1.1 Siemens S5/S7 Series
1.1.1 S5/ S7 Serial Interface
The following section describes the system configuration and interface between Siemens S5/S7
series PLC and TOP using serial communication through link unit.
1.1.1.1 System Configuration
The above figure shows system configuration to connect S5/S7 PLC to TOP. (Use 3964R
protocol)
PLC Comm. Unit Cable TOP
S5 90U
S5 95U
S5 100U
S5 115U
S5 135U
S5 155U
S7-300
S7-400
CP525
CP340
CP441-2
Refer Cable
Connection.
(RS-232 / RS-
422)
All TOP
1.1.1.2 Cable Diagram
(1) RS-232C (CP525 ↔ TOP (for 9/15 Pin Connector))
PLC Comm. Link Module(25Pin) TOP (9/15Pin)
1
CD 2
RD 3 SD
4
DTR 5 SG
6
DSR 7
RTS 8
CTS 9
1 FG
2 SD
3
RD 4
RTS 5
CTS 6
DSR 7 SG
8
CD 20
DTR
(2) RS-232C (CP340, CP441-2 ↔ TOP (for 9/15 Pin Connector))
PLC Comm. Link Module (9Pin) TOP (9/15Pin)
(3) RS-422 (CP340, CP441-2 ↔ TOP (for 5Pin terminal / 15Pin Connector)
PLC Comm. Link Module(15Pin) TOP(5Pin Terminal / 9Pin)
:
11 R(B)
9 T(B)
:
4 R(A)
3
2 T(A)
1
:
11 R(B)
9 T(B)
:
4 R(A)
3
2 T(A)
1
5(15) GND
4(14) SDB
3(13) SDA
2(12) RDB
1(11) RDA
5(15) GND
4(14) SDB
3(13) SDA
2(12) RDB
1(11) RDA
1
CD 2
RD 3 SD
4
DTR 5 SG
6
DSR 7
RTS 8
CTS 9
1
CD 3 SD
2
RD 7
RTS 8
CTS 6
DSR 5 SG
9 RI
4
DTR
(4) RS-485 (CP341, CP441-2 ↔ TOP)
PLC(15Pin) TOP(5/9/15)
※ 9PIN DSUB 의 TOP 422 Pin Connection (1,4,6,9,5)
※ 15PIN DSUB 의 TOP 422 Pin Connection (11,12,13,14,15)
1.1.1.3 CP525/CP340/ CP441-2 Setup
PLC측 설정
Baud Rate 110 bps ~ 76800 bps
Data Length 8 bit
Stop Bit 1 bit
Parity Bit EVEN
Error Detection BCC(SUM)
Priority Low
Select the RK-512 protocol for the S7, while the 3964R protocol for the S5. Also add the
Receive Function Block FB7.
The CP340 is not supported by the latest version of PC software.
< Example Configuration of CPU314 and CP341 RS232C>
Specify the RK512 protocol for the S7.
1
2 T(A)
3
4 R(A)
:
9 T(B)
11 R(B)
:
RDA 1/1/11
RDB 2/4/12
SDA 3/6/13
SDB 4/9/14
GND 5/5/15
Define the communication parameters.
Set the priority to low.
Check the value of the local address LADDR for the configuration of the FB7.
Open OB1, and drag and retrieve the ‘FB7 P_RCV_RK CP341’ from the CP 341 folder in the
program elements.
Enter the DB number (DB7) to be used by the FB7 to receive the communication on the
top. Then the corresponding DB is automatically created. Turn the ‘EN_R’ ON to enable
the communication. R is reset input, and LADDR is the local address value checked in
the previous step.Enter one of DB Nos. to be used. The read/write communication is
available within the assigned DB area only.
1.1.2 < TOP Set up >
(1) TOP Designer Setup
Select the ‘Siemens S5-3964R, S7-3964/RK512 (Link)’ in the external device.
(2) TOP Serial Set Up
The recommended setup information is as follows:
Serial Baud Rate : 38400 bps
Serial Data Bit : 8bit
Serial Stop Bit: 1bit
Serial Parity Bit : EVEN
Serial Signal Level: RS-232
Station Number (0-31) to Diagnose the Communication : N/A
Available Address List
Device Word Address
Data Register *1
D002:000 ~ D255:255
Expansive Data Register *1
X002:000 ~ X255:255
*1 : Data Register and Expansive Data Register are as follows.
D002:000
Data Word(DW) : 000~255
Data Block(DB) : 000~255
Expansive Data Register is available in only S5 135U/155U.
Last two digits are used in Bits.
D002:000:00
REF.
1.1.3 S7-300/400 (CPU MPI Direct Connection)
S7-300/400 (Direct Connection to CPU via MPI Port
The following section describes the system configuration and interface between Siemens S7-
300/400 series PLC and XTOP using direct connection.
1.1.3.1 System Configuration
This figure shows system configuration to connect S7 PLC to TOP.
PLC Comm. Unit Cable TOP
CPU312IFM
CPU313
CPU314
CPU315
CPU315-2DP
CPU MPI Port
Refer Cable
Connection
(RS-485C)
Only for XTOP
Unsupported for
ATOP
1.1.3.2 Cable Diagram
(1) RS-485 (CPU MPI port ↔ XTOP(for 9/15Pin Connector)
PLC (9Pin) TOP (9/15Pin)
1(11) RDA
CD 2
3
4(12) RDB
5(15) SG
6(13) SDA
7
8
9(14) SDB
1
2
3 TRX+
4
5 SG
6
7
8 TRX-
9
1.1.3.3 TOP Setup
(1) TOP Designer Setup
Select the ‘Siemens MPI Direct in the Target PLC type.
Configure the MPI Address of TOP on Station No.,the MPI Address of S7 on PLC Node
(2) TOP Serial Setup
Recommended settings are as follows.
- Serial Baud Rate : 187500 bps
- Serial Data Bit : 8bit(Auto set)
- Serial Stop Bit: 1bit(Auto set)
- Serial Parity Bit : EVEN(Auto set)
- Serial Signal Level : RS-485
- Controller’s Station No. at Comm. Diagnosis(0~31) : Not effect.
PLC node and Top’s station No must be set differently each other.
We recommend Highest Node 15.
1:n, n:1 and n:m connection is not supported, but 1:1 connection is only
supported.
MPI Direct is supported only XTOP model.
REF.
S7-300/400 (CPU MPI Port + PC Adapter)
The following section describes the system configuration and interface between Siemens S7-
300/400 series PLC and TOP using serial communication through PC adapter.
1.1.3.4 System Configuration
This figure shows system configuration to connect S7 PLC to TOP.
PLC Comm. Unit Cable TOP
CPU312IFM
CPU313
CPU314
CPU315
CPU315-2DP
PC Adapter
Refer Cable
Connection
(RS-232C)
All TOP
1.1.3.5 Cable Diagram
(1) RS-232C (PC Adapter ↔ TOP(for 9/15Pin Connector)
PLC PC Adapter(9Pin) TOP (9/16Pin)
1
CD 2
RD 3 SD
4
DTR 5 SG
6
DSR 7
RTS 8
CTS 9
1
CD 3 SD
2
RD 7
RTS 8
CTS 6
DSR 5 SG
9 RI
4
DTR
1.1.3.6 S7-300/400 CPU Setup
PLC Setting
Baud Rate 19200 ~ 38400 bps
Data Length 8 bit
Stop Bit 1 bit
Parity Bit ODD
Error Detection BCC(SUM)
1.1.3.7 TOP Setup
(1) TOP Designer Setup
Select “S7-300/400 MPI(LOADER)” of “Siemens Series” in PLC type.
(2) TOP Serial Setup
Recommended settings are as follows.
- Serial Baud Rate : 19200 bps
- Serial Data Bit : 8bit
- Serial Stop Bit: 1bit
- Serial Parity Bit : ODD
- Serial Signal Level : RS-232
- Controller’s Station No. at Comm. Diagnosis(0~31) : 1
PLC node and Controller’s station No must be set differently each other.
Highest node should not exceed PLC node. For example, If PLC node is set 16
by user, highest node should be set 31 or above.
1.1.4 < S7-300/400 CPU Set up >
1.1.5 Configuration of S7-300/400 CPU >
(1) Hardware Configuration
Assign 187.5Kbps to the Transmission rate in the Network Setting tab of the MPI interface
as shown in the figure below. Change the highest address to 15 for a fast connection in the
communication network.
REF.
(2) Options > Set PG/PC Interface > PC Adapter > MPI
Assign 187.5 Kbps to the Transmission Rate as shown in the figure below. As the Highest
Address is for the PC, the value is different from the MPI address.
※ Select the Highest Node Address in the TOP Designer in case a PC Adapter is used. (see
Project Information in the Designer)
(3) Options > Set PG/PC Interface > PC Adapter > Local Connection
The Local Connection is the speed at which the PC communicates with the TOP in case a
PC Adapter is used. Assign 19200 or 38400 to the Local Connection depending on the
switch value specified on the side of the PC Adapter.
(4) TOP Menu
Assign 19200 or 38400 to the Baud Rate depending on the switch value specified on the
PC Adapter. Other values, including Data Bit, are automatically configured.
S7-200 (CPU Direct Using PPI Port)
The following section describes the system configuration and interface between Siemens S7-
200 and TOP using serial communication.
1.1.5.1 System Configuration
This figure shows system configuration to connect S7 PLC to TOP.
PLC Comm. Unit Cable TOP
S7-200
(CPU212/214/
222/224/226)
None
Refer to Cable
Connection (RS-485) All TOP
1.1.5.2 Cable Diagram
(1) RS-422 (S7-200 ↔ TOP (for 5Pin Terminal Block or 15Pin Connector))
PLC CPU PPI Port(9Pin) TOP
(5Pin Terminal Block/15Pin)
5 GND
3 TR+
8 TR-
1 FG
5 GND
3 TR+
8 TR-
1 FG
5(15) SG
4(14) SDB
3(13) SDA
2(12) RDB
1(11) RDA
5(15) SG
4(14) SDB
3(13) SDA
2(12) RDB
1(11) RDA
1.1.5.3 S7-200CPU Setup
PLC Setting
Baud Rate 9600 bps
Data Length 8 bit
Stop Bit 1 bit
Parity EVEN
Error Detection BCC(SUM)
Setting of Station Num. is default(2).
1.1.5.4 TOP Setup
(1) TOP Designer Setup
Select “Siemens S7-200 PPI(Loader)”in PLC type.
(2) TOP Serial Setup
Recommended settings are as follows.
- Serial Baud Rate : 9600bps
- Serial Data Bit : 8bit
- Serial Stop Bit: 1bit
- Serial Parity Bit : EVEN
- Serial Signal Level : RS-485
- Controller’s Station No. at Comm. Diagnosis(0~31) : 1
1.1.5.5 Available Address List
(1) S7-300 CPU Direct(Using MPI Port)
Device Bit Address Word Address
Input Relay E000 00 ~ E127 07 EW00O ~ EW126
Output Relay A000 00 ~ A127 07 AW000 ~ AW126
Timer T000 ~ T127
Counter Z00 ~ Z63
Data Block DB001 00000 00~
DB256 65535 07
DB001 00000 ~ DB256 65534
Memory M000 00 ~ M255 07 MW000 ~MW254
※In the Designer, select ‘FB’ if you want to read the DB area in real number, while
select ‘FM’ if you want to read the M area in real number. As the real number area
increases by 4, enter 0, 4, 8, … ‘32 bit Word Swap’ is selected only for the 32 bit
positive number, not for the real number.
※The decimal place of an address in real number shall be constant in all screens. Once
the number tag is registered, the decimal place shall be the same in every screen. It is not
applicable if the address is different.
< Note >
*1 : Data Register
DB 034 00002
Word Address: 00000 ~ 65534(even number)
Data Block (DB) No.: 001 ~ 256
* Add two digits to the end in Bit.
DB 034 00002 00
Bit Address: 00 ~ 07
※ Generate the tag in BCD for a timer and counter.
If the word array is allocated in the DB34, 0 and 1 are allocated in the first area, 2 and
3 are in the second area, and 4 and 5 are in the third area.
If you use a number tag or a key tag to read the second area in word value, set the
device address to 2 in the TOP (DB 034 00002).
If you need to access bits, for example, lamp tag or touch tag, set the address to 2 for
the high byte, while set the address to 3 for the low byte.
To access to 00 bit high byte in the second area: DB 034 00002 00
To access to 00 bit low byte in the second area: DB 034 00003 00
The last two digits 00 indicate the location of bit, which is definable from 00 to 07.
Turning the DB 034 00002 00 ON reads 256 in number tag (word).
Select ’32 Bit’ and ’32 Bit Word Swap’ to indicate the 32 bit positive number.
(2) S7-200
Device Bit Address Word Address
Input Relay I00 ~ I77 IWO ~ IW6
Output Relay Q00 ~ Q77 QW0 ~ QW6
Timer T000 ~ T127 TW000 ~ TW127
Counter C00 ~ C63 CW000 ~ CW127
Variable Memory V000 ~ V4095 VW0000 ~ VW4094
Memory M000 ~ M317 MW00 ~MW30
Special Memory SM000 ~ SM857 SMWO ~ SMW84
Analog Input AIWO ~ AIW30
Analog Output AQWO ~ AQW30
High Speed Counting HCO ~ HC2
1. Data Register and Expansive Data Register are described as follows.
DB256 00000
Data Word(DW) : 00000~65534
Data Block(DB) : 001~256
2. Set only “32bit swap” in case of 32bit integer, not set “32bit swap” in case of
floating point.
REF.
<Revisions>
No. Date of
Rev.
Description Rev. 1.1.5.6 Remarks
1 2003-11-03 Added the schematic diagram
of CP441 RS-422
A
2 2006-05-27 Added an example
configuration of CP341
B
3 2007-01-04 Modified the schematic
diagram of CP341 232C
C
4 2007-02-05 Modified the schematic
diagram of CP341/441 RS-422
D
5 2007-03-26 Deleted the CP340
(communication disabled)
E
6 2007-04-24 Changed the digit number of
the S7300 MPI communication
DB
F
7 2007-09-06 Added the description of the
Highest Node on MPI
G
8 2007-11-07 Removed the SG from the
schematic diagram on PPI
H
9 2008-01-24 Modified the schematic
diagram of CP341 485
I
10 2008-03-21 Added the MPI Direct J