ammonia system installation example on operating system using:
DESCRIPTION
AMMONIA SYSTEM INSTALLATION EXAMPLE ON OPERATING SYSTEM USING:. INSTALLATION CONDITIONS. SYSTEM AGE: 16 YEARS 85 – 90° F 85% HUMIDITY 9:30 AM EST SYSTEM TEMPERATURE 24° F 4” O.D. PRIMED STEEL PIPE 4” STYROFOAM INSULATION RG-2400 LT AT AMBIENT (90-96° F) - PowerPoint PPT PresentationTRANSCRIPT
AMMONIA SYSTEM AMMONIA SYSTEM INSTALLATION EXAMPLE ON INSTALLATION EXAMPLE ON OPERATING SYSTEM USING:OPERATING SYSTEM USING:
SYSTEM AGE: 16 YEARSSYSTEM AGE: 16 YEARS
85 – 90° F85 – 90° F
85% HUMIDITY85% HUMIDITY
9:30 AM EST9:30 AM EST
SYSTEM TEMPERATURE 24° FSYSTEM TEMPERATURE 24° F
4” O.D. PRIMED STEEL PIPE4” O.D. PRIMED STEEL PIPE
4” STYROFOAM INSULATION4” STYROFOAM INSULATION
RG-2400 RG-2400 LTLT AT AMBIENT (90-96° F) AT AMBIENT (90-96° F)
INSTALLATION TIME 21 MINUTESINSTALLATION TIME 21 MINUTES
INSTALLATION CONDITIONSINSTALLATION CONDITIONS
PICTORAL INSTALLATIONPICTORAL INSTALLATION
REMOVING METAL JACKET
METAL JACKET REMOVED
ASJ ON STYROFOAM
STYRO
FIBERGLASS EXPANSION JOINT
After removing approximately 6’ of metal jacketing, we knew corrosion would be present due to the fiberglass present, and the lack of a vapor retarder on some of the styrofoam insulation.
REMAINING PRIMER EASILY REMOVED
CLOSE-UP OF EXPANSION JOINT
PRIMER ON INSULATION
CORROSION ON PIPE
REMAINING PRIMER EASILY REMOVED
PIPE IS READY FOR RG-2400 LT
Note slight frost already forming on the pipe surface.
Primer which was well adhered to the pipe does not have to be removed.
INSTALLING RG-2400 LT
INSTALLING RG-2400 LT
Pipe temperature thickens the RG-2400 LT quickly. After 3 passes over an area it gets difficult to spread and achieve adhesion.
The slight frost on the pipe left some voids, however fresh “warm” material could be put over these areas and achieve ahesion.
A WELL COATED PIPE READY FOR INSULATION
CONCLUSIONSCONCLUSIONS
•COATING A 24° PIPE IN OPERATION IS POSSIBLE IN SMALL SECTIONS.
•RG-2400 MUST BE WARM TO IMPROVE COVERAGE AND EASE OF APPLICATION
•INSULATION MUST BE INSTALLED IMMEDIATELY UPON ACHIEVING COVERAGE TO PREVENT CONDENSATION FROM FORMING ON THE RG-2400
•INSULRAP OR FABWRAP VAPOR BARRIER SHOULD BE USED TO KEEP OUT MOISTURE
•TESTING WILL CONTINUE ON -15° F LINES IN OPERATION AND -50° F LINES IN OPERATION. RESULTS WILL BE ADDED TO THIS PPT PRESENTATION.
•GLYCOL WILL BE TESTED TO REMOVE FROST ON THE COLDER LINES.