Line Differential Protection and Control RED615615 series
ABB 2
Application area
RED615, member of ABB’s 615 product series, is a phase-segregated two-end line differential protection and control IED perfectly harmonized for utility and industrial power systems, including looped and meshed distribution networks with or without decentralized power generation. Re-engineered from the ground up, the new 615 series has been designed to unleash the full potential of the IEC 61850 standard for communication and interoperability of substation automation equipment.
RED615 provides phase-segregated high speed, longitudinal differential protection for overhead line and cable feeders in distribution networks. Two RED615s interconnected over a communication link form an absolutely selective unit protection scheme. Protection of ring-type and meshed distribution networks generally requires unit protection solutions, also applied in radial networks containing distributed power generation. Typical RED615 applications include two or multiple parallel lines between substations, meshed cable networks of urban and suburban areas. Line differential protection is also applied to industrial power systems and special object, such as power systems for road and rail tunnels and cable networks of wind turbine farms.
Protection and control
RED615 features two-stage, phase-segregated line differential protection, four-stage phase overcurrent protection, two-stage phase unbalance and loss-of-phase protection, and circuit-breaker failure protection. Further, RED615 incorporates a lockout relay and a second harmonic restraint function to identify inrush current conditions.
Besides protection RED615 also offers the functionality needed for local and remote control of one circuit breaker.
Binary signal transfer
Binary signal transfer (BST) can be used for carrying blocking and intertrip signals as well as status and position information between the local and remote end of the line. The BST functionality features eight binary signals, which are carried between the substations inside protection telegrams transferred over the communication link. The transfer of BST signals is bidirectional and the signal transfer time is extremely short, just a few milliseconds. BST signalling and the logics of RED615 enable adaptive protection and control schemes to be engineered to create tomorrow’s smart power systems.
Standardized communication
RED615 features native support for the new IEC 61850 standard for communication in substations. The relay also supports the industry standard Modbus® protocol 3.0.
The in-depth implementation of the IEC 61850 substation communication standard in RED615 also includes horizontal peer-to-peer communication over a substation-wide Ethernet LAN using the GOOSE-services defi ned by the standard.
Protection communication supervision
The communication channel between either end of the protected line is constantly supervised. Should the communication channel be interrupted or suffer interference the fast-acting line differential protection functions will be restrained immediately. The automatic restraint affects all functions which rely on the continuous availability of the protection communication channel. The channel supervision includes recognition of missing or delayed telegrams carrying sampled analog measurement values or binary information.
The sensitivity of the supervision function and the reset delay are user-selectable. Prolonged interferences and a total interruption of the communication channel will trig an alarm message, which can be used to alert the network operator and to release a back-up protection scheme.
SmartGrid enabled IEDs for tomorrow’s dynamic and autonomus power systems
ABB 3
Pre-emptive monitoring
To secure the operational availability of the protection, RED615 incorporates a range of monitoring and watch-dog functions to supervise the hardware and software, the communication system and the circuit-breaker trip circuit.
Hardware supervision also incorporates the current transformers. CT faults may cause undesired operation of the line differential protection and the phase unbalance protection. Hence, a fast-acting CT supervision system blocks the operation of the line differential protection function and the phase unbalance protection function on detection of any CT signal anomaly.
Rapid set-up and commissioning
Due to the ready-made adaptation of RED615 for the protection of overhead lines and cable feeders, the RED615 can be rapidly set up and commissioned, once it has been given the application-specifi c settings. If adjustments of the application-specifi c settings are needed the fl exibility of the RED615 allows the standard signal confi guration to be altered by means of the signal matrix tool (SMT) included in the PCM600 IED setting and confi guration tool.
By means of Connectivity Packages containing detailed descriptions of ABB’s protection IEDs, with data signals, parameters and addresses, the IEDs can be automatically confi gured via the MicroSCADA Pro system, the COM600 Station Automation series devices or the PCM600 IED setting and confi guration tool.
Unique plug-in design
The plug-in design speeds up installation and testing of the protection. The factory-tested RED615 plug-in units can be withdrawn from their case during factory and commissioning tests. The case provides automatic short-circuiting of the CT secondary circuits to prevent hazardous voltages from arising in the CT secondary circuits when a plug-in unit is withdrawn from its case.
The handle locking the plug-in unit into its case can be provided with a seal to prevent unintentional withdrawal of the plug-in unit.
RED615 highlights
High-speed, two-end, phase-segregated line differential protection with native support for IEC 61850 and GOOSE messaging
Two SmartGrid enabled RED615s interconnected over a communication channel form an absolutely selective unit protection scheme for tomorrow’s dynamic and autonomous power systems
Enhanced disturbance recorder functionality including high sampling frequency, extended length of records, 12 analog and 64 binary channels and fl exible triggering
Patented case design offers fl exible mounting, fast installation and the plug-in design facilitates and speeds-up routine testing and maintenance
One single tool for IED setting, signal confi guration and disturbance record handling
ABB OyDistribution AutomationP. O. Box 699FI-65101 VAASA, FinlandPhone: +358 10 22 11Fax: +358 10 41 094www.abb.com/substationautomation
Prin
ted
in F
inla
nd 1
0/20
08 1
MR
S75
6489
A
Protection IEC ANSILine differential protection, 2 stages 3ID>, 3ID>> 87LThree-phase non-directional overcurrent, 4 stages 3I>, 3I>>(1), 3I>, 3I>>(2) 51P-1, 51P-2, 51P-3, 50P/51P
Negative phase sequence overcurrent, 2 stages I2>, I2>> 46
Circuit-breaker failure protection 3I/I0> BF 51BF/51NBFThree-phase inrush current detection 3I2f> 68Binary signal transfer BST BSTControlCircuit-breaker control with interlocking 1 ↔ 0 CB
Supervision and MonitoringTrip-circuit supervision for two trip coils TCS TCMCurrent circuit supervision MCS 3I MCS 3IProtection communication supervision PCS PCSMeasurementTransient disturbance recorderThree phase currents 3I 3ICurrent sequence components I1, I2, I0 I1, I2, I0Three-phase differential currentBias current
RED615 Technology SummaryTechnical details are available in the RED615 Product Guide 1MRS756500
©C
opyr
ight
200
8 A
BB
. All
right
s re
serv
ed. T
he in
form
atio
n in
thi
s d
ocum
ent
is s
ubje
ct t
o ch
ange
with
out
notic
e.
Energizing inputs
Three phase currents: 1/5 AOne residual current: 1/5 ARated frequency: 50/60 Hz
Binary inputs and outputs
Four binary inputs with common groundTwo NO double-pole outputs including TCSTwo NO single-pole outputsOne change-over signal outputs One NO signal outputOne change-over IRF signal outputSeven binary inputs and three binary outputsSix binary inputs and three binary outputs with a optional extension card
Communication
IEC 61850-8-1 with GOOSE messagingMODBUS TCP and RTU (optional)Time synchronization over Ethernet station bus using SNTP or over separate wiring using IRIG-B signal and line differential with remote-end station time reference
Auxiliary power supply
Variant 1: 48-250 V dc, 100-240 V ac
Dimensions
177 mm (4U) height, 177 mm (4U) width, 140 mm depth, weight 3.5 kg
Tools
PCM600 ver. 2.0 SP1 for setting, signal configuration and disturbance record handlingWeb browser based user interface (IE 7.0 or later)COM600 Station Automation series products Ver. 3.2