2011 firestop handbook 1st september(web2)
Post on 10-Feb-2018
221 Views
Preview:
TRANSCRIPT
-
7/22/2019 2011 FireStop Handbook 1st September(Web2)
1/48
FireStop Handbook53579 2011 / 03
-
7/22/2019 2011 FireStop Handbook 1st September(Web2)
2/48
FireStoppingLegislation
Introduction
Fire Protection
Fire Prevention is a critical consideration or all those who are responsible or creating the design, speci cation andconstruction o new buildings. It also has to be considered in the ongoing maintenance o occupied premesis.
The causes o re vary and are unpredictable. O ten the cause is outside the area o infuence o design engineers and
planners. But the ability to control the spread o re once it has started can still be infuenced.
E ective re ghting within a building is generally achieved through a combination o active and passive FireStop systems.
Active FireStop SytemsActive re prevention systems are designed to react to the outbreak o a re which is then suppressed with the help osprinkler systems, halogen installations, re extinguishers or other proactive machanical systems. The e ects o the remay also be lessened by the removal o smoke rom the equation. By including alarms and emergency lighting, activesystems also serve to provide escape paths or people inside the building.
Passive Fire Prevention SytemsPassive re prevention systems are intergrated in the structure o a building ensuring that once the re starts it is limited
to a re compartment that is composed o re rated walls, foor and ceilings.
To maintain the FireStopping integrity o walls, foors and ceilings, all gaps, openings and channels are to be sealed toprevent the escape o re and smoke.
There ore the Control o Fire Spread and limitation o damage is principally achieved through the compartments o abuilding. These compartments are bounded by re resisting elements: Walls / Floors / CeilingsFire resisting elements are o ten breached to permit access or services or unctional joints. Cables / Pipes / Ventilation systemsGaps between re resisting elements around the penetrations must be sealed so that the re integrity o the re-resistingelement is maintained.
National RegulationsThe ollowing national regulations are published as statutory instruments by Parliament with respect to li e sa ety purposes:
Building Regulations (England & Wales) 1991 These regulations are expressed as unctional requirements. Approved Document B (2000 Edition) Fire Sa ety, gives non-manditory guidance.
Building Standards (Scotland) 2001 These are expressed as unctional requirements. All o the provisions o Technical Standards Part D and Part E are mandatory. These provisions are wavered only by means o a relaxation.
Building Regulations (Northern Ireland) 1994Basic unctional requirements with approval solutions are given in Technical Booklet E which is similar to England andWales Approved Document B.
Building Regulations (Republic of Ireland) 1997The building regulations in the republic o Ireland are similar in arrangement and content to the England & Wales BuildingRegulations and are covered by Technical Guidance Document B.
Q. Why does FireStopping need to be carried out?Approved Document B states the following points with regard to reinstallation of re rated elements:
I a re separating element is to be efective then every joint, or imper ection o t, or opening to allow services to pass through the element should be adequaby sealing or FireStopping so that the re resistance o the element is not impaired 11.2
This is quite categorical in its assertion that every opening in a re rated element needs to be reinstalled.
-
7/22/2019 2011 FireStop Handbook 1st September(Web2)
3/483
In addition to any other provisions in this document or FireStopping:a. Joints between re separating elements should be FireStopped andb. All openings or pipes, ducts, conduits or cables to pass through any part o a re separating element should be:i. kept as ew in number as possible andii. kept as small as practical andiii. FireStopped (which in the case o a pipe or duct should allow or thermal movement) 11.12
The nal sentence states that FireStopping materials should allow for thermal movement rules when usingsand/cement and concrete for lling round services.
Technical Standards (Scotland) state:A compartment wall and compartment foor must have no openings and must provide a barrier to re between the parts o a building to be divided including any roo space.
Except for:Where there is a service opening -
i. Which is o suitable construction or where the services are suitably protected so that in the event o a re the level o resa ety per ormance required o the compartment wall or compartment foor is maintained, andii. Which is suitably FireStopped D3.14
BS7671 further adds:Where a wiring system passes through elements o building construction such as foors, walls, roo s, ceilings, partitions or cavity barriers the openings remaining a ter passage o the wiring systems shall be sealed according to the degree o
re resistance required o the element concerned. 527-02-01where a wiring system such as conduit, cable ducting, cable trunking, busbar or busbar trunking penetrates an element o building construction having speci ed re resistance it shall be internally sealed so as to maintain the degree o re resistance o the respective element as well as being externally sealed to maintain the required re resistance. 527-02- 01
Q. Why do you have to have all your FireStop products tested?
The building Regulations Approved Document B s tates the following with regard to testing The product should be in accordance with a speci cation or design which has been shown by tests to be capable omeeting that per ormance or have been assessed rom test evidence against appropriate standards Appendix A 1A
Provide a propriety sealing system which has been shown by test to maintain re resistance o the wall, foor or cavity barrier. B3 11.6
Technical Standards (Scotland) require:The requirements o D3.14, D4.7, D5.8 and D6.7 or FireStopping o service openings and D6.9 or FireStopping will be met in the case - When di erent movement is anticipated, whether in normal use or during re exposure by the use o a proprietary sealant or sealing system which has shown by test its ability to maintain the required level o sa ety per ormance under the conditions appropriate to its end use B2.2.1
F i r e S t o p p i n g L e g i s l a t i o n
Introduction
Fire Protection Continued
-
7/22/2019 2011 FireStop Handbook 1st September(Web2)
4/48
BS 476-20:1987Fire tests on building materials and structures. Method or determination o the reresistance o elements o construction (general principles).
EN13501-3
Fire classi cation o construction products and building elements.
BS EN 1366-3: 2004Fire resistance tests or service installations - Penetration seals.BS EN 1366-4: 2006Fire resistance tests or service installations - Linear joint seals.
DIN 4102 :Part1Fire behaviour o building material and elements - Part 1: Building materials; concepts,requirements and tests.
AS 1530: Part4: 2005Australian stand - Fire resistance tests of elements of construction.
BS EN ISO 140-3: 1995BS EN ISO 717-1: 1997The laboratory measurement o airborne sound insulation o building elements.
FM Certi cateRecognised or use in local water-based re extinguisher systems (Factory MutualResearch Corporation or Property Conservation, American insurance company).
VdS Certi cateRecognised or the use in local water-based re extinguisher systems ( ormerly:
Association o Property Insurers, now: VdS Damage Prevention).
Fire-tested xingFire test classi cation or anchors up to 120 minutes.
ZulassungProo o compliance o the building product with the general building authorityapproval con rmed by a material testing acility.
ETA Option 1European Technical Approval Option 1 or cracked concrete.
ETA Option 7European Technical Approval Option 7 or non-cracked concrete.
CPDContinual Pro essional Development. Recognised as CPD accredited seminars.
ISO 9001Quality assurance on systems and processes.ISO 14001is a standard or environmental management systems.
BS EN1366-3: 2004
British Standard
BS 476-20
A p p r o v a l s
Introduction
AS
1530: Part 4: 2005
BS EN1366-4: 2006
BS EN13501-3
BS EN ISO 140-3: 1995
BS EN ISO 717-1: 1997
-
7/22/2019 2011 FireStop Handbook 1st September(Web2)
5/485
A c c r e d i t a t i o n S c h e m e s
scher have a dedicated network o approveddistributors ( scher FireStop Centres) stragicallyplaced throughout the UK, keeping stock and o eringnationwide coverage or the supply o passive FireStopproducts .
scher FireStop Centres
scher are working with a group o AccreditedInstallers in the eld o passive re protection. All othe scher installers are members o FIRAS or LPCBThird Party Accreditation Schemes. As members theyare able to o er a Certi cate o Con ormity on all workcarried out in the elds o Compartmentation, steeland Concrete Protection, Acoustics and Air Sealingcon orming to Approved Documents B, E, &L oBuilding Regulations.
scher Accredited Installers
IFC Certi cation Scheme
scher and their range o products have been approvedby the IFC Certi cation Scheme. International FireConsultants Ltd. (IFC), established in 1985, is a
multi aceted practice o re engineers with a widerange o disciplines and expertise, drawn romgovernment scienti c establishments, the re service,manu acturing industry, commercial testing laboratoriesand the construction sector. IFC was established toprovide a source o technical expertise in the eld oFire Sa ety Engineering.International Fire Consultants Ltd. are committed tothe advancement o re sa ety engineering and to thisend are heavily involved in research and developmentprojects as well as striving to standardise practicesthroughout the industry. The Installer Certi cationSchemes are designed to ensure that certi cated andtested products are installed within the approved eldo application by skilled and competent operativesthus giving con dence to speci ers, users, occupiers,owners and en orcement bodies. It involves auditing oan installer companys o ce and site based activities,competence assessment o operatives and supervisorsand certi cates o con ormity.
FIRAS Third Party Certi cation Scheme
As a requirement o the FIRAS Schemes, certi catedcompanies are required to employ, on a permanentor contract basis, competent Supervisors and
Technicians (Operators) whose technical and practicalcompetence is assessed by FIRAS Inspectors in thetrade disciplines or which certi cation scope is held.A register o competent employees is maintained oreach certi cated company, which is regularly reviewedto ensure that the company maintains a competentwork orce whose abilities remain current with theworkscope the company provides.Once certi cated, all FIRAS Registered InstallerCompanies are subject to ongoing random inspectiono their installation work on ongoing contracts alongwith an annual audit o their o ce systems by FIRASInspectors to ensure that compliance with FIRASScheme Requirements is maintained.
Introduction
-
7/22/2019 2011 FireStop Handbook 1st September(Web2)
6/48
At scher our aim is to provide the very best technical support to complementour vast range o quality products. The constant investment in Reasearch &Development has resulted in more than 7000 patents awarded to date. Thisinvestment combined with a constant exchange o in ormation betweenpro essional users, universities and technical research institutions ensuresthat scher remains at the ore ront o the very latest developments within theconstruction industry.The scher group currently lead the way in producing technically advancedproducts having gained more European Technical Approvals (ETAs) than anyother xings manu acturer.All historical developments and subsequent knowledge is available to you viaour highly trained Technical Services Team who can o er support, advice andspeci cations at all stages o the design and construction process.
TechnicalSupport scher Fixings (UK) Ltd.
Special Catalogues & Substrate Reports
The Technical Handbook provides use ul in ormation or speci cationengineers. It contains in depth in ormation relating to the range o technicallyadvanced steel and resin anchor calculation details, reduction actors, spacingsetc. Topics like anchor per ormance in re, corrosion and design methods arealso included.The Fixing Systems Catalogue provides general technical in ormation on therange o nylon, steel and resin anchors and also in ormation on special productranges sanitary, oams and sealants, sca old, insulation xings. More specialistcatalogues are available ocusing on topics such as FireStop, M&E InstallationSystems, EWI and ACT.Detailed substrate reports available indicating the per ormance o suitable
xings in speci c building materials, including manu acturers such as: Bison Knau Thermalite Tarmac Topfoor La arge Forticrete Tarmac Topblock Finlay Concrete Products Cobiax Deck Hanson
British Gypsum
Compu x Anchor Design Programme, a must or every speci cation engineer.Additional eatures: Baseplate Design Approval Details Installation Details CAD Database New post-installed rebar calculation programme
Design Software Compu x & Rebar x
COSHH data sheets available or a ull range o chemical products. Method statemants detailing installation techniques available on request.
Method Statements & COSHH Data SheetsMethod Statement for installation of
Resin fixings
(applicable for Eurobond glass capsule or injection resin systemwith RG M resin studs into solid substrates)
or
Premark the hole positions by using your fixture as a template. Drilldirectly to the substrate on centreline of premarked fixing position, using a correct drilldiameter to the required
depth. (fig 1) Thoroughly clean the hole of dust and drilldebris, using ABG blow-out pump and cleaning brushes. Blow-out Twice,
Brush Twice, Blow-out Twice. (fig 1-3) Place the cartridge in the applicator gun and discharge resin untilthe colour becomes evenly mixed. Inject the resin into the hole, starting with the nozzle at the bottom of the hole. If Eurobond system is used, simply
insert glass capsule in the hole (fig 4) Insert RG M rod. If injection resins are used, rod is inserted by hand, with pushing and twisting action. If glass
capsule is used, insertion must be done with an impact drilling machine. (fig 5) Leave resin to cure completely before applying any load. Curing time is dependant on the temperature and the
correspondent table can be found on the cartridge. Tighten the stud, not exceeding the recommended torque. (fig 6)
For correct dimensions and torque values please always refer to information on product packaging or fischer literature! If in any doubt, please callfischer helpline 01491 827 920
fig 1 fig 2 fig 3 fig 4
fig 5 fig 6
Speci cation Advisory Assistance
Calculations Method Statements Health & Sa ety Data Sheets Technical Data Sheets Full Product Support
Technical Help LinePhone: 01491 827 920Fax: 01491 827 950Email: technical@ scher.co.uk
Introduction
Fixings Systems CatalogueMMVII-1
i i n
y
t m
t l
u
1 1
Fixings Test Report for
-
7/22/2019 2011 FireStop Handbook 1st September(Web2)
7/487
T h e B u i l d i n g - F i r e S t o p i n A p p l i c a t i o n
Compartmentation Guide
scher FireStop CompoundFFSC.
scher intumescent Acoustic MasticFiAM toedges.
scher cavity FireStop CladFCFclto be placedbetween steel girder and outside acade inconjunction with multi-purpose brackets.
scher FireStop Strip / BlockFCFst.
scher coated panel systemFCPS used inconjunction withFFC2 or FFC4. Use scherIntumescent Acoustic MasticFiAMto edge.
scher quickpassFQP.
scher cable FireStopFCbSused in conjunctionwith scher Coated Panel systemFCPS.
scher Conduit IntumescentFCi in conjunctionwith scher FireStop CompoundFFSC.
1
2
3
4
10
Putty PadsFiPP.
scher Cavity FireStop ExpansionFCFex orscher intumescent Acoustic MasticFiAM.
scher FireStop CollarFFC2 or FFC4 used inconjunction with the scher concrete screwFBS6x40TZ or solid material andHM 6x37S ora board material.
scher Intumescent Pipe WrapFiPW 2oRFiPW 4with scher FireStop CompoundFFSC.
5
6
7
8
9
11
12
12
3
45
6
7
8
9
10
11
12
-
7/22/2019 2011 FireStop Handbook 1st September(Web2)
8/48
Image Description Testing BS EN IFC AS DIN Pages
ischer Intumescent Acoustic Mastic - FiAM 9
ischer Intumescent Graphite Mastic - FiGM 11
ischer Silicone Sealant - FFRS 13
ischer Intumescent Putty - FiPP 16
ischer Intumescent Pillow - FiP 17
ischer Fire Collar - FFC 19
ischer Intumescent Pipe wrap - FiPW 21
ischer FireStop Compound - FFSC 23
ischer Intumescent Fire Sleeve - FiFS 26
FireStop Block - FBB 28
FireStop oam and Ahesive - FBS 29
ischer Coated Panel System - FCPS 30
ischer Cable FireStop - FCbF 31
ischer Conduit Intumescent - FCi 32
ischer Cast in Device - FCiD 33
ischer cavity FireStop clad - FCFcl 35
ischer Ventilated Fire Barrier - FVFB 36
ischer Cavity FireStop Strip - FCFst 37
ischer Cavity FireStop Epansion - FiLS 38
FireStop Foam 39
Fxings Guide 40
acoustic testing smoke sealair seal FireStop
Contents
P a g e I n d e x
-
7/22/2019 2011 FireStop Handbook 1st September(Web2)
9/489
Joint Size Depth o Sealant Integrity Insulation Backing Type o Seal
10mm 10mm 240 mins 30 mins Backing Rod Single
15mm 10mm 240 mins 30 mins Backing Rod Single
20mm 15mm 240 mins 120 mins Backing Rod Dual
20mm 20mm 240 mins 60 mins Cavity FireStop Strip Single
30mm 15mm 240 mins 120 mins Backing Rod Dual
30mm 15mm 240 mins 60 mins Cavity FireStop Strip Single
scher Intumescent Acoustic Mastic is used to seal gaps o up to 30mm in block walls, partitions and door rames.
Remove all loose debris, oil and grease rom the joint. Mask the adjacent sur aces to the joint. Ensure that the joint is lled using an appropriate backing material or the re rating you are trying to achieve.
(See Fire Rating) Apply mastic to required depth and width.
Remove masking.
Do not apply the sealant i the ambient temperature is below 5C as adhesion will be impaired.
British Standard
BS 476-20
scher Intumescent Acoustic Mastic is a one part water based acrylicsealant.
scher Intumescent Acoustic Mastic is suitable or sealing joints and servicepenetrations in re walls, partitions, re rated door rames, glazing systemsand linear gap seals. Tested to BS476 Parts 20, scher IntumescentAcoustic Mastic provides up to 4 hours re protection and up to 40dbacoustic rating.
600ml oil cartridge or productivity savings and sustainability / reducedwaste disposal.
The mastic is ast curing approximately 20-30 minutes tack ree time. Onceully cured the mastic can be painted over.
High movement o +/- 10%.
Description
s c h e r I n t u m e s c e n t A c o u s t i c M a s t i c - F i A M
Fire Rating Approvals
Installation
Acoustic Mastic - FiAM
BS EN ISO 717-1: 1997
The laboratory measurement oairborne sound insulation o buildingelements
-
7/22/2019 2011 FireStop Handbook 1st September(Web2)
10/48
scherIntumescentAcousticMastic-FiAM Specifcations
Type Order No. Size[ml]
Qty. Per Box Suitable or use with
FiAM 310 53011 310 25 -
FiAM 600 56006 600 25 -
KP M2 Applicator gun 53117 - 1 FiAM 310
Applicator gun 600ml 97967 - 1 FiAM 600
Weighted sound reduction Index (Rw) o up to 40 db.Please consult our technical o ice or more details.
Acoustic Rating
scher Intumescent Acoustic Mastic will provide a cold smoke seal.
Smoke Seal
scher Intumescent Acoustic Mastic is available in 310ml cartridges. Onecartridge will provide the ollowing coverage rates:
Joint Size Depth o Sealant Yield Per Cartridge
10mm 10mm 3.10lin m
20mm 15mm 1.03lin m30mm 20mm 0.51lin m
Coverage
Technical Data
Density: approx. 1.60-1.65 g/cm3
Cartridge contents: 310 ml
Application temperature: +5C to +40C
Skin- orming time: approx 20-30 min.
Curing rate: approx. 2mm in 48 hours*
Volume shrinkage: approx. 20%Movement capability: +/- 10%
Temperature resistance: -25C to 80C
Shel -li e a ter production: 12 months (under recommended conditions)
* dependant on substrate, air humidity and weather conditions
Acoustic Mastic - FiAM
-
7/22/2019 2011 FireStop Handbook 1st September(Web2)
11/4811
ischer Intumescent Graphite Mastic is used to seal service penetrations in ire rated walls.
Remove all loose debris, oil and grease rom the joint. Mask the adjacent sur aces to the joint. Ensure that the joint is lled using an appropriate backing material or the re rating you are trying to achieve.
(See Fire Rating) Apply mastic to required depth and width. Remove masking. All services must be adequately supported so as not to disrupt the seal during a re. This can be achieved with
the scher Quick-Fix system which was used as part o the approval testing.
Do not apply the sealant i the ambient temperature is below 4C as adhesion will be impaired.
scher Intumescent Graphite Mastic is one part water based fexible acrylicemulsion which contains a high pressure intumescent graphite, extruded
rom a cartridge loaded into a standard sealant gun.
The scher Intumescent Graphite Mastic is suitable or sealing aroundservice penetrations which pass through re rated walls.
Tested to EN1366-3
The scher Intumescent Graphite Mastic will provide up to 4 hours integrityand 4 hours insulation.
The mastic is ast curing approx 40-60 min tack ree.
Description
s c h e r I n t u m e s c e n t G r a p h i t e M a s t i c - F i G M
Fire Rating Approvals
Installation
Service Type Depth o Sealant Integrity Insulation
Cable tray con guration 1 2 x 40mm 250mins 250mins
Cable tray con guration 2 50mm BR* sealed to edge 250mins 61mins
Up to 75mm cable bunch 2 x 40mm 250mins 250mins
Up to 32mm MDPE water pipe 2 x 40mm 250mins 250mins
Up to 50mm ABS pipe 2 x 40mm 250mins 250mins
Up to 110mm PVC waste pipe 2 x 40mm 250mins 250mins
*All application carried out into 140mm block wall with a mineral bre backing material FCP Coated Panel.
BS EN1366-3
Graphite Mastic - FiGM
-
7/22/2019 2011 FireStop Handbook 1st September(Web2)
12/48
Type Order No. Size[ml]
Qty. Per Box Suitable or use with
FiGM 310 508765 310 25 -
KP M2 Applicator gun 53117 310 1 FiGM 310
scherIntumescentGraphiteMastic-FiGM
scher Intumescent Graphite Mastic will provide a cold smoke seal.
Speci cations
Smoke Seal
Graphite Mastic - FiGM
Technical Data
Form: Readt to use thixotropic
Cure System: Water based
Colour: Dark grey
Speci c Gravity: 1.5
Extrusion Rate: 350g / min
Sag: 80%
Application Temperature Range: +4C to +30C
Service Temperature Range: -15C to +70C
Expansion Rate: In a recent test, the expansion was measured at 25 to30 original depth
Shel -li e: Up to 12 months when stored in unopened car-tridges in and cool, dry conditions. Avoid extremes otemperature
* dependant on substrate, air humidity and weather conditions
scher Intumescent Acoustic Mastic is available in 310ml cartridges. Onecartridge will provide the ollowing coverage rates:
Joint Size Depth o Sealant Yield Per Cartridge
10mm 10mm 3.10lin m
20mm 15mm 1.03lin m
30mm 20mm 0.51lin m
Coverage
-
7/22/2019 2011 FireStop Handbook 1st September(Web2)
13/4813
Description
s c h e r F i r e
R a t e d S i l i c o n e S e a l a n t - F F R S
Silicone Sealant - FFRS
Fire Rating Approvals
scher Fire Rated Silicone Sealant is a one part silicone sealant. It is suitableor sealing joints and service penetrations in re walls, partitions, re rated doorrames, glazing systems and linear gap seals.
It provides primerless adhesion to a wide range o substrates such as glass,anodised and mill- nished aluminum, steel, st.steel, rigid PVC, concrete and otherporous sur aces. Once cured, the sealant o ers superb long-term resistance to heat and re as wellas all other general weather elements.
It cross links at room temperature to give a fexible seal o low modulus whichwill withstand movement o + 25% in constant service throughout a widetemperature range.
Joint Size Depth oSealant
Integrity Insulation Backing Type o Seal
15mm 10mm 264 233 Mineral Fiber Dual
15mm 10mm 262 264 Polyethylene Single
25mm 15mm 264 138 Backing Rod Single
40mm 25mm 264 264 Mineral Fiber Dual
BS EN 1366-3
BS EN1366-4
Installation
scher FFRS Sealant is used to seal gaps o up to 40mm in block walls, partitions and door rames.
Remove all loose debris, oil and grease rom the joint. Mask the adjacent sur aces to the joint. Ensure that the joint is lled using an appropriate backing material or the re rating you are trying to achieve.
(See Fire Rating) Apply mastic to required depth and width. Smooth sur ace with a clean wet spatula to ensure maximum adhesion to substrate. Remove masking.
Do not apply the sealant i the ambient temperature is below 5C as adhesion will be impaired.
Type Order No. Size [ml] Qty. Per Box Suitable or use with
FFRS 310 512374 310 25 -
KP M2 Applicator gun 53117 - 1 FFRS 310
Speci cations
-
7/22/2019 2011 FireStop Handbook 1st September(Web2)
14/48
scherFire
RatedSiliconeSealant-FFRS Smoke Seal
Silicone Sealant - FFRS
scher FFRS Sealant will provide a cold smoke seal.
scher FFRS sealant is available in310 and 600ml cartridges. One 310ml cartridge will provide the
ollowing coverage rates (Le t).
Coverage
Technical Data
Cure System: Alcoxy
Speci c Gravity: 1.35-1.38Skinning Time: 5/10 minutes approx. (at 23oC and 50% relative humidity)
Tack Free Time: 25 min approx. (at 23oC and 50% relative humidity)
Full Cure: 2-3mm approx. per 24hrs (at 23oC and 50% relative humidity)
Shore A Hardness: 22
Extrudability g/min: 55 (standard NMRPS 495A 3mm/3 bars)
Movement accomodation: + 25%
Mechanical Properties on a 2mm thick flm (NF T 46002)
Modulus at 100% elongation: 0.37 Mpa
Elongation at break: 550%
Tensile strength: 1.5 Mpa
Mechanical Proporeties on glass slabs (EN 28339)
Modulus at 100% elongation: 0.32 Mpa
Elongation at break: 260%
Tensile strength 0.55 Mpa
Application Temp Range: +5oC to +40oC ServiceTemp Range: -50oC to +150oC Must not be stored above 35oC
Range: -50oC to +150oC Must not be stored above 35oC
Shel Li e: Up to 12 months when stored in unopened cartridges under cool, dry conditions.
Li e Expectancy: When used and applied correctly the sealant will per orm in excess o 20 years.
Chemical Resistance: The cured sealant is unafected by water, dilute acids and alkalis, soap and household detergents. Certain solvents may so ten and swell the cured rubber on prolonged contact.
Joint Size Depth o Sealant Yield Per Cartridge30mm 20mm 1.0 l/m
20mm 15mm 2.0 l/m
15mm 8mm 2.5 l/m
10mm 10mm 6.0 l/m
6mm 6mm 8.5lin m
-
7/22/2019 2011 FireStop Handbook 1st September(Web2)
15/4815
C a l c u l a t i n g M a s t i c C o n s u m p t i o n
How to calculate consumption
a = Hole Diameter in mmb = Depth o Sealant in mm (See recommendations)c = Pipe or Bunched Cables diameter in mmd = Annular space in mm (See recommendations)e = Area o hole in mm 2
= Area o pipe in mm 2
g = Amount o mastic needed per hole in mlh = Cartridge size in mln = Number o Pipe/Bunched Cable Penetrations or Linear holes to be sealed
Round Holes Square Hole Linear Hole / Sealant length
No. of cartridges needed = n x (g
)hl x w Slot width (w) =20mm
Area o hole in mm 2 = x (a 2) 2 Slot depth (j) = 10mm
Area o pipe in mm 2 = x (c 2) 2 Slot length (k) = 3 Meters
Volume o mastic per hole in ml = ((e - ) x b) 1000 Area = w x ja = 90mm l = 90 = 20 x10
b = 40mm w =100 = 200mm 2
c = 50mm
h = 310ml
n = 20
e = x (a 2) 2 e = l x w Volume = Area x k (cm 3 )
= x 45 2 = 200 x 3
= 6361.73 mm 2 = 90000mm 2 1000 = 600 cm 3
= x (c 2) 2
= x 252
As1 cm3
= 1 ml= 1963.50 mm 2 then 600 cm 3 = 600ml
= ((6361.73 - 1963.50) x 40) 1000 = ((9000 - 1963.50) x 40) 1000
= 175,929.2 1000 = 281.4601000
= 175.92 ml = 281.46ml
n x (g
)
hn x (
600)
310
= 20 x (175.92
)
310= 20 x (
281.46)
310= 20 x 1.94
= 20 x 0.56 =20 x 0.91 = 38.7
= 11.35 cartridges =18.1 cartridges = 38.7 cartridges
Calculations
-
7/22/2019 2011 FireStop Handbook 1st September(Web2)
16/48
FiPP is manu actured rom a red, non-setting, silicone based intumescentpolymer and tested in accordance with the BS EN 1366-3 or a 2 hour rerating and 2 hour insulation.
scher Intumescent Putty Pads FiPP have been developed to maintain theacoustic integrity and re resistance o plasterboard partitions, where theyare penetrated by plastic electrical socket boxes and cables. Tested to BSEN1366:3.
FiPP can also be used or upgrading the acoustic per ormance o partitionswhere electrical sockets have penetrated the wall with an acoustic ratingo 66dB.
Shown to maintain the re resistance o partitions, in both 1 and 2 hourre rated constructions.
FiPP / I
FiPP / E
Type Order No. Product Dimensions[mm]
Fire Rating[hours]
Qty. Per Box
FiPP / I-S 53578 170x170 2 20FiPP / I-D 54757 230x170 2 20
FiPP / E-S 506261 155x155 2 20
FiPP / E-D 506262 210x180 2 20
Description
Installation
Fire Rating Approvals
BS EN1366-3
FiPP are used to prevent ire penetration in plastic electrical sockets and cable bundles or speci ied periods up to2 hours. FiPP are available or internal and external use.
Internal Remove the ace plates o the
electrical socket box. Mould the pre ormed putty pads
into the back o the box andaround the cables.
Replace the ace plate.
External Mould the pre ormed putty pads
into the back o the box andaround the cables.
Speci cation
1. 2.
3. 4.
1. 2.
Intumescent Putty Pads - FiPP
scherIntumescentPuttyPads-FiPP
The FiPP has been accepted by Robust Details Ltd as an alternativemechanism o sealing the rear o electrical service penetrations, such assockets, in Robust Detail timber rame and metal rame seperating walls, aspublished in the Robust Details Part E Handbook.
Robust Details BS EN ISO 717-1: 1997
The laboratory measurement oairborne sound insulation o buildingelements
-
7/22/2019 2011 FireStop Handbook 1st September(Web2)
17/4817
Description
Estimating Quantities
Fire Rating Approvals
Installation
s c h e r I n t u m e s c e n t P i l l o w s - F I P
The Pillows are an Intumescent Graphite based product contained in awoven breglass bag. The Intumescent Pillows are simply packed tightly inbetween penetrating services and the wall. In a foor, pillows are additionallysupported by means o a mesh support system. (See diagram). Under reconditions, Intumescent Pillows expand to orm an e ective seal aroundservice penetrations.
Intumescent Pillows are suitable or use with: Metal pipework Cable trays Electrical trunking (inside and outside)
Pillows are available in our sizes and the table below outlines approximatequantities o each size to ll one m 2 area.
Pillow size (mm) Approximate Number300 x 50 x 30 660 per m2 opening
300 x 100 x 30 330 per m2 opening
300 x 150 x 30 220 per m2 opening
300 x 200 x 30 165 per m2 opening
Installation in Walls
Push the rst Intumescent Pillow into the hole to be lled, so that the longest dimension (300mm long) spansacross the wall.
Pack the pillows in a brick bond ashion, to ensure the joints between the pillows are staggered. For electrical trunking, remove the lid and install a pillow inside so it aligns with the depth o the wall. Replace
the lid on the electrical trunking. Pack the hole tightly with more Intumescent Pillows until it is ull. Ensure that the last row o pillows is tight against the edges.
T
T
F I R E S T O P
T
Intumescent Pillows will provide 4 hours re integrity and 2 hoursinsulation rating as tested in accordance with BS476 Part 20 andEN 1366-3.
Suitable or sealing PVC, cPVC, uPVC, PE, PP, MDPE, HDPE and ABS >5mm.
British Standard
BS 476-20
BS EN1366-3
Intumescent Pillows - FiP
-
7/22/2019 2011 FireStop Handbook 1st September(Web2)
18/48
scherIntumescentPillows-FIP
Installation in Floors
Make a basket using galvanised steel mesh (50 x 50 squares x 2.5mm wire diameter) to sit into the hole in thefoor slab. There should be a minimum 50mm overlap onto the surrounding foor slab or wall. Mechanically x totop o foor slab or wall.
Lay Intumescent Pillows standing on end into the wire basket. Pack the pillows tightly into the basket aroundthe penetrating services.
For electrical trunking, remove the lid and install a pillow inside so that it aligns with the depth o the foor.Replace the lid on the electrical trunking.
Lay a sheet o the galvanised steel mesh over the basket and tie together using steel wire.
Type Order No. Dimensions Qty. Per Box
FIP / S 53040 300x50x30mm 100
FIP / M 53041 300x100x30mm 50
FIP / L 53042 300x150x30mm 40
FIP / XL 53043 300x200x30mm 25
Installation
Speci cation
Intumescent Pillows - FiPP
-
7/22/2019 2011 FireStop Handbook 1st September(Web2)
19/4819
s c h e r F i r e C o l l a r - F F C
FireStop Collars consist o a powder coated steel sleeve containing a fexiblegraphite based intumescent liner manu actured to suit the pipework to beFireStopped or a 1, 2 or 4 hour re rating.
Integral toggles are opened up and the collar is simply tted around thepipe. The toggles are closed and the collar is pushed fush to the sur aceo the wall or underside o the foor: The collar is then securely astenedto the structure by means o re resistant xings threaded through xingstabs ( re rated xings pg 34-37).Any gaps o up to 10mm wide around the pipework should be lled withIntumescent Acoustic Mastic or scher Intumescent Graphite Mastic. Forgaps greater than 10mm wide FireStop Compound can be used.
Outside diameter o Pipework Fire Rating in mins
55 - 250mm 120 or 240
275 - 315mm 180
330 - 355mm 60
Installation in Walls
Make the wall around plastic pipe good with either Intumescent Acoustic Mastic, FireStop Compound orConcrete.
Undo the toggle clip on the FireStop Collar and open it out. Slide the FireStop Collar, with its xing tabs pointing towards the ace o the wall, around the plastic pipe. Lock the FireStop Collar around the pipe closing the toggle clip. Push the FireStop Collar back on to the wall. Fix the FireStop Collar to the wall by means o 32mm long, 8mm steel sel - tapping screws, through the xing
tabs. Repeat or the other side o the wall.
F I R E S T O P
F I R E S T O P
Description
Fire Rating Approvals
Installation
Suitable or sealing PVC, cPVC, uPVC, PE, PP, MDPE, HDPE and ABS > 5mm.
British StandardBS 476-20
BS EN1366-3
Fire Collar - FFC
Installation in Floors Make the foor around the plastic pipe good with either Intumescent Acoustic Mastic, FireStop Compound or
Mortar. Undo the toggle clip on the FireStop Collar and open it out. Slide the FireStop Collar, with its xing tabs pointing up towards the ace o the so t, around the plastic pipe. Lock the FireStop Collar around the pipe closing the toggle clip. Push the FireStop Collar back on to the wall. Fix the FireStop Collar to the so t by means o 32mm long, 8mm steel sel -tapping screws, through the xing
tabs.
-
7/22/2019 2011 FireStop Handbook 1st September(Web2)
20/48
Type Order No. Outside Diameter o Pipework[mm]
Fire Rating[hours]
Qty. Per Box
FFC 2 / 30-32 52456 30-32 2 32FFC 2 / 38-40 52480 38-40 2 32
FFC 2 / 55 52481 55 2 100
FFC 2 / 63 52482 63 2 50
FFC 2 / 75 52483 75 2 50
FFC 2 / 82 52486 82 2 50
FFC 2 / 90 52487 90 2 40
FFC 2 / 110 52488 110 2 40
FFC 2 / 125 52489 125 2 25
FFC 2 / 160 52500 160 2 10
FFC 2 / 200 52501 200 2 10
FFC 4 / 30-32 52502 30-32 4 32
FFC 4 / 38-40 52503 38-40 4 32
FFC 4 / 55 52532 55 4 75
FFC 4 / 63 52533 63 4 50
FFC 4 / 75 52535 75 4 50
FFC 4 / 82 52536 82 4 50
FFC 4 / 90 52537 90 4 40
FFC 4 / 110 52539 110 4 40
FFC 4 / 125 52540 125 4 25FFC 4 / 160 52545 160 4 10
Installation in Floors
Make the foor around plastic pipe good with either Intumescent Acoustic Mastic, FireStop Compound orMortar.
Undo the toggle clip on the FireStop Collar and open it out. Slide the FireStop Collar, with its xing tabs pointing up towards the ace o the so t, around the plastic pipe. Lock the FireStop Collar around the pipe closing the toggle clip. Push the FireStop Collar back on to the wall. Fix the FireStop Collar to the so t by means o 32mm long steel sel -tapping screws, through the xing tabs.
scherFireCollar-FFC Installation
Speci cation
Fire Collar - FFC
-
7/22/2019 2011 FireStop Handbook 1st September(Web2)
21/4821
s c h e r i n t u m e s c e n t P i p e W r a p - F i P W
Pipe Wraps comprise o layers o a graphite based intumescent sheetsencapsulated in a polythene sheath. The product is manu actured to bewrapped around the outside diameter o the pipework or trunking and issecured by means o a sel -adhesive strip to give a 2 hour or 4 hour rerating.The Intumescent Pipe Wrap is then positioned within the compartment wallor foor so that the edge o the product is le t exposed at the re side o thewall or so t. The Intumescent Pipe Wrap is then sealed into the structurewith FireStop Compound.Under re conditions, the Intumescent material expands against thestructure and lls the void le t by the burnt out plastic.For walls it will be necessary to t two wraps to prevent re spread respread rom either side. I the thickness o the wall is smaller than the widtho the wrap, then only 1 wrap is needed.
Outside Diamether o Pipework Fire Rating in Hours
55mm 2 or 4
82mm 2 or 4
110mm 2 or 4
160mm 2 or 4
ischer Intumescent Pipe Wraps FiPW are used to prevent ire penetration in plastic pipes which pass through wallsor loors or speci ied period up to 4 hours. They are manu actured as a sealed unit to the correct length and widthto suit the pipe diameter and ire rating.
Check that pipe sur ace is clear o mortar. Ensure that the correct pipe band is installed to suit diameter and ire rating. Wrap around pipe and ix with integral sel -adhesive strip. Slide into position ensuring that the bottom edge is exposed in a loor slab and both edges are exposed in
the wall. Two bands need to be used when the wall thickness exceeds 150mm.
Seal the pipe wrap into the structure with ischer FireStop Compound.
F I R E S T O P
Description
Fire Rating Approvals
Installation
British Standard
BS 476-20
BS EN1366-3
Pipe Wrap - FiPW
-
7/22/2019 2011 FireStop Handbook 1st September(Web2)
22/48
Type Order No. Outside Diameter o Pipework
[mm]
Fire Rating
[hours]
Qty. Per Pack
FiPW 2 / 30-32 52546 30-32 2 150
FiPW 2 / 38-40 52547 38-40 2 100
FiPW 2 / 55 52548 55 2 100
FiPW 2 / 63 52560 63 2 50
FiPW 2 / 75 52561 75 2 150
FiPW 2 / 82 52562 82 2 150
FiPW 2 / 110 52563 110 2 80
FiPW 2 / 125 52890 125 2 35
FiPW 2 / 160 52891 160 2 10
FiPW 1 / 200 53000 200 1 1
FiPW 4 / 30-32 53002 30-32 4 150FiPW 4 / 38-40 53003 38-40 4 100
FiPW 4 / 55 53004 55 4 50
FiPW 4 / 63 53005 63 4 50
FiPW 4 / 75 53006 75 4 150
FiPW 4 / 82 53007 82 4 150
FiPW 4 / 110 53008 110 4 50
FiPW 4 / 125 53009 125 4 35
FiPW 4 / 160 53010 160 4 10
scherIntumescentPipeWrap-FiPW InstallationDescription
Pipe Wrap - FiPW
-
7/22/2019 2011 FireStop Handbook 1st September(Web2)
23/4823
FireStop Compound is a specially ormulated gypsum based mortar, whichis mixed with water to be trowelled or poured around service penetrations.Tested to BS476 Part 20, FireStop Compound provides up to 6 hours reprotection.
scher FireStop Compound is used to provide a re rated seal aroundservice penetrations in re rated walls and foors.In walls, FireStop Compound is mixed into a sti consistency or trowellinginto openings. Plastic pipework must be protected with either scher FireCollars or Intumescent Pipe Wraps.FireStop Compound sets in 30-45 minutes and is capable o accommodating
oot tra c in approximately 72 hours.
Thickness o Compound Fire Rating
75mm Up to 2 hours
100mm Up to 6 hours
ischer FireStop Compound is used to seal service penetration openings against the spread o ire. When used inloor openings it is capable o taking light oot tra ic e.g. For maintenance purposes.
Remove all loose material rom opening o ire barrier. Fit shuttering or temporary plywood or similar material like FCPS. Add the Compound to clean water, and mix either by hand or with a power mixer. Keep dry and protect bag rom impact damage. Clean all tools and equipment immediately a ter use with water.
T
T
T
T
T
T
T
T
F I R E S T O P
Description
Installation
ApprovalsFire Rating
British Standard
BS 476-20 s c h e r F i r e S t o p C o m p o u n d F F S C
Floor Openings Pouring: Mix compound with water in 2.5:1 parts by volume. Do not mix weaker than 2:1. Set the shuttering into the opening ensuring a tight it so that once the required depth o Compound
is installed it inishes lush with the loor slab/screed unless otherwise speci ied. Mix and pour Compound until the required thickness is achieved. Rein orcing requires 12mm dia. bars placed at a maximum o 200mm centres across the short span only. The
bars may be either recessed into the surrounding structure by a minimum o 50mm on both sides or supportedon an angle securely ixed to the structure, all positioned approximately 30mm above the bottom sur ace othe compound to ensure adequate ire protection rom below. Existing compound installations can be easilydrilled or sawn to allow the provision o additional or replacement servises, and subsequently re-sealed.Recommended minimum clearance between services and surrounding strucutre - 50mm or hal the diameter,
which ever is greater.
Compound - FFSC
BS EN ISO 717-1: 1997
The laboratory measurement oairborne sound insulation o buildingelements
-
7/22/2019 2011 FireStop Handbook 1st September(Web2)
24/48
Wall Openings Trowelling: 1 bag o Compound to 7 litres water (3:1). (Guide only. Varies with site conditions). Trowel the Compound, starting at the base o the opening ensuring the correct thickness o material is
installed. Work progressively towards the top o the opening until the barrier is complete. I shuttering panel isset at the centre repeat process on other side.
Mechanical:
Compressive Strength: (MPA) 8 (80kg/cm 2 )
Sur ace Hardness: Cyl/diam 20 (MPA) 8 (Load 4kn)
Cyl/diam 20 (MPA) 13 (Load 15kn)
Thermal:
Speci c Heat at 20 oC (j/kg oC) 575 (0.14kcal/kg oC)
at 1000o
C (j/kgo
C) 986 (0.14kcal/kgo
C)at 20 oC (W/M oC) 0.19 (0.22kcal/kg oC)
at 100 oC (W/M oC) 0.19 (0.22kcal/kg oC)
at 500 oC (W/M oC) 0.17 (0.22kcal/kg oC)
Maximum Working Temperature:FireCombustion (according to ISO 1182 and NT Fire 001) Non-combustible:Corrosive Fumes NoneToxicity Nil
PhysicalDensity (Speci ic Gravity) (g/cm 3 ) 0.8-0.9Expansion during curing 1.1(No explosive e ect) -Curing Time (Hardneing) 1-3 days
ChemicalResistance to: Water Good
Mineral/Oil/Petrol/Solvents GoodAcids Good
Halogen content (trace elements):
Chlorine, Flourides, Bromine Negligible (les than 38 ppm)Ageing No known e ect o age
MiscellaneousColour BeigeBonding to: Concrete 1.0 (10kg/cm 2 )
Steel 0.35 (3.5kg/cm 2 )Blast resistance: (Bar) 7
Air & Gas permeability coe icient (10-14m 2 ) 3.5 as concreteSound Insulation very good 10cm / 50dB
Compound - FFSC
scherFireStopCompoundFFSC
Principal Characteristics
-
7/22/2019 2011 FireStop Handbook 1st September(Web2)
25/4825
Type Order No. Weight[KG]
Qty. Per Box
FFSC / 22Kg 53012 22 1
Thickness o Compound Weighted Sound Reduction Index (Rw)
75mm 39db
100mm 46db
150mm 51db
Thickness o Compound Number o Bags/m2
75mm 3.15
100mm 4.2
150mm 6.5
These are approximate calculations based on 22kgbags. The coverage does not take into account the
percentage o the hole lled with services.
Thickness o Compound Load Bearing Area Free o Services
75mm 500 x 500mm*
100mm 750 x 750mm*
The open area ree o services: thickness o seal ratios or non-rein orced seals given above, allow an amplesa ety margin or normal oot tra c; e.g loads o two men plus equipment with a combined wight up to 200kg.
* As a urther sa ety margin, we would recommend that all foor seals with clear areas o greater than 750mm x750mm must be rein orced.
Speci cations
Acoustic Coverage
Load Bearing
s c h e r F i r e S t o p C o m p o u n d F F S C
Compound - FFSC
-
7/22/2019 2011 FireStop Handbook 1st September(Web2)
26/48
British Standard
BS 476-20
scherInsulatedFireSleeves-FiFS
scher Insulated Fire Sleeves are a unique combination o Mineral Wooland Intumescent Graphite that provide all the bene ts o Mineral Woolsthermal, noise and re bene ts with an added intumescent e ect.
For insulated pipes it is normally necessary to remove the insulation atpoint o penetration to enable standard pipe collars to close plastic pipes.This removal o insulation results in condensation on cold pipes and loss othermal per ormance on hot pipes.
scher Insulated Fire Sleeves avoids this problem by providing bothFireStopping and thermal insulation.
scher Insulated Fire Sleeves are intended or use on Copper, Mild Steel,Polypropylene and PVC pipes and can provide , 1 and 2 hour reresistance.
Pipe Description - Dia 2Hour Batt
2 HourBrickwork
2 hourPlasterboard
2 HourSolid Floor
Steel 22-165mm X X X
Copper 12-160mm X X X
Polypropylene 12-28mm X X X X
PPVC 55-160mm X X X X
scher Insulated Fire Sleeves are supplied 300mm long and are simply cut to the desired length. The sleeve mustully cover the part o the pipe that is located within the depth o the compartment wall or foor. The sleeve may
be fush tting or may protrude rom the wall/foor by 25mm (typ.) to acilitate sealing o the outer oil acing ontoadjacent insulation.All joints to be taped with sel -adhesive oil tape, including the joints where the Insulated re sleeve butts to existinginsulation.No specialist tools or ancillary materials are required or the tting o scherinsulated Fire Sleeves.
scher insulated Fire Sleeves can accommodate irregularities in the annular gap between the wall and the pipe O.D.up to 15mm.Multiple pipe penetrations can be accommodated in conjunction with scher Coated Panel System.
Description
Installation
ApprovalsFire Rating
Insulated Sleeve - FiFS
Type Order No. Dimensions[mm]
Qty. Per Box
FiFS / 17 53051 300mm x 80mm 6
FiFS / 21 53052 300mm x 80mm 6
FiFS / 27 53130 300mm x 83mm 6
FiFS / 34 53171 300mm x 85mm 6
FiFS / 42 53172 300mm x 100mm 6
FiFS / 48 53174 300mm x 107mm 6
FiFS / 54 53175 300mm x 113mm 6
FiFS / 60 53176 300mm x 120mm 6
Speci cations
BS EN ISO 717-1: 1997
The laboratory measurement oairborne sound insulation o buildingelements
-
7/22/2019 2011 FireStop Handbook 1st September(Web2)
27/4827
The use o scher Insulated Fire Sleeves can considerablyreduce the noise emission rom noisy pipework.
scher Insulated Fire Sleeves are used to FireStop pipework operating at temperatures between 0C and180C. At low temperatures, care should be taken tomaintain the vapour barrier.
scher Insulated Fire Sleeves are compatible with mostmaterials with which it is likely to come into contact innormal building and industrial applications.Precautions should be taken when insulating austenitic
stainless steel, regardless o insulation type.
scher Insulated Fire Sleeves o er no sustenance tovermin and does not encourage the growth o ungi,moulds or bacteria.
Type Order No. Dimensions[mm]
Qty. Per Box
FiFS / 67 53177 300mm x 128mm 6
FiFS / 76 53181 300mm x 133mm 6FiFS / 80 53186 300mm x 140mm 6
FiFS / 89 53190 300mm x 145mm 6
FiFS / 108 53195 300mm x 158mm 6
FiFS / 114 53230 300mm x 160mm 6
FiFS / 140 53231 300mm x 195mm 6
FiFS / 169 53232 300mm x 225mm 6
Speci cations
s c h e r I n s u l a t e d F i r e S l e e v e s - F i F S
Acoustics Service Temperature
Compatibility Biological
Insulated Sleeve - FiFS
-
7/22/2019 2011 FireStop Handbook 1st September(Web2)
28/48
FireStop Blocks made rom 2-component special polyurethane oam.Highly elastic moulded parts (similar to oam with high density).Normal fammability according to DIN 4102 B2, density 225 kg/m 2 ,
oams in case o ire; Z-19.11-1808.
FireStop Blocks are placed in running bond in the component opening oritted around installations and can be cut using a kni e.
Quick, easy removable FireStop solution.
Max. degree o use o the seal 60 %. The installation o the seal is to be carried out according to the approvals Z-19.15 -1826 & 1827. According to the approval, retro tting o the system is only permitted with scher products. I the wall thickness < the required seal thickness, a rein orc ing strip must be built (materials:
glass-rein orced plastic, bre-plastic boards, or calcium silicate boards).
The FireStop Blocks should be installed according to the requirement and along the joints. Seals in the ceiling must be secured against breaking out using encing or grating.
FireStopBlock-FBB
Type Order No. Dimensions Qty. Per BoxFBB 45986 230 x 130 x 60mm 10
Cable bulkhead according to DIN 4102, part 9 inwalls S90/S120 and ceilings S90; Z-19.15 -1826and Z-19.15 - 1827.
F I R E S T O P
F I R E S T P
F I R E S T P
F I R E S T O P
T
T
T
T
T
T
T
T
F I R E S T O P
T
Description
FireStop Block - FBB
Approvals
Installation
Speci cation
-
7/22/2019 2011 FireStop Handbook 1st September(Web2)
29/4829
Max. degree o use o the seal 60%. The installation o the seal is to be carried out according to the approval Z-19.15-1829. According to the approval, retro tting o the system is only permitted with scher products. I the ceiling thickness < the required seal thickness, a rein orcing strip must be built (see installation data). When building up the rein orcing strip, FireStop adhesive should be used as joint adhesive. We recommend that you attach ormwork on the underside or ceiling seals. Use FireStop adhesive to completely coat the embrasure in light partition walls with embrasures made o sheet
steel sections.
F i r e S t o p G r a p h i t e F o a m - F B S
Type Order No. Contents Qty. Per Box
FBS 0.5 45987 180g 12
Applicator Gun 503115 1 1
FBS 0.5 503114 45oz 1
F I R E S T O P
F I R E S T O P
F I R E S T P
F I R E S T P
F I R E S T P
F I R E S T P
F I R E S T O P
scher FireStop Graphite Foam is an innovative two-componentpolyurethane expanding re seal. O ering ast FireStop solutions or smallto medium applications. Normal fammability according to DIN 4102 B2,P-3169/784/07-MPA BS. Yield is dependant on application temperature(cartridge contents yield 650 ml at 18C; up to 1000 ml at 23C).
FireStop Graphite Foam - FBS
Description
Approvals
Installation
Speci cation
British Standard
BS 476-20
Cable bulkhead S90 according to DIN 4102, part9, in ceilings and walls; Z-19.15-1829.
-
7/22/2019 2011 FireStop Handbook 1st September(Web2)
30/48
Coated Panel System - FCPS
scher Coated Panel System consists o a 50mm thick mineral breboardcoated both sides with a white ablative coating, 1mm thick.
scher Coated Panel System is used to FireStop mechanical and electricalservices where they pass through re rated walls and foors. Tested toBS476 Parts 20 and 22, scher Coated Panel System provides up to 4hours re protection.
scher Coated Panel System comprises three elements: scher Coated Panel (FCPS) scher Intumescent Acoustic Sealant (FiAM) scher Panel Coating (FPC)
Construction Tested Panel Con guration Fire Rating Integrity Fire Rating Insulation
Block Wall 1 x 50mm 4 hours 1 hourBlock Wall 2 x 50mm 4 hours 2 hour
Concrete Floor 1 x 50mm 4 hours 1 hour
Concrete Floor 2 x 50mm 4 hours 2 hour
Plasterboard Partition 2 x 50mm 1 hours 30 mins
F I E
F I E
F I E
F I E
F I E
F I E
F I E
F I E
The Coated Panels are simply cut and riction itted between the services and the edges o the structure. FiAM orFiGM is then used to seal the joints and it is coated with FPC. * The ire rated coating is used as an adhesive to bondsections o panel together into a barrier and to the surrounding structure. All joints in the barrier are pointed in withintumescent Acoustic Sealant to orm a monolithic layer.*(Plastic pipework needs to be sleeved with ischer Fire Collars prior to installation o the coated panel system.)
In loor applications, ischer Coated Panel has to be protected rom physical damage by oot tra ic (e.g. with aply board or chequer plate plat orm).For large loor openings we would advise using ischer FireStop Compound, or walls, openings (unsupported) max1200 x 600mm. Re er to ischer FireStop specialist or larger openings.
ischer Coated Panel System can be used as a double board system or enchanced acoustic and insulation ratings.
fscherCoatedPanelSystem -FCPS Description
Approvals
Installation
Fire Rating
British Standard
BS 476-20
Weighted sound reduction Index(Rw) of up to 52db. Pleaseconsult our sales office withdetails of: Wall construction Acoustic rating required
fischer Coated Panel System willprovide a smoke seal aroundservices penetrating throughcompartment walls and floors.
Acoustic Smoke Seal Fibre Migration
fischer Coated Panel System willnot allow fibre migration as allexposed edges of mineral fibreare encapsulated with an acrylicbased polymer.
Type Order No. Contents Qty. Per Box
FCPS / 50 53252 1200 x 600 x 50 1
FPC / 5lt 53253 5 litres 1
FiAM 310 53011 310 ml 25
Speci cation
BS EN ISO 717-1: 1997
The laboratory measurement oairborne sound insulation o buildingelements
-
7/22/2019 2011 FireStop Handbook 1st September(Web2)
31/4831
scher Cable FireStop is a compressible re retardant oam which islaminated both sides with a graphite based intumescent polymer. scherCable FireStop is supplied in sections measuring 60mm wide x 25mm thickx 1m long.
scher Cable FireStop has been developed to e ectively seal cable bunchesin electrical trunking and cable trays where they pass through re rated wallsand foors. Tested to BS476 Part 20, scher Cable FireStop will provide upto 4 hours re protection.
Service Penetration Fire Rating
Cable Tray 4 hoursElectrical Trunking 4 hours
scher Cable FireStop will give up to 4 hours re rating with cable bunches, electrical trunking and cable trayswhere they pass through compartment walls and foors.
Remove all loose debris rom around the tray. Cut scher Cable FireStop along its length to ll the width o tray to be lled. Compress scher Cable FireStop immediately under (i neccessary) and on top o cable runs. Add urther layers o scher Cable FireStop untill tray is ull. Create a good seal around cable tray with scher Coated Panel System or FireStop Compound.
Installation in electrical Trunking. Unscrew lid o trunking. Cut length to ll the width o the trunking to be lled. Compress scher Cable FireStop into the bottom o the trunking. Lay Cable runs over the scher Cable FireStop. Add urther layers o scher Cable FireStop untill the trunking is lled. Replace lid o trunking.
f
s c h e r
C a
b l e F i r e
S t o p - F
C b F
Type Order No. Dimensions[mm]
Qty. Per Box
FCbF 53015 60 x 30 x 1000 35
Cable FireStop - FCbF
Description
Approvals
Installation
Fire Rating
Speci cations
British Standard
BS 476-20
-
7/22/2019 2011 FireStop Handbook 1st September(Web2)
32/48
British Standard
BS 476-20
Conduit Intumescent - FCi
Description
Approvals
Installation
Fire Rating
Speci cations
scher Conduit Intumescent is designed to provide a FireStop cablemanagement system or passing electrical and telecommunications cablesthrough re rated walls and foors. Tested to BS 476 and EN1366:3 theproduct has achieved up to 4 hours re rating.
scher Conduit Intumescent (FCi) allows electrical contractors to partiallyor completely ll the product or install and leave it empty ready or uturecable installation.
Percentage Cable Fill Plasterboard Partition100mm Wide
Masonry Wall Concrete Floor
100% 120 mins 120 mins 240 mins
50% 120 mins 120 mins 240 mins
0% 120 mins 120 mins 240 mins
Drill a hole in plasterboard, masonry or concrete to suit the outside diameter o the conduit. For masonry andconcrete substrates, cut the ischer Conduit Intumescent (FCi) to suit the thickness o the wall/ loor and simplypush through the hole. For plasterboard applications, cut the ischer Conduit Intumescent (FCi) leaving 12.5mmo the Conduit exposed on both sides o the wall.
ischer Conduit Intumescent (FCi) can then be linked with standard couplings to ordinary electrical conduit.
For a cold smoke seal, apply ischer Intumescent Acoustic Mastic (FiAM) into the Conduit to a depth o 10mm.
scherConduitIntumescent-FCi
Type Order No. Outside Diameter
[mm]
Internal Diameter
[mm]
Wall Thickness
[mm]
Qty. Per Box
FCi / 20 53016 20 16 2 1
FCi / 25 53017 25 21 2 1
FCi / 32 53019 32 26 3 1
BS EN1366-3
-
7/22/2019 2011 FireStop Handbook 1st September(Web2)
33/4833
FCID is a cast-in-place device designed or plastic pipe applications in solidand other concrete foor assemblies.
The plastic astening fange and extension sleeve are designed to be ruggedenough to withstand the orce o a concrete pour yet lightweight enough topermit easy placement and handling.
It has been tested with various uPVC and HDPE pipes achieving a reresistance o up to 4 hours in accordance with BS 476.20 : 1987 & BS476.22 : 1987.is 250mm high which is suitable or most RC slabs. Where slabs are lessthick the the FCID can be cut fush to size and resealed using scher FCID-CP caps.
For Podium / Trans er slabs over 250mm thick the scher FCID-E/1000Fibreboard Extension Sleeves & FCID-E/C Extension Caps should be usedto extend the devices as required.
Position the Cast-In Device on the ormwork. Nail the Cast-in Device into position through the holes provided. Donot skew the nails. Pour concrete to required depth. A ter orm work has been stripped and the pipe is ready to beplaced into position, knock out the cap rom the top o the collar and insert the pipe through the collar.
It should be noted that i the pipe is pushed in rom the top, the rubber seal will be orced downwards. Li t the pipeslightly to ensure that the rubber seal projects upwards.
f s c
h e r
C a s t - I n
D e v
i c e - F
C I D
Cast-In Device - FCID
Description
Approvals
Installation
British Standard
BS 476-20
Production: Quick installation, with only 4 nails required to x. No timber boxes to orm & less waste. Sealed cap helps provides water tightness at earlier stage.Health & Safety: No power or power tools required Reduction in HAV Exposure. Reduction in number o trip hazards. Reduction in working at height. Less bending and cropping o heavy rebar.Financial: No urther collars or wraps required - Savings! One operation instead o 3-4 = Big savings over traditional methods.Innovation: Greater tolerances mean less risk o misalignment when setting out. NEW Hi-Vis Colour to reduce risk o trips & alls. Easily extended with NEW FCID-E/1000 Extension Sleeves. Increased base opening allows or connections within the device.
System Advantages
1 2 3 4 5 6
AS1530: Part 4: 2005
-
7/22/2019 2011 FireStop Handbook 1st September(Web2)
34/48
Type Order No. Pipe Dia. (Inches) Height x Dia (mm) Base Width x Depth (mm) Fire Rating (hours) Qty. Pe
FCID 65 509532 3 250 x 95 154 x 154 4 1
FCID 100 506324 4 250 x 140 198 x 198 4 1
FCID 150 509533 6 250 x 194 253 x 253 4 1
FCID 65-E/1000 509791 3 1000 x 95 N/A N/A 1
FCID100-E/1000 509792 4 1000 x140 N/A N/A 1
FCID150-E/1000 509793 6 1000 x194 N/A N/A 1
FCID 65 E/C 511450 3 19 x 95 N/A N/A 1
FCID100E/C 509794 4 25 x140 N/A N/A 1
FCID150E/C 511451 6 25 x194 N/A N/A 1
FCID 65-CP 510878 3 19 x 92 N/A N/A 1
FCID100-CP 510879 4 25 x136 N/A N/A 1FCID150-CP 510880 6 25 x194 N/A N/A 1
Suitable or uPVC and HDPE pipes. Provides a smoke and water seal.
Speci cations
Slab less than 250mm thick
Prior to installation this proceedure must be approved by a H&S Advisor.Secure the Cast-In Device on ormwork. Pour concrete to required depth, leavingFCID protruding.
Where a fush nish is required, prior to installing FCID, cut device to suit requiredslab depth & reseal with scher FCID-CP, as indicated right, then ollow installationproceedure as previous.
Podium/Transfer Slabs Greater Than 250mm ThickSet out & secure Cast-In Device on ormwork, as per previous instruction steps 1 2, then remove cap. Calculate Extension Sleeve length using Cutting Guide andcut to size using a ne toothed saw. Slide Extension Sleeve over FCID until it isstopped by tops o ribs and seal o with FCID-E/C Extension Cap. Pour concreteto required depth, lling cap i fush nish is required. Remove Extension Capwhen pipe is ready to be installed.
FCID extension sleeveand FCID-E/C cap
FCID and FCID-CP cap
fscherCast-InDevice-FCID
Cast-In Device - FCID
-
7/22/2019 2011 FireStop Handbook 1st September(Web2)
35/4835
Cavity FireStop Clad - FCFcl
FCFcl are manu actured rom a high density, low phenolic binder content, rockbre. FCFcl is supplied in one metre lengths to suit the size o the cavity to belled. The depth o the product is dependant on the re rating required. (Seere rating).
FCFcl provides FireStopping between edge o a foor slab and curtain walling/cladding system, or within a cavity wall construction. Tested to BS476 Part 20,FCFcl gives up to 2 hours re protection in cavities o up to 600mm wide ttedvertically and horizontally.For cavities in excess o 100mm wide, FCFcl multi purpose brackets must be
tted to provide additional support.It is recommended that a xing rail is positioned as close as possible to the cavitybarrier to restrict movement/expansion o the cladding or curtain walling.
Cavity Size Fire Integrity Rating Fire Insulation Rating Depth o Product
10 - 100 120 minutes 30 minutes 80mm
101 - 1000 120 minutes 30 minutes 100mm
Keep material dry and protect rom impact damage. Ensure correct width is installed to suit the required Fire Rating.
Horizontal FireStop Apply adhesive to edge o concrete slab and push FCFcl into position, or i using multi purpose brackets spike
into material at 500mm centres, insert into cavity and ix to concrete i instructed. Ensure tight butt joints. I using ischer Cavity FireStop Strip FCFst pro iled blocks to cladding, coat edges with adhesive and
compress and it making sure blocks are in line with FCFcl. Where applications require a total smoke seal, coat with ischer Panel Coating as directed. For brick/block cavities insert a damp-proo membrane (DPM) between outer skin and FCFcl.
Vertical Adhere FCFcl to blockwork. Ensure DPM is in place as outer skin is constructed. Ensure tight joints.
f s c
h e r
C a v
i t y
F i r e
S t o p
C l a
d - F
C F c l
FireStop Clad
Multi Purpose Bracket
Description
ApprovalsFire Rating
Installation
British Standard
BS 476-20
Type Order No. Dimensions Qty. Per Box
FCFcl 53046 Size on Application 1
Multi Purpose Bracket 58577 300 x 29 x 1mm 2
Acoustic Rating Smoke Seal Fibre Migration
FCFcl has been acoustically assessedin a variety o constructions. TwoFCFcl (220 wide x 75mm thick)compressed into a 210mm gapbetween edge o slab and a 46mminsulated wall cladding. The productmust be coated with ischer PanelCoating. Weighted Sound ReductionIndex (Rw) o up to 48db.
FCFcl can provide a smoke seal byeither: Painting the exposed aceswith ischer Panel Coating FPC.Using oil encapsulated FCFcl andsealing joints with oil aced tape.
FCFcl can provide a smoke seal byeither: Painting the exposed aceswith ischer Panel Coating FPC,Using oil encapsulated FCFcl andsealing joints with oil aced tape.
Speci cation
-
7/22/2019 2011 FireStop Handbook 1st September(Web2)
36/48
FVFB 102/25 & FVFB 102/50 have sel adhesive on the back or initialpositioning and should then be mechanically xed along their centre lineo the cladding system with 25 mm long small headed tacks at 250 mmcentres.
FVFB 109/125 & FVFB + Sytems should be mechanically xed within thecavity. The seal should be xed along its centre line onto steel installation
spikes or scher Multi-Purpose brackets at 250 mm centres.
Care should be taken when xing not to restrict the product rom expandingin a re situation. Adjacent Fire Barriers should be butt jointed together. All
xings used on re systems should be re rated as per page 34-37.
scherVentilatedFireBarrier-FVFB
Type Order No. Cavity Size (mm) Dimensions (mm) Fire Rating(hours)
Qty. Per Box
FVFB 102/25 513203 upto 25 4 x 35 x 1000 1 TBC
FVFB 102/50 513204 upto 50 6 x 75 x 1000 1 TBCFVFB + System *505250 upto 450 >125 x 100 x 1000 1 TBC
*Made to size - please quote re erence 505250/FVFB+For larger cavities, please contact the fscher technical department on 01491 827 920 or more solutions.
Creates a re barrier behind therainscreen.
Fire Tested or up to 60 minutes Intumescent Material expands
to ll the cavity. Suitable or cavities up to
450mm.
Simple & quick installation -time saving o up to 50%over other re barriers.
Tested in the most demandingo combustible rainscreendesigns.
Fire tested both horizontally andvertically.
Allows ventilation and moisturedissipation thus preventingdamp problems.
Cost e ective.
Supplied in 1 metre lengths -can easily be cut with a kni e.
All Fire Barriers are sealed too er excellent weather protectionand are una ected by moisture.
scher Ventilated Fire Barriers are designed to maintain the open cavitywhere the external acade/rainscreen is suspended away rom the buildingstructure. The re barriers will expand to seal the cavity in a re situation.The Fire Barriers are suitable or a variety o cavity depths.
scher Ventilated Fire Barriers have been tested in both combustibletimber rame and non-combustible constructions unlike other Fire Barrierproducts.
FVFB + System
Cavity Size (mm) Fire Rating (hours)
up to 25 1
up to 50 1
up to 125 1
up to 450 1
Ventilated Fire Barrier - FVFB
Description
ApprovalsFire Rating
Bene ts
British Standard
BS 476-20
Installation
Installation
-
7/22/2019 2011 FireStop Handbook 1st September(Web2)
37/4837
scher Cavity FireStop Strips provide FireStopping or vertical and horizontalconstruction joints and at the inter ace between compartment walls and so ts.Tested to BS476 Part 20, scher Cavity FireStop Strips provide up to 6 hours reprotection.
scher Cavity FireStop Strip is used or FireStopping joints which are reasonablyuni orm in size and may be subject to movement. scher Cavity FireStop Strip ismanu actured rom a high density, low phenolic binder, rock bre. scher CavityFireStop Strip is supplied in one metre lengths to suit the size o the joint to be
lled. The width o the strip is dependent on the re rating required. (See FireRating) scher Cavity FireStop Strip thickness is slightly oversized compared to the
joint size so that the FireStop Strip is tted or installed under slight compression.
Fire Rating Minimum Widths
1 hour 75mm2 hour 100mm
3 hour 150mm
4 hour 175mm
6 hour 200mm
ischer Cavity FireStop Strips are used to prevent ire penetration at the junction o compartment walls and loors/roo s
or a speci ied period up to 6 hours. They are generally supplied to it under slight compression. Remove all loose debris and mortar rom the gap. Ensure correct width is installed to suit the required Fire Rating. Keep material dry and protect rom impact damage.
FireStop Strip Gaps up to 25mm. It is easier to install prior to completion o the last course o brick/blockwork wall. Larger gaps. Compress and insert the strip ensuring tight butt joints.
s c h e r C a v i t y F i r e S t o p S t r i p - F C F s t
scher Cavity FireStop Strips being a component o structure satis es bothintegrity and insulation requirements as shown in the table opposite.
Description
ApprovalsFire Rating
Installation
British Standard
BS 476-20
Type Order No. Dimensions Qty. Per Box
FCFst 53045 Size on Application 1
Acoustic Rating Smoke Seal Fibre Migration
ischer Cavity FireStop Strips havebeen acoustically assessed in avariety o applications.Two ischer Cavity FireStop Strips30mm thick by 60mm widecompressed into a 25mm joint in140mm thick (2000 kg) block wallis capable o providing a WeightedSound Reduction Index (Rw) o46db, i coated both sides with
ischer Panel Coating.
ischer Cavity FireStop Strips providea smoke seal i external aces arecoated with ischer Panel Coating.
Fibre migration is prevented byeither: Shrink wrapping. Painting the exposed aces o
the product with Flexi-coat paint.
Speci cation
Cavity FireStop Strip - FCFst
-
7/22/2019 2011 FireStop Handbook 1st September(Web2)
38/48
Intumescent Linear Seal - FiLS
ischer Intumescent Linear Seal is a highly compressible strip ormed bylaminating re retardant oam to a graphite based intumescent polymer.
ischer Intumescent Linear Seal is a compressible product to ll re rated joints in compartment foors and walls. Tested to BS476 Part 20, ischer
Cavity FireStop Expansion provides up to 4 hours re protection.ischer Intumescent Linear Seal is delivered to site in pre- ormed sections.
The section size depends on the joint size and the re rating that needs tobe achieved (See Fire Rating).
ischer Intumescent Linear Seal is simply compressed by hand and is thenpushed into the gap. Adjacent pieces o the product are simply buttedtogether. There is no need to use any adhesives or intumescent sealant inconjunction with the product.In a re, the graphite based intumescent material swells to orm a hard charwhich prevents the passage o re and smoke through the joint.
Joint Size Integrity Insulation Size o Product
1 - 10mm 240 mins 235 mins 14 x 12mm
11 - 25mm 120 mins 16 mins 29 x 12mm
11 - 25mm 240 mins 145 mins 29 x 25mm
26 - 50mm 120 mins 23 mins 56 x 25mm
ischer Intumescent Linear Seal is used to prevent ire penetration through movement joints and gaps in
walls and concrete loors or a speci ied period up to 6 hours. They are manu actured oversize to it undercompression.
Remove all loose debris and mortar rom the gap. Ensure correct width is installed to suit the required Fire Rating. Where the gap varies in the length to be sealed, ensure that the correct thickness is installed under
compression. Do not remove sleeving. Keep material dry and protect rom impact damage. Compress and insert the strip into the gap ensuring tight butt joints.
fscherIntumescentLinearSeal-FiLS
Type Order No. Dimensions Qty. Per Box
FiLS / 12x12 53047 14 x 12mm 1
FiLS / 25x12 53048 29 x 12mm 1
FiLS / 25x25 53049 29 x 25mm 1FiLS / 50x25 53050 56 x 25mm 1
Description
ApprovalsFire Rating
Installation
Speci cation
British Standard
BS 476-20
-
7/22/2019 2011 FireStop Handbook 1st September(Web2)
39/4839
FireStop Hand & Gun Foam
Description
Approvals
Bene tsInstallation
Speci cation
FireStopHand Foam
FireStopGun Foam
Installation information - Hand Foam Shake cartridge be ore use. Hold cartridge upside down when extruding oam. Foam yield ( ree oaming) up to 35 litres / 750ml can. Resistance to temperature of hardened foam: -30 C to +80 C. Non-tacky a ter approx. 8 minutes, load-bearing a ter approx.
6-12 hours,ully hardened a ter 24 hours (all details based on temperature o
+20 C).
Installation information - Gun Foam Extrude with a choice o oam gun. Foam yield ( ree oaming) up to 45 litres. Resistance to temperature of hardened foam: -30 C to +80 C. Non-tacky a ter approx. 8 minutes, load-bearing a ter approx. 6-12 hours,
ully hardened a ter 24 hours (all details based on temperature o+20 C).
F i r e
S t o p
F o a m
Type Order No. Contents Qty. Per BoxHand Foam 42757 750ml 12
Gun Foam 43712 750ml 12
Standard Gun 62400 n/a 1
Pro essional Gun 33208 n/a 1
The scher FireStop Foam is a one component polyurethane oam whichis sel curing via the absorbtion o moisture rom the atmosphere. The
oam has excellent adhesive properties joining wood, brick, stone, cement.plaster wall boards, hard board and metal sur aces. Foam sets in a semi-ridged structure, xes rmly, yet yields to movement and vibration. It is ideal
or areas where up to 4hour FireStop per ormance is required.
Tested to BS EN 13501 & BS EN1366-4, the foam is perfect for sealinglinear gaps in walls, ceilings and oors. Insulating pipes and electricalinstallation, sealing window / door joints, sills and frames.
Wall Depth Gap Width Sealant Depth Backing Integrity Insulation
100mm 31mm 100mm None 50 mins 50 mins
100mm 11mm 100mm None 103 mins 104 mins
200mm 11mm 200mm None 229 mins 229 mins
200mm 41mm 200mm None 110 mins 110 mins
High oam yield. Pro essional application with use
o gun. High pressure, shear and weather
resistant. Can be rendered, cut, painted and
sanded. No post shrinkage or expansion CFC- ree propellant.
Fire Rating
British Standard
BS 476-20
BS EN1366-4: 2006
BS EN ISO 140-3: 1995
DIN 4102: Part1
-
7/22/2019 2011 FireStop Handbook 1st September(Web2)
40/48
AirSealFoam
Air Seal Gun Foam
Description
Approvals
Bene ts
Installation
Speci cation
Type Order No. Contents Qty. Per Box
Air Seal Gun Foam 512377 750ml 12
Gun 1 m or urther in ormation please call 01491 827 900
The scher Air Seal GunFoam is a B2 rapid curing, highly elastic gun gradepolyurethane oam. scher Air Seal is ideal or use as an air tight gap llerand water resistant seal around windows and doors.It is also suitable or sealing foor to wall and wall to ceiling joints; themovement accommodation actor (MAF) o 35% ensures that the integrityo the seal is maintained in the event o movement and settlement.
A high per ormance PU oam withexcellent acoustic and airtightper ormance.
B2 Foam Rating
Airtight ormulation - tested toEN1026 0.1 m/h @10 Pa.
Acoustic dampening - up to 58 dB joint insulation index.
Up to 35% movementaccomodation ensures integrity othe seal in the event o movement.
Sub-zero ormulation - can still beused at temperatures as low as-3C .
Installation in ormation - Gun Foam Shake the canister vigorously at least 20 times be ore use. Screw the gun care ully onto the canister. Invert can and gently press
on the trigger or correct fow rate. The oam will be tack ree in approximately 10 minutes, trimmable
within 45-60 minutes and loadable within 24 hours (depending onthickness temperature and humidity).
This oam is not UV resistant. Once cured, oam should be coveredwith scher FFRS sealant, Intumescent Acrylic or Fire Rated Paint. For
urther in ormation check the product data sheet.
Air SealGun Foam
Airtight ormulation - tested to
EN10260.1 m/h @10 Pa
-
7/22/2019 2011 FireStop Handbook 1st September(Web2)
41/4841
The ollowing examples will help you to nd the anchors intended or re protection o your application range.
Application Regulations or use In ormation about anchoring Suitable fxing/anchor
Fire-proo ed ventila-tion conduits and in-stallation equipmentL 30 to L 120
DIN 4102, part 4,8.5.7.5
Building regulation approved steelanchors M8, double depth, 6 cmminimum anchoring depth, calculatedload: max. 500 N per anchor, and max.6 N/mm2 based on the steel cross-section orfre test certifcate roma recognised test centre.
scher Zykon anchor FZAscher Zykon hammerset anchor
FZEA IIscher anchor bolt FAZ II + FAZ A4/Cscher nail anchor FNA IIscher injection mortar FIS Vscher high per ormance anchor FH IIscher ceiling nail FDNscher concrete screw FBS
Sprinkler systems Guidelines or sprinkler/water spray systems
rom VdS [Vertrauendurch SicherheitSchadenverhtungGerman Loss PreventionSa ety and SecurityInstitution](new guidelines willappear in 2008)
Made o non- ammable material andtested and approved by VdS; minimum
M8.
scher Zykon anchor FZAscher Zykon hammerset anchor
FZEA IIscher anchor bolt FAZ II + FAZ A4/Cscher hammerset anchor EA IIscher high per ormance anchor FH IIscher hollow-ceiling anchor FHY
General pipelines DIN 4102, part 4, 8.5.7.5 Building regulation approved steelanchors M8, double depth, 6 cmminimum anchoring depth, calculatedload: max. 500 N per anchor, and max.6 N/mm2 based on the steel cross-section orfre test certifcate roma recognised test centre.
scher nail anchor FNA IIscher Zykon hammerset anchor
FZEA IIscher anchor bolt FAZ II + FAZ A4/Cscher hammerset anchor EA IIscher concrete screw FBSscher hollow-ceiling anchor FHYscher ceiling nail FDN
Cable trays DIN 4102, part 4,8.5.7.5 andDIN 4102, part 12
or unctionalendurance
Building regulation approved steelanchors M8, double depth, 6 cmminimum anchoring depth, calculatedload: max. 500 N per anchor, and max.6 N/mm2 based on the steel cross-section orfre test certifcate roma recognised test centre.
scher Zykon anchor FZAscher Zykon hammerset anchor
FZEA IIscher anchor bolt FAZ II + FAZ A4/Cscher high per ormance anchor FH IIscher hollow-ceiling anchor FHYscher hammerset anchor EA IIscher nail anchor FNA IIscher concrete screw FBS
scher injection mortar FIS V
Heavy pipelines andcable trays
DIN 4102, part 4, 8.5.7.5 Building regulation approved steelanchors M8, double depth, 6 cmminimum anchoring depth, calculatedload: max. 500 N per anchor, and max.6 N/mm2 based on the steel cross-section orfre test certifcate roma recognised test centre.
scher anchor bolts FAZ II + FAZ A4/Cscher high per ormance anchor FH IIscher Zykon hammerset anchor
FZEA IIscher highbond anchor FHB IIscher Zykon anchor FZAscher injection mortar FIS V
F i r e p r o
t e c t
i o n
i n f x i n g
t e c h n o
l o g yDescription
Fixing Technology
-
7/22/2019 2011 FireStop Handbook 1st September(Web2)
42/48
Fire testing according to DIN 4102 and TR 020applications in the concrete tensile zone
Description Fixing type Material Max. permitted load in case o a ire [kN] Test reportApproval no. *
Certi icate Applicationgvz A4 C
(1.4529)F30 F60 F90 F120 VdS FM
Tensileloads
Transverseloads
Tensileloads
Transverseloads
Tensileloads
Transverseloads
Tensileloads
Transverseloads
ischer highbond anchor FHB II FHB II 8 x 60 2.3 2.8 1.8 2.1 1.2 1.4 0.9 1.0 PB III /B-06-065(18.04.2006)
Cracked andnon-crackedconcrete
FHB II 10 x 60 3.4 4.1 2.4 2.9 1.4 1.8 0.9 1.2FHB II 10 x 95 3.6 4.3 2.7 3.3 1.8 2.4 1.4 1.9FHB II 12 x 75 4.4 4.9 3.5 4.0 2.6 3.1 2.1 2.7FHB II 12 x 120 5.1 6,1 3.8 4.9 2.4 3.6 1.7 3.0FHB II 16 x 95 8.3 9.2 6.6 7.5 4.8 5.9 4.0 5.0FHB II 16 x 160 9.5 11.4 7.0 9.1 4.5 6.8 3.3 5.6FHB II 20 x 210 14.9 17.8 11.0 14.2 7.1 10.6 5.2 8.8FHB II 24 x 170 18.7 20.8 14.8 17.0 10.9 13.3 8.9 11.4
ischer highbond anchor dynamic FHB dyn FHB-A dyn 12 x 100/25 7.0 4.0 2.5 3038/8141-1(o 12.10.2001)
Cracked andnon-cracked
concreteFHB-A dyn 12 x 100/50 7.0 4.0 2.5 FHB-A dyn 16 x 125/25 15.0 7.0 5.0 4.0 FHB-A dyn 16 x 125/50 15.0 7.0 5.0 4.0 FHB-A dyn 20 x 170/50 2.0 9.5 7.0 5.0 FHB-A dyn 24 x 220/50 25.0 12.0 9.5 7.5 FHB-A dyn 16 x 125/50C 15.0 7.0 5.0 4.0
ischer Zykon anchor FZA FZA M6 1.0 0.5 0.35 0.25 3277/0531-1(o 23.11.2001)
Cracked andnon-cracked
concreteFZA M8 1.5 0.8 0.5 0.4 FZA M10 4.5 2.2 1.3 0.9 FZA M12 8.5 3.5 2.0 1.5 FZA M16 13.5 6.5 4.0 3.0 FZA M6 A4/C 2.1 1.2 0.85 0.7 FZA M8 A4/C 10.0 4.0 1.8 1.0 FZA M10 A4/C 18.0 7.0 3.5 2.0 FZA M12 A4/C 22.0 9.0 5.0 3.5 FZA M16 A4/C 24.0 12.0 7.5 6.0
ischer Zykon through anchor FZA-D FZA M8 D 1.5 0.8 0.5 0.4 3277/0531-1(o 23.11.2001)
Cracked andnon-cracked
concreteFZA M10 D 4.5 2.2 1.3 0.9 FZA M12 D 8.5 3.5 2.0 1.5 FZA M16 D 13.5 6.5 4.0 3.0 FZA M8 D A4/C 10.0 4.0 1.8 1.0 FZA M10 D A4/C 18.0 7.0 3.5 2.0 FZA M12 D A4/C 22.0 9.0 5.0 3.5 FZA M16 D A4/C 24.0 12.0 7.5 6.0
ischer internally-threaded anchor FZA-I FZA M6 I 1.0 0.5 0.35 0.25 3277/0531-1
(o 23.11.2001)
Cracked and
non-crackedconcreteFZA M8 I 1.5 0.8 0.5 0.4 FZA M10 I 4.5 2.2 1.3 0.9 FZA M12 I 8.5 3.5 2.0 1.5 FZA M6 I A4/C 2.1 1.2 0.85 0.7 FZA M8 I A4/C 10.0 4.0 1.8 1.0 FZA M10 I A4/C 18.0 7.0 3.5 2.0 FZA M12 I A4/C 22.0 9.0 5.0 3.5
ischer ZYKON hammerset anchor FZEA-IIFZEA II 10 x 40 M8 1.0 0.9 0.9 0.8 0.8 0.7 0.7 0.6ETA-06/0271 Cracked andnon-cracked
concrete
FZEA II 12 x 40 M10 1.8 2.3 1.8 1.7 1.6 1.1 1.2 0.9 FZEA II 14 x 40 M12 1.8 2.3 1.8 2.1 1.8 1.4 1.5 1.0
ischer anchor bolt FAZ II FAZ II M8 1.25 1.8 1.2 1.6 0.9 1.3 0.8 1.2PB III/B-05-001( rom 10.02.2005)
ETA-05/0069
Cracked andnon-cracked
concreteFAZ II M10 2.25 3.6 2.25 2.9 1.9 2.2 1.6 1.9 FAZ II M12 4.0 6.3 4.0 4.9 3.2 3.5 2.8 2.8 FAZ II M16 9.4 11.7 7.7 9.1 6.0 6.6 5.2 5.3 FAZ II 8 A4/C 1.7 1.7 1.7 1.7 PB III/B-02-316
(o 31.01.2003)
FAZ II 10 A4/C 2.5 2.5 2.5 2.5 FAZ II 12 A4/C 4.5 4.5 4.5 4.5 FAZ II 16 A4/C 8.0 8.0 8.0 8.0
ischer high per ormance anchor FH/FH IIFH 10 B / S / H 0.4 0.4 0.4
3355/0530-2(25.5.00)
Cracked and non-cracked concrete
FH II 12 B / S / H /SK 0.4 0.4 0.3 0.3 0.3 0.3 0.2 0.2ETA-07/0025 FH II 15 B / S / H /SK 0.9 0.9 0.8 0.8 0.6 0.6 0.5 0.5 FH II 18 B / S / H 1.7 1.7 1.3 1.3 1.1 1.1 0.8 0.8 FH II 24 B / S / H 3.1 3.1 2.4 2.4 2.0 2.0 1.6 1.6
ischer concrete screw FBS FBS 8 0.8 0.8 902 07
top related