01 capm software introduction

Post on 15-Jul-2015

394 Views

Category:

Technology

2 Downloads

Preview:

Click to see full reader

TRANSCRIPT

CAPM Software

The CAPM Evolution

First Generation

CAPM1 CAPM2 CAPM3

Second Generation

CAPM4 CAPM5

CAPM2 Software version naming scheme

Major Version Number Minor Version Number Protocol Variant Functional Variant

V9. 71 zz aa

Software version naming scheme for CAPM4/5

Version 21 Version 22 Version 23 Version 24

CAPM4

CAPM5

Version 26 Version 27 Version 28

Version 26 Version 27 Version 28

Version 25

Exclusive CAPM5 Features

Frequency Measurement Under/Over Frequency Protection

Fast Trip Input Module

19.2K Baud Rate on RS-232 Port P8

Auxiliary Panel Support

CAPM4/5 Software version naming scheme

The Software Version XXX-XX.XX

The Configuration Number 2XXXX

Examples

Software 028-07.00Configuration 21186

Software 528-07.00Configuration 21187

CAPM4 CAPM5

Software Version Details on Operator Panel

CAPM Software Version via WSOS On-Line

Compatibility of CAPM and WSOS Software

Each CAPM software version released is supported by a Windows Switchgear Operating System (WSOS) update.

Always ensure that you have the latest release WSOS and that it is compatible with the release version of CAPM software being installed.

http://www.nulec.com.au/

http://www.nulec.com.au/service/

STAR

*****

Searching for Controller Software

Filtering the Search Conditions

Searching for N Series CAPM5 Software

Search Results

Filtering on Search Description

DNP3

CAPM4/5 Software Upgrade

OBJECTIVE:

To Install the latest revision software over an existing version of CAPM4/5 software, whilst retaining all previous control and protection settings.

Equipment Required

Nu-Lec Industries Serial Cable Part No: N05-902

Laptop Personal Computer (32 bit system) with the latest version of WSOS installed.

The replacement software file.

(i.e. 21728528.13a)

The cap5load.exe file.

CAPM Software and Executable Files

CAPM4/5 Software Upgrade Procedure

Save the existing Switchgear Configuration Settings.

Download the CAPM software file to the controller using cap5load.exe.

Confirm new software is installed.

Reload Switchgear Configuration Settings.

Compare On-Line and Off-Line files.

Restore the Switchgear to Service.

Saving the Existing Switchgear Configuration

Using cap5load to load Software

Trip and Close must be isolated

Download Completed OK

Confirm New Software is Installed

Reloading Switchgear Configuration Settings

Compare Switchgear Settings

Restore ACR to Service

View the Event Log on the Operator Control Panel to confirm that a Pickup event has not been generated.

Enable the Trip and Close solenoids by returning both switches to the Enable position.

Go off-line with WSOS, disconnect and store the PC and serial cable.

CAPM Software Summary

The latest release of CAPM4/5 software is version 28.

Under/Over Frequency Protection is available on CAPM5 but not CAPM4.

CAPM4 CAPM5Software 028-07.00 Software 528-07.00

Configuration 21186 Configuration 21187

Each CAPM4/5 software release is supported by a release of WSOS Ver 4.

CAPM4/5 software is loaded using cap5load.exe from the Command Prompt.

The WSOS Compare command can be used to check that the configuration has been correctly restored following a CAPM software upgrade.

top related