alarm larm handling / ems / day - nfpa · nighttime alarm handling, there were unexpected diff...
TRANSCRIPT
Quantitative Evaluat
51
EMS/Daytime
As noted for alarm handling for Fire
overall rate from Table 3. Alarm Han
60 seconds and an additional 1% to 9
range of observed processing times
raises a question regarding what fact
EMS Calls
n = 66,202
NFP
Ben
Cr
Alarm Handling
60 s
90 s
Table 10. Alarm Handling Time / EMS
Figure 21. Percent of Daytime EMS Ca
46%
33%
0%
10%
20%
30%
40%
50%
0 - 30 31 - 60
Alarm
ve Evaluation of Fire and EMS Mobilization Times
Fire / Daytime responses, the EMS compliance rate is v
andling Time / EMS, down only 1% to 79% of all calls
to 91% for calls processed at or under 90 seconds (Tab
imes noted in Fire / Daytime appears once again in E
factors contribute to this difference.
NFPA 1221
Benchmark
Criteria
Observed
Compliance
60 seconds
90 %
90 seconds
99%
79%
85 seconds
91%
182 seconds / EMS / Daytime
MS Calls Handled over Time
12%
5%2% 1%
61 - 90 91 - 120 121 - 150 151 - 180
Elapsed Seconds
larm Handling / EMS / Day
EM
is very similar to the
alls processed within
Table 10). The wide
in EMS. This result
Median
Mean
Max
33
44
3565
1%
> 180
EMS Responses
Quantitative Evaluat
52
EMS/Nighttime
In contrast to daytime alarm handli
percent each from their overall va
processed within 90 seconds. This r
processing times (Table 11).
EMS Calls
n = 17,442
NFP
Ben
Cr
Alarm Handling
60 s
90 s
Table 11. Alarm Handling Time / EMS
There is no explanation for the maxi
one hour, in the data. Further resea
toward more extreme outliers during
Figure 22. Percent of /ighttime EMS C
49%
33%
0%
10%
20%
30%
40%
50%
0 - 30 31 - 60
Alarm
ve Evaluation of Fire and EMS Mobilization Times
ndling time, recorded nighttime criteria compliances i
l values to 81% of calls processed at or below 60 s
his result was accompanied by a much more narrow ra
NFPA 1221
Benchmark
Criteria
Observed
Compliance
60 seconds
90 %
90 seconds
99%
81%
80 seconds
93%
181 seconds / EMS / /ighttime
aximum processing time for EMS recorded responses,
esearch may offer some explanation of why alarm han
uring the daytime for both fire and EMS calls.
EMS Calls Handled over Time
11%
4%2% 1%
61 - 90 91 - 120 121 - 150 151 - 180
Elapsed Seconds
larm Handling / EMS / Night
ces increased by one
0 seconds and 93%
w range of observed
Median
Mean
Max
31
42
1532
ses, slightly less than
handling time tends
1%
180 > 180
EMS Responses
Quantitative Evaluat
53
Discussion Points
In the analysis of daytime versus nig
handling times that are not address
and EMS responses were typically co
Benchmark compliance for
85% at night.
Benchmark compliance for
83% at night.
The largest elapsed alarm ha
Are there differences in the r
o Are the calls differen
o Are the callers differ
Figure 23. Comparative Percent of Da
46%
33%
51%
27%
49%
33%
57%
28%
0%
10%
20%
30%
40%
50%
60%
0 - 30 31 - 60
Alarm Handl
ve Evaluation of Fire and EMS Mobilization Times
nighttime alarm handling, there were unexpected diff
ressed in the NFPA 1221 standard. Alarm handling t
ly completed in less time during the nighttime period th
for alarm handling for fire calls improved from 78% d
for alarm handling for EMS calls improved from 81% d
handling times occurred during the day.
the range of processing complexity for day versus night
erent?
ifferent?
of Day & /ight Fire & EMS Calls Handled over Time
12%
5%
2%1%
11%
5%
2% 1%
11%
4%
2%1%
8%
3%2%
1%
61 - 90 91 - 120 121 - 150 151 - 180
Elapsed Seconds
andling / Fire & EMS / Day & Night
EMS Re
Fire Res
EMS Re
Fire Res
differences in alarm
times for both fire
d than daytime.
% during the day to
% during the day to
ight calls for aid?
1%3%
1%1% 1%
180 > 180
ight
Responses / Day
Responses / Day
Responses / Night
Responses / Night
Quantitative Evaluation of Fire and EMS Mobilization Times
54
Turnout Time
Figure 24. Turnout / Fire & EMS / Day & /ight over Time
The current NFPA 1710 standard does not address the difference in day or night turnout using separate
benchmark times16
. The turnout standard for fire and EMS responses, regardless of time of day, is:
90% of all emergency responses to fire calls must turnout within 80 seconds or less.
90% of all emergency responses to EMS calls must turnout within 60 seconds or less.
The tasks common to all turnouts from the ERF were summarized in the previous section and still apply
here with changes and additions accounting for nighttime activity:
Notification of the alarm
Gathering critical response information
Disengagement from tasks in process
o Disengagement from task in progress may now include waking and orienting
o Dressing to the level of station wear required by local practice
16 “The committee does not see the need to establish separate turnout times by time of day. Fire departments
that experience significant differences depending on the time of day should evaluate what is going on during those
periods and determine if there are ways to improve those response times.” (NFPA 1710 ROC 2009, 1710-5)
0
2
4
6
8
10
0 15 30 45 60 75 90 105 120 135 150 165 180
Pe
rce
nta
ge
Elapsed Seconds
Turnout / Fire & EMS / Day & Night
Fire Daytime Turnout
EMS Daytime Turnout
Fire Nighttime Turnout
EMS Nighttime Turnout
Quantitative Evaluation of Fire and EMS Mobilization Times
55
Travel within the ERF to the ERU
o Detour to restroom
Donning PPE
Mounting the ERU and securing seatbelts
Opening ERF bay doors
Starting the ERU
Signaling “en route”
Fire/ Daytime
Analysis of a set of 13,463 daytime fire response records (Table 12) revealed that two-thirds (67%) of all
recorded daytime turnouts were accomplished in 80 seconds or less, with half of them accomplished in
66 seconds (median) or less. This is below the criterion set by NFPA 1710 for fire responses, and the
mean average of 68 seconds is below the NFPA benchmark.
Looking at how much time was actually needed to achieve the performance criteria required by the
standard, it is noted that it took 112 seconds to reach the 90% criterion for reported fire responses. This
is slightly more than one and one-third times the time allotted by the standard benchmark.
Fire Calls
n = 13,463
NFPA 1710
Benchmark
Criteria
Observed
Compliance
Median
Mean
Max
Turnout 80 seconds
90 %
67%
112 seconds
66
68
2629 Table 12. Turnout Time / Fire / Daytime
The 45 minute maximum reported turnout time and other extreme outliers noted in the overall analysis
(Table 4. Turnout Time / Fire) appear during the daytime hours continuing the trend of outliers occurring
during the day.
Quantitative Evaluat
56
Figure 25. Percent of Daytime Fire Tu
16%
28%
0%
10%
20%
30%
40%
0 - 30 31 - 60
ve Evaluation of Fire and EMS Mobilization Times
re Turnouts Completed over Time
33%
16%
5%
1%
61 - 90 91 - 120 121 - 150 151 - 180
Elapsed Seconds
Turnout / Fire / Day
1%
180 > 180
Fire Responses
Quantitative Evaluat
57
Fire/Nighttime
There was a significant drop in benc
(Table 13). Only 21%, about one res
response during this period took 10
90% compliance criterion.
Fire Calls
n = 2,681
NFP
Ben
Cr
Turnout 80 s
Table 13. Turnout Time / Fire / /ightt
Figure 26. Percent of /ighttime Fire T
4%6%
0%
10%
20%
30%
40%
0 - 30 31 - 60
Tu
ve Evaluation of Fire and EMS Mobilization Times
benchmark compliance during the 2,681 recorded nigh
response in five, met the 80-second benchmark. The
k 108 seconds, and 158 seconds are required to achiev
NFPA 1710
Benchmark
Criteria
Observed
Compliance
80 seconds
90 %
21%
158 seconds
ighttime
Fire Turnouts Completed over Time
20%
34%
23%
8%
61 - 90 91 - 120 121 - 150 151 - 180
Elapsed Seconds
Turnout / Fire / Night
nighttime responses
The median turnout
hieve the standard’s
Median
Mean
Max
108
110
1058
5%
180 > 180
Fire Responses
Quantitative Evaluation of Fire and EMS Mobilization Times
58
Examining the cumulative distribution function shown in Error! Reference source not found., it can be
noted that the main body of responses, represented by the steepest part of the curve, has not begun by
the time the benchmark has passed. The majority of turnouts do not occur until between 80 seconds
and 150 seconds.
Figure 27. CDF Fire Turnout Time / /ighttime
0
10
20
30
40
50
60
70
80
90
100
0 15 30 45 60 75 90 105 120 135 150 165 180
Cu
mu
lati
ve
Pe
rce
nta
ge
Elapsed Seconds
Turnout / Fire / Night
Fire Turnout
Fire Benchmark
90% Criterion
Quantitative Evaluat
59
EMS/Daytime
Daytime EMS responses totaled 66,
recorded daytime turnouts were acc
52 seconds (median) or less. This is
weighted average of 54 seconds (me
Looking at how much time was actu
be shown that it took 87 seconds t
almost one and one-half times the ti
EMS Calls
n = 66,202
NFP
Ben
Cr
Turnout 60 s
Table 14. Turnout Time / EMS / Dayti
The 52 minute maximum time repor
5. Turnout Time / EMS) appears du
day.
Figure 28. Percent of Daytime EMS Tu
20%
45%
0%
10%
20%
30%
40%
50%
0 - 30 31 - 60
ve Evaluation of Fire and EMS Mobilization Times
66,202 (Table 14). For this group, just under two-th
accomplished in 60 seconds or less, with half of them
is is below the criterion set by NFPA 1710 for EMS re
(mean) is close to the NFPA benchmark.
actually needed to achieve the criteria required by the
ds to reach the 90% criterion for reported fire call re
e time allotted by the standard benchmark.
NFPA 1710
Benchmark
Criteria
Observed
Compliance
60 seconds
90 %
65%
87 seconds
Daytime
eported and other extreme outliers noted in the overa
during the daytime hours, continuing the trend of ou
MS Turnouts Completed over Time
27%
6%2% 0%
61 - 90 91 - 120 121 - 150 151 - 180
Elapsed Seconds
Turnout / EMS / Day
thirds (65%) of all
hem accomplished in
responses, and the
the standard, it can
ll responses. This is
Median
Mean
Max
52
54
3112
verall analysis (Table
f outliers during the
0%
180 > 180
EMS Responses
Quantitative Evaluat
60
EMS/Nighttime
Nighttime turnout compliance drops
fire responses. With only 12% of re
one response in eight – the averag
are required to achieve the standard
EMS Calls
N= 17,442
NFP
Ben
Cr
Turnout 60 s
Table 15. Turnout Time / EMS / /ight
Figure 29. Percent of /ighttime EMS T
4%
8%
0%
10%
20%
30%
40%
50%
0 - 30 31 - 60
Tu
ve Evaluation of Fire and EMS Mobilization Times
rops considerably in the 17,442 recorded EMS respon
f recorded responses completing turnout in 60 second
erage nighttime turnout response takes 101 seconds
ard’s 90% compliance criterion.
NFPA 1710
Benchmark
Criteria
Observed
Compliance
60 seconds
90 %
12%
144 seconds
/ighttime
EMS Turnouts Completed over Time
26%
35%
19%
5%
61 - 90 91 - 120 121 - 150 151 - 180
Elapsed Seconds
Turnout / EMS / Night
ponses than it did in
onds or less – about
, and 144 seconds
Median
Mean
Max
100
101
2142
3%
180 > 180
EMS Responses
Quantitative Evaluation of Fire and EMS Mobilization Times
61
Examining the cumulative distribution function shown in Error! Reference source not found., it can be
noted that the responses have only begun when the benchmark has passed. The majority of turnouts
occur between 60 seconds and 140 seconds.
Figure 30. CDF EMS Turnout Time / /ighttime
Discussion Points
The analysis of daytime versus nighttime response turnout noted differences not specifically addressed
in the NFPA 1710 standard. Nighttime turnout times for both fire and EMS responses were significantly
below the standard benchmarks:
80 second benchmark compliance for Turnout Time for fire responses decreased from 67%
during the day to 21% at night.
60 second benchmark compliance for Turnout Time for EMS responses decreased from 65%
during the day to 12% at night.
Conversely, the largest elapsed Turnout Times occurred during the day.
0
10
20
30
40
50
60
70
80
90
100
0 15 30 45 60 75 90 105 120 135 150 165 180
Cu
mu
lati
ve
Pe
rce
nta
ge
Elapsed Seconds
Turnout / EMS / Night
EMS Turnout
EMS Benchmark
90% Criterion
Quantitative Evaluat
62
Observed turnout times for Fire and
average difference of 14 seconds (m
with the 20-second allowance in di
nighttime period turnouts, which inc
EMS, become similar, with an avera
90% criterion). The fact that the
elapsed time suggests that the m
requirements -- becomes less import
EMS median Δ) of turnout time are a
Turnout Da
Seconds median
Fire 66
EMS 52
Δ -14 Table 16. Turnout Time / Fire vs EMS
Figure 31. Comparative Percent of Da
20%
45%
16%
28%
4%
8%
4%
6%
0%
5%
10%
15%
20%
25%
30%
35%
40%
45%
50%
0 - 30 31 - 60
Turnout
ve Evaluation of Fire and EMS Mobilization Times
and EMS during the daytime period, compared in Ta
s (medians) to 25 seconds (time to 90% criterion). This
n different benchmarks for Fire and EMS set by NFPA
increase from daytime turnouts by similar increments
verage difference of only 8 seconds (medians) to 14
the two types of responses become more aligned as
e main variation between fire and EMS turnout
portant as new common tasks responsible for 42 to 48
re added during the nighttime turnout response.
Daytime Nighttime
dian 90% median 90% media
112 108 158 +42
87 100 144 +48
-25 -8 -14 EMS
of Day & /ight Fire & EMS Turnouts Completed over Tim
27%
6%
2%0%
33%
16%
5%
1%
26%
35%
19%
5%
20%
34%
23%
8%
61 - 90 91 - 120 121 - 150 151 - 180
Elapsed Seconds
out / Fire & EMS / Day & Night
EMS Re
Fire Res
EMS Re
Fire Res
Table 16, show an
his is commensurate
FPA 1710. Average
ents for both fire and
14 seconds (time to
as they increase in
ut -- different PPE
48 seconds (fire and
Δ
edian 90%
+42 +46
+48 +57
r Time
0% 1%3%
8%
5%
180 > 180
Responses / Day
Responses / Day
Responses / Night
Responses / Night
Quantitative Evaluat
63
Mobilization Time
Because the two response segments
of each, it is unlikely that the extrem
could occur. Therefore when the da
compliance with the combined stand
Figure 32. Percent of Day & /ight Fire
18%
59%
12%
54%
3%
32%
2%
0%
10%
20%
30%
40%
50%
60%
0 - 60 61 - 120
Mobilizatio
ve Evaluation of Fire and EMS Mobilization Times
ents, alarm handling time and turnout time, are essenti
tremes of each would coincide in the same response in
e data for these two response segments were combined
tandard benchmarks during daytime responses.
ht Fire & EMS Mobilizations Completed over Time
18%
4%
1%
23%
6%
2%
2%
48%
13%
3%
27%
51%
14%
3%
120 121 - 180 181 - 240 241 - 300
Elapsed Seconds
zation / Fire & EMS / Day & Night
EMS Re
Fire Res
EMS Re
Fire Res
entially independent
se incident, though it
ined, there was near
1%2%
1% 2%
> 300
Responses / Day
Responses / Day
Responses / Night
Responses / Night
Quantitative Evaluat
64
Fire/Daytime
As noted, daytime compliance is
Mobilization Time / Fire.
Fire Calls
N=13,463
(328)
Ben
Mobilization
140
Table 17. Mobilization Time / Fire / Da
Figure 33. Percent of Daytime Fire Mo
12%
54%
0%
10%
20%
30%
40%
50%
60%
0 - 60 61 - 120
Mo
ve Evaluation of Fire and EMS Mobilization Times
is slightly better than overall compliance as sho
Implicit
Benchmark
Criteria
Observed
Compliance
140 seconds
81 %
90%
78%
148 seconds
184 seconds
re / Daytime
re Mobilizations Completed over Time
4%
23%
6%
2%
120 121 - 180 181 - 240 241 - 300
Elapsed Seconds
Mobilization / Fire / Day
shown in Table 6.
Median
Mean
Max
103
134
5966
2%
> 300
Fire Responses
Quantitative Evaluat
65
Fire/Nighttime
Mobilization compliance (Table 18
compliance with the combined perfo
1710, and required 32 seconds beyo
Fire Calls
N=2,681
(125)
Ben
Mobilization
140
Table 18. Mobilization Time / Fire / /i
Figure 34. Percent of /ighttime Fire M
2%
27%
0%
10%
20%
30%
40%
50%
60%
0 - 60 61 - 120
Mob
ve Evaluation of Fire and EMS Mobilization Times
18) drops considerably during the nighttime peri
erformance criterion created from the criteria in NFPA
eyond the benchmark to achieve compliance.
Implicit
Benchmark
Criteria
Observed
Compliance
140 seconds
81 %
90%
52%
180 seconds
208 seconds
re / /ighttime
Fire Mobilizations Completed over Time
7%
51%
14%
3%
120 121 - 180 181 - 240 241 - 300
Elapsed Seconds
Mobilization / Fire / Night
period to only 55%
FPA 1221 and NFPA
Median
Mean
Max
138
149
1671
2%
> 300
Fire Responses
Quantitative Evaluat
66
EMS/Daytime
Daytime compliance (Error! Referen
compliance as shown in Table 7 Mob
compliance with the implied criterion
EMS Calls
N= 66,202 Ben
Mobilization
120
Table 19. Mobilization Time / EMS / D
Figure 35. Percent of Daytime EMS M
18%
59%
0%
10%
20%
30%
40%
50%
60%
0 - 60 61 - 120
Mo
ve Evaluation of Fire and EMS Mobilization Times
rence source not found.) improved by 7% compared to
Mobilization Time / EMS. As occurred with Fire / Daytim
erion is very nearly achieved.
Implicit
Benchmark
Criteria
Observed
Compliance
120 seconds
81 %
90%
77%
127 seconds
153
S / Daytime
MS Mobilizations Completed over Time
9%
18%
4%1%
120 121 - 180 181 - 240 241 - 300
Elapsed Seconds
Mobilization / EMS / Day
d to overall
ytime responses,
Median
Mean
Max
88
99
3615
1%
> 300
EMS Responses
Quantitative Evaluat
67
EMS/Nighttime
Mobilization compliance (Table 20) d
implied criterion requiring 48 second
EMS Calls
N= 17,442
(822)
Ben
Mobilization
120
Table 20. Mobilization Time / EMS / /
Figure 36. Percent of /ighttime EMS M
3%
32%
0%
10%
20%
30%
40%
50%
60%
0 - 60 61 - 120
Mob
ve Evaluation of Fire and EMS Mobilization Times
) drops considerably during the nighttime period to o
onds beyond the benchmark to achieve compliance.
Implicit
Benchmark
Criteria
Observed
Compliance
120 seconds
81 %
90%
35%
176 seconds
203 seconds
S / /ighttime
EMS Mobilizations Completed over Time
2%
48%
13%
3%
120 121 - 180 181 - 240 241 - 300
Elapsed Seconds
Mobilization / EMS / Night
to only 37%, with the
Median
Mean
Max
135
143
2219
1%
> 300
EMS Responses
Quantitative Evaluation of Fire and EMS Mobilization Times
68
6.3 Firefighter Crew Proficiency in Baseline Turnout Exercise
Results from a total of 106 turnout exercises were submitted, representing 13 participating fire
departments. Since there is no definition provided in NFPA 1710 and no clear peer consensus of criteria
on “en route” status, results were collected and are reported using both the moment the apparatus’
wheels were visibly rolling17
(“wheels rolling”) and the moment when the front bumper of the apparatus
crossed the garage door sill18
(“crosses sill”).
Turnout Exercise
n = 106
NFPA 1710
Benchmark
Criteria
Observed
Compliance
Median
Mean
Max
En Route “Wheels Rolling”
80 seconds
90 %
81%
85 seconds
68
67
112
En Route “Crosses Sill”
80 seconds
90 %
70%
92 seconds
72
74
114
Table 21. Turnout Exercise Summary
Figure 37. CDF Baseline Turnout Exercise
17 This criterion has been suggested informally in conversation with members of the NFPA 1710 committee.
18 The “crosses sill” criterion is suggested in NFPA Structural Firefighting Strategy and Tactics: “The third segment is
the turnout time. This is the time from the receipt of the alarm until the apparatus crosses the front door sill of the
station.” (Klaene and Sanders 2008, 125)
0%
20%
40%
60%
80%
100%
0 15 30 45 60 75 90 105 120
Cu
mu
lati
ve
Pe
rce
nta
ge
Elapsed Seconds
Turnout Exercise
"Wheels Rolling"
"Crosses Sill"
Fire Benchmark
90% Criterion
Quantitative Evaluation of Fire and EMS Mobilization Times
69
The results indicate that, even under ideal conditions, the process of turnout requires substantially
longer than the NFPA 1710 standard currently allows. Using the more liberal “wheels rolling” criterion,
benchmark compliance is achieved only 81% of the time rather than the 90% target established by the
standard. In order to reach the 90% target, 85 seconds were required (Figure 37. CDF Baseline Turnout
Exercise). Using the more conservative “crosses sill” criterion, benchmark compliance is achieved only
70% of the time, with 92 seconds required to achieve the targets established by the standard (Figure 37.
CDF Baseline Turnout Exercise).
These results are slightly slower but consistent with the preliminary results of the original study utilizing
the Baseline Turnout Exercise.19
19 With n = 38, mean “en route” times of 68 and 70 seconds respectively were recorded for “wheels rolling” and
“crosses sill” criteria. A third criteria, “rear bumper crosses sill” (mean “en route” time of 74 seconds) was
dropped from the standardized version of the exercise for this study to make it more portable. (Upson 2009)
Quantitative Evaluation of Fire and EMS Mobilization Times
70
6.4 Effects of Station Layout on Turnout Response
The physical attribute of an ERF has a direct influence on firefighter turnout time. Responding crews
must traverse between work and other activity areas and the ERU itself. Both horizontal and vertical
foot travel distances add time to any emergency turnout.
Horizontal Travel
A commonly cited factor for calculating travel times by average adults without a locomotor disability is a
mean walking speed of 4.10 fps (1.25 m/s). This factor has been measured for horizontal travel while
evacuating a building (Boyce, Shields and Silcock 1999, 54). This measure is cited in both The SFPE
Handbook of Fire Protection Engineering (Bryan, Behavioral Response to Fire and Smoke 2002, 3-360)
and in the Fire Protection Handbook (Bryan, Human Behavior and Fire 2008, 4-40). For this study a
factor closer to 5.8 fps, the highest speed recorded by Boyce, Shields and Silcock, was assumed to be
more appropriate for firefighters moving to their ERU during turnout.
To empirically assess this factor, firefighters from 13 participating fire departments were timed over a
measured indoor course walking as if they were responding to an emergency call. Firefighters
participating in the timed walking exercise were instructed “not to run.” This exercise established a
reasonable estimation of how quickly firefighters might be expected to travel safely to reach their
apparatus when actually responding to an alarm.
Alarm Response Walk
(Horizontal Travel)
Mean walking speed
(fps) Seconds per 50’
n = 335 4.98 10.03 Table 22. Alarm Response / Horizontal
The mean walking speed recorded was 5 fps, or 10 seconds for every 50 feet of horizontal foot travel, as
shown in Table 22. This exercise, conducted by multiple raters in 13 fire departments, is slightly slower
but not inconsistent with the results of an earlier study that recorded an average speed of 5.7 fps using
a highly motivated and competitive subject pool associated with the DHS-funded Firefighter Safety and
Deployment Study (Upson 2009).
Vertical Travel
A smaller, more closely controlled set of timed exercises was used to estimate firefighter travel times for
travel up and down stairs and down fire poles. A conservative value of 1.71 fps for vertical travel was
chosen to represent a reasonable estimation of all typical vertical indoor travel. This value is actually
slower than the value of 2.3 fps cited by Boyce, Shields and Silcock (Boyce, Shields and Silcock 1999) but
Quantitative Evaluation of Fire and EMS Mobilization Times
71
is within the lower average range20
. Firefighters participating in timed stair exercises were instructed
not to run and to “touch every step” as a safety measure consistent with instructions used in CPAT
program,21
which conceivably resulted in more conservative average speeds.
Alarm
Response
(Vertical
Travel)
Down
(seconds)
Down
(fps)
Up
(seconds)
Up
(fps)
n 11 11 10 10
Straight Run
Stair (8.5') 3.46 2.46 2.94 2.89
Return Run
Stair (10') 6.53 1.53 6.16 1.62
Fire Pole (10') 5.52
Estimated
Typical 2.13
Table 23. Alarm Response / Vertical
In order to more easily quantify travel time using combined horizontal and vertical components, a
horizontal equivalency was calculated for a nominal 10-foot flight of stairs. Based on the mean
horizontal and vertical speeds noted above, a conversion factor of 2.17 was derived. This is equivalent
to 22 feet of horizontal travel for each nominal 10 feet of vertical travel.
Horizontal
Equivalency
Horizontal
Travel
(fps)
Vertical
Travel
(fps)
Conversion
(Horizontal/Vertical)
Horizontal
Equivalent
Nominal 10’
Stair
(feet)
4.98 2.30 2.17 21.7
Table 24. Alarm Response / Conversion
20 With n = 8, that study cites a mean descending speed of 2.3 fps with a range of 1.5 – 3.6 fps and an interquartile
range of 1.7 – 2.9 fps. 21
Candidate Physical Ability Test Program (The IAFF/IAFC Wellness-Fitness Task Force n.d.)
Quantitative Evaluation of Fire and EMS Mobilization Times
72
Station Layout
The Baseline Turnout Exercise is based on an event in which all the crew members are within 50 feet of
their assigned apparatus at the time of alarm. To estimate times in which foot travel exceeds 50 feet, a
walking speed of 5 fps22
, or 10 seconds for every additional 50 feet of travel, can reasonably be used to
project the minimum turnout time required.
Measurements of horizontal travel distances were made from the door of the primary apparatus to
various key locations in 197 fire stations. Where vertical components were part of the path of travel,
the horizontal equivalency calculated above was added to the horizontal distance. Based on the average
travel distances recorded, it is reasonable to assume that firefighters responding to an alarm may
typically have to travel in excess of 100 feet inside the station to reach their assigned ERU. This measure
equates to another 10 seconds of turnout time beyond the baseline established by the Ideal Turnout
Exercise.
Station
Layout
n = 197
Day Room
Travel
n = 195
Training
Room
Travel
n = 179
Dining /
Kitchen
Travel
n = 195
Fitness
Room
Travel
n = 190
Sleeping
Room
Travel
n = 197
min
median
mean
std dev
max
11
72
70
34
192
6
72
71
37
237
8
69
71
30
155
5
68
74
43
226
13
75
84
36
212 Table 25. Station Layout Summary
22 With n = 131, mean walking speed was calculated at 5.7fps. (Upson 2009)
Quantitative Evaluation of Fire and EMS Mobilization Times
73
7 Conclusions
I. The actual recorded alarm handling times, provided to this study from a group of large fire
departments, were compiled, statistically analyzed, and compared to the target alarm handling
times given in NFPA 1221. Results demonstrated that:
a. For both fire and EMS calls, the mean average alarm handling times observed were less
than 60 seconds
b. For approximately 80% of the fire and EMS calls, alarm handling was completed in the
required 60 seconds or less.
c. 80% of calls processed in 60 seconds or less falls below the 90% targeted in the
standard.
d. The time required for alarm handling of 90% of the calls was 92 seconds for fire (slightly
over one and one-half times the standard) and 84 seconds for EMS (slightly less than
one and one-half times the standard).
e. A second benchmark is set in the standard, which targets 90 seconds to process 99% of
the calls. At an elapsed time of 90 seconds, approximately 90% of the calls were
processed rather than the 99% required. Given the observed distribution of alarm
handling times, where a very long tail is observed, the 99% criterion may not be
particularly useful for benchmarking. A long tail is observed in the distribution, which
represents long alarm handling times for a certain fraction of the fire and EMS calls.
0
10
20
30
40
50
60
70
80
90
100
0 15 30 45 60 75 90 105 120 135 150 165 180
Cu
mu
lativ
e P
erc
en
tag
e
Elapsed Seconds
Alarm Handling / Fire & EMS (combined)
Fire & EMS Alarm Handling
Fire & EMS Benchmark #1
90% Criterion
Fire & EMS Benchmark #2
99% Criterion
Quantitative Evaluation of Fire and EMS Mobilization Times
74
II. The actual recorded turnout times, provided to this study from a group of large fire
departments, were compiled, statistically analyzed, and compared to the target alarm handling
times given in NFPA 1710.
a. For both fire and EMS calls, the mean average turnout times observed fell well within
their respective current benchmarks of 80 seconds for fire and 60 seconds for EMS.
i. For approximately 60% of the fire calls, turnout was completed in the required
80 seconds or less.
ii. For approximately 54% of the EMS calls, turnout was completed in the required
60 seconds or less.
b. The time actually required and recorded for turnout of 90% of the calls was 123 seconds
for fire (slightly over one and one-third times the standard) and 109 seconds for EMS
(slightly more than one and two-thirds times the standard).
III. The actual recorded turnout times, provided to this study from a group of large fire
departments, showed a highly significant difference in turnout times between daytime and
nighttime hours, a factor not currently addressed in NFPA 1710.
a. Turnout Times were compared between daytime hours (0600 to 1800), when crews are
presumably at their highest readiness, and nighttime hours (0000 to 0600), when they
are presumably at their lowest readiness.
b. For both fire and EMS nighttime calls, the mean average turnout times observed fell
well above their current NFPA 1710 benchmarks.
0
10
20
30
40
50
60
70
80
90
100
0 15 30 45 60 75 90 105 120 135 150 165 180
Cu
mu
lativ
e P
erc
en
tag
e
Elapsed Seconds
Turnout / Fire & EMS
EMS Turnout
Fire Turnout
EMS Benchmark
Quantitative Evaluation of Fire and EMS Mobilization Times
75
i. For only approximately 21% of the nighttime fire calls, turnout was completed in
the required 80 seconds or less.
ii. For only approximately 12% of the nighttime EMS calls, turnout was completed
in the required 60 seconds or less.
c. The time required for turnout of 90% of the nighttime calls was 158 seconds for fire (just
under two times the standard) and 144 seconds for EMS (slightly more than two and
one-third times the standard).
IV. The simulated turnout times recorded in the Baseline Turnout Exercise, reported from a diverse
group of fire departments, exceeded the benchmarks set in NFPA 1710.
a. For simulated fire EMS calls, the mean average turnout times observed fell well within
their respective current benchmark of 80 seconds.
i. For approximately 80% of the exercise trials using the “wheels rolling” criterion,
turnout was completed in the required 80 seconds or less.
ii. For approximately 70% of the exercise trials using the “crosses sill” criterion,
turnout was completed in the required 80 seconds or less.
b. Both percentages of simulated turnouts completed in 80 seconds or less fall well below
the 90% targeted in the standard.
c. The time actually required and recorded for turnout of 90% of the calls was 86 seconds
for the “wheels rolling” criterion and 96 seconds for the “crosses sill” criterion.
0
10
20
30
40
50
60
70
80
90
100
0 15 30 45 60 75 90 105 120 135 150 165 180
Cu
mu
lativ
e P
erc
en
tag
e
Elapsed Seconds
Turnout / Fire & EMS / Night
Fire Turnout
Fire Benchmark
EMS Turnout
EMS Benchmark
90% Criterion
Quantitative Evaluation of Fire and EMS Mobilization Times
76
V. The Station Layout Data collected indicates that the average station requires as much as twice
the travel distance and time to reach the ERU from common station areas as is provided in the
Baseline Turnout Exercise.
a. Foot travel distance and time to sleeping areas is, on the average, significantly greater
than travel distance to any other part of the ERF.
b. Foot travel requires 10 seconds for every 50 feet traveled within the ERF, and stairs
more than double that rate.
Station
Layout
n =
197
Day Room
Travel
n = 195
Training Room
Travel
n = 179
Dining /
Kitchen Travel
n = 195
Fitness Room
Travel
n = 190
Sleeping Room
Travel
n = 197
min
median
mean
std dev
max
11
72
70
34
192
6
72
71
37
237
8
69
71
30
155
5
68
74
43
226
13
75
84
36
212
0
10
20
30
40
50
60
70
80
90
100
0 15 30 45 60 75 90 105 120 135 150 165 180
Cu
mu
lativ
e P
erc
en
tag
e
Elapsed Seconds
Turnout / Fire / Responses & Exercise
Fire Response
Fire Benchmark
90% Criterion
"Wheels Rolling"
"Crosses Sill"
Quantitative Evaluation of Fire and EMS Mobilization Times
77
8 Future Study Questions
Are there differences in the range of processing complexity for fire versus EMS calls for aid?
Are there differences in the efficiency of processing algorithms for fire versus EMS calls for aid?
Does the nature and complexity of calls vary by time of day?
Are fire versus EMS calls for aid similarly classified and processed as “emergency” responses?
How much transmission delay is typically introduced between dispatcher initiation and ERF
notification of an alarm?
How does advanced technology impact alarm handling times?
o CAD to CAD interfaces among PSAPs and response agencies
o Enhanced mapping data/software
o Call taker / Dispatcher workflow analysis
How does the method of alarm notification affect ERU crew turnout times?
o Automated dispatch messaging / locution systems
What are the variations in ERU crew turnout times based on the perceived severity of the
emergency?
Quantitative Evaluation of Fire and EMS Mobilization Times
78
(This page left intentionally blank)
Quantitative Evaluation of Fire and EMS Mobilization Times
79
Works Cited
Averill, Jason D., Lori Moore-Merrell, Kathy A. Notarianni, Robert Santos, and Adam Barowy. "Multi-
Phase Study on Firefighter Safety and Deployment Study Year 1 Final Report." FireReporting.org.
September 19, 2008. http://www.firereporting.org/pdfs/2008_Year_1_Final_Report.pdf (accessed
March 2010).
Boyce, K. E., T. J. Shields, and G. W. H. Silcock. "Toward the Characterization of Building Occupancies
fore Fire Safety Engineering: Capabilities of Disabled People Moving Horizontally and on an Incline." Fire
Technology 35, no. 1 (1999): 51 - 67.
Bryan, John L. "Behavioral Response to Fire and Smoke." Chap. 12 in The SFPE Handbook of Fire
Protection Engineering, edited by Philip J. DiNenno. Quincy, MA: NFPA, 2002.
Bryan, John L. Human Behavior and Fire. Vol. 1, chap. 4-1 in Fire Protection Handbook, edited by Arthur
E. Cote, 4-3 - 4-47. Quincy, M: NFPA, 2008.
CPSE/Deccan International. Turnout Investigation. internal report to NFPA 1710 Technical Committee,
Center for Public Safety Excellence, unpublished, 2007.
Gill, Chris. unpublished correspondence, 2 13, 2009.
—. "IRMP Year III – Turnout Times." Royal Berkshire Fire and Rescue Service. 4 23, 2007.
http://library.rbfrs.co.uk/public_agendas/osrqj100.doc (accessed March 2010).
Klaene, Bernard J., and Russell E. Sanders. NFPA Structural Firefighting Strategy and Tactics. 2nd.
Sudbury, MA: Jones and Bartlett Publishers, 2008.
Microsoft Corporation. "Excel 2007." Part of Microsoft Office Small Business Edition 2007. 2006.
NFPA 1221. NFPA 1221, Standard for the Installation, Maintenance, and Use of Emergency Services
Communications Systems. 2010. Quincy, MA: NFPA, 2009.
NFPA 1710. NFPA 1710, Standard for the Organization and Deployment of Fire Suppression Operations,
Emergency Medical Operations, and Special Operations to the Public by Career Fire Departments. 2010.
Quincy, MA: NFPA, 2009.
NFPA 1710 ROC. 2009 Annual Revision Cycle Report on Comments. Quincy, MA: NFPA, 2009, 1710-5 --
1710-10.
Office of Strategic Planning and Information Systems of the Greensboro (NC) Fire Department; Guilford
Metro 911 Emergency Communications Center. "MCT Enroute 800MHz Timing Study." internal study,
Office of Strategic Planning and Information Systems, Greensboro (NC) Fire Department, NC, 2007.
SAS Institute Inc. "SAS." Cary, NC: SAS Institute Inc., 2003.
Quantitative Evaluation of Fire and EMS Mobilization Times
80
The IAFF/IAFC Wellness-Fitness Task Force. IAFF: Wellness-Fitness Initiative.
http://www.iaff.org/hs/CPAT/cpat_index.html (accessed March 2010).
U.S. Fire Administration. USFA Fire Departments. 2008.
http://www.usfa.dhs.gov/statistics/departments/index.shtm (accessed March 2010).
Upson, Robert P.S. Turnout Validation Study. Independent Study Project, Fire Protection Engineering,
Worcester Polytechnic Institute, Worcester, MA: unpublished, 2009.
Quantitative Evaluation of Fire and EMS Mobilization Times
81
Appendices
A Project Summary
B Participant Invitation / Questionnaire
C Participant Survey
D Request for Historical Data
E Station Layout / Turnout Exercise Forms
F Turn Out Exercise Instructions
G Raw Versus Filtered Data
1 Batterymarch Park, Quincy, MA 02169-7471
Telephone: +1.617.984.7281 Fax: +1.617.984.7010 Email: [email protected]
www.nfpa.org/foundation
QUANTITATIVE EVALUATION OF FIRE & EMS MOBILIZATION TIMES
Project Summary 17 March 2009
Background:
Comprehensive data on fire emergency and EMS call processing and turnout time is largely absent
from the published literature. A critical factor in the effectiveness of any emergency response
agency is the ability to get personnel and equipment to the scene of the emergency in a timely
manner.
Mobilization time is measureable time interval from call receipt at a public safety answering point
until the first assigned emergency response unit is physically en route to the emergency. Operational
benchmarks for call processing and resource turnout would be greatly enhanced with strong
empirical validation, and this information would be of direct benefit to the following three NFPA
standards that address certain aspects of this topic: NFPA 1221, Public Fire Service Communications
Systems, NFPA 1710, Career Fire Department Deployment, and NFPA 1720, Volunteer Fire
Department Deployment.
It is generally accepted that certain factors will cause mobilization times to increase or decrease.
Examples of such factors include: combined versus distinct public safety answering points and
communications centers; method of notification for emergency response facilities and emergency
response units; type of emergency dispatched; emergency response unit crew activity at time of
response; emergency response facilities layout; emergency response unit crew travel in station; and
emergency response unit crew proficiency in basic turnout tasks. What is not known is the
importance of each of these factors or combinations of factors to the magnitude of that change.
Collection of a large amount of mobilization time data for stations with different types of
communications centers, methods of notification, etc. would provide insight as to each factor’s
relative importance to mobilization time. These results will provide an objective basis for
further development of the NFPA standards addressing this topic, as well as contributing
critical information for chiefs and city managers tasked with optimum deployment of
emergency response facilities and emergency response units.
Project Goal and Objectives:
The goal of this study is to provide a quantitative evaluation of fire emergency and EMS mobilization
times, and to identify the key factors affecting their performance. This study will achieve this goal by
developing a clear statistical picture of actual fire emergency and EMS call processing and turnout
times for a variety of emergency types across a large representative population of fire departments.
Additionally, the study will identify the most significant factors that affect variation in call processing
and turnout times in those departments.
Page 2 of 2
Scope/Tasks:
This study will utilize a large pool of available fire department information that has already been
collected for a related study on fire fighter safety and deployment study. This information represents
approximately 400 agencies, and a subset will be asked to participate in this study on mobilization
time study based on the availability of communications center time segment documentation that
they are generally required to individually collect. Mobilization time data will be collected,
coordinated and analyzed in relation to the effects of specific factors potentially affecting variance in
mobilization time.
This project involves the following steps:
1) Task 1 – Project Technical Panel. Formation of a Project Technical Panel by FPRF from the
community of directly affected parties and technical experts on the subject.
2) Task 2 – Survey Population and Form. Identify a representative cross-section of participant
emergency response organizations from the available sample population, sufficient to include at
least 100 emergency response facilities, and develop survey form.
3) Task 3 – Data Collection. Implement and finalize data collection efforts based on survey form
results, and historical and other available data sources.
4) Task 4 – Data Analysis. Analyze mobilization time data through statistical evaluation and follow-
up of data outliers to identify cause.
5) Report and Dissemination. Develop the final report based on review from the Project Technical
Panel, and circulate to the applicable NFPA Technical Committees and other interested parties.
Implementation and Final Report:
The research program will be conducted under the auspices of the Fire Protection Research
Foundation and will be guided by a Project Technical Panel consisting of technical experts that will
review periodic reports of progress, research results, and the final project report. The schedule for
this study intends to have a final report by 15 December 2009.
MOBILIZATION STUDY Robert Upson, MSFPE Candidate
Kathy Notarianni, PhD, P.E. Department of Fire Protection Engineering
Worcester Polytechnic Institute
100 Institute Road
Worcester, MA 0169
June 1, 2009
Dear Chief:
You can accomplish something meaningful with just a small amount of your time. As a participant in the Department of
Homeland Security sponsored Firefighter Safety and Deployment Study, we invite your department to participate in a
new study, sponsored by the NFPA’s Fire Protection Research Foundation. The goal of this complimentary study is to
collect and document fire department call processing and turnout times. This study will provide useful information for
NFPA committees, other policy setting groups, and most importantly, fire department planners and managers.
As part of this project, data will be collected nationwide on emergency call processing, dispatch, and turnout times for
fire service based fire and EMS emergencies. This data will be used to establish an accurate estimate of the time typically
needed to mobilize emergency forces. We will also collect data on factors that affect mobilization time in order to
provide practical guidance for improving mobilization speed.
All participants will be asked to complete an online survey (estimated 30 – 45 minutes):
• Identifying characteristics of their department’s call handling and dispatching methods
• Providing summary information about each of their fire stations and assigned response units
Selected participants will be asked to:
• Conduct a simple timed turnout exercise to help establish minimum recommended standards
• Share call processing and turnout time data from some of your actual responses
This study is endorsed by Association of Public-Safety Communications Officers, Center for Public Safety Excellence,
International Association of Fire Chiefs, International Association of Fire Fighters, Metropolitan Fire Chiefs, National
League of Cities, and National Volunteer Fire Council.
Please take a few moments to complete and return the brief attached questionnaire and indicate if your department
would be willing to participate in this study. Study data, results, and conclusions will be shared with all participating
departments. Study information is available at our website, http://MobilizationStudy.org, and we would be more than
happy to personally answer any questions that you might have about our study.
Your time and assistance is our most valuable resource.
Best regards,
Robert Upson Kathy Notarianni Robert Upson Kathy Notarianni
Deputy Fire Marshal, New Hartford, CT Chair, Department of FPE, WPI
[email protected] [email protected]
Chief Sample
Your Fire Department
123 Main Street
Anytown, USA 01234-5678
MOBILIZATION STUDY PARTICIPANT SCREENING QUESTIONNAIRE
Please complete and return by as soon as possible to: Department of Fire Protection Engineering, Worcester
Polytechnic Institute, 100 Institute Road, Worcester, MA 01609-2280 or fax: (508) 831-5862 or email:
Chief Sample
Your Fire Department
123 Main Street
Anytown, USA 01234-5678
(Please correct any errors in your department contact information for our records.)
Please complete this brief Call Processing/Dispatch Questionnaire:
1) Who operates the Primary Public Service Answering Point (PSAP) for 9-1-1 calls for your department?
FD Comm Center ______ Police Dept ______ Other Agency _____ Specify __________________________
2) Who receives Direct Dialed Emergency Calls for your department?
FD Comm Center ______ Police Dept ______ Other Agency _____ Specify __________________________
3) Who receives Automatic Alarms for your department?
FD Comm Center ______ Police Dept ______ Other Agency _____ Specify __________________________
4) Does your PSAP and/or FD Comm Center maintain call processing records in accordance with NFPA 1221?
(This includes documentation of type of call, call receipt, transfer (if applicable), dispatch, and unit response times.)
Yes _____ No _____ Unknown _____
a) If Yes, are these times documented in computer a file format that can be exported in a portable format?
Yes _____ No _____ Unknown _____
Would you be willing to participate further in the full 2009 Mobilization Study?
Yes, I Accept _____ No, I Decline _____ Authorized Signature _________________________
What is your department’s NFIRS FDID? ___ ___ ___ ___ ___ NA / No FDID ______
(This information will help us merge your data with additional data from the NFIRS database.)
Who will be your department’s designated contact for this study?
Self _____ Other _____ _________________________________________________
(If Other, Contact’s full name and title)
Please supply an email address that we may use to reach your department’s designated
contact in connection with this study: _______________@___________________._____
WPI Mobilization Study
General Participant Survey
1 Revision 3
It may be helpful to print out this list as a guide and data gathering sheet before
filling in the online survey. You may complete the online survey in multiple
sessions if you do not have all the information requested at once.
Fire Department Demographics
1) Please enter your Username
2) What is the approximate population served by your department?
3) How many fire stations does your department operate? (fill in all that apply)
a) Manned 24/7 by career staff?
b) Manned 24/7 by career staff with additional paid-on-call or volunteer staff?
c) Manned part-time by career staff?
d) Manned part-time by career staff with additional paid-on-call or volunteer staff?
e) Manned entirely by paid-on-call or volunteer staff?
4) How many fire incidents as defined by NFIRS v5.0 did your department respond to during
2008?
�FIRS v5.0 I�CIDE�T TYPE CODES (Series 100)
Fire. Includes fires out on arrival and gas vapor explosions (with extremely rapid combustion).
This number should include all responses to hostile fires. It should not include calls
for controlled burning, authorized or otherwise.
WPI Mobilization Study
General Participant Survey
2 Revision 3
5) How many structure fire incidents as defined by NFIRS v5.0 did your department respond to
during 2008?
6) How many non-fire life threatening emergencies, excluding EMS calls, did your department
respond to during 2008?
�FIRS v5.0 I�CIDE�T TYPE CODES (Series 100)
Structure fire
111 Building fire. Excludes confined fires (113–118).
112 Fire in structure, other than in a building. Included are fires on or in piers, quays, or pilings: tunnels or underground
connecting structures; bridges, trestles, or overhead elevated structures; transformers, power or utility vaults or
equipment; fences; and tents.
113 Cooking fire involving the contents of a cooking vessel without fire extension beyond the vessel.
114 Chimney or flue fire originating in and confined to a chimney or flue. Excludes fires that extend beyond the chimney
(111 or 112).
115 Incinerator overload or malfunction, but flames cause no damage outside the incinerator.
116 Fuel burner/boiler, delayed ignition or malfunction, where flames cause no damage outside the fire box.
117 Commercial compactor fire, confined to contents of compactor. Excluded are home trash compactors.
118 Trash or rubbish fire in a structure, with no flame damage to structure or its contents.
Fire in mobile property used as a fixed structure. Includes mobile homes, motor homes, camping
trailers.
121 Fire in mobile home used as a fixed residence. Includes mobile homes when not in transit and used as a structure for
residential purposes; and manufactured homes built on a permanent chassis.
122 Fire in a motor home, camper, or recreational vehicle when used as a structure. Includes motor homes when not in
transit and used as a structure for residential purposes.
123 Fire in a portable building, when used at a fixed location. Includes portable buildings used for commerce, industry, or
education and trailers used for commercial purposes.
120 Fire in mobile property used as a fixed structure, other.
�FIRS v5.0 I�CIDE�T TYPE CODES for non-life threatening emergencies
Series Heading
200 Overpressure Rupture, Explosion, Overheat (No Ensuing Fire)
300 Rescue and Emergency Medical Service (EMS) Incidents
400 Hazardous Condition (No Fire)
800 Severe Weather and Natural Disaster
Typically these calls are represented by NFIRS Series 200, 300 (Excluding 321, EMS only
321), 400, & 800. These include but are not limited to explosions without fire, rescue
calls, hazardous materials incidents, and natural disasters.
WPI Mobilization Study
General Participant Survey
3 Revision 3
7) Does your department provide EMS services?
8) If Yes, does your department provide EMS primary response and ambulance
transportation?
9) If Yes, how many BLS calls did your department respond to during 2008?
10) If Yes, how many ALS calls did your department respond to during 2008?
11) Does your department assign response priorities at the time of dispatch?
12) If yes, are these response priorities documented as part of your dispatch
records?
13) If yes, what priority levels are used by your department?
14) What does your department call each level used? (check all that apply)
Emergency Response; lights and sirens to full extent of law
Urgent Response; lights and sirens with restrictions
Prompt Response; respond immediately with normal flow of traffic
Routine Response; respond when available with normal flow of traffic
Other level of response
Call Processing and Emergency Dispatching System
15) 9-1-1 Emergency Call intake for your department is handled by:
Your Fire Department Operated PSAP/Communications Center
Local Police Department Operated PSAP/Communications Center
Other Local Agency Operated PSAP/Communications Center
Regional Public Safety Answering Point/Communications Center
WPI Mobilization Study
General Participant Survey
4 Revision 3
16) Direct Dialed Emergency Call intake for your department is handled by:
(Include reports of automatic fire alarms relayed by commercial monitoring services)
Your Fire Department Operated PSAP/Communications Center
Local Police Department Operated PSAP/Communications Center
Other Local Agency Operated PSAP/Communications Center
Regional Public Safety Answering Point/Communications Center
17) Automatic Alarm intake for your department is handled by:
Your Fire Department Operated PSAP/Communications Center
Local Police Department Operated PSAP/Communications Center
Other Local Agency Operated PSAP/Communications Center
Regional Public Safety Answering Point/Communications Center
18) Are emergency calls/alarms for your department dispatched by the same agency that
receives them or transferred to a separate Communication Center for Dispatching?
PSAP dispatches calls directly
PSAP transfers calls to Communication Center
19) Do your Call Intake Communicators process calls using written Standard Operating
Procedures?
WPI Mobilization Study
General Participant Survey
5 Revision 3
20) What kind of training is provided to your Call Intake Communicators? (check all that apply)
Certified to APCO standard (PST, EMD)
Certified to NAED standard (ETC, EFD, EMD, EPD,)
Certified to NFPA 1061 standard (Level I, II, III)
Certified to NHSTA/DOT standard (EMD)
Certified to State/Local standard
Certified by State/Local Agency
Certified by Private Training Agency
Trained by State/Local Agency program
Trained by Private Training Agency
Trained in-house
Recertified periodically (i.e. annually, bi-annually)
Continuing Education required (i.e. minimum required hours per year of approved training)
21) What kind of training is provided to your Communications Center Dispatchers? (check all
that apply)
Certified to APCO standard (PST, EMD)
Certified to NAED standard (ETC, EFD, EMD, EPD,)
Certified to NFPA 1061 standard (Level I, II, III)
Certified to NHSTA/DOT standard (EMD)
Certified to State/Local standard
Certified by State/Local Agency
Certified by Private Training Agency
Trained by State/Local Agency program
Trained by Private Training Agency
Trained in-house
Recertified periodically (i.e. annually, bi-annually)
Continuing Education required (i.e. minimum required hours per year of approved training)