1st ltex 22 june 2009d.lacarrere1 protection of ux85 edms no 1005700 ip8 current status & plans ...

Post on 14-Jan-2016

215 Views

Category:

Documents

0 Downloads

Preview:

Click to see full reader

TRANSCRIPT

1st LTEX 22 June 2009 D.LACARRERE 1

Protection of UX85

EDMS No 1005700

IP8

Current Status & Plans

UX85 Expt Area

RB84 (8-7 sector)

RB86 (8-1 sector)

Works to be done

Remarks 15 June 2009

1st LTEX 22 June 2009 D.LACARRERE 2

Pit 8 – LHCb - UX85 Area

ACCESSPERSONNEL

PM SHAFTUXA

IP8

ACCESSEQUIPMENTPX SHAFT

RADIATION SHIELD

UXCUXB

Access - CheckingPersonnel & Materials

UXA – LHCb Protected AreaUXB – LHCb Detector AreaUXC – LHC Cryogenics

Accessible Area when LHC operates

BEAM 2

BEAM 1

POINT 1(ATLAS)

ACCESSPERSONNEL

PZ SHAFT

UX85 CAVERN

RB86

RB84

SHIELDING PLUGS

FIG. 1

UJX Gallery

1st LTEX 22 June 2009 D.LACARRERE 3

Shielding Plug – RB84 Area

2200

REF. : Document edms no 38083FIG. 2

Beam Axis

IP8

10400Fe Concrete

Concrete

8001200800

Air flux

holes

1st LTEX 22 June 2009 D.LACARRERE 4

RB84 - Segmentation (reminder)

January 2008

Mobile door

Concrete blocks

Aperturefor survey

View from LHC tunnel FIG. 3

1st LTEX 22 June 2009 D.LACARRERE 5

August 2008

Air tightness – First Improvements (August 08)

Metallicjoints

View from LHC tunnel FIG. 4

1st LTEX 22 June 2009 D.LACARRERE 6

18 June 2009FIG. 5

RB84 side - Current Status (June 09)

- Joints filled with PUR- Joints sealed with concrete- Painting

1st LTEX 22 June 2009 D.LACARRERE 7

Aluminium Cover Sheets

Al sheet removable

FIG. 6

Al sheetsremovable

View from LHC tunnel

Al sheetsfixed to tunnel

Additional Improvements (?) (not yet decided)

Installation of Al cover sheets

1st LTEX 22 June 2009 D.LACARRERE 8

19900 from IP8

FIG. 7

Beam Axis

24622 from IP8

FeConcrete

REF. : Document edms no 38083

1200 800

RB86 Area - Improvement Tightness

MF4

MF

4

1st LTEX 22 June 2009 D.LACARRERE 9

Hole 800 x 800 mm2

MF4 – Central Part

NO ACTION

FIG. 8

1st LTEX 22 June 2009 D.LACARRERE 10

Joint PUR + concreteMetallic sheets (Al 8 mm thick)

Joints & Metallic sheets

FIG. 9

1st LTEX 22 June 2009 D.LACARRERE 11

Holes in the chicane

PROPOSED ACTIONS 1 - STRENTHEN SECTOR DOOR2 – FILL HOLE DEDICATED TO SURVEY PIPE

1st LTEX 22 June 2009 D.LACARRERE 12

False floor in the chicane

ADDITIONAL CONCRETE BRICKSIN THE FALSE FLOOR

1st LTEX 22 June 2009 D.LACARRERE 13

RB84 Side- Mechanical stability of the 1st concrete shield (front of VELO) to be checked with a pressure of 40 mbar. Calculations has been performed by J.C. Batista Lopes DG-SC edms 1005362/1 19 June 2009) – Conclusion : Good stability up to pressure 75 mbar – sliding of upper part - Installation of aluminium cover sheets (LHC tunnel side)- Work scheduled fro week 26

RB86 Side- All main joints (MF4) will be filled with PUR or plastic seal (in particular small gaps) + special concrete (repair cement) + cover sheets.- Strengthen of the sector door (?) . But how. - Cover the cryo-line with aluminium sheets (8-10 mm thick)- Work scheduled for wks 30 – 31

Summary – Main Works on going

1st LTEX 22 June 2009 D.LACARRERE 14

Remarks UJX Tunnel (from UJ87 up to PX shaft)

- Mechanical stability of the wall between tunnel & UJX to be checked with a pressure of 40 mbar. Contact with GS-CE Group

US85/UX85- Wall between US85 & UX85 is made of “SIPOREX” concrete (20 cm thick) Mechanical stability to be check (?)

BUDGET & COORDINATION

- Budget code to be used ? Machine side ?- How to proceed ? - Coordination on site – Who ?