ballast
for fluorescent and compact fluorescent lamps TL/TC/TCD-EL 4-18 W.EVG 4-6 designed for low power loss at 4 Watt. Automatic deactivation of electronics in case of lamp failure.Suitable for emergency lighting systems to EN 50171 / EN 50172.Designed to be installed inside of luminaires. For the connection to INOTEC low power- or central power battery systems like ELS or CPS.
Voltage:230V AC 50/60 Hz220V DC ±20 %
Perm. temp.: -15°C ... +50°CEMC protected to EN 55015
J-EVG 4-6 SVJ-EVG 4-13 SVJ-EVG 18 SVCompensated high frequency electronic ballast
for fluorescent and compact fluorescent lamps TL/TC/TCD-EL 4-18 W, with easy accessible address switch, JOKER function and individual lamp monitoring. The JOKER function allows luminaries to be operated in maintained and non-maintained mode on the same final end circuit. Automatic deactivation of electronics in case of lamp failure.Suitable for emergency lighting systems to EN 50171 / EN 50172.Designed to be installed inside of luminaires.For the connection to INOTEC low power- or central power battery systems like ELS or CPS.
Voltage:230V AC 50/60 Hz220V DC ±20 %
Perm. temp.: -15°C ... +50°CEMC protected to EN 55015
J-SV-Modul.L/SLSNS
N-L+
N-
L+
J-SV Modul.L/S
CircuitCPS 220 J/SV
Inpu
t
Out
Fluorescent lamps withhigh frequency electronic ballaststandard bulbs or halogen lamps
Fluorescent lamps withhigh frequency electronic ballaststandard bulbs or halogen lamps
Light switch
General lighting
PENL
N-N-
L+L+
J-SV-Modul/SJ-SV-Modul.2/SJ-SV-Modul.3/SJ-SV-Modul.4/S
LSNS
N-L+
J-EVG4-6/SV-SJ-EVG 4-13/SV-SJ-EVG 18/SV-S
34
12
N-N-
L+L+
LSNS
15
CPS 220/SVLuminaire monitoring and supply modules
Circuit monitoring
Component Type Joker technology Load Sense-input Order numberEVG 4-6 EVG no 4-6W no 860007EVG 4-13 EVG no 4-13W no 860003EVG 18 EVG no 18W no 861002J-Modul/S Module yes max. 600W yes 851018
J-EVG 4-6 SV/SJ-EVG 4-13 SV/SJ-EVG 18 SV/SCompensated high frequency electronic ballast
for fluorescent and compact fluorescent lamps TL/TC/TCD-EL 4-18 W, with easy accessible address switch, JOKER function and individual lamp monitoring. This electronic ballast features a sense-input or an inverted phase monitor too.J-EVG 4-6 SV designed for low power loss at 4 Watt.The JOKER/S function allows luminaires to be operated in maintained, non-maintained and switched mode on the same final end circuit. Automatic deactivation of electronics in case of lamp failure.Suitable for emergency lighting systems to EN 50171 / EN 50172.Designed to be installed inside of luminaires. For the connection to INOTEC low power- or central power battery systems like ELS or CPS.
Voltage:230V AC 50/60 Hz220V DC ±20 %
Perm. temp.: -15°C ... +50°CEMC protected to EN 55015
J-SV-Modul/SJ-SV-Modul.2/SJ-SV-Modul.3/SJ-SV-Modul.4/SJ-SV-Modul.L/SSingle luminaire monitoring module
for fluorescent- (T16/T5…) compact fluorescent,halogen and incandescent lamps. With easy accessible address switch, JOKER function and individual lamp monitoring. This module features a sense-input or an inverted phase monitor too.The JOKER/S function allows luminaries to be operated via these J-SV-modules in maintained, non-maintained and switched mode on the same final end circuit.
Suitable for emergency lighting systems to EN 50171 / EN 50172.Designed to be installed inside of luminaries. For the connection to INOTEC low power- or central power battery systems like ELS or CPS.
Voltage:230 V AC, 50/60 Hz220 V DC, ±20 %
Perm. temp.: -15°C ... +50°CEMC protected to EN 55015
Individual lamp monitoringComponent Type Joker technology Load Sense-input Treshhold Order numberJ-EVG 4-6 SV EVG yes 4-6W no 860008J-EVG 4-13 SV EVG yes 4-13W no 860004J-EVG 18 SV EVG yes 18W no 861003J-EVG 4-6 SV/S EVG yes 4-6W yes 860010J-EVG 4-13 SV/S EVG yes 4-13W yes 860005J-EVG 18 SV/S EVG yes 18W yes 861004 Failure O.k SV Modul.1 Module no 5-120W no < 10mA > 20mA 851001SV Modul.2 Module no 20-300W no < 45mA > 70mA 851003J-SV Modul/S Module yes 5-120W yes < 10mA > 20mA 851002J-SV Modul.2/S Module yes 20-300W yes < 45mA > 70mA 851004J-SV Modul.3/S Module yes 2-30W yes < 8mA > 12mA 851025J-SV Modul.4/S Module yes 18-120W yes < 45mA > 70mA 851029J-SV Modul.L/S Module yes 5-120W yes < 10mA > 20mA 851026
43
74
90 58
Betrieb
Notlicht
INOTEC
Ein
Aus
Batt.-BetriebStörung
90 58
Betrieb
Notlicht
INOTEC
Ein
Aus
Batt.-BetriebStörung
16
CPS 220/SVExternal supervision and display
RTG interface
Interface between PC-serial port and internal INOTEC RTG-BUS. The SVPC-software is required to view all relevant data of CPS -systems on a standard PC.
Displayed:· Yellow LED - SVPC recieves data· Greene LED - SVPC transmitt data
Technical data:1 m power cord 230V with Euro-plug INOTEC RTG cable (1m)Socket for serial port (1m cable)
Voltage: UN = 230V +/-10%Mode: Permanent operationTemp.-range: -15°C ... +40°CProtection: IP20 Housing: Thermoplast
EMC protection to EN 55015
SVPC-software
The INOTEC-SVPC-software is used to central supervise and programme up to 32 central battery-, group battery- or self-contained battery systems. For standard and mixed installations with CPS 220-, CPUS 220-, LPS24-, ELS/SV and BNS 32/59.
Status- and failure information of luminaires, batteries and other system components are monitored, stored and displayed. Luminaire failures and localisation can be individually identified / verified due to free destination text programming. A resulting printout can help during the repair process.
System requirements:Operating system: Windows 2000 / XPScreen: VGA (640 x 480), 256 colours and aboveHard disc capacity: min. 50 MBInterface: serial port
MTBThe MTB-remote mimic panel (MTB/AP = wall mounting, MTB/UP = recessed wall-/panel mounting) are used for external status- and failure indication of emergency lighting systems. Furthermore it allows to block the system via the integrated key-switch.
Functions:Key-switch free programmable for:· maintained and non maintained light ON / OFF· maintained light ON / OFF
Displayed:· Green LED - operation· Yellow LED - battery operation· Red LED - failure (battery / luminaire)
Connection to RIF-module of CPS-system; max cable length with 0,8mm² 500m
Voltage: UN= 24V DC +/-10%Mode: Permanent operationTemp.-range: -15°C ... +40°CProtection: IP20 MTB/UP; IP 30 MTB/APHousing: Stainless steel/polycarbonate
EMC protection to EN 55015
Wall mounting:
Recessed wall mounting:
90
45
48 58
36
17
CPS 220/SVExternal supervision and display
InoWeb-module
To display all relevant data of CPS -systems as a HTML-page via standard-web-browser (Explorer, Mozilla, Opera…..) on an existing Ethernet. An IP-address can be programmed or allocated via a DHCP-server.
Function indication and technical data: seeInoLan.
InoWeb-control-softwareThe InoWeb control software can be installed on a standard PC with Ethernet access. This software will start automatically and run in the background once the PC is started. A small icon in the taskbar shows the current status of the entire system. By double clicking on the icon in the taskbar you open the main screen of the software.
Features:· Set time for function test and start test· Set time for battery duration test (endurance
test) and start test· Logbook function for all connected systems· Automatic sending of e-mails after test or
failure found
System requirements: Operating system: Win 98/2000/XP/Vista Ultimate/Vista Business/Vista EnterpriseScreen: VGA (800x600), 256 colours and aboveHard disc capacity: min. 200 MB (without log book 25MB)Interface: Network interfaceNetwork protocol: Ethernet (IEEE 802.3), TCP/IP v4, HTTPSoftware: MS Internet Explorer Version min. 6.0.2800.1106
InoLan-module
Interface between Ethernet and internal INOTEC RTG-BUS. The SVPC-software is required to view all relevant data of CPS -systems via an existing Ethernet on a standard PC.
Displayed:Yellow LED - Ethernet connected Green LED - Network active
Connection possibilities:· Ethernet RJ45 port· INOTEC RTG BUS-terminals· RS 232 terminals or DB9-port
Voltage: UN= 24V DC +/-10%Load: 1,7 VAMode: Permanent operationTemp.-range: -15°C bis +40°CProtection: IP20 (terminals); IP40 (housing)Housing: Thermoplast, for DIN rail mountingSwitch "Reset" for configurationSwitch RS 232 / RTG
EMC protection to EN 55015
HUBEthernet
InoWebControl
CPS CPS CPS
InoLan
T
INOTECTxD
RS
232
GND
+24V
990 063RxD
R
rese
tR
TG
G/
InoLan
T
INOTECTxD
RS
232
GND
+24V
990 063RxD
R
rese
tR
TG
G/
InoLan
T
INOTECTxD
RS
232
GND
+24V
990 063RxD
R
rese
tR
TG
G/
InoWeb InoWeb InoWeb
CPS 220/SVTechnical data, systems overview
1030
mm
1200
mm
800 mm
830
mm
1200
mm
800 mm
830
mm
1200
mm
800 mm
800
mm
1000
mm
600 mm
18
TEST
+
-UH
5AT
Betrieb
Batt.-Betrieb
Störung
Ladestörung
Key-board
Drucker Cetronics
INOTEC
TEST
+
-UH
5AT
Betrieb
Batt.-Betrieb
Störung
Ladestörung
Key-board
Drucker Cetronics
INOTEC
TEST
+
-UH
5AT
Betrieb
Batt.-Betrieb
Störung
Ladestörung
Key-board
Drucker Cetronics
INOTEC
TEST
+
-UH
5AT
Betrieb
Batt.-Betrieb
Störung
Ladestörung
Key-board
Drucker Cetronics
INOTEC
Technical data: CPS 220 / 48 CPS 220 / 32 CPS 220 / 16 CPS 220 / 11 / SC Rated voltage: 1~N/PE, 230V AC 10%, 50/60Hz 3~N/PE, 400V AC 10%, 50/60Hz Protection class: I Protection category: IP20
Perm. ambient temperature for system: - 5°C bis + 35°C for battery: see battery data sheet Battery voltage: 220V DC Charger: 3Amp or 7,5Amp Housing color: RAL 7035Plinth (optional) 100mm or 200mmCable inlet from top Free module slots 24 16 8 11 (2 x 3A or 1 x 6A) Space for options *2 14 TE 19 TE 25 TE 12 TE - with function preservation - - 13 TE 12 TE Supply 3-phase (option) yes yes yes -
Max. installed battery capacity 70 Ah 70 Ah 70 Ah 27,8 Ah Conductor cross section, max. (mm²)Mains supply 35 35 35 16 Battery supply 35 35 35 35 Outgoing to luminaires 4 4 4 4 Outgoing data line (RTG) 4 4 4 4 Outgoing 24V monitoring 4 4 4 4 Outgoing mains to CPUS 35 35 35 - Outgoing battery to CPUS 35 35 35 - Dimensions H x W x D (mm) 2230 x 800 x 400 2030 x 800 x 400 2030 x 800 x 400 1800 x 600 x 300 with function preservation (option) - BRS 10 *1 BRS 10 *1 BRS 10 *1 - with function preservation - 2460 x 1200 x 595 2460 x1200 x 595 2460 x 1200 x 595 Cable inlets 22 x M 20 22 x M 20 22 x M 20 4 x M 32 64 x M 25 64 x M 25 64 x M 25 33 x M 25 6 x M 32 6 x M 32 6 x M 32 10 x M 20 2 x M 50 2 x M 50 2 x M 50
1TE 2TE 3TE 4TE 5TE 6TE 7 TEJ-Modul S/U Fuse protection Battery supply RIF 5 LSA 8.1 INV 24V TLS 5 for sub-station (Neozed) incl. 4 terminalsDSM/U1 INOLAN LSA 8.1 INOWEB SKW DPÜ DPÜ/B1 PSU 24 Fuse protection Battery NH00 (as a replacement for Neozed) (CPS 5/11) TLS 1 + terminal PSU 48 Terminal - requirement for Terminals for mains supply 3-phase sub-station at CPS 16/32/48 Mains supply terminals for sub-station - 3-phase
Required space for options
Depth400 mm
Depth400 mm
Depth400 mm
Depth300 mm
19
CPS 220/SVTechnical data, systems overview
600
mm
1000
mm
600 mm
600
mm
600
mm
600 mm
830
mm
800 mm
830
mm
800 mm
600
mm
600 mm
CPS 220 / 5 / SC CPS 220 / 5 / SC CPUS 220 / 48 CPUS 220 / 32 CPUS 220 / 16
5 5 24 16 8 15 TE 15 TE 11 TE 16 TE 22 TE 15 TE - - 3 TE 9 TE - - yes - - 27,8 Ah 12 Ah - - -
16 16 35 35 35 35 35 35 35 35 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 - - - - - - - - - - 1600 x 600 x 300 1200 x 600 x 300 830 x 800 x 400 830 x 800 x 400 600 x 600 x 300 BRS 10 BRS 10 BRS 08 BRS 08 BRS 082460 x 1200 x 595 2460 x 1200 x 595 1374 x 624 x 334 1374 x 624 x 334 1374 x 624 x 334 4 x M 40 4 x M 40 22 x M 20 22 x M 20 4 x M 40 33 x M 25 33 x M 25 64 x M 25 64 x M 25 33 x M 25 10 x M 20 10 x M 20 6 x M 32 6 x M 32 10 x M 20 2 x M 50 2 x M 50
*1 max. 55Ah*2 Standard: mains 1ph., 24V-monitoring loop, ext.-dataline, terminals for outgoing circuits, battery fuse (Neozed) Attention: take care of the max. cable inlet number!!!
TEST
+
-UH
5AT
Betrieb
Batt.-Betrieb
Störung
Ladestörung
Key-board
Drucker Cetronics
INOTEC
TEST
+
-UH
5AT
Betrieb
Batt.-Betrieb
Störung
Ladestörung
Key-board
Drucker Cetronics
INOTEC
TEST
+
-UH
5AT
Betrieb
Batt.-Betrieb
Störung
Ladestörung
Key-board
Drucker Cetronics
INOTEC
TEST
+
-UH
5AT
Betrieb
Batt.-Betrieb
Störung
Ladestörung
Key-board
Drucker Cetronics
INOTEC
TEST
+
-UH
5AT
Betrieb
Batt.-Betrieb
Störung
Ladestörung
Key-board
Drucker Cetronics
INOTEC
Depth300 mm
Depth300 mm
Depth400 mm
Depth400 mm
Depth300 mm
CPS 220/SVTechnical data, systems overview
600
mm
400 mm
874
mm
500
mm
624 mm
574
mm
500
mm
624 mm
335
mm
380 mm
800
mm
1200
mm
200
800 mm 800 mm 800 mm 800 mm
20
Technical data: CPUSB 220 / 6 CPUSB 220 / 6 CPUSB 220 / 6 CPUSB 220 / 6 Wall mounting enclosure F30 wall mounting F30 recessed mounting for panel mounting
Rated voltage: 1~/N/PE, 230V AC 10%, 50/60Hz Protection class: I Protection category: IP54 optional for electronics compartment Perm. ambient temperaturefor system: -5°C bis +35°C Housing color: RAL 7035 Cable inlet from top
Number of circuits 3A CPUSB 220 / SKÜ 2 / 4 / 6 2 / 4 / 6 2 / 4 / 6 2 / 4 / 6 CPUSB 220 / SV 2 / 4 / 6 2 / 4 / 6 2 / 4 / 6 2 / 4 / 6 CPUSB 220 / J / SV or J / SKÜ 2 / 4 / 6 2 / 4 / 6 2 / 4 / 6 2 / 4 / 6 Conductor sizes(mm²): Mains supply 10 10 10 10Battery supply 10 10 10 10Outgoing to luminaires 4 4 4 4Outgoing data line (RTG) 4 4 4 4 Dimensions H x W x D (mm) 600 x 400 x 150 1374 x 624x 334 1074 x 624 x 334 335 x 380 x 65 Cable inlets 4 x M 32 2 x d=36mm 4 x d=29mm - 13 x M 25 16 x d=21mm 13 x d=21mm -
*1 fixed number of circuits
Technical data:
Rated voltage: 1~/N/ PE, 230V AC 10%, 50/60Hz 3~/N/PE, 400V AC 10%, 50/60Hz
Protection class: I Protection category: IP20 for battery compartmentIP54 for electronicsPerm. ambient temperaturefor system: -5 C to +35 C for battery: see datasheetBattery: 220V DC, max. 182AhCharger: 2 x 7,5A
Color: RAL 7035Plinth (optional) 100mm or 200mmCable inlet from topDimensions H x W x D (mm)2030 x 3200 x 4002130 / 2230 x 3200 x 400 (optional)
Custom built, sample design
Depth65 mm
Depth334 mm
Depth334 mm
Depth150mm
Netz
Netz
Ladeteil 220V / 7,5A
Ein
Batterie
10AT
CPS 220
TEST
+
-UH
5AT
Netz
Netz
Ladeteil 220V / 7,5A
Ein
Batterie
10AT
098
1
3456
72
098
1
3456
72
SU / SV - J 2x3A
Si 5AT
Si 5AT
Störung
BLEin
DLEin
Störung
BLEin
DLEin
SU / SV - 2x3A
Si 5AT
Si 5AT
Si 5AT
Si 5AT
Ein
Störung
Ein
Störung
SU / SKÜ - 2x3A
Si 5AT
Si 5AT
Si 5AT
Si 5AT
Ein
Störung
Ein
Störung
SU / SKÜ- J 2x3A
Si 5AT
Si 5AT
Störung
BLEin
DLEin
Störung
BLEin
DLEin
SU / SV - 2x3A
Si 5AT
Si 5AT
Si 5AT
Si 5AT
Ein
Störung
Ein
Störung
SU / SKÜ- J 2x3A
Si 5AT
Si 5AT
Störung
BLEin
DLEin
Störung
BLEin
DLEin
SU / SV - 1x6A
Si 10AT
Si 10AT
Ein
Störung
SU / SKÜ - 1x6A
Si 10AT
Si 10AT
Ein
Störung
SU / SV - J 2x3A
Si 5AT
Si 5AT
Störung
BLEin
DLEin
Störung
BLEin
DLEin
SU / SV - 2x3A
Si 5AT
Si 5AT
Si 5AT
Si 5AT
Ein
Störung
Ein
Störung
SU / SKÜ - 2x3A
Si 5AT
Si 5AT
Si 5AT
Si 5AT
Ein
Störung
Ein
Störung
SU / SKÜ- J 2x3A
Si 5AT
Si 5AT
Störung
BLEin
DLEin
Störung
BLEin
DLEin
SU / SV - 2x3A
Si 5AT
Si 5AT
Si 5AT
Si 5AT
Ein
Störung
Ein
Störung
SU / SKÜ- J 2x3A
Si 5AT
Si 5AT
Störung
BLEin
DLEin
Störung
BLEin
DLEin
SU / SV - 1x6A
Si 10AT
Si 10AT
Ein
Störung
SU / SKÜ - 1x6A
Si 10AT
Si 10AT
Ein
Störung
SU / SV - J 2x3A
Si 5AT
Si 5AT
Störung
BLEin
DLEin
Störung
BLEin
DLEin
SU / SV - 2x3A
Si 5AT
Si 5AT
Si 5AT
Si 5AT
Ein
Störung
Ein
Störung
SU / SKÜ - 2x3A
Si 5AT
Si 5AT
Si 5AT
Si 5AT
Ein
Störung
Ein
Störung
SU / SKÜ- J 2x3A
Si 5AT
Si 5AT
Störung
BLEin
DLEin
Störung
BLEin
DLEin
SU / SV - 2x3A
Si 5AT
Si 5AT
Si 5AT
Si 5AT
Ein
Störung
Ein
Störung
SU / SKÜ- J 2x3A
Si 5AT
Si 5AT
Störung
BLEin
DLEin
Störung
BLEin
DLEin
SU / SV - 1x6A
Si 10AT
Si 10AT
Ein
Störung
SU / SKÜ - 1x6A
Si 10AT
Si 10AT
Ein
Störung
Betrieb
SV-ZENTRALE01.07.95 12:00
Funktionstest 2.7.95 8:30
Betrieb
Batt.-Betrieb
Störung
Ladestörung
Key-board
Drucker Cetronics
INOTEC
INOTEC 990013
BIF
+
+
+ +
+
+24V
24V
24V BUS
BUS
BUS
extern
Depth400 mm
Depth400 mm
Depth400 mm
Depth400 mm
CPS 220/SVDesigning a CPS-system
The dimensioning of a CPS-central battery system can be achieved with the given table contents and the below described way in a fast and easy way. Step 1 - Select number and type of luminairesThe positioning of the required luminaires on a given project drawings has given us the number of safety- and Exit-luminaires. The Exit luminaire types have been selected out of the INOTEC range (see table A / sample); for the safety luminaire we do supply 200 electronic ballasts type J-EVG 4-13W for 13W TC-DEL. Step 2 - Calculate battery current Table 1 gives IBat per luminaire which allows us to calculate the total required battery current; 14,08A in our sample. Step 3 - Define circuits and change over devicesAs we do not want to have more than 10 luminaires on every circuit we can define the total number required (36). But want to have the possibility to mix maintained and non-maintained on the same output and therefore use J-SU/SV 2x3A change-over modules. Step 4 - Select batteryThe building type and local standards define the required emergency duration (1h, 2h, 3h or 8h). With this in mind and the calculated IBat total we select the battery required. Considering specific project requirements (spare capacity / aging effect 25%) we should at least have 14,8 + 25% = 18,8A. Table 4 shows us at the 3h column that we do require a 75,3Ah battery with Imax 19,2A. Step 5 - Select charger requiredTable 5 gives us the number and type of charger(s) required (as per EN 50171 for recharge of 80% capacity within 12hours) for the selected battery. We have to use 7,5A.
Step 6 - Mains load and back-up fusesTable 1 gives us the load for all luminaires which we put into Table B / sample. The charger selected we can now complete Table B / sample and calculate the complete mains load. The complete load gives us in table 6 the back-up fuse for the system (single phase supply). After completion of this data we are now in a position to select a CPS - system. Depending on the building limitations, installation preferences and space available we can choose (see pages 18 - 20) various system options with/without substations.
Some possibilities are: - One CPS 220 SV/48 with 7.5A charger, 36 circuits 3A (18 modules J-SU/SV 2x3A) and 75,3Ah battery compartment
- One CPS 220 SV/32 with 7.5A charger, 26 circuits 3A (13 modules J-SU/SV 2x3A) and 75,3Ah battery compartment plus one substation CPUS 220/16 with 10 circuits 3A (5 modules J-SU/SV 2x3A)
Luminaire type Qty. Load [VA] Load [kVA] mains mains over all SNP 1018 J/SV 40 8,4 0,34(8W FL)SNP 7188 J/SV 120 8,4 1,01(8W FL)J-EVG 4-13W 200 14,0 2,80für 13W TC-DELCharger 3 A - 1109 -Charger 7,5 A 1 2587 2,59Over all 6,73
Table B our example
21
Luminaire type Qty. IBat. [A] IBat. [A] Outgoing Circuit modules luminaire over all circuit 2 x 3 ASNP 1018 J/SV 40 0,033 1,32 4 2(8W FL)SNP 7188 J/SV 120 0,033 3,96 12 6(8W FL)J-EVG 4-13W 200 0,044 8,80 20 10for 13W TC-DELOver all 360 14,08 36 18
Table A our example
CPS 220/SVSystem design and tables
Battery current for lamps used for emergency / safety lights.
Table 1 Data for INOTEC high frquency ballasts during mains- and battery operation.
Table 2 Data for INOTEC LED luminaire with Power LED. (J-ET 9/24 ... SV) For specific luminaire details see luminaire catalogues.
Table 3 Data for glow wire lamps (AGL) and halogen lamps with electronic transformer.
22
Lamp Base INOTEC EVG Lamp IBat. Mains type [mA] load [VA]T 16 G5 4-6W / 4-13W 4W 20 4,2 4-6W / 4-13W 6W 25 6,3 4-13W 8W 33 8,4 4-13W 13W 44 14TC-SEL 2G7 4-13W 5W 24 5,3 4-13W 7W 26 7,4 4-13W 9W 33 10 4-13W 11W 44 12TC-DEL G 24 q1 4-13W 10W 35 11 4-13W 13W 44 14 G 24 q2 18W 18W 90 19TC-TEL GX 24 q1 13W 13W 44 14 GX 24 q2 18W 18W 90 19T 26 G 13 18W 18W 90 19 36W 36W 100 / 150 37 (50% / 100% Light output)
58W 58W 140 / 235 60 (50% / 100% Light output)
TC-F 2 G 10 18W 18W 90 19TC-L 2 G 11 18W 18W 90 19
220V Glow IBat. Halogen IBat. wire lamp [mA] lamp [mA] 7 W 30 20 W 115 15 W 70 35 W 210 25 W 110 50 W 285 40 W 180 75 W 420 60 W 270 100 W 560 75 W 340 100 W 450
Qty. LED IBat. Mains 1W [mA] load [VA] 1 12 4,8 2 18 8,3 3 25 9,8 4 32 11,1 5 40 13,2 6 45 14
23
CPS 220/SVSystem design and tables
Table 4 Battery data
*1 Battery housing included in CPS assembly*2 1 Battery housing included in CPS assembly
Table 5 Chargers and ventilationRecharging 12 hours / 80%
Table 6Fuse protection mains supply
Table 6
The specificaton are min. conductur cross-sections. For the max. permissible line drop the dimensioning of the conductor is to be made according to the distance and the connection power. (max.line drop: 3%)
C10 -1,8V/Z 3,0 A 7,5 A [m³ / h] [ cm² ] 5,0 1 0,03 0,90 8,0 1 0,04 1,20 12,0 1 0,06 1,70 18,1 1 0,10 2,80 28,7 1 0,15 4,20 33,0 1 0,18 5,10 45,4 1 0,25 7,00 50,9 1 0,27 7,60 69,2 1 0,37 10,40 74,0 1 0,40 11,20 75,3 1 0,41 11,50 81,4 1 0,44 12,40 91,8 1 0,50 14,00 91,0 1 0,49 13,80 102,1 1 0,55 15,40 134,0 1 1 0,72 20,20 153,6 1 1 0,83 23,30 205,2 2 1,11 31,10
Capacity Qty. charger Free airflow Ventilation
Capacity Weight [kg] Housing Max. discharge current [A] C10-1,8V/Z Block Total Batt. 8h 3h 1h 5,0 2,5 45,0 1*1 0,7 1,5 3,2 8,0 3,6 64,8 1*1 1,0 2,1 4,5 12,0 5,6 100,8 1*1 1,3 2,8 6,2 18,1 5,9 106,2 1*1 2,0 4,8 11,0 27,8 10,0 180,0 1*1 3,4 8,3 20,8 33,0 11,8 212,4 1*1 4,0 9,2 22,8 45,4 14,9 268,2 1*1 5,3 12,0 28,9 50,9 18,2 327,6 1*1 6,2 14,5 35,2 69,2 26,1 469,8 1*1 8,4 19,6 46,5 74,0 31,3 563,4 1*1 8,9 20,3 51,0 75,3 24,1 433,8 1*1 8,7 19,2 47,5 81,4 26,4 475,2 2*2 9,6 21,6 55,1 91,8 30,1 541,8 2*2 10,8 24,1 60,3 91,0 37,2 669,6 2*2 11,1 25,3 64,0 102,1 33,1 595,8 2*2 12,2 28,6 69,8 134,0 42,5 765,0 2*2 15,8 35,2 78,0 153,6 47,0 846,0 18,2 41,4 102,2 205,2 67,2 1209,6 24,7 58,2 143,2
Over all connection power to 8 kVA 8 - 11 kVA 11 - 14 kVA 14 - 18 kVA 18 - 22 kVAFuse protection 35A 50A 63A 80A 100AMin. conductur cross-section 6mm² 10mm² 16mm² 25mm² 35mm²
top related