a method for synchronization
TRANSCRIPT
-
8/13/2019 A Method for Synchronization
1/8
IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 19, NO. 3, AUGUST 2004 1263
A Method for Synchronization of PowerElectronic Converters in Polluted and
Variable-Frequency EnvironmentsMasoud Karimi-Ghartemani , Member, IEEE, and M. Reza Iravani , Fellow, IEEE
Abstract—This paper presents a new synchronization methodwhich employs an enhanced phase-locked loop (EPLL) system.The operational concept of the EPLL is novel and based ona nonlinear dynamical system. As compared with the existingsynchronization methods, the introduced EPLL-based syn-chronization method provides higher degree of immunity andinsensitivity to noise, harmonics and other types of pollutionsthat exist in the signal used as the basis of synchronization. Thesalient feature of the EPLL-based synchronization method overconventional synchronization methods is its frequency adaptivitywhich permits satisfactory operation when the centre frequency
of the base signal varies. The proposed EPLL-based method of synchronization is also capable of coping with the unbalancedsystem scenarios. Structural simplicity of the EPLL-based methodgreatly simplifies its implementation in digital software and/orhardware environments as an integral part of a digital controlplatform for power electronic converters. The primary applicationof the proposed synchronization method is for the distributedgeneration units, e.g., wind generation systems, which utilizepower electronic converters as an integral part of their systems.
Index Terms—Distributed generators, phase angle estimation,synchronization, PLL, power systems.
I. INTRODUCTION
INTERFACING power electronic converters to the utilitygrid, particularly at medium and high voltages, necessitates
proper synchronization for the purpose of operation andcontrol of the power electronic based apparatus [1], [2]. Thesynchronization is usually carried out with respect to the phaseangle of voltage (or current) signal(s) of the utility system.The signal(s) used for synchronization are often corrupted byharmonics, voltage sags and swells, commutation notches,noise, phase angle jump and unbalanced operating conditions[3]–[8]. A desired synchronization method must detect thephase of the utility signal as fast as possible while adequatelyeliminating the impacts of corrupting sources on the signal.The synchronization process should be updated not only at thesignal zero-crossing, but continuously over the fundamental
period of the signal [1].The need for improvements in the existing converter syn-
chronization approaches stems from rapid proliferation of distributed generation (DG) units in electric networks. Aconverter-interfaced DG unit, e.g., a wind generator unit, a
Manuscript received August 20, 2003.The authors are with the Centre for Applied Power Electronics (CAPE),
Department of Electrical and Computer Engineering, University of Toronto,Toronto, ON M5S 3G4, Canada (e-mail: [email protected]; [email protected]).
Digital Object Identifier 10.1109/TPWRS.2004.831280
photovoltaic-based unit and a micro-turbine-generator unit,under both grid-connected and micro-grid (islanding) scenariosrequires converter synchronization under polluted and/orvariable -frequency environment.
This paper presents a new synchronization method which notonly demonstrates a superior performance as compared with theexisting methods with respect to corrupting factors of the signal,it also provides frequency adaptivity and tolerance to unbal-anced system conditions. The main building block of the syn-chronization method is an enhanced phase-locked loop (EPLL)
systemwhich operates as a nonlinear dynamical system [9]. An-other salient feature of the proposed method is the simplicity of structure which renders itself for digital implementation in bothsoftware environment, e.g., a DSP, or a digital hardware envi-ronment, e.g., FPGA or ASIC, as an integral part of a digitalcontrol platform for power electronic converters.
The paper is organized as follows. Section II is devotedto a brief study of the existing synchronization schemes.They are categorized into two general branches of open-loopand closed-loop strategies. Principles of operation of fouropen-loop and two closed-loop methods are explained andtheir advantages and shortcomings are described. The proposedmethod of synchronization is presented in Section III. Sec-
tion IV is devoted to overview the EPLL system which is themain building block of the proposed synchronization method.Performance of the method is investigated with referenceto different conditions and its advantages over the existingmethods are shown in Section V. Some properties of the methodwhich make it advantageous for digital implementation areexplained in Section VI. Section VII provides a comparisonsummary and conclusions are stated in Section VIII.
II. EXISTING METHODS OF SYNCHRONIZATION
This section outlines various existing methods of synchro-
nization. They are categorized into open-loop and closed-loop
methods. Open-loop methods directly estimate phase angle of the voltage based on -frame signals. In closed-loop methods,
while the -frame voltages are being processed, the estimation
of the phase is adaptively updated through a loop mechanism.
This loop is aimed at locking the estimated value of the phase
angle to its actual value.
A. Open-Loop Synchronization Methods
In an ideal case that no distortion/unbalance is present,
represent the grid voltages for which the transformed
0885-8950/04$20.00 © 2004 IEEE
-
8/13/2019 A Method for Synchronization
2/8
-
8/13/2019 A Method for Synchronization
3/8
KAR IM I- GHART EM ANI AND I RAVANI : A ME THOD FOR S YNCHRONI ZAT ION OF P OW ER ELE CT RONI C CONVERTE RS 1 265
Fig. 3. Block diagram of the three-phase PLL system.
should also take into account the PLL environment. More
specifically, distortion types, noise level, and the rates of phase
and frequency variations should not be overlooked.
2) Extended Three-Phase PLL-Based Method: The major
disadvantage of the three-phase PLL is its sensitivity to grid
voltage unbalance. Some attempts have been made to extendthis method for unbalanced voltages based on the concept of
symmetrical components.
Although the concept of symmetrical components is origi-
nally defined with respect to phasors, one can extend it to the
signals as functions of time. The idea is to replace the com-
plex phasor with a phase-shift operator in
time domain [6]. The phase-shift operator of 90-degree is easier
to implement [7]. Using , one
can derive the time-domain positive sequence components. The
time-domain positive sequence system is defined as
(2)
where superscript stands for the fundamental component
Rewriting (2) in terms of 90-degree phase-shift operator yields
(3)
In (3), is a 90-degree phase-shift operator. A block dia-
gram of the positive sequence extractor based on (3) is shown
in Fig. 4, [7]. This block diagram is a modified version of the
one presented in [7]. In [7], (5) does not fully take care of unbal-
ance. More specifically, it ignores the unbalance at some points.
The filters in Fig. 4 should be all-pass and generate a 90-degree
phase-shift at the center frequency . A simple first-order filter
such as can be used for this purpose.
The idea of using the positive sequence component for robust
phase detection, under unbalanced conditions, is conceptually
Fig. 4. Positive sequence extractor based on all-pass filters with 90-degreephase shift at the center frequency.
interesting. However, the method of [7] for detecting the instan-
taneous positive sequence has the following shortcomings.
1) All-pass filters are not frequency-adaptive. Therefore,
they can not make appropriate 90-degree phase shift
when the frequency varies from its nominal value of .
2) All-pass filters do not block harmonics and distortions.
Therefore, the performance of the phase detection scheme
to some degree is compromised. A low-pass filter is rec-
ommended to be used after -component extraction to re-
duce the impact of harmonics, [7].
III. PROPOSED METHOD OF SYNCHRONIZATION
A block diagram of the proposed method is shown in Fig. 5.
The positive sequence component is extracted by the first block
and then is passed to the EPLL to estimate its phase angle. In
other words, this structure is based on extracting the positive se-quence of the input voltages and then extracting the phase angle
based on this component. This strategy considers the effect of
all three phases of the system while maintaining adequate in-
sensitivity with respect to unbalanced conditions.
The block diagram for extracting the positive sequence com-
ponent is also shown in Fig. 5. This unit is comprised of three
EPLLs and arithmetic operations. The EPLLs adaptively extract
the fundamental components of the system voltages and their
90-degree phase-shifted versions. The arithmetic blocks receive
the fundamental components and the corresponding 90-degree
phase-shifted components and calculates the positive sequence
component of the utility voltages based on (3). The computa-
tional procedure is the same as the computational unit shown inFig. 4.
Advantages of this method with respect to the extended three-
phase PLL-based method are as follows. The all-pass filters
are replaced with EPLLs in the proposed structure. EPLL is
an adaptive notch filter whose frequency moves based on the
center frequency of the grid. This prevents sensitivity of the
method with respect to frequency variations which is a major
deficiency of the method of [7]. Moreover, since the EPLL is a
bandpass filter rather than an all-pass filter, the extracted posi-
tive sequence is highly distortion-free. Indeed, the input signal
undergoes two stages of filtering: one in the positive sequence
extraction stage and then in the phase estimation stage.
-
8/13/2019 A Method for Synchronization
4/8
1266 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 19, NO. 3, AUGUST 2004
Fig. 5. Block diagram of the proposed method of phase detection.
Fig. 6. EPLL Structure.
IV. EPLL SYSTEM
This section is devoted to the EPLL of [9] which isused asthe
building block of the proposed synchronization scheme of this
paper. EPLL is well suitedfor powersystem applications since it
not only provides an output signal whose phase is locked to that
of the fundamental component of the input signal, the output
signal is also locked to the fundamental component of the input
signal in its amplitude and frequency. In other words, EPLL
is capable of providing an on-line estimate of the fundamentalcomponent of the input signal while following its variations in
amplitude, phase, and frequency.
In addition to the on-line estimate of the fundamental compo-
nent, EPLL also provides an on-line estimate of the basic param-
eters of this component including its amplitude, phase, and fre-
quency. This is the salient feature of EPLL. Another important
feature of EPLL is that it provides the 90-degree phase-shifted
version of the fundamental component. This is readily done by
EPLL since it directly estimates the phase angle of the funda-
mental component of its input.
An implementation of EPLL of [9] is shown in Fig. 6, in ac-
cordance with the conventional PLL structure which consists of
a PD, LF, and VCO. The input signal is compared with itsextracted smooth version to generate an error signal
which is used by LF to generate a driving signal for VCO.
The basic structure of Fig. 6 has three independent internal
parameters: , and . Parameter dominantly
controls the speed of convergence of amplitude . Parameters
and control the rates of convergence of phase
and frequency. A low-pass filter can be incorporated after the
integration unit in the VCO to obtain a smoother estimate of
the phase angle when the utility signal is distorted.
The EPLL is originally applicable to a single-phase signal.
All the previous methods, except EKF, are suited only for three-
phase situations. However, four units of similar EPLL units are
Fig. 7. Performance comparison of five existing methods and the EPLL-basedmethod in the presence of noise.
Fig. 8. Performance comparison of five existing methods and the EPLL-basedmethod in the presence of harmonics.
linked together in the proposed synchronization method to build
a three-phase structure which is highly immune to distortions
and unbalanced conditions.
V. PERFORMANCE EVALUATION
Performance of the EPLL-based method of synchronization
is evaluated by means of a number of simulations.
Fig. 7 shows the steady-state error which occurs in phase
angle detection due to the presence of noise. For a high
signal-to-noise-ratio (SNR) of 0 dB, the error is almost 5degrees and decreases to less than one degree as SNR goes
above 10 dB. Among the existing methods, the LPF-based
method generates the largest error while the EKF-based,
the PLL-based, the SVF-based, and the LSE-based methods
perform better, respectively. Comparing with the conventional
three-phase PLL-based method, the proposed method performs
almost twice as good.
The proposed method provides a highly distortion-free esti-
mate of the phase angle in the presence of harmonic pollution. A
set of study results are shown in Fig. 8. The input signal is com-
prised of a fundamental component and a fifth harmonic com-
ponent. The amplitude of this harmonic is taken as the variable,
-
8/13/2019 A Method for Synchronization
5/8
KAR IM I- GHART EM ANI AND I RAVANI : A ME THOD FOR S YNCHRONI ZAT ION OF P OW ER ELE CT RONI C CONVERTE RS 1 267
Fig. 9. Response of the EPLL-based method to a phase jump of 10 degrees at ms.
Fig. 10. Response of the EPLL-based method to a frequency jump of 5 Hz at ms.
and its effect on the steady-state performance is shown. As the
parameter varies from zero to 0.4, a maximum error of almost
0.2 degrees is generated by the EPLL-based method. The LSE-
based method generates an error which is almost twice. Theerror associated with the conventional three-phase PLL-based
method is around 20 times larger.
Effects of jumps in phase and frequency are shown by Figs. 9
and 10. A phase jump of 10 degrees occurs in the input signal at
time msec and the error in tracking this variation by the
EPLL-based method is shown in Fig. 9. A transient error with
a peak of about 10 degrees is observed which dies out in a few
cycles. In Fig. 10, a frequency step of 5 Hz occurs in the input
voltage at time msec and the error introduced in the
estimated phase angle using the EPLL-based method is shown.
Similarly, a transient error is generated which decays to zero in
a few cycles. The EPLL-based method adaptively follows the
phase and frequency variations with no steady-state errors.Unbalance tolerance is another main feature of the
EPLL-based synchronization scheme. In Fig. 11, a 50% voltage
sag occurs simultaneously in phases and at msec.
The method is able to adjust itself to the new condition with
no steady-state error. In a very significant unbalance scenario
(Fig. 12), a random voltage sag is imposed on all three phases
of the utility voltages. Fig. 12(a) shows the input signals. The
estimated phase angle has no steady-state error, Fig. 12(b).
In the last case, a step-up of 10 degrees occurs in the phase
angle of at ms. Fig. 13 shows that the method
adjusts itself to the new condition within a few cycles and no
steady-state error.
Fig. 11. Response of the EPLL-based method to 50% voltage sag on phases and at ms.
Fig. 12. Response of the EPLL-based method to a random voltage sag on allthree phases at m: (a) input signals and (b) error in estimated phaseangle.
Fig. 13. Response of the EPLL-based method when the phase angle of undergoes a 10-degree step-up at ms.
The proposed system is employed for synchronization pur-
pose in a DG system to investigate micro-grid operational sce-
narios [17]. The system of Fig. 14 is a single-line diagram of a
three-phase system which is used to investigate micro-grid op-
erational scenarios [17]. The basic configuration and parameters
come from the IEEE Standard 399-1997. This system is com-
posed of a 13.8 kV, three-feeder distribution subsystem which
is connected to a large network through a 69-kV radial line. A
combination of conventional and nonconventional loads ( to
) are supplied through three radial feeders. Loads to
are composed of linear RL loads. Load is a diode-rectifier
load. The aggregate of and constitutes a sensitive load
-
8/13/2019 A Method for Synchronization
6/8
1268 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 19, NO. 3, AUGUST 2004
Fig. 14. Single-line diagram of the DG system.
within the distribution system. The system includes two gen-
eration units: DG1 (5 MVA) and DG2 (2.5 MVA) located on
the first and third feeders. A voltage-source converter (VSC) is
utilized by DG2 as an interface to control exchange of active
and reactive powers for the sensitive load [17]. Conventional
three-phase PLL [3], [15] is optimally set and its performance
is compared with the proposed EPLL-based system in this sec-
tion. To make the comparison, both the PLL and the EPLL areused to measure the frequency. The DG1 speed is used as an
index to judge accuracy and convergence. The power system is
modeled in PSCAD/EMTDC environment and the EPLL-based
system is simulated in Matlab/Simulink and is properly inter-
faced to the power system.
A line-to-ground fault occurs on the 69-kV line at s.
The fault is cleared by triple-pole operation of CBs at both ends
of the line, five cycles after the fault inception, i.e., at
s, and a micro-grid is formed due to the accidental islanding.
The islanding phenomenon is detected five cycles after the CBs
open, i.e., at s, at which time the micro-grid control
strategy of the DG units is activated. Results of frequency and
phase angle estimation are shown in Fig. 15 that confirms closebehavior of the PLL and EPLL. However, the zoomed version
of the graph over the fault period, Fig. 16, reveals that the PLL
is not capable of providing an accurate estimate for frequency
neither for phase angle. The reason isdue to the presence of fault
which makes the voltages unbalanced. Oscillatory behavior in
estimated frequency by the PLL is observed [Fig. 16(a)] even
though some low-pass filters are already employed to smoothen
its response. On the contrary, the EPLL is capable of providing
a smooth and accurate estimate of the frequency [Fig. 16(a)].
Similar error is also observed in the estimated phase angle by
the PLL, which is shown in Fig. 16(b).
Another case study investigates the micro-grid for-
mation and its electrical transients due to a permanentline-to-line-to-line-to-ground (L-L-L-G) fault on the 69-kV
line. The time intervals corresponding to fault clearing, is-
landing detection and reclosure attempts are the same as those
of the previous case studies except that system islanding is
detected in two cycles (as opposed to five cycles in the previous
cases). Islanding detection in two cycles is possible in this case
because of the severe voltage drop due to the L-L-L-G fault.
Fig. 17 shows the estimated frequency and phase angle by the
PLL and the EPLL. The EPLL provides more accurate results
with better transient response. A zoomed version of this graph
is shown in Fig. 18 for better view of the performance of PLL
and EPLL during unbalanced conditions.
Fig. 15. Temporary line-to-ground fault at s, islanding at s, and reclosure at s: (a) DG1 speed, estimated frequency by PLL,and estimated frequency by EPLL and (b) difference between estimated phaseangles by PLL and EPLL.
Fig. 16. Zoomed version of Fig. 15 over the fault period of [0.5 0.583] s.
Fig.17. Three-phase line-to-ground fault. (a) DG1 speed, estimatedfrequencyby PLL, and estimated frequency by EPLL. (b) Difference between estimatedphase angles by PLL and EPLL.
VI. DIGITAL IMPLEMENTATION
This section studies advantages of the EPLL-based method
from the standpoint of digital implementation. The proposed
method is fundamentally comprised of a number of EPLLs. The
-
8/13/2019 A Method for Synchronization
7/8
KAR IM I- GHART EM ANI AND I RAVANI : A ME THOD FOR S YNCHRONI ZAT ION OF P OW ER ELE CT RONI C CONVERTE RS 1 269
Fig. 18. Zoomed version of Fig. 17.
continuous-time differential equations governing an EPLL are
derived from the block diagram of Fig. 6 as
(4)
where d ot o n top s tands f or t ime d erivative, is
the error signal, is the input signal,
is its fundamental component, and , and are the
amplitude, frequency, and phase angle, respectively.
A discrete-time version of (4) can be derived based on the first
approximation of the derivative for digital implementation pur-
poses. The investigations show that the first-order approximated
system adequately maintains the desired properties of the algo-
rithm due to the structural robustness of the EPLL. Assuming
sampling period of , the discrete-time recursive equations are
(5)
where , and are called
step sizes. These equations resemble the LMS algorithm used
in signal processing applications. The LMS algorithm is known
for its simple structure and efficient performance in many ap-
plications.
Equations (5) are well suited for implementation on software
(e.g., DSP) platforms or hardware (e.g., FPGA or ASIC) plat-
forms due to their simplicity of structure. An important feature
of this algorithm is that its three parameters arequalitative parameters. These parameters are directly related to
, and , respectively. This indicates that small varia-
tions of these parameters do not affect theperformance of EPLL.
This is very important in fixed-point implementations for which
bit-length limitations exist.
The feasibility of the EPLL algorithm is verified in laboratory
using the TMS320C6711 Texas Instruments™ floating point
platform. It comprises an on-board power supply, peripherals
providing A/D and D/A units and the shell program through
which the DSP is controlled. The C programming language is
used to write the code. Fig. 19 shows a distorted signal whose
phase angle is extracted by the proposed method.
Fig. 19. Implementation on DSP: (a) distorted input and (b) extracted phaseangle.
Further evaluations have been carried out regarding the per-
formance of the discrete version of the synchronization method
using Fixed-Point Blockset in Matlab Simulink environment.
The results confirm that the method performs well even when
it is implemented with a relatively low number of bits, e.g., 8 or
10 bits.
VII. SUMMARY OF COMPARISONThis section provides a qualitative comparison of the EPLL-
based method with the existing synchronization methods. The
methods are compared from the following standpoints.
• Noise immunity.
• Distortion/disturbance rejection.
• Phase angle adaptivity.
• Frequency adaptivity.
• Unbalance robustness.
• Structural simplicity (ease of design, tuning and imple-
mentation),
An index is defined with respect to each item to relatively com-
pare performances of the methods. The possible range of per-formance is divided into six regions, as follows.
• (0) Lacking: means that the method takes no account of
that parameter and hence the performance of the method is
completely prone to that specific parameter. For example,
the LPF-based method does not consider frequency varia-
tions and its performance with respect to frequency varia-
tions is not acceptable.
• (1) Bad : means that although the method has not taken that
parameter into consideration in its structure, nevertheless,
its performance can be acceptable in some scenarios. Ex-
amples of this are all the open-loop methods with respect
to unbalance. Although they do not consider any precau-
-
8/13/2019 A Method for Synchronization
8/8
1270 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 19, NO. 3, AUGUST 2004
TABLE ICOMPARISON OF THE SYNCHRONIZATION METHODS
tions for unbalanced conditions, nevertheless, due to the
symmetry of the to transformation, they may re-
ject impact of some types of unbalance.
• (2) Average: means that the method inherently has the ten-
dency to improve its performance in this regard but it can
not reach the desired level, even though, some improve-
ments are achieved. For example, the extended SVF-based
method tries to accommodate frequency variations but it
can not perform a satisfactory job.
• (3) Good : means that the performance is “good enough”.For example, most of the methods offer a good harmonic
rejection. This is as far as some ordinary applications are
concerned, but the estimated value may not be sufficiently
precise for more crucial applications.
• (4) Very Good : means that the method performs very well,
however, there might still be some room for improvement.
• (5) Excellent : means that the method performs as good as
possible for the prescribed application and no further im-
provement is desired with regard to this specific factor. For
example, all the methods properly follow the step changes
in the phase angle. No more improvement in this regard is
needed.
Table I shows the comparison results. Major shortcomingsof the existing methods can be summarized as follows. The
LPF-based method is not capable of adjustment to frequency
variations. Its performance is also affected by the utility voltage
unbalance. The SVF-based method has the same shortcomings
as the LPF-based method while it performs better with respect
to utility distortions and noise. The main drawback of the three-
phase PLL method is that it cannot accommodate voltage un-
balance. Although the extended three-phase PLL method elim-
inates this shortcoming, it is sensitive to frequency variations.
The introduced EPLL-based method has no major shortcoming
comparable to the other methods.
VIII. CONCLUSION
A new synchronization method is proposed and its perfor-
mance is evaluated. The method is based on an EPLL system
which offers structural simplicity and robustness. The EPLL-
based method of synchronization is immune to noise, harmonics
and other types of distortion. It is capable of coping with unbal-
anced conditions and it is frequency adaptive. Its structural sim-
plicity and robustness makes it suitable for digital implementa-
tion as an integral part of digital controller platforms for power
electronic converters.
REFERENCES
[1] J. Svensson, “Synchronization methods for grid-connected voltagesource converters,” in Proc. Inst. Elect. Eng. Generation, Transmission,
Distribution, vol. 148, May 2001, pp. 229–235.[2] N. Mohan, T. M. Undeland, and W. P. Robbins, Power Electronics-Con-
verters, Applications, and Design. New York: Wiley, 1995.[3] V. Kaura and V. Blasko, “Operation of a phase locked loop system under
distorted utility conditions,” IEEE Trans. Ind. Applicat., vol. 33, pp.58–63, Jan. 1997.
[4] Voltage Characteristics of Electricity Supplied by Public DistributionSystems, 1994. European Standard EN50160, CENELEC.
[5] R. Weidenbrug̈, F. P. Dawson, and R. Bonert, “New synchronizationmethod for thyristor power converters to weak AC systems,” IEEE Trans. Ind. Electron., vol. 40, pp. 505–511, Oct. 1993.
[6] C.-C. Chenand Y.-Y. Hsu, “A novel approach tothe designof a shunt ac-tive filterfor an unbalanced three-phase four-wire system undernonsinu-soidal conditions,” IEEE Trans. Power Delivery, vol.15, pp.1258–1264,Oct. 2000.
[7] S.-J. Lee, J.-K. Kang, and S.-K. Sul, “A new phase detecting methodfor power conversion systems considering distorted conditions in powersystem,” in Proc. Industry Applications Conf., 34th IAS Annu. Meeting,vol. 4, 1999, pp. 2167–2172.
[8] M. H. J. Bollen, “Fast assessment methods for voltage sags in distribu-tion systems,” IEEE Trans. Ind. Applicat., vol. 32, pp. 1414–1423, Nov.1996.
[9] M. Karimi-Ghartemani and M. R. Iravani, “A nonlinear adaptive filter
for on-line signal analysis in power systems: Applications,” IEEE Trans.Power Delivery, vol. 17, pp. 617–622, Apr. 2002.
[10] G. H. Jung et al., “DSP based control of high power static VAR com-pensator using novel vector product phase locked loop, ” in Proc. 27th
Annu. IEEE Power Electronics Specialists Conf. (PESC’97), Baveno,Italy, 1996, pp. 238–243.
[11] H.-S. Song and K. Nam, “Instantaneous phase-angle estimation algo-rithm under unbalanced voltage-sag conditions,” in Proc. Inst. Elect.
Eng. Generation, Transmission, and Distribution, vol. 147, 2000, pp.409–415.
[12] M. F. Lai and M. Nakano, “Special section on phase-locked loop tech-niques,” IEEE Trans. Ind. Electron., vol. 43, pp. 607–608, Dec. 1996.
[13] G. C. Hsieh and J. C. Hung, “Phase-locked loop techniques—A survey,” IEEE Trans. Ind. Electron., vol. 43, pp. 609–615, Dec. 1996.
[14] W. C. Lindsey andC. M. Chie, “A survey of digital phase-locked loops,”Proc. IEEE , vol. 69, pp. 410–431, Apr. 1981.
[15] S.-K. Chung, “A phase tracking system for three phase utility inter-
face inverters,” IEEE Trans. Power Electron., vol. 15, pp. 431–438, May2000.
[16] W. Leonhard, Control of Electrical Drives. Berlin, Germany:Springer-Verlag, 1985.
[17] F. Katiraei, M. R. Iravani, and P. W. Lehn, “Micro-grid autonomous op-eration during and subsequent to islanding process,” IEEE Trans. Power Syst., to be published.
Masoud Karimi-Ghartemani (M’01) received the B.Sc. and M.Sc. degrees inelectrical engineering from Isfahan University of Technology, Isfahan, Iran, in1993 and 1995 and the Ph.D. degree in electrical engineering from Universityof Toronto, Toronto, ON, Canada, in 2004.
He was with the Center for Applied Power Electronics (CAPE), Departmentof Electrical and Computer Engineering, University of Toronto, from 1998 to2001. His research is focused on developing control and signal processing algo-rithms for power systems protection, control and power quality.
M. Reza Iravani (M’85–F’03) received the B.Sc. degree fromTehranPolytech-nique University, Tehran, Iran, in 1976 and the M.Sc. and Ph.D. degrees fromthe University of Manitoba, Winnipeg, MB, Canada, in 1981 and 1985, respec-tively, all in electrical engineering.
He started his career as a Consulting Engineer in 1976. Presently, he is a Pro-fessor at the University of Toronto, Toronto, ON, Canada. His research interestsinclude power electronics and power system dynamics and control.