air handling units mandÍk - vzduchotechnika, protipožární … · 4 photo gallery air handling...

16
AIR HANDLING UNITS MANDÍK ®

Upload: doanque

Post on 08-Apr-2019

221 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: AIR HANDLING UNITS MANDÍK - Vzduchotechnika, protipožární … · 4 Photo Gallery Air handling unit M3.15 with rotary heat exchanger, after-heating and cooling, and with control

AIR HANDLING UNITS MANDÍK

®

Page 2: AIR HANDLING UNITS MANDÍK - Vzduchotechnika, protipožární … · 4 Photo Gallery Air handling unit M3.15 with rotary heat exchanger, after-heating and cooling, and with control

2

SAFAN Press Brakes TRUMPF TC 5000 Die-Cutting Presses Powder Paint Shop

MA

ND

ÍK, a

. s. The Company . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

Photo Gallery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

Unit Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

Air handling unit parameters according to Eurovent . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

Product Range of the Air Handling Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

Types of Internal Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

Control System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

Compact Air Handling Unit Mandík . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

Company Headquarters

CONTENTS

Page 3: AIR HANDLING UNITS MANDÍK - Vzduchotechnika, protipožární … · 4 Photo Gallery Air handling unit M3.15 with rotary heat exchanger, after-heating and cooling, and with control

3

ABOUT MANDÍK, a. s.

MA

ND

ÍK, a

. s.Established in 1990, MANDÍK, a. s. is

a  Czech, family owned company. At present it is one of the most significant manufacturers of air-handling and fire fighting components, air handling units and industrial heating systems.

The company wins recognition on the European market above all by its focus on high quality, flexibility and services to support the delivered products. The current level of the company‘s techni-cal ability is documented by supplies for subways, tunnels and nuclear power plants in many European countries.

The company observes the rules of quality management according to ISO 9001, KTA 1401, 10CFR APP10, and is a  member of RLT, the German association of air-handling equipment manufacturers. The company has all the required certificates according to Euro-pean standards, and has been certified by Eurovent, TUV SUD Industrie Service GmbH according to EN 1886.

In addition to the domestic market, the sales activities of MANDÍK, a. s. also cover a number of other Europe-an countries, where its products are delivered in collaboration with our for-eign partners.

At everyday work the company places emphasis on environment protection and occupational safety. Observance of strict European environmental and OHS standards is a common rule, which is uncompromisingly required by the company management. The company contributes to environment protection also by operating its own renewable en-ergy resources and by the widest possi-ble use of energy-saving appliances.

Our objective is maximum satisfaction of our customers, and last but not least creating comfortable working environ-ment for our employees.

Certificates

ISO 9001

Energy efficiency certificate RLT-TÜV-01

Eurovent certificate

Certificate of electrical safety AHUs, including control system

Testing protocol TÜV SÜD

Certificate of electromagnetic compatibility in residential and industrial buildings

Declaration of Conformity

Declaration of Conformity AHUs in Atex design

Hygienic survey

KTA 1401

AHU – Product certificate

Page 4: AIR HANDLING UNITS MANDÍK - Vzduchotechnika, protipožární … · 4 Photo Gallery Air handling unit M3.15 with rotary heat exchanger, after-heating and cooling, and with control

4

Phot

o G

alle

ry

Air handling unit M3.15 with rotary heat exchanger, after-heating and cooling, and with control system Energy Class A+ according to requirements of EN 13053

Page 5: AIR HANDLING UNITS MANDÍK - Vzduchotechnika, protipožární … · 4 Photo Gallery Air handling unit M3.15 with rotary heat exchanger, after-heating and cooling, and with control

5Air handling unit M4 with plate heat exchanger, after-heating and cooling, indoor design

Phot

o G

alle

ry

Page 6: AIR HANDLING UNITS MANDÍK - Vzduchotechnika, protipožární … · 4 Photo Gallery Air handling unit M3.15 with rotary heat exchanger, after-heating and cooling, and with control

6

Uni

t Des

crip

tion Use and working conditions

MANDÍK air handling units of M series (square cross sec-tion) and P series (rectangular cross section) are intend-ed for distribution and conditioning of air in heating, ventilation and air-conditioning systems. Mechanical im-purities and gaseous foreign matters, which could cause

clogging of built-in elements or corrosion of materials the unit is made from must be separated from the air handled by the unit. The units are designed for non-ex-plosive environment with temperatures around the unit from –30 °C to +40 °C.

Air handling unit variantsThe Mandík air handling units can be designed in various versions. It is possible to select surface finish of the in-ternal and external side of the panels (galvanized steel sheet, stainless steel sheet and powder coated panels). Powder coating is performed in own powder paint shop and brings great advantage of corrosion protection of shear surfaces of the steel sheet after cutting. Indoor version of the unit sections is designed for installation in closed machine rooms.

Outdoor version of the unit sections is de-signed for installation in outdoor room. The units can also be designed in hygienic ver-sion. The Mandík air handling units of hygien-ic version have been certified by the National Institute of Public Health. Air handling units Mandík can be designed in different “energy efficiency classes” and marked with official label of RLT-association, determining the “energy efficiency class”.

Unit casing parameters according to EN 1886. Tests performed by TÜV SÜD Munich:

Casing strength: D1 (M)Casing leakage class: L1 (M)Leakage between the filter and the frame < 0.5 % – F9 (M)Thermal insulation T3: (with standard insulation of specific density 50 kg/m3)

Thermal bridges: TB2Casing attenuation in the range Hz: 125 250 500 1000 2000 4000 8000 dB 15.8 23.6 31.3 37.3 39.5 39.7 43.2

Manufacture of air handling units

UNIT DESCRIPTION

Page 7: AIR HANDLING UNITS MANDÍK - Vzduchotechnika, protipožární … · 4 Photo Gallery Air handling unit M3.15 with rotary heat exchanger, after-heating and cooling, and with control

7

Mandík Air handling units were tested in TÜV Süd Munich and certified by Eurovent. Designing program for Air handling units Mandík is called AHUman. AHUman was certified as approved tool as well.Certified parameters of Mandík´s modular Air handling units are: D1, L1, F9, TB2, T3.

Prod

uct R

ange

of T

he A

ir H

andl

ing

Uni

ts

�� Product range of the units according to EN 12 7001

�� Base frame height:

– up to size M16/P16 – 120 mm– from size M20/P20 – 150 mm– from size T56 – 150 mm

Dimensions of the MANDÍK unit of M series – square cross section

size dimension A x B [mm]

nominal airflow [m3/h] size dimension A x B

[mm]nominal airflow

[m3/h]

M 2 550 × 550 2 000 M 20 1500 × 1500 20 000

M 2.2 570 × 570 2 200 M 22 1600 × 1600 22 000

M 2.5 600 × 600 2 500 M 25 1700 × 1700 25 000

M 2.8 630 × 630 2 800 M 28 1750 × 1750 28 000

M 3.15 660 × 660 3 150 M 31.5 1900 × 1900 31 500

M 3.5 700 × 700 3 500 M 34 1950 × 1950 34 000

M 4 730 × 730 4 000 M 36 2000 × 2000 36 000

M 4.5 770 × 770 4 500 M 40 2100 × 2100 40 000

M 5 800 × 800 5 000 M 45 2200 × 2200 45 000

M 5.6 850 × 850 5 600 M 48 2250 × 2250 48 000

M 6.3 900 × 900 6 300 M 50 2300 × 2300 50 000

M 7.1 950 × 950 7 100 M 53 2400 × 2400 53 000

M 8 1000 × 1000 8 000 M 56 2500 × 2500 56 000

M 9 1050 × 1050 9 000 M 63 2600 × 2600 63 000

M 10 1100 × 1100 10 000 M 67 2700 × 2700 67 000

M 11 1150 × 1150 11 000 M 75 2800 × 2800 75 000

M 12.5 1200 × 1200 12 500 M 80 2900 × 2900 80 000

M 14 1300 × 1300 14 000 M 90 3100 × 3100 90 000

M 16 1350 × 1350 16 000 M 100 3250 × 3250 100 000

M 18 1450 × 1450 18 000

PRODUCT RANGE OF THE AIR HANDLING UNITS

AIR HANDLING UNIT PARAMETERS ACCORDING TO EUROVENT

Page 8: AIR HANDLING UNITS MANDÍK - Vzduchotechnika, protipožární … · 4 Photo Gallery Air handling unit M3.15 with rotary heat exchanger, after-heating and cooling, and with control

8

Dimensions of MANDÍK unit of P series – rectangular cross section

size dimension A x B [mm]

nominal airflow [m3/h] size dimension A x B

[mm]nominal airflow

[m3/h]

P 1 450 × 400 1 000 P 18 1800 × 1150 18 000

P 2 750 × 400 2 000 P 20 1900 × 1200 20 000

P 2.2 770 × 430 2 200 P 22 2000 × 1250 22 000

P 2.5 800 × 460 2 500 P 25 2100 × 1350 25 000

P 2.8 850 × 480 2 800 P 28 2200 × 1450 28 000

P 3.15 900 × 500 3 150 P 31.5 2300 × 1500 31 500

P 3.5 950 × 530 3 500 P34 2400 × 1550 34 000

P 4 1000 × 550 4 000 P 38 2500 × 1600 36 000

P 4.5 1050 × 570 4 500 P 40 2600 × 1700 40 000

P 5 1100 × 600 5 000 P 45 2600 × 1900 45 000

P 5.6 1100 × 660 5 600 P 48 2600 × 2000 48 000

P 6.3 1100 × 730 6 300 P 50 2600 × 2100 50 000

P 7.1 1150 × 770 7 100 P 53 2700 × 2150 53 000

P 8 1200 × 800 8 000 P 56 2800 × 2200 56 000

P 9 1300 × 850 9 000 P 63 2900 × 2300 63 000

P 10 1350 × 900 10 000 P 67 3000 × 2400 67 000

P 11 1400 × 950 11 000 P 75 3150 × 2500 75 000

P 12.5 1500 × 1000 12 500 P 80 3250 × 2600 80 000

P 14 1600 × 1050 14 000 P 90 3500 × 2700 90 000

P 16 1700 × 1100 16 000 P 100 3600 × 2900 100 000

Dimensions of MANDÍK unit of T series – rectangular cross section

size dimension A x B [mm]

nominal airflow [m3/h] size dimension A x B

[mm]nominal airflow

[m3/h]

T 56 2400 x 2500 56 000 T 80 2400 x 3450 80 000

T 63 2400 x 2750 63 000 T 90 2450 x 3600 90 000

T 67 2400 x 2900 67 000 T 100 2450 x 4050 100 000

T 75 2400 x 3250 75 000

Prod

uct R

ange

of T

he A

ir H

andl

ing

Uni

ts

Page 9: AIR HANDLING UNITS MANDÍK - Vzduchotechnika, protipožární … · 4 Photo Gallery Air handling unit M3.15 with rotary heat exchanger, after-heating and cooling, and with control

9

TYPES OF USED INTERNAL MODULES

Fan sections with direct-driven fan�� Compact built-in fan with backward- curved

blades

�� Composite or steel fan impeller

�� Fan parameters correspond to difficult working conditions (high air flows, high pressures, high efficiency, optimal acoustic characteristics)

�� The fans satisfy the requirements of ErP 2015 Directive

Filter sections with frame filters�� The most frequently used as the first filtration

stage – pre-filter

�� Filter class G2 to M5

�� Filtration medium from glass or synthetic fibre

�� Leakage between the filter element and the frame < 0.5 %

Filter sections with bag filters�� Filter class G3 to F9

�� Filter element length 360, 500 or 630 mm

�� Filtration medium from glass or synthetic fibre

�� Leakage between the filter element and the frame < 0.5 %

Filter sections with metallic filters�� The most frequently used for separation of fat

and oil aerosols

�� Filter class G3

�� Filtration medium from braided aluminium fi-bres

�� Leakage between the filter element and the frame < 0.5 %

Type

s uf

Use

d In

tern

al M

odul

es

Page 10: AIR HANDLING UNITS MANDÍK - Vzduchotechnika, protipožární … · 4 Photo Gallery Air handling unit M3.15 with rotary heat exchanger, after-heating and cooling, and with control

10

Filter sections with active carbon�� Filtration medium is placed in metallic car-

tridges

�� It serves for separation of harmful substances and odour on molecular level

�� Possibility of recovery of the filtration medium

Steam heating sections�� Cu/Al plate heat exchanger

�� Heat carrier: saturated steam

�� Heat exchanger connections have threaded ends

Water heating sections�� Cu/Al plate heat exchanger

�� Heat carrier: water/anti-freeze mixtures

�� Heat exchanger connections have threaded ends

�� The heat exchangers are equipped with vent valves

Electrical heating sections�� Braided heating bars of various outputs

�� Stainless steel or iron

�� Connection of heating bar groups in sections

Type

s uf

Use

d In

tern

al M

odul

es

Page 11: AIR HANDLING UNITS MANDÍK - Vzduchotechnika, protipožární … · 4 Photo Gallery Air handling unit M3.15 with rotary heat exchanger, after-heating and cooling, and with control

11

Water cooling sections�� Cu/Al plate heat exchanger

�� Heat carrier: water/anti-freeze mixtures

�� Heat exchanger connections have threaded ends

�� The heat exchangers are equipped with vent valves

�� The section is equipped with shaped tray for condensate removal

�� Optional droplet eliminator

Steam humidifying sections�� The section is designed for installation of dis-

tribution tubes of the steam humidifier

�� The section is equipped with shaped tray for condensate removal

Cooling sections with evaporator�� Cu/Al plate heat exchanger

�� Heat carrier: coolant R407C, R410A or other

�� Exchanger connections are ready for soldering

�� The section is equipped with shaped tray for condensate removal

�� Optional droplet eliminator

Gas heating sections�� Tubular two-draught heat exchanger with in-

direct air heating of own design

�� With or without by-pass

�� Stainless version of the heat exchanger

�� Working fuel: natural gas or propane, or other fuel

�� Optional delivery including flue gas exhaust

Type

s uf

Use

d In

tern

al M

odul

es

Page 12: AIR HANDLING UNITS MANDÍK - Vzduchotechnika, protipožární … · 4 Photo Gallery Air handling unit M3.15 with rotary heat exchanger, after-heating and cooling, and with control

12

Typy

pou

žitý

ch v

esta

veb

Recuperation sections with plate heat exchanger�� Possibility of choice from various recuperation

efficiencies

�� Aluminium heat exchanger with optional anti-corrosive coating

�� The heat exchanger equipped with by-pass damper

�� Optional mixing damper

�� Optional droplet eliminator

Recuperation sections with liquid circuit�� Heat recovery by means of plate heat ex-

changers�� Heat carrier: water/anti-freeze mixtures

Recuperation sections with rotary heat exchanger�� Possibility of choice from various recupe-

ration efficiencies�� Aluminium heat exchanger with optional

surface finish for transfer of moisture�� Optional flushing section�� The heat exchanger equipped with a mo-

tor and belt drive

Silencer sections�� Baffle silencers�� Baffle length 600, 1000, 1200, 1500 mm�� Baffle shape optimized to reduce own

aerodynamic noise

Type

s uf

Use

d In

tern

al M

odul

es

View from the side of service

Front view

Page 13: AIR HANDLING UNITS MANDÍK - Vzduchotechnika, protipožární … · 4 Photo Gallery Air handling unit M3.15 with rotary heat exchanger, after-heating and cooling, and with control

13

Typy

pou

žitý

ch v

esta

veb

Counter-flow heat exchanger section

Damper sections�� The sections equipped with internal or exter-

nal regulation dampers

�� Optional tray for condensate removal

Empty sections�� Possibility to select section length

�� Optional tray for condensate removal

�� Optional service hole

End walls�� Various optional end elements

�� Regulation dampers, damping pads, rain pro-tective and directing adapters

CUSTOM-MADE AIR HANDLING UNITSOur company is ready to offer the customer the units which meet any performance or lay-out requirement.

That is why the company processes and strat-egy are implemented so that we are able to offer custom-made unit immediately.

Thus, individual internal modules can be put together with other modules to make a com-pact unit, and section length can be changed without substantial increase of price for atyp-ical design and extension of delivery dates.

Thanks to unique firm know-how we can also offer atypical front cross section of the air handling unit.

Type

s uf

Use

d In

tern

al M

odul

es

Page 14: AIR HANDLING UNITS MANDÍK - Vzduchotechnika, protipožární … · 4 Photo Gallery Air handling unit M3.15 with rotary heat exchanger, after-heating and cooling, and with control

14

COMPACT AIR HANDLING UNIT MANDÍK

Com

pact

Air

Han

dlin

g U

nit M

andí

k Compact air handling units MANDÍK are intended for air ventilation systems in residential and non-residen-tial buildings. The units are equipped with heat recov-ery exchanger, air heater and also possibility for mix-ing of exhaust/fresh air. The air temperature might be adjusted by mixing (recirculating) damper. The range consists of the units with air volume from the size 500 m3/h up to size 6800 m3/h. The compact units are fabri-cated in “plug & play“ design, including fully automatic control system.

CHARACTERISTICSEnergy efficiency

�� construction, design and fabri-cation meeting requirements of EcoDesign 2016 a 2018

�� high energy efficiency and i low pressure drop

�� continuously conducted energy re-covery of heat exchanger

�� permanent anti-freeze protection on heat exchanger

�� possibility of „free-cooling“

�� option to mix fresh air with exhaust air for heating power optimization

�� EC fans have significant power re-serve to cover external pressure drop coming from ventilation ductwork

�� excellent insulation value of the casing is supported by special seal-ing profile which eliminates poten-tial thermal bridges

�� air streams inside the compact unit are fully separated

Construction:

�� design “Plug&Play” – unit is equipped with control automatics and tested

�� very compact size

�� air inlets and air exhausts are placed on upper side

�� tubes for media and electrical con-nectors are all placed on upper side

�� smooth surface of interior inside the unit

�� clean and smooth external design out-look

�� special tightening profile secures air-tightness and optimal thermal insulation of the casing

�� control system is placed inside unit

�� all air regulating dampers are inte-grated inside unit

�� each unit is standardly equipped with base frame

Operation and maintenance:

�� intelligent and “user friendly” con-trol of unit´s operation (web inter-face, visualization etc.)

�� controlling panel´s connectivity to PC, tablet, smartphone, control display etc.

�� access doors with „over pressure“ safety function

�� easy and fast access for dismounting of all panels from maintenance side

�� construction focus on easy and sim-ple maintenance of all parts of unit

�� special mechanism for sliding out of fans for easy access to connec-tion box

FITTINGS:Air-inlet side:

�� compact filter F7 (as a standard)

�� regulating multi-blade air damper

�� „by-pass“ air damper on recuperator

�� counter-flow heat recovery exchanger

�� EC fan

�� water heater/electrical heater/con-densator

�� damping pads on air intake and ex-haust

�� air intake – circular with rubber gas-ket sealing for spiral duct connection

�� rectangular air intake with flexible joint/damping pad

Air-outlet side:

�� compact filter M5 (as a standard)

�� counter-flow heat recovery ex-changer

�� air-regulating damper for mixing of the fresh and exhausted air

�� EC fan

�� damping pads on air intake and ex-haust

�� air outlet – circular with rubber gas-ket sealing for spiral duct connection

�� rectangular air outlet with flexible joint/damping pad

Performance range of compact units MANDÍK

Many different technical variants (like for example: filtration class, heater´s medium, condensator) can be offered and recalculated individually.

Page 15: AIR HANDLING UNITS MANDÍK - Vzduchotechnika, protipožární … · 4 Photo Gallery Air handling unit M3.15 with rotary heat exchanger, after-heating and cooling, and with control

15

Refe

renc

es

REFERENCES

Page 16: AIR HANDLING UNITS MANDÍK - Vzduchotechnika, protipožární … · 4 Photo Gallery Air handling unit M3.15 with rotary heat exchanger, after-heating and cooling, and with control

MANDÍK, a. s. Dobříšská 550267 24 HOSTOMICE Czech Republic Tel.: +420 311 706 706 Fax: +420 311 584 810 E-mail: [email protected] www.mandik.cz

Issue date: March 2017