8. evaluation of discharges 2003. 10. 18. 8. evaluation of discharges ultimate goal is to evaluate...

31
8. Evaluation of Discharges 2003. 10. 18

Upload: clarence-douglas

Post on 02-Jan-2016

214 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: 8. Evaluation of Discharges 2003. 10. 18. 8. Evaluation of Discharges Ultimate goal is to evaluate Must be ascertain - Observed discharges : Harmful or

8. Evaluation of Discharges

2003. 10. 18

Page 2: 8. Evaluation of Discharges 2003. 10. 18. 8. Evaluation of Discharges Ultimate goal is to evaluate Must be ascertain - Observed discharges : Harmful or

8. Evaluation of Discharges

Ultimate goal is to evaluateMust be ascertain - Observed discharges : Harmful or not ? - Absence of discharges : safe level ? (minimum detectable discharge)

In connection with other test( tanδ, overvoltage test..) : make clear that observed dielectric will be sufficiently safe

Three section

- Recognition : Type of discharge

- Mechanism : deterioration of the insulation

- Evaluation : discharge levels

Page 3: 8. Evaluation of Discharges 2003. 10. 18. 8. Evaluation of Discharges Ultimate goal is to evaluate Must be ascertain - Observed discharges : Harmful or

8.2 Recognition

8.2 Recognition1. Oscillogram - discharge pattern -> valuable indication to the type and origin of discharges - distribution of phase angle - ratio between positive and negative pulses2. X-Y diagram - discharge magnitude (function of the test voltage) - recorded in pC(logarithmic scale)3. Time effect - in some cases discharge magnitude and the extinction voltage change(when testing for sometime at high voltage) - X-Y diagram(good practice) : rising and declining voltage - ignition effects and time effects can be shown

Page 4: 8. Evaluation of Discharges 2003. 10. 18. 8. Evaluation of Discharges Ultimate goal is to evaluate Must be ascertain - Observed discharges : Harmful or

8.2 Recognition

4. Ambience

- Character or location of the discharge determined

by making changes in or around the sample

a. Immersion in oil or applying grease : surface discharge

b. changing pressure in GIS : distinguish between

discharges in the pressurized gas

and isolated discharges

c. increasing the temperature : fissures

- temperature cycles : interstices

- good tool : combined with antecedents of the sample and

with the results of other tests

Page 5: 8. Evaluation of Discharges 2003. 10. 18. 8. Evaluation of Discharges Ultimate goal is to evaluate Must be ascertain - Observed discharges : Harmful or

8.2 Recognition

8.2.1 Dielectric-bounded discharges

- Occur between dielectric bounds(internal or superficial)

: fairly symmetric patterns(Fig8.1)

- Occur in advance of the test voltage peaks

- Impulse (same amplitude, number and location) appear at the positive and negative half cycles

- There is some random variation (amplitude and phase angle)

Page 6: 8. Evaluation of Discharges 2003. 10. 18. 8. Evaluation of Discharges Ultimate goal is to evaluate Must be ascertain - Observed discharges : Harmful or

8.2 Recognition

8.2.1 Dielectric-bounded discharges

1. A squarely shaped diagram : limited cavity(Fig 8.2,3)

- Further discharges not possible (after ignition of the cavity, the available space is occupied)

Page 7: 8. Evaluation of Discharges 2003. 10. 18. 8. Evaluation of Discharges Ultimate goal is to evaluate Must be ascertain - Observed discharges : Harmful or

8.2 Recognition

2. A triangular diagram(Fig8.4) : somewhat larger cavity - discharges can expand first and remain constant (fill with

discharge)

Page 8: 8. Evaluation of Discharges 2003. 10. 18. 8. Evaluation of Discharges Ultimate goal is to evaluate Must be ascertain - Observed discharges : Harmful or

8.2 Recognition

3. An ever increasing diagram(Fig8.5) - surface discharge(Fig8.6 a) - discharge in a large gap(Fig8.6 b) : 100,000pC observed - discharge in an interface(Fig8.6 c)

Page 9: 8. Evaluation of Discharges 2003. 10. 18. 8. Evaluation of Discharges Ultimate goal is to evaluate Must be ascertain - Observed discharges : Harmful or

8.2 Recognition

4. Effect of time (1)

- at its maximum value : keep for some time(e.g. 30min)

: discharge magnitude may change

- magnitude decrease and higher extinction voltage(Fig8.7)

- longer period(e.g. 24hr) : more

Page 10: 8. Evaluation of Discharges 2003. 10. 18. 8. Evaluation of Discharges Ultimate goal is to evaluate Must be ascertain - Observed discharges : Harmful or

8.2 Recognition

- Elastomeric insulation : fissures (direction of the electric field, Fig 8.8) - Round cavities in thermoplastics(Fig 8.9) : gradual increase in discharge magnitude (a number of cavities of

various sizes) : higher extinction voltage (formation of electrically conducting lay

ers at the surface of the cavity) : rested for sometime(e.g. 24h) : restored

Page 11: 8. Evaluation of Discharges 2003. 10. 18. 8. Evaluation of Discharges Ultimate goal is to evaluate Must be ascertain - Observed discharges : Harmful or

8.2 Recognition

5. Effect of time (2)

- inception voltages are lowered instead of increased by testing the sample at high voltage(Fig 8.10,11)

Fig 8.10 : Voltage is kept at maximum value, discharge level is gradually increased and becomes stable(e.g.15min)

- Extinction voltage is lower than the inception voltage

: epoxy resin(small amount of moisture during manufacture)

Page 12: 8. Evaluation of Discharges 2003. 10. 18. 8. Evaluation of Discharges Ultimate goal is to evaluate Must be ascertain - Observed discharges : Harmful or

8.2 Recognition

5. Effect of time (2)

Fig 8.11 : extreme case of deterioration by voltage

- oil-impregnated paper(not sufficiently dry)

- bubbles are generated and increase in size and number during testing.

- rested for some time : discharges will disappear

Page 13: 8. Evaluation of Discharges 2003. 10. 18. 8. Evaluation of Discharges Ultimate goal is to evaluate Must be ascertain - Observed discharges : Harmful or

8.2 Recognition

8.2.2 Electrode-bounded discharges- pattern : asymmetric(Fig 8.12) Between electrode and dielectric boundary- Accur : in advance of the test voltage peaks One half cycle : small number of large discharges The other cycle : larger number of smaller discharges Amplitude differece : 3 – 10 times

Page 14: 8. Evaluation of Discharges 2003. 10. 18. 8. Evaluation of Discharges Ultimate goal is to evaluate Must be ascertain - Observed discharges : Harmful or

8.2 Recognition

8.2.2 Electrode-bounded discharges

- squarely shape X-Y diagram(Fig8.2) : internal discharge in an

electrode-bounded cavity(Fig 8.13 a)

- Ever-growing X-Y diagram(Fig8.14) : surface discharge

( starting from one of the electrodes)

Page 15: 8. Evaluation of Discharges 2003. 10. 18. 8. Evaluation of Discharges Ultimate goal is to evaluate Must be ascertain - Observed discharges : Harmful or

8.2 Recognition

8.2.2 Electrode-bounded discharges

- Time effect : small

Self-healing effect : with surface discharge spurious

discharges are seen and extinguish again

(voltage is increased or kept constant for observation)

- Fig8.15

: internal discharge : lower voltage

surface discharge : higher voltage

Page 16: 8. Evaluation of Discharges 2003. 10. 18. 8. Evaluation of Discharges Ultimate goal is to evaluate Must be ascertain - Observed discharges : Harmful or

8.2 Recognition

8.2.4 Floating objectsMetallic parts : peculiar discharge patterns(Fig8.16) - Equal : amplitude, number and phase angle at both half cycles - More-or-less equally spaced, sometimes occur in pairs - Move around the time base, disappear(certain point) and restart(moment) - X-Y diagram : square (Fig8.2) - Unaffected by time

Page 17: 8. Evaluation of Discharges 2003. 10. 18. 8. Evaluation of Discharges Ultimate goal is to evaluate Must be ascertain - Observed discharges : Harmful or

8.2 Recognition

8.2.4 Floating objects

Peculiar behavior is caused :

- bad contact(floating parts or floating part and

electrodes,

loose connection to a screen or unwanted metal

particle)

- serious defect in insulation

Disturbances in a discharge test

- metallic objects laying on the floor

- Clean floor : 30kV or more

Page 18: 8. Evaluation of Discharges 2003. 10. 18. 8. Evaluation of Discharges Ultimate goal is to evaluate Must be ascertain - Observed discharges : Harmful or

8.2 Recognition

8.2.5 Corona discharges in SF6 gas and air

Corona discharges : Typical patterns(Fig 8.17)

- Negative half cycle : sharp edge is at high voltage

- Positive half cycle : “ at the earth side

Page 19: 8. Evaluation of Discharges 2003. 10. 18. 8. Evaluation of Discharges Ultimate goal is to evaluate Must be ascertain - Observed discharges : Harmful or

8.2 Recognition

8.2.5 Corona discharges in SF6 gas and air

X-Y diagram(Fig8.18) : at higher voltage large corona discharge

- opposite half cycle and second step is added

Time effect : discharge pattern is little affected

Page 20: 8. Evaluation of Discharges 2003. 10. 18. 8. Evaluation of Discharges Ultimate goal is to evaluate Must be ascertain - Observed discharges : Harmful or

8.2 Recognition

8.2.5 Corona discharges in SF6 gas and airCorona discharge cause - sharp edges in a construction - disturbances(sharp edges in the high-voltage test circuit) - Free of sharp edges or points : high-voltage leads and earth side(30 – 100kV)

8.2.6 Corona in oil- Occur Both half cycles, Symmetric : about the voltage peaks (Fig 8.19)- equally spaced in time

: greater magnitude and spacing than the other half cycle

Page 21: 8. Evaluation of Discharges 2003. 10. 18. 8. Evaluation of Discharges Ultimate goal is to evaluate Must be ascertain - Observed discharges : Harmful or

8.2 Recognition

8.2.6 Corona in oil - smaller discharges : equal magnitude - larger discharges : equal magnitude or vary- In contrast with corona in air : larger discharges start first- X-Y diagram : similar Fig8.18-Time effect : little affected, take a short time to stabilize (first apply the voltage)- Larger discharge on positive half cycle : the point is at high voltage

Page 22: 8. Evaluation of Discharges 2003. 10. 18. 8. Evaluation of Discharges Ultimate goal is to evaluate Must be ascertain - Observed discharges : Harmful or

8.2 Recognition

8.2.7 Contact noise - Coarse and irregular noise : about zero points Make clear : distinguished from normal discharges- Occur : sample under test or itself from test circuit - Frequently in capacitors : connection to the foils short-circuiting the capacitor after charging

8.2.8 Interference - external sources(Fig8.20)

Page 23: 8. Evaluation of Discharges 2003. 10. 18. 8. Evaluation of Discharges Ultimate goal is to evaluate Must be ascertain - Observed discharges : Harmful or

8.2 Recognition

8.2.9 Expert systems- Can provide a possible diagnosis : After the discharge characteristics have been answered- Further automation : Pulse height analyser is coupled to the discharge detector- Analyser builds pulse height histograms- Algorithm programmed using the language of an expert system- Cannot give better answer than are allowed by the physical correlation between pulse patterns and discharges

8.2.10 Recording - make of both the discharge pattern and the X-Y diagram

Page 24: 8. Evaluation of Discharges 2003. 10. 18. 8. Evaluation of Discharges Ultimate goal is to evaluate Must be ascertain - Observed discharges : Harmful or

8.3 Mechanisms of deterioration

8.3 Mechanisms of deterioration

Internal and surface discharges

: cause deterioration to dielectrics

1. Heating the dielectric boundary

2. Charges trapped in the surface

3. Attack by ultraviolet rays and soft X-rays

4. Formation of chemicals such as nitric acid and ozone

Cause depolymerization, stress cracking, gassing

leading to erosion of dielectric surface

Page 25: 8. Evaluation of Discharges 2003. 10. 18. 8. Evaluation of Discharges Ultimate goal is to evaluate Must be ascertain - Observed discharges : Harmful or

8.3 Mechanisms of deterioration

8.3.1 Internal discharges in polymers

Three stages of deterioration

1. A uniform surface erosion

: thermal degradation, ultraviolet radiation

- ions laid down by consecutive discharges cannot

neutralize electrons(be trapped below the

surface)

- Close proximity of charges : high field strengths

in the dielectric -> reach breakdown strength ->

surface erosion

Page 26: 8. Evaluation of Discharges 2003. 10. 18. 8. Evaluation of Discharges Ultimate goal is to evaluate Must be ascertain - Observed discharges : Harmful or

8.3 Mechanisms of deterioration

8.3.1 Internal discharges in polymers

2. Discharges become concentrated

: because stress cracking cause micro-crack

-> deep pits are formed -> discharges further

concentrate, carbonization occur

- First two stages : major part of the time to breakdown

high stress(at 10 to 20kV/mm) : a few hours

lower stress(at 3 to 5kV/mm) : many years

Page 27: 8. Evaluation of Discharges 2003. 10. 18. 8. Evaluation of Discharges Ultimate goal is to evaluate Must be ascertain - Observed discharges : Harmful or

8.3 Mechanisms of deterioration

8.3.1 Internal discharges in polymers

3. Field concentration around sharp tip

-> approach dielectric strength over a distance of some microns -> dielectric breakdown

-> field concentration moves new tip

and narrow channels propagate

- found in polyethylene and rubber(Fig8.21)

- Third stage : breakdown take place in a few voltage cycles

Page 28: 8. Evaluation of Discharges 2003. 10. 18. 8. Evaluation of Discharges Ultimate goal is to evaluate Must be ascertain - Observed discharges : Harmful or

8.3 Mechanisms of deterioration

8.3.2 Internal discharges in paper insulation

- Discharges in voids adjacent to the conductor

attack the insulation, penetrate the first paper layer

-> surface discharges occur along the layer

-> trees or carbonized tracks are formed

-> tracks follow the weakest points in the insulation(butt gap) Fig8.22

Page 29: 8. Evaluation of Discharges 2003. 10. 18. 8. Evaluation of Discharges Ultimate goal is to evaluate Must be ascertain - Observed discharges : Harmful or

8.3 Mechanisms of deterioration

8.3.2 Internal discharges in paper insulation

- At the foot of the tree : local overheating

-> thermal breakdown -> trees and corbonize track attain enormous lengths

Page 30: 8. Evaluation of Discharges 2003. 10. 18. 8. Evaluation of Discharges Ultimate goal is to evaluate Must be ascertain - Observed discharges : Harmful or

8.3 Mechanisms of deterioration

8.3.3 Surface discharges - Deterioration by surface discharges : same patterns internal discharges - Discharge resistance of different materials - Time to breakdown taken as a measure. (Fig8.23)

Page 31: 8. Evaluation of Discharges 2003. 10. 18. 8. Evaluation of Discharges Ultimate goal is to evaluate Must be ascertain - Observed discharges : Harmful or

8.3 Mechanisms of deterioration

8.3.4 Corona discharges - Occur around bare conductors - Indirect action by ozone formed by corona : deteriorate neighbouring dielectrics- Corona discharge In SF6 gas : not acceptable at all : create aggressive by-products (very detrimental to dielectric

surfaces)