Page 1: 615 Series Installation Manual

Relion® Protection and Control

615 seriesInstallation Manual

Page 2: 615 Series Installation Manual
Page 3: 615 Series Installation Manual

Document ID: 1MRS756375Issued: 2012-05-11

Revision: KProduct version: 4.0

© Copyright 2012 ABB. All rights reserved

Page 4: 615 Series Installation Manual

CopyrightThis document and parts thereof must not be reproduced or copied without writtenpermission from ABB, and the contents thereof must not be imparted to a thirdparty, nor used for any unauthorized purpose.

The software or hardware described in this document is furnished under a licenseand may be used, copied, or disclosed only in accordance with the terms of suchlicense.

TrademarksABB and Relion are registered trademarks of the ABB Group. All other brand orproduct names mentioned in this document may be trademarks or registeredtrademarks of their respective holders.

WarrantyPlease inquire about the terms of warranty from your nearest ABB representative.

http://www.abb.com/substationautomation

Page 5: 615 Series Installation Manual

DisclaimerThe data, examples and diagrams in this manual are included solely for the conceptor product description and are not to be deemed as a statement of guaranteedproperties. All persons responsible for applying the equipment addressed in thismanual must satisfy themselves that each intended application is suitable andacceptable, including that any applicable safety or other operational requirementsare complied with. In particular, any risks in applications where a system failure and/or product failure would create a risk for harm to property or persons (including butnot limited to personal injuries or death) shall be the sole responsibility of theperson or entity applying the equipment, and those so responsible are herebyrequested to ensure that all measures are taken to exclude or mitigate such risks.

This document has been carefully checked by ABB but deviations cannot becompletely ruled out. In case any errors are detected, the reader is kindly requestedto notify the manufacturer. Other than under explicit contractual commitments, inno event shall ABB be responsible or liable for any loss or damage resulting fromthe use of this manual or the application of the equipment.

Page 6: 615 Series Installation Manual

ConformityThis product complies with the directive of the Council of the EuropeanCommunities on the approximation of the laws of the Member States relating toelectromagnetic compatibility (EMC Directive 2004/108/EC) and concerningelectrical equipment for use within specified voltage limits (Low-voltage directive2006/95/EC). This conformity is the result of tests conducted by ABB inaccordance with the product standards EN 50263 and EN 60255-26 for the EMCdirective, and with the product standards EN 60255-1 and EN 60255-27 for the lowvoltage directive. The product is designed in accordance with the internationalstandards of the IEC 60255 series.

Page 7: 615 Series Installation Manual

Safety information

Dangerous voltages can occur on the connectors, even though theauxiliary voltage has been disconnected.

Non-observance can result in death, personal injury or substantialproperty damage.

Only a competent electrician is allowed to carry out the electricalinstallation.

National and local electrical safety regulations must always befollowed.

The frame of the IED has to be carefully earthed.

When the plug-in unit has been detached from the case, do nottouch the inside of the case. The IED case internals may containhigh voltage potential and touching these may cause personal injury.

The IED contains components which are sensitive to electrostaticdischarge. Unnecessary touching of electronic components musttherefore be avoided.

Whenever changes are made in the IED, measures should be takento avoid inadvertent tripping.

Page 8: 615 Series Installation Manual
Page 9: 615 Series Installation Manual

Table of contents

Section 1 Introduction.......................................................................5This manual........................................................................................5Intended audience..............................................................................5Product documentation.......................................................................5

Product documentation set............................................................5Document revision history.............................................................6Related documentation..................................................................6

Symbols and conventions...................................................................7Symbols.........................................................................................7Document conventions..................................................................7

Section 2 Environmental aspects.....................................................9Sustainable development...................................................................9Disposing of the IED...........................................................................9

Section 3 Unpacking, inspecting and storing.................................11Removing transport packaging.........................................................11Inspecting the product......................................................................11

Identifying the product.................................................................11Checking delivery items...............................................................11Inspecting the IED.......................................................................11Returning an IED damaged in transit..........................................12

Storing..............................................................................................12

Section 4 Mounting.........................................................................13Checking environmental conditions and mounting space................13Detaching and installing the plug-in unit...........................................13

Detaching the plug-in unit............................................................13Installing the plug-in unit..............................................................14Sealing the plug-in unit................................................................16Securing the handle.....................................................................17

Mounting the IED..............................................................................18Required tools.............................................................................18Flush mounting the IED...............................................................19Semi-flush mounting the IED.......................................................22Semi-flush mounting the IED inclined..........................................25Rack mounting the IED................................................................27Wall mounting the IED.................................................................29Rack mounting the IED and test switch RTXP to a 19”equipment frame..........................................................................32

Table of contents

615 series 1Installation Manual

Page 10: 615 Series Installation Manual

Rack mounting the IED in a combiflex 19" equipment frame(Type RHGT 19" 4U variant C)....................................................34Mounting lens sensors for an arc protection system...................36Replacing a Strömberg SP_J40 series relay by a 615series IED....................................................................................38Replacing two Strömberg SP_J3 series relays by a 615series IED....................................................................................39Replacing a Strömberg SP_J3/J6 series relay in 19" rackby a 615 series IED.....................................................................41Replacing a Strömberg SP_J6 series relay by a 615 seriesIED...............................................................................................43Replacing three BBC S_ series relays by a 615 series IED........45Replacing a SPA 300 series relay by a 615 series IED...............49Replacing a SPA 300 series relay in 19" rack by a 615series IED....................................................................................50

Section 5 Connecting.....................................................................51Required tools..................................................................................51Connecting wires..............................................................................51

Connecting ring-lug type wires....................................................52Connecting protective earthing.........................................................52Connecting analog signals...............................................................53

Connecting current and voltage inputs........................................53Connecting RTD and mA inputs..................................................58Connecting IED with a test switch...............................................58

Connecting binary signals................................................................59Connecting power supply.................................................................60Connecting communication..............................................................61Energizing the IED............................................................................61

Section 6 Removing, repairing and exchanging.............................63Product lifecycle...............................................................................63Checking IED information.................................................................63Removing the IED............................................................................64Sending the IED for repair................................................................64Exchanging the IED..........................................................................64

Section 7 Technical data................................................................65Case and HMI display variants.........................................................65

Front side of the IED....................................................................65Rear side of the IED....................................................................67

Dimensions.......................................................................................68Enclosure class................................................................................69

Section 8 Accessories and ordering data.......................................71

Table of contents

2 615 seriesInstallation Manual

Page 11: 615 Series Installation Manual

Section 9 Glossary.........................................................................73

Table of contents

615 series 3Installation Manual

Page 12: 615 Series Installation Manual

4

Page 13: 615 Series Installation Manual

Section 1 Introduction

1.1 This manual

The installation manual contains instructions on how to install the IED. Themanual provides procedures for mechanical and electrical installation. The chaptersare organized in chronological order in which the IED should be installed.

1.2 Intended audience

This manual addresses the personnel responsible for installing the product hardware.

The installation personnel must have basic knowledge of handling electronicequipment.

1.3 Product documentation

1.3.1 Product documentation setThe application manual contains application descriptions and setting guidelinessorted per function. The manual can be used to find out when and for what purposea typical protection function can be used. The manual can also be used whencalculating settings.

The communication protocol manual describes a communication protocolsupported by the IED. The manual concentrates on vendor-specific implementations.

The engineering guide provides information for IEC 61850 engineering of the 615series protection IEDs with PCM600 and IET600. This guide concentratesespecially on the configuration of GOOSE communication with these tools. Theguide can be used as a technical reference during the engineering phase,installation and commissioning phase, and during normal service. For more detailson tool usage, see the PCM600 documentation.

The engineering manual contains instructions on how to engineer the IEDs usingthe different tools in PCM600. The manual provides instructions on how to set up aPCM600 project and insert IEDs to the project structure. The manual alsorecommends a sequence for engineering of protection and control functions, LHMIfunctions as well as communication engineering for IEC 61850 and othersupported protocols.

1MRS756375 K Section 1Introduction

615 series 5Installation Manual

Page 14: 615 Series Installation Manual

The installation manual contains instructions on how to install the IED. Themanual provides procedures for mechanical and electrical installation. The chaptersare organized in chronological order in which the IED should be installed.

The operation manual contains instructions on how to operate the IED once it hasbeen commissioned. The manual provides instructions for monitoring, controllingand setting the IED. The manual also describes how to identify disturbances andhow to view calculated and measured power grid data to determine the cause of afault.

The point list manual describes the outlook and properties of the data pointsspecific to the IED. The manual should be used in conjunction with thecorresponding communication protocol manual.

The technical manual contains application and functionality descriptions and listsfunction blocks, logic diagrams, input and output signals, setting parameters andtechnical data sorted per function. The manual can be used as a technical referenceduring the engineering phase, installation and commissioning phase, and duringnormal service.

1.3.2 Document revision historyDocument revision/date Product series version HistoryA/2007-12-20 1.0 First release

B/2008-02-08 1.0 Content updated

C/2008-07-02 1.1 Content updated to correspond to theproduct series version

D/2008-10-03 1.1 Content updated

E/2009-03-04 2.0 Content updated to correspond to theproduct series version

F/2009-07-03 2.0 Content updated

G/2010-06-11 3.0 Content updated to correspond to theproduct series version

H/2011-09-14 3.0 Content updated

K/2012-05-11 4.0 Content updated to correspond to theproduct series version

Download the latest documents from the ABB Web sitehttp://www.abb.com/substationautomation.

1.3.3 Related documentationProduct series- and product-specific manuals can be downloaded from the ABBWeb site http://www.abb.com/substationautomation.

Section 1 1MRS756375 KIntroduction

6 615 seriesInstallation Manual

Page 15: 615 Series Installation Manual

1.4 Symbols and conventions

1.4.1 Symbols

The electrical warning icon indicates the presence of a hazardwhich could result in electrical shock.

The warning icon indicates the presence of a hazard which couldresult in personal injury.

The caution icon indicates important information or warning relatedto the concept discussed in the text. It might indicate the presenceof a hazard which could result in corruption of software or damageto equipment or property.

The information icon alerts the reader of important facts andconditions.

The tip icon indicates advice on, for example, how to design yourproject or how to use a certain function.

Although warning hazards are related to personal injury, it is necessary tounderstand that under certain operational conditions, operation of damagedequipment may result in degraded process performance leading to personal injuryor death. Therefore, comply fully with all warning and caution notices.

1.4.2 Document conventionsA particular convention may not be used in this manual.

• Abbreviations and acronyms in this manual are spelled out in the glossary. Theglossary also contains definitions of important terms.

• Push-button navigation in the LHMI menu structure is presented by using thepush-button icons.To navigate between the options, use and .

• HMI menu paths are presented in bold.Select Main menu/Settings.

• LHMI messages are shown in Courier font.To save the changes in non-volatile memory, select Yes and press .

• Parameter names are shown in italics.

1MRS756375 K Section 1Introduction

615 series 7Installation Manual

Page 16: 615 Series Installation Manual

The function can be enabled and disabled with the Operation setting.• Parameter values are indicated with quotation marks.

The corresponding parameter values are "On" and "Off".• IED input/output messages and monitored data names are shown in Courier font.

When the function starts, the START output is set to TRUE.

Section 1 1MRS756375 KIntroduction

8 615 seriesInstallation Manual

Page 17: 615 Series Installation Manual

Section 2 Environmental aspects

2.1 Sustainable development

Sustainability has been taken into account from the beginning of the product designincluding the pro-environmental manufacturing process, long life time, operationreliability and disposing of the IED.

The choice of materials and the suppliers have been made according to the EURoHS directive (2002/95/EC). This directive limits the use of hazardous substanceswhich are the following:

Table 1: Maximum concentration values by weight per homogeneous material

Substance Proposed maximum concentrationLead - Pb 0.1%

Mercury - Hg 0.1%

Cadmium - Cd 0.01%

Hexavalent Chromium Cr (VI) 0.1%

Polybrominated biphenyls - PBB 0.1%

Polybrominated diphenyl ethers - PBDE 0.1%

Operational reliability and long life time have been assured with extensive testingduring the design and manufacturing processes. Moreover, long life time issupported by maintenance and repair services as well as by the availability of spareparts.

Design and manufacturing have been done under a certified environmental system.The effectiveness of the environmental system is constantly evaluated by anexternal auditing body. We follow environmental rules and regulationssystematically to evaluate their effect on our products and processes.

2.2 Disposing of the IED

Definitions and regulations of hazardous materials are country-specific and changewhen the knowledge of materials increases. The materials used in this product aretypical for electric and electronic devices.

All parts used in this product are recyclable. When disposing of an IED or its partscontact a local waste handler who is authorized and specialized in disposing

1MRS756375 K Section 2Environmental aspects

615 series 9Installation Manual

Page 18: 615 Series Installation Manual

electronic waste. These handlers can sort the material by using dedicated sortingprocesses and dispose of the product according to the local requirements.

Table 2: Materials of the IED parts

IED Parts MaterialCase Metallic plates, parts and screws Steel

Plastic parts PC1), LCP2)

Electronics plug in module Various

Plug-in unit Electronics plug in modules Various

Electronics LHMI module Various

Plastic parts PC, PBT3), LCP, PA4)

Metallic parts Aluminium

Package Box Cardboard

Attached material Manuals Paper

1) Polycarbonate2) Liquid crystal polymer3) Polybutylene terephthalate4) Polyamide

Section 2 1MRS756375 KEnvironmental aspects

10 615 seriesInstallation Manual

Page 19: 615 Series Installation Manual

Section 3 Unpacking, inspecting and storing

3.1 Removing transport packaging

IEDs require careful handling.

1. Examine the delivered products to ensure that they have not been damagedduring the transport.

2. Remove the transport packing carefully without force.3. Attach the protective film (supplied with the IED) on the top side of the unit

for the installation phase.

Before connecting the auxiliary power, remove the protectivefilm from top of the IED.

The cardboard packaging material is 100% recyclable.

3.2 Inspecting the product

3.2.1 Identifying the product

1. Locate the IED's order number from the label on top of the plug-in unit.2. Compare the IED's order number with the ordering information to verify that

the received product is correct.

3.2.2 Checking delivery itemsCheck that all items are included in the delivery in accordance with the deliverydocuments.

3.2.3 Inspecting the IEDIEDs require careful handling before installation on site.

1MRS756375 K Section 3Unpacking, inspecting and storing

615 series 11Installation Manual

Page 20: 615 Series Installation Manual

• Check the IED to see if any damage occurred during transportation.

If the IED has damaged during transportation, make a claim against the transportcontractor, and notify the local ABB representative.

3.2.4 Returning an IED damaged in transitIf damage has occurred during transport, appropriate actions must be taken againstthe latest carrier. Please inform the nearest ABB office or representative. NotifyABB immediately if there are any discrepancies in relation to the delivery documents.

3.3 Storing

If the IED is stored before installation, it must be done in the original transportpackaging in a dry and dust free place. Observe the environmental requirementsstated in the technical manual.

Section 3 1MRS756375 KUnpacking, inspecting and storing

12 615 seriesInstallation Manual

Page 21: 615 Series Installation Manual

Section 4 Mounting

4.1 Checking environmental conditions and mountingspace

The mechanical and electrical environmental conditions at the installation site mustbe within the limits described in the technical manual.

• Avoid installation in dusty, damp places.Avoid places susceptible to rapid temperature variations, powerful vibrationsand shocks, surge voltages of high amplitude and fast rise time, strong inducedmagnetic fields or similar extreme conditions.

• Check that sufficient space is available.Sufficient space is needed at the front and rear of the IED to allow access towires and optical fibres and to enable maintenance and future modifications.

• Ensure that flush-mounted IEDs can be added and replaced without excessivedismantling.

4.2 Detaching and installing the plug-in unit

4.2.1 Detaching the plug-in unit

Before detaching the plug-in unit from the case, the auxiliaryvoltage must be disconnected.

1. Turn off the power.2. Open the seal on the front panel by removing the sealing wire and screw the

sealing screw all the way in.3. Lift the handle to 90 degrees to release the latching mechanism.

The plug-in unit is pushed about 7 mm out of the case and the connectors areseparated.

4. Pull the unit out of the case.

1MRS756375 K Section 4Mounting

615 series 13Installation Manual

Page 22: 615 Series Installation Manual

A070577 V4 EN

Figure 1: Detaching a plug-in unit from the case

The IED features an automatic short-circuit mechanism in the CTconnector. Therefore, detaching the plug-in unit will not open thesecondary circuit of the CT which could cause dangerously highvoltages.

Do not touch terminals inside the case after removing the plug-inunit. Live terminals can be inside the case.

The signal connectors are left open when the plug-in unit is detached.

4.2.2 Installing the plug-in unitThe IED is built (or constructed) in a way that a plug-in unit with voltage or currentmeasuring inputs can only be plugged into a corresponding case. This preventsfitting a non-suitable plug-in unit into a wrong case.

Section 4 1MRS756375 KMounting

14 615 seriesInstallation Manual

Page 23: 615 Series Installation Manual

Before fitting the plug-in unit into the case, check that the unit andthe case have the same serial number.

1GUID-BCE48661-E92A-460E-8E72-4F0EA261FB9E V1 EN

Figure 2: Serial number in the case

1 Rating label with serial number

Forcing a non-suitable plug-in unit into the case can break both theplug-in unit and the case and may cause danger.

1. Lift the handle to its fully opened position (90 degrees).2. Push the plug-in unit into the case as far as it goes.3. Turn down the handle completely to push plug-in unit into it's final position

in the case.

1MRS756375 K Section 4Mounting

615 series 15Installation Manual

Page 24: 615 Series Installation Manual

A071115 V5 EN

Figure 3: Installing a plug-in unit into the case

4.2.3 Sealing the plug-in unitThe front panel of the IED has an integrated sealing screw. By default the screw isscrewed all the way in and is not used when installing or detaching the plug-in unit.

1. Open the sealing screw about nine turns.2. Thread a sealing wire through the holes in the sealing screw and the handle.

Section 4 1MRS756375 KMounting

16 615 seriesInstallation Manual

Page 25: 615 Series Installation Manual

1 2

GUID-8158C704-BD99-42EB-A495-6BD015C240CD V1 EN

Figure 4: Sealing screw

1 Sealing screw

2 Sealing wire and seal

4.2.4 Securing the handleThe front panel of the IED has an integrated sealing screw. By default, the screw isscrewed all the way in and not used when installing or detaching the plug-in unit.Instead of sealing the plug-in unit, the sealing screw and the spacer supplied withthe IED can be used for securing the handle in place.

1. Fully open the sealing screw and remove it.2. Re-insert the sealing screw with the spacer.

1MRS756375 K Section 4Mounting

615 series 17Installation Manual

Page 26: 615 Series Installation Manual

1 2GUID-10D2039E-4C58-4372-B0B2-EDFF0C2A451C V1 EN

Figure 5: Sealing screw with spacer

1 Spacer

2 Sealing screw

4.3 Mounting the IED

4.3.1 Required tools• T25 Torx screwdriver for mounting the case• T20 Torx screwdriver for connecting the protective earthing

Only use adjustable torque screwdrivers.

Section 4 1MRS756375 KMounting

18 615 seriesInstallation Manual

Page 27: 615 Series Installation Manual

4.3.2 Flush mounting the IEDAll the mounting elements are integrated in the IED.

Requirements for installation:

• Panel cut-out of 165.5 x 161.5 mm• Depth behind the panel 153 mm

An IED equipped with optical connections requires a minimumdepth of 180 mm. The allowed minimum bending radius has to bechecked from the optical cable manufacturer.

1. Loosen the four M5 fixing screws in the case to fit the case into the panel cut-out.

2. Mount the case to the panel cut-out.

1MRS756375 K Section 4Mounting

615 series 19Installation Manual

Page 28: 615 Series Installation Manual

A

B

1

1A070581 V4 EN

Figure 6: Flush mounting a case into a panel cut-out

A 165.5 ±1 mm 1 M5 fixing screws

B 161.5 ±1 mm

3. Tighten the M5 (T25) screws.

The allowed range for the fixing screws’ tightening torque is0.7...1 Nm.

Section 4 1MRS756375 KMounting

20 615 seriesInstallation Manual

Page 29: 615 Series Installation Manual

A070582 V4 EN

Figure 7: Flush mounted case, tightening the M5 fixing screws

4. Install the plug-in unit into the case.

1MRS756375 K Section 4Mounting

615 series 21Installation Manual

Page 30: 615 Series Installation Manual

A

B

DE F

G

C

A070584 V4 EN

Figure 8: Flush mounted case and plug-in unit

A 177 mm

B 177 mm

C 164 mm

D 201 mm

E 153 mm

F 48 mm

G 160 mm

4.3.3 Semi-flush mounting the IEDA mounting kit is needed for semi-flush mounting the IED. In addition to thedetailed mounting instructions, the mounting kit includes:

Section 4 1MRS756375 KMounting

22 615 seriesInstallation Manual

Page 31: 615 Series Installation Manual

• Raising frame• Gasket• Screws

Requirements for installation:

• Panel cut-out of 165.5 x 161.5 mm with mounting holes• Depth behind the panel 103 mm• When IP 54 degree of protection (according to IEC 60529) is required for the

front side, a gasket has to be used in the installation.

1. Mount the raising frame into the panel cut-out with four M4 screws.

AB E

CD

1 2 3A070589 V4 EN

Figure 9: Mounting the raising frame

A 173.5 ±0.3 mm 1 Panel

B 165.5 ±1 mm 2 Raising frame

C 161.5 ±1 mm 3 M4 screw

D 133 ±0.3 mm

E ∅ 5.5 mm

2. Loosen the four M5 fixing screws in the case to fit the case to the raising frame.3. Mount the case to the raising frame.

1MRS756375 K Section 4Mounting

615 series 23Installation Manual

Page 32: 615 Series Installation Manual

A070590 V4 EN

Figure 10: Mounting the case

4. Tighten the M5 screws.

The allowed range for the fixing screws’ tightening torque is0.7...1 Nm.

5. Install the plug-in unit into the case.

Section 4 1MRS756375 KMounting

24 615 seriesInstallation Manual

Page 33: 615 Series Installation Manual

A

B

CD E

F

A070591 V4 EN

Figure 11: Semi-flush mounted IED

A 186 mm

B 177 mm

C 201 mm

D 103 mm

E 98 mm

F 160 mm

Check the allowed minimum bending radius from the optical cablemanufacturer.

4.3.4 Semi-flush mounting the IED inclinedA mounting kit is needed for semi-flush mounting the IED inclined. In addition tothe detailed mounting instructions, the mounting kit includes:

• Angle frame• Gasket• Screws

Requirements for installation:

1MRS756375 K Section 4Mounting

615 series 25Installation Manual

Page 34: 615 Series Installation Manual

• Panel cut-out of 167 x 203 mm with mounting holes• Depth behind the panel 107 mm• When IP 54 degree of protection (according to IEC 60529) is required for the

front side, a gasket has to be used in the installation.

1. Mount the angle frame into the panel cut-out with four M4 screws.

AB

CD

E

F

G

H

A070586 V4 EN

Figure 12: Mounting the angled frame

A 177 ±0.3 mm

B 167 ±1 mm

C 203 ±1 mm

D 40.5 mm

E 122 mm

F 40.5 mm

G ∅ 5.5 mm

H 190 mm

2. Loosen the four M5 fixing screws in the case to fit the case into the angle frame.3. Mount the case to the angle frame.

With the angled frame, the IED can be mounted inclined downward to a 25°angle.

4. Tighten the screws.

The allowed range for the fixing screws’ tightening torque is0.7...1 Nm.

5. Install the plug-in unit into the case.

Section 4 1MRS756375 KMounting

26 615 seriesInstallation Manual

Page 35: 615 Series Installation Manual

A

B

C

G

1 2 3 4 5

D E

F

A071314 V4 EN

Figure 13: IED semi-flush mounted inclined

A 25 ° 1 M4 screws

B 221 mm 2 Gasket

C 9 mm 4 Case

D 107 mm 3 Angled frame

E 133 mm 5 Plug-in unit

F 230 mm

G 190 mm

4.3.5 Rack mounting the IEDA mounting kit is needed for rack mounting the IED. In addition to the detailedmounting instructions, the 19" rack mounting kit includes:

• Mounting panel; the type of the mounting panel depends on the number ofmounted relays

• Screws

1. Mount the mounting panel to a 19" rack.2. Loosen the four M5 fixing screws in the case to fit the case into the panel cut-

out.3. Mount the case to the panel cut-out.

1MRS756375 K Section 4Mounting

615 series 27Installation Manual

Page 36: 615 Series Installation Manual

A

B

A070580 V3 EN

Figure 14: 19” rack mounting panels

A 482.6 mm (19")

B 177 mm (4U)

4. Tighten the screws.

Section 4 1MRS756375 KMounting

28 615 seriesInstallation Manual

Page 37: 615 Series Installation Manual

The allowed range for the fixing screws’ tightening torque is0.7...1 Nm.

5. Install the plug-in unit into the case.

A070579 V4 EN

Figure 15: Rack mounted IED

4.3.6 Wall mounting the IEDA mounting kit is needed for wall mounting the IED. In addition to the detailedmounting instructions, the wall mounting kit includes:

• Wall mounting frame and rail parts• Back plate• Screws• Dimensions for screw holes

1. Drill screw holes according to the dimensional drawing.2. Mount the wall mounting frame and the rails.3. Install the back plate.4. Loosen the four M5 fixing screws in the case to fit the case into the mounting

frame.5. Mount the case between the rails.

1MRS756375 K Section 4Mounting

615 series 29Installation Manual

Page 38: 615 Series Installation Manual

A

A070593 V4 EN

Figure 16: Wall mounting the IED

A 430 mm

6. Tighten the screws.

The allowed range for the fixing screws’ tightening torque is0.7...1 Nm.

Section 4 1MRS756375 KMounting

30 615 seriesInstallation Manual

Page 39: 615 Series Installation Manual

A

B

C

A070592 V4 EN

Figure 17: Wall mounted IED

A 214 mm

B 177 mm

C 270 mm

Minimum of 50 mm space is needed between two kits.

When connecting the wires, a wall-mounted IED can be pulled out and turned 45°(or 90°) degrees downwards or upwards.

• To release the IED for pulling it out, push the locks beside the mounting frame.• To rotate the IED, loosen the knurled-head screws in the rails.

1MRS756375 K Section 4Mounting

615 series 31Installation Manual

Page 40: 615 Series Installation Manual

A

A070594 V4 EN

Figure 18: Wall mounted IED in rotated position

A 455 mm

Minimum of 50 mm space is needed above and below the frame forrotating.

4.3.7 Rack mounting the IED and test switch RTXP to a 19”equipment frameA mounting kit is needed for rack mounting the IED in a 19" equipment frame. Inaddition to the detailed mounting instructions, the mounting kit includes:

Section 4 1MRS756375 KMounting

32 615 seriesInstallation Manual

Page 41: 615 Series Installation Manual

• Mounting panel• Metallic frame for mounting the RTXP 18 or 24 test switch to the panel

An IED equipped with optical connections requires a minimumdepth of 180 mm. The allowed minimum bending radius has to bechecked from the optical cable manufacturer.

To rack mount the IED into a 19" equipment frame:

1. Mount the mounting panel into the 19" rack.2. Loosen the four M5 fixing screws in the case to fit the case into the panel cut-

out.3. Mount the case to the panel cut-out.4. Install the optional metallic frame to mount the RTXP 18 or 24 test switch to

the panel.

A071312 V3 EN

Figure 19: Mounting of the metallic frame for an RTXP 18 test switch

1MRS756375 K Section 4Mounting

615 series 33Installation Manual

Page 42: 615 Series Installation Manual

A070588 V4 EN

Figure 20: IED and the test switch RTXP 18 mounted into a 19" equipment panel

4.3.8 Rack mounting the IED in a combiflex 19" equipment frame(Type RHGT 19" 4U variant C)A mounting bracket is needed for rack mounting the IED into a combiflex 19"equipment frame, a different bracket is in installation with test switch. In additionto the detailed mounting instructions, the mounting kit includes:

• Mounting bracket for the case and optionally with RTXP test switch

1. Install the mounting bracket into the combiflex equipment frame by usingtapping screws ST3.5x13 from rear side.

The type of mounting bracket to be used depends on whetherthe IED is installed into the frame on its own or with a testswitch.

2. Loosen the four M5 fixing screws in the case to fit the case into the mountingbracket.

3. Mount the case to the mounting bracket.4. Tighten the M5 screws.

The allowed range for the fixing screws’ tightening torque is 0.7...1 Nm.5. Install the plug-in unit into the case.

Section 4 1MRS756375 KMounting

34 615 seriesInstallation Manual

Page 43: 615 Series Installation Manual

1

2 3

A070576 V4 EN

Figure 21: Mounting the IED into a 19" combiflex equipment frame

1 RHGT 19" 4U equipment frame, variant C, with support frame

2 Tapping screw ST3.5x13

3 Mounting bracket

6. Install the optional RTXP 18 or 24 test switch.

1MRS756375 K Section 4Mounting

615 series 35Installation Manual

Page 44: 615 Series Installation Manual

1

2 3

A070575 V4 EN

Figure 22: IED and the test switch

1 RHGT 19" 4U equipment frame, variant C, with support frame

2 Tapping screw ST3.5x13

3 Mounting bracket for mounting with test switch RTXP 18

4.3.9 Mounting lens sensors for an arc protection systemArc protection is used to detect arc situations in air insulated metal-clad switchgear.

The arc protection system determines where in the switchgear cubicle the optionallens sensors are installed. See the application examples in the application manualfor further information on the alternatives.

1. Drill a hole (Ø 10 mm) in the wall of the supervised space.

Section 4 1MRS756375 KMounting

36 615 seriesInstallation Manual

Page 45: 615 Series Installation Manual

A

B

C

D

A040183 V2 EN

Figure 23: Dimensions of the lens sensor

A 3.5 mm

B 10 mm

C ∅ 9.5 mm

D 19 mm

2. Fit the lens sensor into the hole and fasten it with a self-tapping M3 screw.Alternatively, the lens sensor can be fastened with a cable tie. To do this,secure the cable tie to a suitable point of attachment on the cubicle wall andwrap the cable tie tightly around the sensor.

A040182 V1 EN

Figure 24: Mounting the lens sensor

3. Make sure that the cable tie lies in the groove of the sensor to prevent it fromblocking the light.

1MRS756375 K Section 4Mounting

615 series 37Installation Manual

Page 46: 615 Series Installation Manual

4.3.10 Replacing a Strömberg SP_J40 series relay by a 615series IED

1. Drill new screw holes (∅4.5 mm) to the panel according to the dimensionaldrawing.

E

C D C

B

A

GUID-C7CA77AA-74EA-40D2-B98E-84735BCADDA2 V1 EN

Figure 25: Screw hole and existing panel cut-out dimensions forreplacing a SP_J40 series IED

A 442 mm

B 183 mm

C 150 mm

D 152 mm

E 194 mm

2. Mount the installation plate to the existing panel cut-out with M5 threadforming screws.

Section 4 1MRS756375 KMounting

38 615 seriesInstallation Manual

Page 47: 615 Series Installation Manual

1

2GUID-B5A98F9F-E10D-4F92-A1ED-73D9B7719916 V1 EN

Figure 26: Installation plates for replacing SP_J40 relay

1 Installation plate

2 Torx head screw M5x10

3. Tighten the screws.4. Mount the new IED.

For ordering numbers, see the ordering number table.

4.3.11 Replacing two Strömberg SP_J3 series relays by a 615series IED

1. Make a new panel cut-out to the existing mounting panel according to thedimensional drawing.

1MRS756375 K Section 4Mounting

615 series 39Installation Manual

Page 48: 615 Series Installation Manual

1D

E

AB

C

A

GUID-7D44F5DE-6452-455A-8076-2A67FD463CC7 V1 EN

Figure 27: New panel cut-out and screw hole dimensions for replacingtwo SP_J3 series relays

A 155 mm 1 New panel cut-out line

B 15 mm

C 196 mm

D Min. 165,5 mm

E Min. 161,5 mm

2. Drill new screw holes (∅4.5 mm) to the panel according to the dimensionaldrawing.

3. Mount the installation plate to the panel cut-out with M5 thread forming screws.

Section 4 1MRS756375 KMounting

40 615 seriesInstallation Manual

Page 49: 615 Series Installation Manual

1

2

GUID-24CF4D5D-1EAE-487A-A1DE-557DF59658B0 V1 EN

Figure 28: Installation plate for replacing two SP_J3 relays

1 Installation plate

2 Torx head screw M5x10

4. Tighten the screws.5. Mount the new IED.

For ordering numbers, see the ordering number table.

4.3.12 Replacing a Strömberg SP_J3/J6 series relay in 19" rackby a 615 series IED

1. Mount the installation plate to the existing panel cut-out with M6 screws andnuts.Use the existing screw holes.

1MRS756375 K Section 4Mounting

615 series 41Installation Manual

Page 50: 615 Series Installation Manual

D

A

C

B

GUID-F1B5DA9A-05ED-419F-A795-6FD6E2A4CF95 V1 EN

Figure 29: Screw hole and existing panel cut-out dimensions forreplacing a SP_J3/J6 series relay

A 446 mm

B 196 mm

C 460 mm

D 114,5 mm

Section 4 1MRS756375 KMounting

42 615 seriesInstallation Manual

Page 51: 615 Series Installation Manual

1

2

3

GUID-90BDC1BA-F671-4178-8136-8E8D9E56A7A3 V1 EN

Figure 30: Installation plates for replacing SP_J3/J6 relay in 19" rack

1 Installation plate

2 Torx head screw M6x20

3 Hexagon nut M6

2. Tighten the screws.3. Mount the new IED with the mounting frame to the installation plate.

For ordering numbers, see the ordering number table.

4.3.13 Replacing a Strömberg SP_J6 series relay by a 615 seriesIED

1. Drill new screw holes (∅4.5 mm) to the panel according to the dimensionaldrawing.

1MRS756375 K Section 4Mounting

615 series 43Installation Manual

Page 52: 615 Series Installation Manual

D

C

B

A

GUID-57FA3F1B-C6EB-43A4-80E8-5D13CD08D9FF V1 EN

Figure 31: Screw hole and existing panel cut-out dimensions for aSP_J6 series relay

A 186 ± 1 mm

B 186 ± 1 mm

C 196 mm

D 196 mm

2. Mount the installation plate to the existing panel cut-out with M5 threadforming screws.

Section 4 1MRS756375 KMounting

44 615 seriesInstallation Manual

Page 53: 615 Series Installation Manual

11

22

GUID-2B059F45-1287-4D8D-92A6-E6583B0ADAEB V1 EN

Figure 32: Installation plate for replacing SP_J6 relay

1 Installation plate

2 Torx head screw M5x10

3. Tighten the screws.4. Mount the new IED.

For ordering numbers, see the ordering number table.

4.3.14 Replacing three BBC S_ series relays by a 615 series IED

1. Make a new panel cut-out to the existing mounting panel according to thedimensional drawing.

1MRS756375 K Section 4Mounting

615 series 45Installation Manual

Page 54: 615 Series Installation Manual

A

B

C C

D

GUID-A309A8C4-5AB1-4859-91D2-CD8C4556BA7F V1 EN

Figure 33: Existing panel cut-out and screw hole dimensions for threeBBC S_ series relays

A 92 mm

B 234 mm

C 100 mm

D 250 mm

Section 4 1MRS756375 KMounting

46 615 seriesInstallation Manual

Page 55: 615 Series Installation Manual

1

GUID-FEC7A3B8-7A65-4ACF-BDEB-DD8BB2BF5F57 V1 EN

Figure 34: New panel cut-out for replacing BBC S_ series relays

1 New panel cut-out line

2. Mount the installation plate to the panel cut-out with M5 screws, nuts andwashers.Use the existing screw holes.

1MRS756375 K Section 4Mounting

615 series 47Installation Manual

Page 56: 615 Series Installation Manual

2

3

4

11

GUID-71136C37-E662-426D-B378-9BF21ADFC51A V1 EN

Figure 35: Installation plate for replacing three BBC S_ relays

1 Installation plate

2 Torx head screw M5x16

3 Hexagon nut M5

4 Spring washer

3. Tighten the screws.4. Mount the new IED.

For ordering numbers, see the ordering number table.

Section 4 1MRS756375 KMounting

48 615 seriesInstallation Manual

Page 57: 615 Series Installation Manual

4.3.15 Replacing a SPA 300 series relay by a 615 series IED

1. Make a new panel cut-out to the existing mounting panel according to thedimensional drawing.

B

A

E

D

CGUID-F20D587E-5E99-4593-B9EE-A1B125A95524 V1 EN

Figure 36: New panel cut-out and screw hole dimensions for replacing aSPA 300 series relay

A Min. 186 mm

B 161.5 ± 1 mm

C 224 mm

D 176 mm

E 7 mm

2. Drill new screw holes (∅4.5 mm) to the panel according to the dimensionaldrawing.

3. Mount the installation plate to the panel cut-out with M5 thread forming screws.

1MRS756375 K Section 4Mounting

615 series 49Installation Manual

Page 58: 615 Series Installation Manual

11

22

GUID-A8741360-1066-494D-9340-3DA0AF81E778 V1 EN

Figure 37: Installation plate for replacing SPA 300 relay

1 Installation plate

2 Torx head screw M5x10

4. Tighten the screws.5. Mount the new IED.

Use a raising frame if needed.

For ordering numbers, see the ordering number table.

4.3.16 Replacing a SPA 300 series relay in 19" rack by a 615series IED• Mount the IED with the mounting frame to the panel cut-out according to the

rack mounting instructions.No modifications are needed to the panel.

For replacement kit ordering numbers, see the ordering number table.

Section 4 1MRS756375 KMounting

50 615 seriesInstallation Manual

Page 59: 615 Series Installation Manual

Section 5 Connecting

5.1 Required tools

Only use a screwdriver and insert bits for Phillips (PH 1) cross-recessed headscrews (M3.5) when handling CT/VT terminals (X120) of screw-compression type.

A

B

A071178 V2 EN

Figure 38: Screwdriver for CT/VT terminals of screw-compression type

A MAX ∅5.5 mm

B MAX ∅5 mm

A

A071180 V2 EN

Figure 39: Insert bits for CT/VT terminals of screw-compression type

A MIN 15 mm

5.2 Connecting wires

All connections are made on the rear of the case. No soldering is needed.

• Open the screw-compression type terminals before inserting any wires. Bydefault the terminals are closed at the time of delivery.

• Use fine wire in door mounting.

1MRS756375 K Section 5Connecting

615 series 51Installation Manual

Page 60: 615 Series Installation Manual

See the application manual for product-specific connection diagrams.

5.2.1 Connecting ring-lug type wiresRing-lug type insulated terminal can be used for signal connector X120. Themaximum outside diameter for the M4 ring-lug type terminals is 9 mm.

5.3 Connecting protective earthing

The earth lead must be at least 6.0 mm2. If the length of the earthlead is long, the cross section of the wire must be increased.

Use fine copper wire as the earth lead.

To connect a separate earth protection lead:

1. Loosen the protective earth screw (T20) to connect a separate earth protectionlead.

7

6

7

8

24

23

22

21

20

19

18

17

16

15

14

13

12

11

10

9

5

4

3

2

1

8

6

23

1

2

3

4

5

9

10

11

12

13

14

15

16

17

18

19

20

21

22

24

A070772 V1 EN

Figure 40: The protective earth screw is located between connectorsX100 and X110

Section 5 1MRS756375 KConnecting

52 615 seriesInstallation Manual

Page 61: 615 Series Installation Manual

The earth lead should be as short as possible but notice thatextra length is required for door mounting.

Each IED must have its own earth lead connected to the earthcircuit connector.

2. Connect the earth lead to the earth bar.Use either stripped wire screwed between a washer cup and the protectiveearth screw or a ring-lug.

Select a suitable ring-lug to fit under the M4 screw.

3. Tighten the protective earth screw.4. Support the earth lead so that it cannot break or weaken.

Be aware of the mechanical, chemical and electrochemical environment.

5.4 Connecting analog signals

A connection diagram is needed to connect the analog signals.

When using the ring-lug type for CT/VT terminals.

1. Open the lid that covers the ring-lug fixing screw with the tip of ascrewdriver. Every fixing screw has its own lid.

2. Remove the fixing screw.3. Slide the screw through the terminal lug and screw it back on.4. Close the lid.

5.4.1 Connecting current and voltage inputsConnect the wires from the CTs/VTs to the correct device according to the phaseorder and the connection diagram. Each terminal for CTs/VTs is dimensioned forone 0.5...6.0 mm2 wire or for two wires of maximum 2.5 mm2.

See the specific card variants from the application manual.

1MRS756375 K Section 5Connecting

615 series 53Installation Manual

Page 62: 615 Series Installation Manual

GUID-CC5FAADB-60C3-43EF-A172-7572FF85FC44 V1 EN

Figure 41: Example of AIM0004 card variant (4 I + 3 U with 1/5 A Io channel)

GUID-CAB8DAAA-8A15-4AF6-AFC7-CA232D253F3D V3 EN

Figure 42: Example of AIM0005 card variant (7 I with 1/5 A Io channel)

Section 5 1MRS756375 KConnecting

54 615 seriesInstallation Manual

Page 63: 615 Series Installation Manual

GUID-7FC759CB-AFC5-4029-972A-BFC8677763F9 V3 EN

Figure 43: Example of AIM0006 card variant (5 U)

GUID-7473CEBA-AA9C-4F58-8091-F9717AEE7F3A V1 EN

Figure 44: Example of AIM0013 card variant (4 I + 3 U with 0.2/1 A Io channel)

1MRS756375 K Section 5Connecting

615 series 55Installation Manual

Page 64: 615 Series Installation Manual

A071228 V4 EN

Figure 45: Example of AIM0016 card variant (4 I with 1/5 A Io channel)

A071232 V4 EN

Figure 46: Example of AIM0017 card variant (4 I with 0.2/1 A Io channel)

Section 5 1MRS756375 KConnecting

56 615 seriesInstallation Manual

Page 65: 615 Series Installation Manual

A071230 V4 EN

Figure 47: Example of AIM0018 card variant (4 I + Uo with 1/5 A Io channel)

A071234 V4 EN

Figure 48: Example of AIM0019 card variant (4 I + Uo with 0.2/1 A Io channel)

1MRS756375 K Section 5Connecting

615 series 57Installation Manual

Page 66: 615 Series Installation Manual

5.4.2 Connecting RTD and mA inputsConnect the wires from the transducers to the correct device according to theconnection diagram. Each terminal for RTDs and mA inputs is dimensioned forone 0.5...2.5 mm2 wire or for two 0.5...1.0 mm2 wires.

See the specific card variant from the application manual.

Connect the RTD earth cable shield to the protective earth. Tosuppress RF interference, connect the RTD earth cable shieldstraight to the lead that connects to the protective earth screw andnot to the protective screw itself. The connection must be at least355 mm from the protective earth screw.

GUID-965E94AF-4E0F-48D3-A46D-72228BD3A7E6 V1 EN

Figure 49: Example of RTD0001 card variant (6 RTD + 2 mA channel)

5.4.3 Connecting IED with a test switchWhen the IED is used with a test switch, connect the current and voltagetransformers directly to the switch.

Section 5 1MRS756375 KConnecting

58 615 seriesInstallation Manual

Page 67: 615 Series Installation Manual

5.5 Connecting binary signals

Connect the wires for the binary signals to the correct device according to theconnection diagram. Each terminal for binary input and output signal isdimensioned for one 0.5...2.5 mm2 wire or for two 0.5...1.0 mm2 wires.

See the specific card variant from the application manual.

GUID-1BE0210A-D182-4354-916E-EBEAF8F2BD48 V1 EN

Figure 50: Example of BIO0005 card variant (8 BI + 4 BO)

1MRS756375 K Section 5Connecting

615 series 59Installation Manual

Page 68: 615 Series Installation Manual

GUID-ED2EA005-C136-4DB1-B71F-B828997A6EDB V1 EN

Figure 51: Example of BIO0006 card variant (6 BI + 3 BO)

5.6 Connecting power supply

The IED's auxiliary voltage is connected to terminals X100-1 and X100-2. Thepositive lead is connected to terminal X100-1. The permitted auxiliary voltagerange of the IED is marked on top of the IED's LHMI.

Section 5 1MRS756375 KConnecting

60 615 seriesInstallation Manual

Page 69: 615 Series Installation Manual

7

6

7

8

24

23

22

21

20

19

18

17

16

15

14

13

12

11

10

9

5

4

3

2

1

8

6

23

1

2

3

4

5

9

10

11

12

13

14

15

16

17

18

19

20

21

22

24

12

A070770 V1 EN

Figure 52: Connecting auxiliary voltage

5.7 Connecting communication

Before connecting communication, check that the HW module has the correctcommunication interfaces. The communication module is located on the left side ofthe IED when viewing the case from the rear.

See the technical manual for product-specific communicationinterfaces.

5.8 Energizing the IED

Before connecting the auxiliary power, check that the protectivefilm is removed from top of the IED.

1MRS756375 K Section 5Connecting

615 series 61Installation Manual

Page 70: 615 Series Installation Manual

Before connecting the auxiliary power, check that the terminal strip is wired andplaced correctly. Remove the protective film from the top side of the unit. Checkthat there is no debris visible in the ventilation holes.

GUID-97A2D4BA-29FC-4E2F-8C4D-81EE5E77CF79 V1 EN

Figure 53: Removing the protective film

During the start-up all LEDs are lit for a short period.

• Green Ready LED starts to flash• LCD lights up and IED start-up is displayed• The main menu is displayed. A steady green Ready LED indicates a successful

start-up.

If the IED detects a diagnostic error during start-up, the green Ready LED flashesand the internal fault code is displayed on the LCD.

Section 5 1MRS756375 KConnecting

62 615 seriesInstallation Manual

Page 71: 615 Series Installation Manual

Section 6 Removing, repairing and exchanging

6.1 Product lifecycle

At some point of the product lifecycle, the IED will be upgraded to a nextgeneration unit. When selecting the original product, already consider theupgrading and extension possibilities that the specific product offers for its wholelifecycle.

IED-specific options can be found from Retrofit Solutions Database on the Internetwww.abb.com by following the links within ABB Service Guide or via ABBProduct Guide from the product specific Service & Support sheet.

6.2 Checking IED information

The IED information includes detailed information about the device, such asversion and serial number. The IED information is shown on the display for a fewseconds when the device starts up. The same information is found also in the IEDmenu.

1. Select Main Menu/Information.2. Select a submenu with and .3. Enter the selected submenu with .4. Browse the information with and .

The Product identifiers submenu contains product related information likeproduct type, serial number, order number, production date, configuration name,SW version, SW date and HW revision.

The Site identifiers submenu contains information about the site where the IEDhas been installed.

The HW modules submenu contains information about the HW modules.

The System identifiers submenu contains the unique Technical key which cannotbe changed.

1MRS756375 K Section 6Removing, repairing and exchanging

615 series 63Installation Manual

Page 72: 615 Series Installation Manual

6.3 Removing the IED

1. Turn off the power.2. Detach the plug-in unit from the case.3. Disconnect the wiring.4. Loosen the four M5 fixing screws.

A070582 V4 EN

5. Detach the case from the panel cut-out.

6.4 Sending the IED for repair

In case of product problems, contact the nearest ABB office or representative forconsultation and instructions.

6.5 Exchanging the IED

To exchange the IED with another identical unit, remove the IED and install thenew one. The exchangeable units can be found from the PartsOnLine system, seewww.abb.com/partsonline. Use of PartsOnLine requires user registration.

To exchange an IED to a different unit, change the case and connect the wires.

Section 6 1MRS756375 KRemoving, repairing and exchanging

64 615 seriesInstallation Manual

Page 73: 615 Series Installation Manual

Section 7 Technical data

7.1 Case and HMI display variants

7.1.1 Front side of the IED

IECA070904 V3 EN

Figure 54: Small display

1MRS756375 K Section 7Technical data

615 series 65Installation Manual

Page 74: 615 Series Installation Manual

IECA070901 V3 EN

Figure 55: Large display

Table 3: Small display

Character size1) Rows in the view Characters per rowSmall, mono-spaced (6x12 pixels) 5 20

Large, variable width (13x14 pixels) 4 8 or more

1) Depending on the selected language

Table 4: Large display

Character size1) Rows in the view Characters per rowSmall, mono-spaced (6x12 pixels) 10 20

Large, variable width (13x14 pixels) 8 8 or more

1) Depending on the selected language

Section 7 1MRS756375 KTechnical data

66 615 seriesInstallation Manual

Page 75: 615 Series Installation Manual

7.1.2 Rear side of the IED

A070596 V1 EN

Figure 56: Rear view of an 615 series IED with communication module

1MRS756375 K Section 7Technical data

615 series 67Installation Manual

Page 76: 615 Series Installation Manual

7.2 Dimensions

A

C

D

F

E

B

GUID-6BA24DB4-935E-4B81-AEE6-FD8B7FC4140F V2 EN

Figure 57: 615 series main dimensions

A 177 mm

B 177 mm (4U)

C 164 mm

D 153 mm

E 48 mm

F 160 mm

Table 5: Dimensions

Description Value Width frame 177 mm

case 164 mm

Height frame 177 mm (4U)

case 160 mm

Table continues on next page

Section 7 1MRS756375 KTechnical data

68 615 seriesInstallation Manual

Page 77: 615 Series Installation Manual

Description Value Depth 201 mm (153 + 48 mm)

Weight complete IED 4.1 kg

plug-in unit only 2.1 kg

7.3 Enclosure class

Table 6: Degree of protection of flush-mounted IED

Description ValueFront side IP 54

Rear side, connection terminals IP 20

1MRS756375 K Section 7Technical data

615 series 69Installation Manual

Page 78: 615 Series Installation Manual

70

Page 79: 615 Series Installation Manual

Section 8 Accessories and ordering data

Table 7: Cables

Item Order numberCable for optical sensors for arc protection 1.5 m 1MRS120534-1.5

Cable for optical sensors for arc protection 3.0 m 1MRS120534-3.0

Cable for optical sensors for arc protection 5.0 m 1MRS120534-5.0

Table 8: Mounting accessories

Item Order numberSemi-flush mounting kit 1MRS050696

Wall mounting kit 1MRS050697

Inclined semi-flush mounting kit 1MRS050831

19” rack mounting kit with cut-out for one IED 1MRS050694

19” rack mounting kit with cut-out for two IEDs 1MRS050695

Mounting bracket for one IED with test switch RTXP in 4U Combiflex (RHGT19” variant C)

2RCA022642P0001

Mounting bracket for one IED in 4U Combiflex (RHGT 19” variant C) 2RCA022643P0001

19” rack mounting kit for one IED and one RTXP18 test switch (the testswitch is not included in the delivery)

2RCA021952A0003

19” rack mounting kit for one IED and one RTXP24 test switch (the testswitch is not included in the delivery)

2RCA022561A0003

Replacement kit for a Strömberg SP_J40 series relay (cut-out in the centerof the installation plate)

2RCA027871A0001

Replacement kit for a Strömberg SP_J40 series relay (cut-out on the left orthe right of the installation plate)

2RCA027874A0001

Replacement kit for two Strömberg SP_J3 series relays 2RCA027880A0001

19” rack replacement kit for Strömberg SP_J3/J6 series relays (one cut-out) 2RCA027894A0001

19” rack replacement kit for Strömberg SP_J3/J6 series relays (two cut-outs) 2RCA027897A0001

Replacement kit for a Strömberg SP_J6 series relay 2RCA027881A0001

Replacement kit for three BBC S_ series relays 2RCA027882A0001

Replacement kit for a SPA 300 series relay 2RCA027885A0001

1MRS756375 K Section 8Accessories and ordering data

615 series 71Installation Manual

Page 80: 615 Series Installation Manual

72

Page 81: 615 Series Installation Manual

Section 9 Glossary

615 series Series of numerical IEDs for low-end protection andsupervision applications of utility substations, and industrialswitchgear and equipment

CT Current transformerEMC Electromagnetic compatibilityHMI Human-machine interfaceIEC International Electrotechnical CommissionIEC 61850 International standard for substation communication and

modelingIED Intelligent electronic deviceIET600 Integrated Engineering Toolbox in PCM600LCD Liquid crystal displayLCP Liquid crystal polymerLED Light-emitting diodeLHMI Local human-machine interfacePA PolyamidePBT Polybutylene terephthalatePC 1. Personal computer

2. PolycarbonatePCM600 Protection and Control IED ManagerRoHS Restriction of the use of certain hazardous substances in

electrical and electronic equipmentVT Voltage transformer

1MRS756375 K Section 9Glossary

615 series 73Installation Manual

Page 82: 615 Series Installation Manual

74

Page 83: 615 Series Installation Manual

75

Page 84: 615 Series Installation Manual