Manual Converter Module UV-14
A_EN_05806_00D1
Magnetic Inductive Flowmeter
Converter Module UV-14 Version : 001
Description
The converter module UV-14 is for the connection the transmitter families MDS and NFD on a PLC.
The module converts the voltages, coming from the transmitter, in a pulse frequency proportional to the flow. The output frequency is set to 50 kHz at 10 m/sec..Additional to the pulse output a signal Zero point O.K. is available.
For controlling the functions of the converter card a signal from the status of the valve and a signal for starting the calibration of zero point is necessary.
A dynamic pulse shut off function is installed, which is controlled from the status signal of the valve.
The zero point setting can be activated with a external input.
During the batch is running it is possible to control the zero point which was set in this time the valve was opening.
The converter module is for installation on a DIN Rail.
Bopp & Reuther Messtechnik GmbHAm Neuen Rheinhafen 467346 Speyerwww.bopp-reuther.de
-
Manual Converter Module UV-14
M_GB_05806_00D2
Technical Data
Housing DIN- Rail mounted acc. DIN EN 60715 Wide 35 mmProtection class IP 20Power Supply Nominal 24 VDCPower Supply range 18 VDC to 36 VDCNoise < 1%Current consumption max. 100 mA at 24 VDCAmbient temperature 0 to 50 CHumanity 50%
Measuring Range
Full scale 10 m/sec.
Accuracy at reference conditions
10-100% of full scale 0,5% of real value0-10% of full scale 0,5% of real value 0,01% of full scale
Repeatability 0,1% of real value 0,005% of full scale
Pulse output
Frequency max. 50 kHzPulse wide 10 sec.
Digital inputs isolated via optocoupler
Input voltage range same as Power Supply rangeHigh- Level > 10 VDCLow- Level < 5V VDCInput resistance 2,4 kOhm
Digital outputs isolated via optocoupler
Output voltage range same as Power Supply range high sides witch 20mA max.short- circuit proof
K-factor depending of diameter of the transmitter
DN pulses / l
10 6366015 2829320 1591525 1018532 621640 3978
-
Manual Converter Module UV-14
M_GB_05806_00D3
Function of In- and Outputs
Outputs
Volume pulses
The output frequency is 50 kHz at 100 % Full scale and the pulse length is 10s.
A pulse standardizing is not implemented. For the calculation of the preset value the k-factor must be selected depending of the diameter of the Flowmeter.
Example:
Diameter DN 15K-Factor for DN15 28293 pulses/LBatch quantity 100mL
Preset for counter = 0,1L x 28293 pulses / L = 2829 pulses
Zero point O.K.
The flow at the closed valve is always measured, after the flow have reached the half value of the flow rate in the time of closing the valve. If valve opens, the status of the last measuring is saved.
Output " HIGH
The output goes high, if the flow is < 1 % of full scale before the valve opens.
Output " LOW
The output goes low, if the flow is > 1 % of full scale before the valve opens.
The output is saved during the valve is open ( Input valve open/ closed " LOW ). It is therefore possible, to control the zero point during the valve is open and start- if the zero point is wrong- a zero point setting at the next dosing cycle.
Inputs
Valve OPEN / CLOSED
This input control the switch off of the pulse output
Controlling
Valve open : Input "HIGH"Valve closed : Input "LOW
If the input is LOW , then the pulse output is closed if :
- the flow goes constant or- the flow have a oscillation
-
Manual Converter Module UV-14
M_GB_05806_00D4
Zero Point
With the input Zero Point the zero point setting can be started.
The adjustment of the Zero Point is always automatically.
Input HIGH Zero Point setting activated, LED Zero Point is ONInput LOW Zero Point setting deactivated, LED Zero Point is OFF
Zero Point setting is only possible if
- The dosing valve is closed and- The pulse output is switched off.
If the Zero point is calibrated correctly, the LED FLOW must be off. The PLC can also control the output Zero Point O.K. .
Fuse for Power Supply 24 VAC for transmitter
To protect the Converter Module a fuse between the Power Supply 24 VAC and the wires red / blue is installed.The Fuse is soldered on the printed circuit. The value of this fuse is 630 mA Time Lag T.
DisplayIn front of the module 4 LED are installed24VDC LED is ON, if 24VDC is connected on terminal connectors 6 and 1224VAC LED is ON, if 24VAC is connected on terminal connector 10 and 11. The LED can anyway be
OFF if the internal Fuse is damaged.FLOW LED is ON, if the flow is > 0,5% of full scaleZEROPOINT LED is ON, if the calibration of the Zero Point is active.
-
Manual Converter Module UV-14
M_GB_05806_00D5
+ 24
VD
C
24 VA
C / 5
0-60
Hz
-24
VD
C / G
rou
nd
blu
e
red
bro
wn
whi
te
gree
n
yello
w
Valv
e o
pen
/ c
lose
d
Zero
Po
int
Zero
Po
int O
.K.
Volu
me
Puls
es
Measuring cable
24 VDC
FLOW
ZERO
24 VAC
INPUTS OUTPUTS
Terminal connector2nd level
Terminal connectortop level
7 8 9
1 2 3 4 5 6
10 11 12
13 14 15
16 17 18
-
Manual Converter Module UV-14
M_GB_05806_00D6
=
+ / - 15VDC
Fuse 0,63A Time Lag T
RedBlue
Shield
White
Brown
Green
Yellow
612
1011
4
5
2
1
3
7
9
13
14
17
16
Me
sska
bel
+ / - 15 VDC
Valve open / closed
Zero Point
Volume Pulses
Zero Point O.K.
24VDC
24VAC
Optocoupler
PLC
Inpu
tsO
utp
uts
UV-14
+
-
-
Manual Converter Module UV-14
M_GB_05806_00D7
Volu
me
Puls
esFl
ow
Valve closing ( = 100% )
50%
Flow constant or goes higher
Pulse output switched ON
Pulse output switched OFF
Valv
e o
pen
/ c
lose
d
Valve closed
Zero
Po
int
Zero
Po
int s
ettin
g
Zero Point setting and pulse output switching
Zero
Po
int O
.K.
-
Manual Converter Module UV-14
M_GB_05806_00D8
Volu
me
Puls
esFl
ow
Valve closing ( = 100% )
50%
Flow is constant or goes higher
Pulse output switched ON
Pulse output switched OFF
Valv
e o
pen
/ c
lose
d
Valve closed
Zero
Po
int
Zero
Po
int S
ettin
g
Zero Point setting and pulse output switching : Zero Point wrong
Zero
Po
int O
.K.
Zero Point > 1% , must be calibrated
-
Manual Converter Module UV-14
M_GB_05806_00D9
Volu
me
puls
esFl
ow
Valve closing ( = 100% )
50%
Flow is constant or goes higher
Pulses output switched ON
Pulses output switched OFF
Valv
e o
pen
/ c
lose
d
Valve closed
Zero
Po
int
Zero
Po
int S
ettin
g
Controlling output Zero Point O.K. and activation of Zero Point setting
Zero
Po
int O
.K.
-
Manual Converter Module UV-14
M_GB_05806_00D10
Volu
me
puls
esFl
ow
Valve closing ( = 100% )
50%
Flow is constant or goes higher
Pulse output switched ON
Pulse output switched OFF
Valv
e o
pen
/ c
lose
d
Valve closed
Updating output Zero Point O.K.
Zero < 1%Zero > 1%Zero
po
int O
.K.
Output Zero Point O.K :
Zero < 1%