air-water heat pumps for outdoor or indoor … · allows the circulation of the water on the plant...

32
HMP HT AIR-WATER HEAT PUMPS FOR OUTDOOR OR INDOOR INSTALLATION TECHNICAL MANUAL R E F R I G E R A N T G A S E C O - F R I E N D L Y .0 65

Upload: others

Post on 15-Jul-2020

0 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: AIR-WATER HEAT PUMPS FOR OUTDOOR OR INDOOR … · Allows the circulation of the water on the plant side keeping constant the temperature difference between inlet and outlet. Domestic

HMP HTAIR-WATERHEAT PUMPSFOR OUTDOOR OR INDOOR INSTALLATION

TECHNICAL MANUAL

RE

FRIGERANT G

AS

E

CO-FRIEND

LY

.065

Page 2: AIR-WATER HEAT PUMPS FOR OUTDOOR OR INDOOR … · Allows the circulation of the water on the plant side keeping constant the temperature difference between inlet and outlet. Domestic

2

The manufacturer declines all the responsabilities regarding inaccuracies contained in this manual, if due to printing or typing mi-stakes. The manufacturer reserves the right to apply changes and improvements to the products at any time without notice.

Page 3: AIR-WATER HEAT PUMPS FOR OUTDOOR OR INDOOR … · Allows the circulation of the water on the plant side keeping constant the temperature difference between inlet and outlet. Domestic

3

TABLE OF CONTENTS

GENERAL FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5Unit description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5Unit identification code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5Description of components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6Control system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

TECHNICAL DATA AND PERFORMANCES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11Technical data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11NOMINAL performances - VERY HIGH TEMPERATURE plants . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12NOMINAL performances - HIGH TEMPERATURE plants . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13NOMINAL performances - STANDARD plants . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14NOMINAL performances - RADIANT plants . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15HEATING performances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16COOLING performances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17Plant side hydraulic performances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18Source side aeraulic performances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21DESUPERHEATER performances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22Operating limits. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23Electrical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24Noise levels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26Overall dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27Minimum operating area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

Page 4: AIR-WATER HEAT PUMPS FOR OUTDOOR OR INDOOR … · Allows the circulation of the water on the plant side keeping constant the temperature difference between inlet and outlet. Domestic

4

Page 5: AIR-WATER HEAT PUMPS FOR OUTDOOR OR INDOOR … · Allows the circulation of the water on the plant side keeping constant the temperature difference between inlet and outlet. Domestic

5

GENERAL FEATURES

Unit description

This series of air-water heat pumps satisfies the heating, coo-ling and domestic hot water production requirements of residen-tial plants of small and medium size.All the units are suitable both for outdoor or indoor installation. The possibiliy to produce water at high temperatures makes the-se units particularly suitable to be applied to radiators plants as well as to fan coil plants and radiant floor plants.The control system allows to manage not only the refrigerant circuit but the whole plant with the possibility to choose different solutions both for the heating and cooling plant and for the do-mestic hot water management. The possibility of solar panels or other heating sources integration is also available.The heating function optimizes the flow water temperature ac-cording both to the ambient temperature and to the outdoor tem-perature through climatic curves adaptable to the building featu-res. It’s possible to manage a storage tank and two independent circuits (a direct one and a mixed one).The domestic hot water management allows to control the th-ree way valve, the storage tank and the anti-legionella cycles (if necessary).The cooling function can be realized through “active cooling” (refrigerant circuit inversion). When the unit is used in radiant floor plants, to avoid condensate generation, a room humidity sensor can be installed. During cooling mode operation a part of the heating power in excess can be recovered for the domestic hot water production (VD version).The internal programmer clock allows to define different daily switching programs for heating, cooling and domestic hot water production.

The refrigerant circuit, contained in a box repaired from the air flow to simplify the maintenance operations, is equipped with scroll compressor mounted on damper supports, brazed pla-te heat exchangers, electronic expansion valve, reverse cycle valve, centrifugal fan (plug fan), finned coil realized with cop-per pipes and alluminium fins. The circuit is protected by high and low pressure switches and flow switches on the plate heat exchanger.The compressor is equipped with vapour and liquid injection and is placed on an economized refrigerant circuit with plate heat exchanger and electronic expansion valve dedicated to the injection. The plate heat exchanger and all the hydraulic pipes are ther-mally insulated in order to avoid condensate generation and re-duce thermal losses.The plug fan with electronic control of the rotational speed gua-rantees high efficiencies and low noise in all the operating con-ditions and allows to install the unit both outdoor (with protection caps) or indoor (with ducted air inlet and outlet). It is moreover possible to reduce the noise during the night.All the units with three-phase power supply are provided with a phase sequence and correct sequence controller device and with an outdoor temperature sensor in order to realize the clima-tic control.All the units are accurately built and individually tested in the factory. Only electric and hydraulic connections are required for installation.

IP 45 .1 VB AB 0 H 5

Unit identification code

The codes that identify the units and the meaning of the letters used are described below.

Unit type

IP - Units suitable for hydronic plant in-stallation operating as reversible heat pumps

Power supply

1 - 230V - 1 - 50 Hz5 - 400V - 3N - 50 Hz

Operating range

H - High temperature.The unit is suitable to produce water at high temperature.

Refrigerant type

0 - R410A

Acoustic setting up

AB - Base setting up

N° compressors

Unit model

Unit version

VB - Base versionVD - Desuperheater version

HMP HT

Page 6: AIR-WATER HEAT PUMPS FOR OUTDOOR OR INDOOR … · Allows the circulation of the water on the plant side keeping constant the temperature difference between inlet and outlet. Domestic

6

GENERAL FEATURES

External structure . Basement, supporting structure and lateral panels are made of galvanized and painted sheet-steel to guarantee good resistance to atmospheric agents. Accessibility to internal parts is possible removing the lateral panels. For extraordinary manteinances also the other panels can be removed.Refrigerant circuit . It is contained inside a compartment separated from the air flow to simplify maintenance and control operations.

The hermetic scroll compressor (1) is mounted on damper supports and is protected against overtemperatures and overcurrents. It is equipped with an electrcal heater, that is activated when the compressor turns off, to keep the compressor crankcase oil temperature high enough to prevent migration of the refrigerant during winter stops and to evaporate any liquid present in the crankcase, in order to prevent possible liquid rushes on starting.The compressor is equipped with vapour and liquid injection and is placed on an economized refrigerant circuit with plate heat exchanger and electronic expansion valve dedicated to the injection. The plant side heat exchanger (2) is a brazed stainless steel plate heat exchanger, properly insulated to avoid condensate generation and to minimize thermal losses, and protected by a flow switch that detects whatever water flow lack.The source side heat exchanger (3) is a finned coil realized with grooved copper pipes and hydrophilic aluminium fins with waved profile to increase the heat exchange coefficient. A tray is placed under the coil to collect the condensate generated in heating mode.The expansion device (4), an electronic expansion valve, allows the unit to adjust itself to the different operating conditions keeping steady the set superheating.

The refrigerant circuit of each unit contains moreover solid core hermetic filter dryer (5) to restrain impurity and moisture residuals that could be present in the circuit, high and low pressure switches in order to assure the compressor to operate inside the permitted limits, 4 way reverse cycle valve (6) to allow operating mode change reversing the refrigerant flow, liquid receiver (7) to compensate the different refrigerant charge required in heating and in cooling mode and pressure connections SAE 5/16” - UNF 1/2” - 20 equipped with pin, gasket and blind nut, as required for the use of R410A refrigerant (they allow the complete check of the refrigerant circuit: compressor inlet pressure, compressor outlet pressure and expansion valve upstream pressure). All the pipes of the refrigerant circuit are properly insulated to avoid condensate generation and minimize thermal lossesThe plug fan (8) is equipped with an high efficiency electronically commutated (EC) motor and guarantees enough available static pressure to allow both the outdoor and the indoor installation.Hydraulic circuit . All the pipes are thermally insulated to avoid condensate generation and minimize thermal losses. The circuit can be equipped with a standard, high head or modulating circulation pump (option). The circuit is always equipped also with expansion vessel, safety valve and air vents.Electrical panel . It contains all the power, control and security components necessary to guarantee the unit to work properly. The unit is managed by a microprocessor controller to which all the electrical loads and the control devices are connected. The user interface, to be placed indoor, allows to view and to modify, if necessary, all the parameters of the unit.All the units are supplied with an outdoor temperature sensor, to be installed outside, in order to realize the climatic control.

Description of components

2

83

6

7

4

5

1

Page 7: AIR-WATER HEAT PUMPS FOR OUTDOOR OR INDOOR … · Allows the circulation of the water on the plant side keeping constant the temperature difference between inlet and outlet. Domestic

7

GENERAL FEATURES

The microprocessor controller is able to manage not only the unit itself but also all that components of the plant which allow to realize a complete system.The main functions of the control system are :- room temperature control according to the outdoor temperatu-

re (climatic control)- domestic hot water production (management of 3 way valve,

storage tank, anti legionella cycles…)- management of a heating and/or cooling mixed circuit (pump

and 3 way mixing valve)- management of a heating direct circuit (only pump)- management of a storage tank for heating and/or cooling- management of electrical heaters for heating and domestic

hot water (3 steps logic)- solar panels integration- room humidity control for cooling with radiant systems- internal programmer clock (for heating, cooling and domestic

hot water)- digital input for electrical energy low tariff- alarm memory management and diagnostic- compressor and pump operating hour counter- possibility to manage more units in cascade (maximum 16)

Besides the user interface of the unit to be placed indoor, wi-red or wireless remote thermostats are available which allow to control all the operating parameters of the unit and to acquire the temperature in the different zones in order to realize a more precise and comfortable control.

The unit controller is able to manage a lot of different plant so-lutions enabling automatically the necessary control algorythms according to the components which have been connected. The management of such components is possible through additional expansion modules which communicate with the unit by means of an internal bus and provide all the inputs and outputs required to fulfil a complete system.

Room temperature

20.5 C18:28

FS

The controller is able to manage up to two zones in heating (one by means of a mixed circuit and the other by means of a direct circuit) and one zone in cooling (by means of a mixed circuit).It’s possible to realize more complex plants connecting to the heat pump controller further expansion modules in order to extend without limits the number of zones to be managed.

For each zone the following parameters can be set :- set point- daily or weekly operating time table- climatic control curve- room control sensor : it can be in common with the other

zones or independent (in that case it’s necessary to install an additional room thermostat)

Control system

Page 8: AIR-WATER HEAT PUMPS FOR OUTDOOR OR INDOOR … · Allows the circulation of the water on the plant side keeping constant the temperature difference between inlet and outlet. Domestic

8

GENERAL FEATURES

Options

Version VD - Desuperheater version Allows to recover a part of the available heating power (and otherwise not used during cooling operating mode) for the domestic hot water production.

Plant sideflow ratemanagement

Standard pump Allows the circulation of the water on the plant side.

High head pump Allows the circulation of the water on the plant side and guarantees a higher available static head.

Modulating pump Allows the circulation of the water on the plant side keeping constant the temperature difference between inlet and outlet.

Domestic hot waterproduction 3 way valve Allow to divert the hot water produced by the heat pump from the heating circuit

to the domestic hot water circuit.

Integrative electrical heaters Integrate or replace the heating power supplied by the heat pump and are managed by the unit controller with a 3 step logic.

Soft starter Reduces the compressor start current.

The controller flexibility and the big number of options available allow to get, for each model, a lot of different configurations that integrate inside the heat pump many components of the plant and allow to realize compact and tested installations.In order to select the right configuration it is necessary to define

the type of plant to which the heat pump will be connected, both for what concerning the heating and cooling circuits, and for what concerning the domestic hot water management.

Option “Plant side flow rate management”Pump (standard or high head or modulating)

Reversible heat pump (IP) without options

Option “Integrative electrical heaters”

Opzione "Version" : "Desuperheater version (VD)"

Page 9: AIR-WATER HEAT PUMPS FOR OUTDOOR OR INDOOR … · Allows the circulation of the water on the plant side keeping constant the temperature difference between inlet and outlet. Domestic

9

GENERAL FEATURES

3 way valveOption “Domestic hot water production”

In this configuration the heat pump can be coupled to a domestic hot water tank equipped with a coil designed for a maximum water temperature between 55°C and 60°C.The anti legionella cycles have to be performed by means of electrical heaters placed on the heat pump outlet (see option “Integrative electrical heaters”) or directly inside the tank.

Page 10: AIR-WATER HEAT PUMPS FOR OUTDOOR OR INDOOR … · Allows the circulation of the water on the plant side keeping constant the temperature difference between inlet and outlet. Domestic

10

Accessories

GENERAL FEATURES

Rubber vibration dampers Allow to reduce the transmission to the unit support plane of the mechanical vibrations generated by the compressor and by the fans in their normal operating mode.

Adjustable rubbervibration dampers

Allow to reduce the transmission to the unit support plane of the mechanical vibrations generated by the compressor and by the fans in their normal operating mode. Their height can be adjusted to fit to the ground unevenness.

Protection cap Protect th external surface of the finned coil when it is installed on the air suction side) and the fan (when it is installed on the air expulsion side) and reduce the noise emitted by the unit.

Lateral expulsion cap Protect the fan and reduce the noise emitted by the unit. It must be connected to one of the two lateral air flow openings and requires the installation of the accessory “Frontal shutting panel”.

Frontal shutting panel Allow to close the frontal air flow opening when the lateral air flow openings are used.

3 way valvefor domestic hot water Allow to divert the hot water produced by the heat pump from the heating circuit to the domestic hot water circuit.

Remote thermostat(wired or wireless)

Allows operating mode selection and set point adjustment. The on board temperature sensor can be used in order to realize a climatic control.

Remote control(wired or wireless)

Replicates all the control and visualization functionalities of the controller installed on the unit. The on board temperature sensor can be used in order to realize a climatic control.

LPB bus interface Connected to the unit controller, allows to communicate on the LPB bus, required for the cascade management.

Wireless transmitter Connected to the unit controller, allows to communicate with wireless remote control and wireless outdoor temperature sensor.

BSB wireless transmitter Connected to the communication bus (BSB) of the unit controller, allows to communicate with the wireless remote control and the wireless outdoor temperature sensor.

Wireless repeater Extends wireless operating range.

Wireless adaptor for outdoor temperature sensor Allows to transform the wired outdoor temperature sensor, standard for all the units, in a wireless sensor.

Condensate sensor In cooling mode it allows the minimum flow temperature control when condensate generation occurs.

Room hygrostat In cooling mode it allows the minimum flow temperature control according to the room humidity.

Room humidity sensor(with or without display)

In cooling mode it allows the minimum flow temperature control according to the room dew point, calculated from the measured room humidity.

Transformer230V / 24V - 3VA It assures the correct power supply for the condensate sensor and for the room humidity sensor.

N .B . For OUTDOOR INSTALLATION is MANDATORY one of the two following solutions : - installation of the accessory “Protection cap” on the air expulsion side - installation of the accessories “Lateral expulsion cap” and “Frontal shutting panel”

Page 11: AIR-WATER HEAT PUMPS FOR OUTDOOR OR INDOOR … · Allows the circulation of the water on the plant side keeping constant the temperature difference between inlet and outlet. Domestic

11

TECHNICAL DATA AND PERFORMANCES

Technical data

RefrigerantType R410A -

CompressorType scroll with vapour injection (EVI) -

Quantity 1 n°

Power steps 0 - 100 %

Oil charge 3,4 3,4 3,4 3,4 3,4 kg

Plant side heat exchangerType stainless steel brazed plates -

Quantity 1 n°

Water volume 4,18 4,18 4,18 5,14 5,14 l

Source side heat exchangerType finned coil -

Quantity 1 n°

Frontal surface 1,10 1,10 1,10 1,43 1,43 m2

FansType plug fan with high efficiency EC motor -

Quantity 1 n°

Diameter 630 630 630 630 630 mm

Maximum rotational speed 680 680 680 1200 1200 rpm

Total installed power 0,54 0,54 0,54 2,80 2,80 kW

Plant side hydraulic circuitExpansion vessel volume 10 10 10 10 10 l

Safety valve set point 3 bar

Plant pump - standard (option)Type centrifugal pump -

Quantity 1 n°

Installed power 0,7 0,7 0,7 1,0 1,0 kW

Plant pump - high head (option)Type centrifugal pump -

Quantity 1 n°

Installed power 1,2 1,2 1,2 1,6 1,6 kW

Plant pump - high efficiency (option)Type inverter glandless pump -

Quantity 1 n°

Installed power 0,31 0,31 0,31 0,31 0,31 kW

Integrative electrical heaters (option)Total installed power 18,0 18,0 18,0 18,0 18,0 kW

Power steps 0 - 33 - 66 - 100 %

Frame 1 2Model 30 .1 35 .1 40 .1 45 .1 50 .1 U.M.

Power supply 400 -3N- 50 400 -3N- 50 400 -3N- 50 400 -3N- 50 400 -3N- 50 V-ph-Hz

Page 12: AIR-WATER HEAT PUMPS FOR OUTDOOR OR INDOOR … · Allows the circulation of the water on the plant side keeping constant the temperature difference between inlet and outlet. Domestic

12

TECHNICAL DATA AND PERFORMANCES

Frame 1 2Model 30 .1 35 .1 40 .1 45 .1 50 .1 U.M.

Power supply 400 -3N- 50 400 -3N- 50 400 -3N- 50 400 -3N- 50 400 -3N- 50 V-ph-Hz

NOMINAL performances - VERY HIGH TEMPERATURE plants

IP

Heating A7W65 ( source : air in 7°C d.b. 6°C w.b. / plant : water in 55°C out 65°C )Heating capacity 30,7 36,1 40,5 46,3 53,0 kW

Power input 12,3 14,5 16,2 18,6 21,3 kW

COP 2,50 2,49 2,50 2,49 2,49 -

Water flow rate plant side 2686 3158 3543 4051 4628 l/h

Pressure drops plant side 6 9 11 9 12 kPa

Heating A2W65 ( source : air in 2°C d.b. 1°C w.b. / plant : water in 55°C out 65°C )Heating capacity 26,3 31,0 34,7 39,7 45,3 kW

Power input 12,4 14,5 16,2 18,6 21,2 kW

COP 2,12 2,14 2,14 2,13 2,14 -

Water flow rate plant side 2301 2712 3036 3473 3963 l/h

Pressure drops plant side 5 6 8 7 9 kPa

Heating A-7W65 ( source : air in -7°C d.b. -8°C w.b. / plant : water in 55°C out 65°C )Heating capacity 23,0 27,1 30,3 34,7 39,6 kW

Power input 12,4 14,6 16,3 18,7 21,3 kW

COP 1,85 1,86 1,86 1,86 1,86 -

Water flow rate plant side 2012 2371 2651 3036 3464 l/h

Pressure drops plant side 4 5 6 5 7 kPa

Data declared according to EN 14511 . The values are referred to units without options or accessories.

Page 13: AIR-WATER HEAT PUMPS FOR OUTDOOR OR INDOOR … · Allows the circulation of the water on the plant side keeping constant the temperature difference between inlet and outlet. Domestic

13

TECHNICAL DATA AND PERFORMANCES

Frame 1 2Model 30 .1 35 .1 40 .1 45 .1 50 .1 U.M.

Power supply 400 -3N- 50 400 -3N- 50 400 -3N- 50 400 -3N- 50 400 -3N- 50 V-ph-Hz

NOMINAL performances - HIGH TEMPERATURE plants

IP

Heating A7W55 ( source : air in 7°C d.b. 6°C w.b. / plant : water in 47°C out 55°C )Heating capacity 30,0 35,3 39,7 45,4 51,7 kW

Power input 9,89 11,6 13,1 15,0 17,1 kW

COP 3,03 3,04 3,03 3,03 3,02 -

Water flow rate plant side 3269 3846 4315 4936 5623 l/h

Pressure drops plant side 9 12 15 14 17 kPa

Heating A2W55 ( source : air in 2°C d.b. 1°C w.b. / plant : water in 47°C out 55°C )Heating capacity 25,6 30,1 33,7 38,6 44,1 kW

Power input 9,91 11,6 13,0 14,9 17,1 kW

COP 2,58 2,59 2,59 2,59 2,58 -

Water flow rate plant side 2789 3280 3672 4206 4794 l/h

Pressure drops plant side 7 9 11 10 13 kPa

Heating A-7W55 ( source : air in -7°C d.b. -8°C w.b. / plant : water in 47°C out 55°C )Heating capacity 22,1 26,1 29,2 33,4 38,1 kW

Power input 9,94 11,7 13,1 15,0 17,1 kW

COP 2,22 2,23 2,23 2,23 2,23 -

Water flow rate plant side 2408 2844 3182 3639 4152 l/h

Pressure drops plant side 5 7 9 8 10 kPa

Data declared according to EN 14511 . The values are referred to units without options or accessories.

Page 14: AIR-WATER HEAT PUMPS FOR OUTDOOR OR INDOOR … · Allows the circulation of the water on the plant side keeping constant the temperature difference between inlet and outlet. Domestic

14

TECHNICAL DATA AND PERFORMANCES

NOMINAL performances - STANDARD plants

Data declared according to EN 14511 . The values are referred to units without options or accessories.

Frame 1 2Model 30 .1 35 .1 40 .1 45 .1 50 .1 U.M.

Power supply 400 -3N- 50 400 -3N- 50 400 -3N- 50 400 -3N- 50 400 -3N- 50 V-ph-Hz

IP

Heating A7W45 ( source : air in 7°C d.b. 6°C w.b. / plant : water in 40°C out 45°C )Heating capacity 29,6 34,8 39,1 44,6 51,0 kW

Power input 8,07 9,54 10,7 12,2 14,0 kW

COP 3,67 3,65 3,65 3,66 3,64 -

Water flow rate plant side 5127 6013 6761 7716 8811 l/h

Pressure drops plant side 22 29 36 32 41 kPa

Heating A2W45 ( source : air in 2°C d.b. 1°C w.b. / plant : water in 40°C out 45°C )Heating capacity 25,1 29,5 33,1 37,8 43,2 kW

Power input 8,06 9,52 10,6 12,2 14,0 kW

COP 3,11 3,10 3,12 3,10 3,09 -

Water flow rate plant side 4345 5109 5735 6552 7473 l/h

Pressure drops plant side 16 21 27 23 30 kPa

Heating A-7W45 ( source : air in -7°C d.b. -8°C w.b. / plant : water in 40°C out 45°C )Heating capacity 21,5 25,4 28,4 32,5 37,1 kW

Power input 8,08 9,54 10,7 12,2 13,9 kW

COP 2,66 2,66 2,65 2,66 2,67 -

Water flow rate plant side 3737 4397 4918 5631 6430 l/h

Pressure drops plant side 12 16 20 17 22 kPa

Cooling A35W7 ( source : air in 35°C d.b. / plant : water in 12°C out 7°C )Cooling capacity 22,7 26,6 29,9 34,1 38,9 kW

Power input 7,15 8,42 9,44 10,8 12,4 kW

EER 3,17 3,16 3,17 3,16 3,14 -

Water flow rate plant side 3896 4582 5148 5869 6710 l/h

Pressure drops plant side 13 18 22 19 25 kPa

Page 15: AIR-WATER HEAT PUMPS FOR OUTDOOR OR INDOOR … · Allows the circulation of the water on the plant side keeping constant the temperature difference between inlet and outlet. Domestic

15

NOMINAL performances - RADIANT plants

Data declared according to EN 14511 . The values are referred to units without options or accessories.

TECHNICAL DATA AND PERFORMANCES

Frame 1 2Model 30 .1 35 .1 40 .1 45 .1 50 .1 U.M.

Power supply 400 -3N- 50 400 -3N- 50 400 -3N- 50 400 -3N- 50 400 -3N- 50 V-ph-Hz

IP

Heating A7W35 ( source : air in 7°C d.b. 6°C w.b. / plant : water in 30°C out 35°C )Heating capacity 29,2 34,4 38,6 44,1 50,4 kW

Power input 6,32 7,48 8,40 9,59 11,0 kW

COP 4,62 4,60 4,60 4,60 4,58 -

Water flow rate plant side 5039 5923 6650 7602 8676 l/h

Pressure drops plant side 21 28 35 31 40 kPa

Heating A2W35 ( source : air in 2°C d.b. 1°C w.b. / plant : water in 30°C out 35°C )Heating capacity 24,7 29,0 32,6 37,2 42,5 kW

Power input 6,32 7,46 8,36 9,55 11,0 kW

COP 3,91 3,89 3,90 3,90 3,86 -

Water flow rate plant side 4260 5005 5628 6425 7325 l/h

Pressure drops plant side 15 21 26 22 29 kPa

Heating A-7W35 ( source : air in -7°C d.b. -8°C w.b. / plant : water in 30°C out 35°C )Heating capacity 21,0 24,8 27,8 31,7 36,2 kW

Power input 6,34 7,47 8,37 9,57 10,9 kW

COP 3,31 3,32 3,32 3,31 3,32 -

Water flow rate plant side 3637 4277 4797 5472 6252 l/h

Pressure drops plant side 11 15 19 17 21 kPa

Cooling A35W18 ( source : air in 35°C d.b. / plant : water in 23°C out 18°C )Cooling capacity 29,8 35,0 39,3 44,9 51,2 kW

Power input 7,74 9,15 10,2 11,7 13,4 kW

EER 3,85 3,83 3,85 3,84 3,82 -

Water flow rate plant side 5155 6069 6811 7776 8880 l/h

Pressure drops plant side 22 30 37 32 42 kPa

Page 16: AIR-WATER HEAT PUMPS FOR OUTDOOR OR INDOOR … · Allows the circulation of the water on the plant side keeping constant the temperature difference between inlet and outlet. Domestic

16

TECHNICAL DATA AND PERFORMANCES

HEATING performances

Inlet air temperature w.b. [°C] Inlet air temperature w.b. [°C]

Power input COP

Heating capacity

Inlet air temperature w.b. [°C]

The graphs allow to get the corrective factors to be applied to the nominal performances in order to obtain the real performances in the selected operating conditions.

The reference nominal condition is :A7W35source : air in 7°C d.b. 6°C w.b.plant : water in 30°C out 35°C

Outlet temperatureplant side :A = 65°CB = 55°CC = 45°CD = 35°CE = 25°C

0.2

0.4

0.6

0.8

1.0

1.2

1.4

1.6

1.8

2.0

2.2

-20 -15 -10 -5 0 5 10 15 20 25 300.2

0.4

0.6

0.8

1.0

1.2

1.4

1.6

1.8

2.0

2.2

-20 -15 -10 -5 0 5 10 15 20 25 30

B

C

D

E

B C D E

0.4

0.6

0.8

1.0

1.2

1.4

1.6

-20 -15 -10 -5 0 5 10 15 20 25 30

E

D

C

B

A

A

A

Page 17: AIR-WATER HEAT PUMPS FOR OUTDOOR OR INDOOR … · Allows the circulation of the water on the plant side keeping constant the temperature difference between inlet and outlet. Domestic

17

TECHNICAL DATA AND PERFORMANCES

COOLING performances

Cooling capacity

Inlet air temperature d.b. [°C]

Inlet air temperature d.b. [°C] Inlet air temperature d.b. [°C]

Power input EER

The graphs allow to get the corrective factors to be applied to the nominal performances in order to obtain the real performances in the selected operating conditions.

The reference nominal condition is :A35W7source : air in 35°C d.b.plant : water in 12°C out 7°C

Outlet temperatureplant side :A = 24°CB = 18°CC = 12°CD = 7°C

0.4

0.6

0.8

1.0

1.2

1.4

1.6

1.8

2.0

2.2

0 5 10 15 20 25 30 35 40 45 500.4

0.6

0.8

1.0

1.2

1.4

1.6

1.8

2.0

2.2

0 5 10 15 20 25 30 35 40 45 50

0.4

0.6

0.8

1.0

1.2

1.4

1.6

1.8

2.0

2.2

0 5 10 15 20 25 30 35 40 45 50

A B C D

A

B

C

D

A

B

C

D

Page 18: AIR-WATER HEAT PUMPS FOR OUTDOOR OR INDOOR … · Allows the circulation of the water on the plant side keeping constant the temperature difference between inlet and outlet. Domestic

18

TECHNICAL DATA AND PERFORMANCES

Plant side hydraulic performances

The graphs are referred to units operating with water at the temperature of 10°C (density 1000 kg/m3).

Flow rate [ l/h ]

Flow rate [ l/h ]

Pressure drops - unit without options

Pressure drops to be added - unit with option “Integrative electrical heaters”

Pre

ssur

e dr

ops

[ kP

a ]

Pre

ssur

e dr

ops

[ kP

a ]

0

10

20

30

40

50

60

0 1000 2000 3000 4000 5000 6000 7000 8000 9000

0

10

20

30

40

50

60

0 1000 2000 3000 4000 5000 6000 7000 8000 9000

40.1

45.1

35.1

30.1

50.1

Page 19: AIR-WATER HEAT PUMPS FOR OUTDOOR OR INDOOR … · Allows the circulation of the water on the plant side keeping constant the temperature difference between inlet and outlet. Domestic

19

TECHNICAL DATA AND PERFORMANCES

Flow rate [ l/h ]

Flow rate [ l/h ]

The graphs are referred to units operating with water at the temperature of 10°C (density 1000 kg/m3).

Available static head - unit with option “Plant side flow rate management” : “Standard pump”

Available static head - unit with option “Plant side flow rate management” : “High head pump”

Avai

labl

e st

atic

hea

d [ k

Pa

]Av

aila

ble

stat

ic h

ead

[ kP

a ]

0

40

80

120

160

200

240

0 1000 2000 3000 4000 5000 6000 7000 8000 9000

0

40

80

120

160

200

240

0 1000 2000 3000 4000 5000 6000 7000 8000 9000

35.140.1

45.150.1

30.1

35.140.1

45.150.1

30.1

Page 20: AIR-WATER HEAT PUMPS FOR OUTDOOR OR INDOOR … · Allows the circulation of the water on the plant side keeping constant the temperature difference between inlet and outlet. Domestic

20

TECHNICAL DATA AND PERFORMANCES

The graphs are referred to units operating with water at the temperature of 10°C (density 1000 kg/m3).

Available static head - unit with option “Plant side flow rate management” : “Modulating pump”

Flow rate [ l/h ]

Avai

labl

e st

atic

hea

d [ k

Pa

]

0

40

80

120

160

200

240

0 1000 2000 3000 4000 5000 6000 7000 8000 9000

45.150.1

35.140.1

30.1

Page 21: AIR-WATER HEAT PUMPS FOR OUTDOOR OR INDOOR … · Allows the circulation of the water on the plant side keeping constant the temperature difference between inlet and outlet. Domestic

21

The graphs are referred to units operating with air at the temperature of 15°C (density 1,2 kg/m3).

Frame 1 2Model 30 .1 35 .1 40 .1 45 .1 50 .1 U.M.

Maximum static headavailable for ducted installation 50 50 50 150 150 U.M.

Available static head - unit without accessory “Protection cap” or “Lateral expulsion cap”

In case of ducted installation the total pressure drops in the inlet and outlet ducts can not exceed the maximum available static head.The minimum duct section must guarantee that the medium air velocity does not exceed 2,5 m/s in order to avoid noise problems and to keep the pressure drops as lower as possible.

Flow rate [ m3/h ]

Source side aeraulic performances

TECHNICAL DATA AND PERFORMANCESAv

aila

ble

stat

ic h

ead

[ Pa

]

0

10

20

30

40

50

60

70

80

90

0 2000 4000 6000 8000 10000 12000 14000 16000 18000 20000

45.1

50.1

30.1

35.1

40.1

Page 22: AIR-WATER HEAT PUMPS FOR OUTDOOR OR INDOOR … · Allows the circulation of the water on the plant side keeping constant the temperature difference between inlet and outlet. Domestic

22

Performances DESUPERHEATER

The graphs are referred to units operating with water at the temperature of 10°C (density 1000 kg/m3).

Flow rate [ l/h ]

Pressure drops desuperheater - unit "VD - Desuperheater version"

Pre

ssur

e dr

ops

[ kP

a ]

IP

Cooling A35W7-W45( source : air in 35°C d.b. / plant : water in 12°C out 7°C / heat recovery : water in 40°C out 45°C )

Cooling capacity 23,5 27,7 31,1 35,5 40,5 kW

Power input 6,94 8,18 9,18 10,5 12,1 kW

EER 3,39 3,39 3,39 3,38 3,35 -

Water flow rate plant side 4050 4771 5354 6109 6985 l/h

Pressure drops plant side 14 19 24 21 26 kPa

Heating capacity (desuperheater) 6,97 8,20 9,20 10,5 12,0 kW

EER with heat recovery 4,39 4,39 4,39 4,38 4,34 -

Water flow rate desuperheater side 1211 1425 1599 1825 2086 l/h

Pressure drops desuperheater side 0,7 0,9 1,2 1,5 1,9 kPa

Frame 1 2Model 30 .1 35 .1 40 .1 45 .1 50 .1 U.M.

Power supply 400 -3N- 50 400 -3N- 50 400 -3N- 50 400 -3N- 50 400 -3N- 50 V-ph-Hz

Data declared according to EN 14511. The values are referred to units with the only option "VD - Desuperheater version".

TECHNICAL DATA AND PERFORMANCES

0

5

10

15

20

25

30

0 500 1000 1500 2000 2500 3000 3500 4000 4500

Page 23: AIR-WATER HEAT PUMPS FOR OUTDOOR OR INDOOR … · Allows the circulation of the water on the plant side keeping constant the temperature difference between inlet and outlet. Domestic

23

TECHNICAL DATA AND PERFORMANCES

Operating limits

Temperature difference between unit inlet and outlet Plant side

DT max Maximum value 11 °C

DT min Minimum value 3 °C

HEATING

Inlet air temperature d.b. [°C]

Out

let t

empe

ratu

re -

plan

t sid

e [°

C]

The graphs reported below show the operating area inside which the correct working of the unit is guaranteed.

COOLING

Inlet air temperature d.b. [°C]

Out

let t

empe

ratu

re -

plan

t sid

e [°

C]

5

10

15

20

25

30

35

40

45

50

55

60

65

70

75

-25 -20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45 50 55

DT = 10 °C

-5

0

5

10

15

20

25

30

35

40

45

-25 -20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45 50 55

Page 24: AIR-WATER HEAT PUMPS FOR OUTDOOR OR INDOOR … · Allows the circulation of the water on the plant side keeping constant the temperature difference between inlet and outlet. Domestic

24

TECHNICAL DATA AND PERFORMANCES

Electrical data

Unit

Plant side pump - standard (option)

Plant side pump - high head (option)

Plant side pump - modulating (option)

Integrative electrical heaters (option)

Frame 1 2Model 30 .1 35 .1 40 .1 45 .1 50 .1 U.M.

Power supply 400-3N-50 400-3N-50 400-3N-50 400-3N-50 400-3N-50 V-ph-Hz

F.L.A. Maximum total current input 22,0 24,5 27,0 34,7 39,2 A

F.L.I. Maximum total power input 13,9 15,5 17,1 21,6 24,5 kW

M.I.C.Maximum total start current 160 171 183 209 243 AMaximum total start currentwith soft starter (option) 94 102 111 131 151 A

Power supply 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 V-ph-Hz

F.L.A. Maximum total current input 3,6 3,6 3,6 5,1 5,1 A

F.L.I. Maximum total power input 0,7 0,7 0,7 1,0 1,0 kW

Power supply 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 V-ph-Hz

F.L.A. Maximum total current input 6,1 6,1 6,1 8,2 8,2 A

F.L.I. Maximum total power input 1,2 1,2 1,2 1,6 1,6 kW

Power supply 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 V-ph-Hz

F.L.A. Maximum total current input 1,6 1,6 1,6 1,6 1,6 A

F.L.I. Maximum total power input 0,31 0,31 0,31 0,31 0,31 kW

Power supply230-1-50 230-1-50 230-1-50 230-1-50 230-1-50

V-ph-Hz400-3N-50 400-3N-50 400-3N-50 400-3N-50 400-3N-50

F.L.A.

Maximum total current input( 230V - 1 - 50Hz ) 78,3 78,3 78,3 78,3 78,3 A

Maximum total current input( 400V - 3N - 50Hz ) 26,0 26,0 26,0 26,0 26,0 A

F.L.I. Maximum total power input 18,0 18,0 18,0 18,0 18,0 kW

Page 25: AIR-WATER HEAT PUMPS FOR OUTDOOR OR INDOOR … · Allows the circulation of the water on the plant side keeping constant the temperature difference between inlet and outlet. Domestic

25

TECHNICAL DATA AND PERFORMANCES

Unit without accessory “Protection cap” or “Lateral expulsion cap”

Unit with accessory “Protection cap” on the air suction sideand with accessory “Protecion cap” or “Lateral expulsion cap” on the air expulsion side

Noise levels

Reference conditionsPerformances referred to units operating in heating mode at nominal conditions A7W35.Unit placed in free field on reflecting surface (directional factor equal to 2).The sound power level is measured according to ISO 3744 standard.The sound pressure level is calculated according to ISO 3744 and is referred to a distance of 1 meter from the external surface of the unit.

Reference conditionsPerformances referred to units operating in heating mode at nominal conditions A7W35.Unit placed in free field on reflecting surface (directional factor equal to 2).The sound power level is measured according to ISO 3744 standard.The sound pressure level is calculated according to ISO 3744 and is referred to a distance of 1 meter from the external surface of the unit.

ModelSound power levels [dB]

by octave bands [Hz]Sound power

level

Sound pressure level

at 1 metre at 5 metres at 10 metres

63 125 250 500 1000 2000 4000 8000 [dB] [dB(A)] [dB(A)] [dB(A)] [dB(A)]30 .1 84,7 79,0 73,9 72,8 70,9 68,0 62,2 57,2 86 76 60 50 44

35 .1 85,8 80,1 75,0 73,9 72,0 69,1 63,3 58,3 88 77 61 51 45

40 .1 85,8 80,1 75,0 73,9 72,0 69,1 63,3 58,3 88 77 61 51 45

45 .1 86,8 81,1 76,0 74,9 73,0 70,1 64,3 59,3 89 78 62 52 46

50 .1 86,8 81,1 76,0 74,9 73,0 70,1 64,3 59,3 89 78 62 52 46

ModelSound power levels [dB]

by octave bands [Hz]Sound power

level

Sound pressure level

at 1 metre at 5 metres at 10 metres

63 125 250 500 1000 2000 4000 8000 [dB] [dB(A)] [dB(A)] [dB(A)] [dB(A)]30 .1 81,2 75,5 70,4 69,3 67,4 64,5 58,7 53,7 83 72 56 46 41

35 .1 82,3 76,6 71,5 70,4 68,5 65,6 59,8 54,8 84 73 57 47 42

40 .1 82,3 76,6 71,5 70,4 68,5 65,6 59,8 54,8 84 73 57 47 42

45 .1 83,3 77,6 72,5 71,4 69,5 66,6 60,8 55,8 85 74 58 48 43

50 .1 83,3 77,6 72,5 71,4 69,5 66,6 60,8 55,8 85 74 58 48 43

Page 26: AIR-WATER HEAT PUMPS FOR OUTDOOR OR INDOOR … · Allows the circulation of the water on the plant side keeping constant the temperature difference between inlet and outlet. Domestic

26

TECHNICAL DATA AND PERFORMANCES

Weights

Components weights

Transport weights

Operating weights

Frame 1 2Model 30 .1 35 .1 40 .1 45 .1 50 .1 U.M.

Unit without options 364 366 369 428 430 kg

Opt

ions

Version Desuperheaterversion (VD) 12 12 12 12 12 kg

Plant sideflow ratemanagement

Standard pump 9 9 9 11 11 kg

High head pump 12 12 12 13 13 kg

High efficiency pump 6 6 6 7 7 kgDomestic hot water production :3 way valve 6 6 6 7 7 kg

Integrative electrical heaters 10 10 10 11 11 kg

Acce

ssor

ies Protection cap 19 19 19 23 23 kg

Lateral expulsion cap 10 10 10 10 10 kg

Frontal shutting panel 10 10 10 13 13 kg

Unit without options 369 371 374 438 440 kg

Opt

ions

Version Desuperheaterversion (VD) 18 18 18 18 18 kg

Plant sideflow ratemanagement

Standard pump 10 10 10 13 13 kg

High head pump 13 13 13 15 15 kg

High efficiency pump 7 7 7 8 8 kgDomestic hot water production :3 way valve 9 9 9 10 10 kg

Integrative electrical heaters 14 14 14 15 15 kg

Acce

ssor

ies Protection cap 19 19 19 23 23 kg

Lateral expulsion cap 10 10 10 10 10 kg

Frontal shutting panel 10 10 10 13 13 kg

Unit without options 375 377 380 443 445 kg

Opt

ions

Version Desuperheaterversion (VD) 12 12 12 12 12 kg

Plant sideflow ratemanagement

Standard pump 9 9 9 11 11 kg

High head pump 12 12 12 13 13 kg

High efficiency pump 6 6 6 7 7 kgDomestic hot water production :3 way valve 6 6 6 7 7 kg

Integrative electrical heaters 10 10 10 11 11 kg

Acce

ssor

ies Protection cap 30 30 30 38 38 kg

Protection caps (quantity 2) 49 49 49 61 61 kg

Lateral expulsion cap 21 21 21 25 25 kg

Frontal shutting panel 11 11 11 14 14 kg

Page 27: AIR-WATER HEAT PUMPS FOR OUTDOOR OR INDOOR … · Allows the circulation of the water on the plant side keeping constant the temperature difference between inlet and outlet. Domestic

27

TECHNICAL DATA AND PERFORMANCES

Overall dimensions

Unit with accessory “Protection cap” on the air suction side and on the air expulsion side

Unit with accessories “Lateral expulsion cap” and “Frontal shutting panel” on the air expulsion side

The accessory “Lateral expulsion cap” can be installed both on the left side or the right side of the unit.

Frame 1 Frame 21 Plant return 1" 1/4 M 1" 1/4 M2 Plant flow 1" 1/4 M 1" 1/4 M3 Domestic hot water flow 1" 1/4 M 1" 1/4 M4 Desuperheater inlet 1" M 1" M5 Desuperheater outlet 1" M 1" M

Frame 1 Frame 2A1 1180 mm 1480 mmA2 615 mm 615 mmB1 880 mm 880 mmB2 465 mm 465 mmH 1620 mm 1620 mm

2 23 31 1

231

231

54

54

Page 28: AIR-WATER HEAT PUMPS FOR OUTDOOR OR INDOOR … · Allows the circulation of the water on the plant side keeping constant the temperature difference between inlet and outlet. Domestic

28

Minimum operating area

Respect the free area around the unit as shown in figure in order to guarantee a good accessibility and facilitate maintenance and control operations.

Configuration 1

Configuration 3(left side)

Configuration 4(left side)

Configuration 2

Configuration 3(right side)

Configuration 4(right side)

C 600 mmD 600 mmE 700 mm

TECHNICAL DATA AND PERFORMANCES

Page 29: AIR-WATER HEAT PUMPS FOR OUTDOOR OR INDOOR … · Allows the circulation of the water on the plant side keeping constant the temperature difference between inlet and outlet. Domestic

29

Configuration 5(left side)

Configuration 6(left side)

Accessories used to realize the configurations shown above

Configuration 5(right side)

Configuration 6(right side)

TECHNICAL DATA AND PERFORMANCES

Type ofinstallation Configuration

Air suction side Air expulsion side

“Protection cap” “Protection cap” “Lateralexpulsion cap”

“Frontalshutting panel”

Outdoor

1 x2 x x3 x x4 x x x

Indoor56 x

Page 30: AIR-WATER HEAT PUMPS FOR OUTDOOR OR INDOOR … · Allows the circulation of the water on the plant side keeping constant the temperature difference between inlet and outlet. Domestic

30

����

Page 31: AIR-WATER HEAT PUMPS FOR OUTDOOR OR INDOOR … · Allows the circulation of the water on the plant side keeping constant the temperature difference between inlet and outlet. Domestic

31

����

The manufacturer declines all responsibility for any inaccuracies in this manual due to printing or typing errors.The reserves the right to modify the products contents in this catalogue without previous notice.

Page 32: AIR-WATER HEAT PUMPS FOR OUTDOOR OR INDOOR … · Allows the circulation of the water on the plant side keeping constant the temperature difference between inlet and outlet. Domestic

32

Cod

. 3Q

E37

950