8kW, 11kW, 16kW, 20kW & 22kW Standby Generators

Restoring Power with Confidence

GENERATOR 8 kW 11 kW 16kW 20kW 22kW

Rated Maximum Continuous Power Capacity (LP) 8,000 Watts 11,000 Watts 16,000 Watts 20,000 Watts 22,000 Watts

Rated Maximum Continuous Power Capacity (NG) 7,000 Watts 10,000 Watts 16,000 Watts 18,000 Watts 19,500 Watts

Rated Voltage 120/240 120/240 120/240 120/240 120/240

Rated Maximum Continuous Load Current 240 Volts 33.3 LP/29.2 NG 41.6 LP/37.5 NG 66.6 LP/66.6 NG 83.3 LP/75 NG 91.6 LP/81.3 NG

Phase 1 1 1 1 1

Number of Rotor Poles 2 2 2 2 2

Rated AC Frequency 60Hz 60Hz 60Hz 60Hz 60Hz

Power Factor 1 1 1 1 1

Main Line Circuit Breaker 35 Amp 50 Amp 65 Amp 90 Amp 100 Amp

Battery Specifications (not included) Group 26R Group 26R Group 26R Group 26R Group 26R

12 Volts and 12 Volts and 12 Volts and 12 Volts and 12 Volts and

350 Cold-cranking 525 Cold-cranking 525 Cold-cranking 525 Cold-cranking 525 Cold-cranking

Amperes Minimum Amperes Minimum Amperes Minimum Amperes Minimum Amperes Minimum

Unit Weight 360 Pounds 407 Pounds 513 Pounds 516 Pounds 526 Pounds

Dimensions (L” x W” x H”) 48 x 25 x 29 48 x 25 x 29 48 x 25 x 29 48 x 25 x 29 48 x 25 x 29

Sound output in dB(A) at 23 ft. 62 63 66 (60 Quiet Test) 66 (60 Quiet test) 67 (58 Quiet test)

ENGINE 8 kW 11 kW 16kW 20kW 22kw

Type of Engine OHVI OHVI V-TWIN OHVI V-TWIN OHVI V-TWIN OHVI V-TWIN

Number of Cylinders 1 2 2 2 2

Displacement 410cc 530cc 992cc 999cc 999cc

Cylinder Block Aluminum w/Cast Aluminum w/Cast Aluminum w/Cast Aluminum w/Cast Aluminum w/Cast

Iron Sleeve Iron Sleeve Iron Sleeve Iron Sleeve Iron Sleeve

Oil Capacity Including Filter Approx. 1.5 Qts. Approx. 1.7 Qts. Approx. 1.9 Qts. Approx. 1.9 Qts. Approx. 1.9 Qts.

Operating RPM 3,600 3,600 3,600 3,600 3,600

Fuel Consumption

Natural Gas 1/2 Load 78 124 193 205 184

Full Load 121 195 312 308 281

Liquid Propane 1/2 Load 32 (0.87) 43 (1.18) 72 (1.99) 76 (2.08) 83 (2.16)

Full Load 52 (1.42) 71 (1.92) 130 (3.57) 140 (3.85) 127 (3.68)

Required fuel pressure to generator fuel inlet at all load ranges 3.5 to 7 inches of water column for natural gas, 10 to 12 inches of water column for LP gas

CONTROLS (8kW, 11kW, 16kW, 20kW & 22kW)

2-Line Plain Text LCD Display Simple user interface for ease of operation

Mode Switch

-Auto Automatic Start on Utility failure. 7 day exerciser. Programmeable on 16kW and larger to weekly, bi-weekly, or monthly. (Requires product registration to run in Auto mode.)

-Off Stops unit. Power is removed. Control and charger still operate.

-Manual/Test (start) Start with starter control, unit stays on. If utility fails, transfer to load takes place.

Automatic Voltage Regulator w/Overvoltage Protection Standard

Automatic Low Oil Pressure Shutdown Standard

Overspeed Shutdown Standard, 72Hz

High Temperature Shutdown Standard

Overcrank Protection Standard

Safety Fuse Standard

Engine Start Sequence Transition time utility to generator approximately 30 seconds

Battery Charger Standard