  • 8/9/2019 6035-510A Instruction Manual

    1/72

    Instruction Bulletin

    6035-510A

    November 1998

    Middletown, OH USA

    DIGITRIP

    RMS Trip Units:

    DIGITRIP RMS 510, DIGITRIP RMS 610, and

    POWERLOGIC

    DIGITRIP RMS 810DFor Use in Types DS/DSL and DSII/DSLIILow Voltage Circuit BreakersClass 6035

  • 8/9/2019 6035-510A Instruction Manual

    2/72

  • 8/9/2019 6035-510A Instruction Manual

    3/72

    Bulletin No. 6035-510A DIGITRIP RMS Trip Units

    November 1998 Table of Contents

    i

    1998 Square D All Rights Reserved

    INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

    Organization of this Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1

    SAFETY PRECAUTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2

    RECEIVING, HANDLING, AND STORAGE . . . . . . . . . . . . . . . . . . . . . . . .2

    DIGITRIP RMS TRIP UNITS DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . 3

    DIGITRIP RMS 510 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3

    DIGITRIP RMS 610 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3

    POWERLOGIC DIGITRIP RMS 810D . . . . . . . . . . . . . . . . . . . . . . . 4

    Available Protection Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4

    BASIC OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6

    General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

    Fixed Instantaneous Override . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7

    Zone Interlocking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7

    Trip and Operation Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7

    Discriminator (Making Current Release) . . . . . . . . . . . . . . . . . . . . . . . 8

    Frame Rating, Sensor Rating, and Rating Plugs . . . . . . . . . . . . . . . . . 8

    PROTECTION SETTINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12

    Changing Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12

    Long Delay Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

    Long Delay Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13

    Long Time Memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13

    Short Delay Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15

    Short Delay Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15

    Instantaneous Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16

    Ground Fault Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17

    Ground Fault Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

    DIGITRIP RMS 610 OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

    General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19Four Character Information Display Window . . . . . . . . . . . . . . . . . . . 19

    Value Displayed During Normal Service . . . . . . . . . . . . . . . . . . . . . .20

    Current Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

    Messages Displayed After Alarm or Trip . . . . . . . . . . . . . . . . . . . . . .21

    Rating Plug Missing or Disconnected Indication . . . . . . . . . . . . . . . .22

    POWERLOGIC DIGITRIP RMS 810D OPERATION . . . . . . . . . . . . . . . .23

    General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

    Four Character Information Display Window . . . . . . . . . . . . . . . . . . . 23

    Values Displayed During Normal Service . . . . . . . . . . . . . . . . . . . . .23

    Current Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

    Power and Energy Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26

    Messages Displayed after Alarm or Trip . . . . . . . . . . . . . . . . . . . . . .28

    Rating Plug Missing or Disconnected Indication . . . . . . . . . . . . . . . .28

    Potential Transformer Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30

    Communication Power Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30

    TRIP UNIT COMMUNICATIONS:POWERLOGIC DIGITRIP RMS 810D. . . . . . . . . . . . . . . . . . . . . . . . . . . .31

    Trip Unit Address and Baud Rate . . . . . . . . . . . . . . . . . . . . . . . . . . .31

    Personal Computer Workstations . . . . . . . . . . . . . . . . . . . . . . . . . . .33

    TABLE OF CONTENTS

  • 8/9/2019 6035-510A Instruction Manual

    4/72

  • 8/9/2019 6035-510A Instruction Manual

    5/72

    Bulletin No. 6035-510A DIGITRIP

    RMS Trip Units

    November 1998 List of Figures

    iii

    1998 Square D All Rights Reserved

    Figure 1: DIGITRIP RMS 510 Trip Unit . . . . . . . . . . . . . . . . . . . . . . . . 3

    Figure 2: DIGITRIP RMS 610 Trip Unit . . . . . . . . . . . . . . . . . . . . . . . . 3

    Figure 3: POWERLOGIC DIGITRIP RMS 810D Trip Unit. . . . . . . . . . 4

    Figure 4: DIGITRIP RMS 510 Block Diagramwith Circuit Breaker Interface . . . . . . . . . . . . . . . . . . . . . . . . 6

    Figure 5: Trip Unit Face. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

    Figure 6: Changing Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

    Figure 7: Long Delay Current Settings . . . . . . . . . . . . . . . . . . . . . . . 13

    Figure 8: Long Delay Time Settings . . . . . . . . . . . . . . . . . . . . . . . . . 13

    Figure 9: Typical Rating Plug. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

    Figure 10: Removing the Rating Plug . . . . . . . . . . . . . . . . . . . . . . . . . 14

    Figure 11: Long Time Memory (LTM) Jumper. . . . . . . . . . . . . . . . . . . 14

    Figure 12: Short Delay Current Settings . . . . . . . . . . . . . . . . . . . . . . . 15

    Figure 13: Short Delay Time Settings . . . . . . . . . . . . . . . . . . . . . . . . . 16

    Figure 14: Instantaneous Current Settings . . . . . . . . . . . . . . . . . . . . . 16

    Figure 15: Ground Fault Current Settings . . . . . . . . . . . . . . . . . . . . . . 17

    Figure 16: Ground Fault Time Delay Settings . . . . . . . . . . . . . . . . . . . 18

    Figure 17: DIGITRIP RMS 610 Block Diagramwith Circuit Breaker Interface . . . . . . . . . . . . . . . . . . . . . . . 19

    Figure 18: DIGITRIP RMS 610 Trip Unit . . . . . . . . . . . . . . . . . . . . . . . 20

    Figure 19: POWERLOGIC DIGITRIP RMS 810D Block Diagramwith Circuit Breaker Interface . . . . . . . . . . . . . . . . . . . . . . . .24

    Figure 20: POWERLOG DIGITRIP RMS 810D Trip Unit. . . . . . . . . . . 25

    Figure 21: Potential Transformer Module . . . . . . . . . . . . . . . . . . . . . . 30

    Figure 22: POWERLOGIC with Personal Computer Workstation . . . . 33

    Figure 23: System Display Model SD-300. . . . . . . . . . . . . . . . . . . . . . 33

    Figure 24: System Display Connections . . . . . . . . . . . . . . . . . . . . . . . 34

    Figure 25: POWERLOGIC Network with Personal ComputerWorkstation and System Display . . . . . . . . . . . . . . . . . . . . . 34

    Figure 26: Power/Relay Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38

    Figure 27: Auxiliary Power Module . . . . . . . . . . . . . . . . . . . . . . . . . . . 39

    Figure 28: Integral Test Panel (Lower Right Corner of Trip Unit) . . . . 40

    Figure 29: Typical Rating Plug. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44

    Figure 30: Rating Plugs Shown with Covers Closed and Open . . . . . 44

    Figure 31: Typical Schematic Diagram of Basic Connectionsin Tripping System of the DSII Circuit Breaker . . . . . . . . . .45

    Figure 32: Typical Zone Interlocking (Ground Fault Protection) . . . . . 49

    Figure 33: Typical Zone Interlocking Connections with Two Main

    Circuit Breakers (M1, M2) and a Tie Circuit Breaker (T)(Short Delay Protection) . . . . . . . . . . . . . . . . . . . . . . . . . . .50

    Figure 34: Types DS and DSL Circuit Breakers with DIGITRIP RMSTrip Units Typical Instantaneous Time-Phase Current

    Characteristic Curve (l) . . . . . . . . . . . . . . . . . . . . . . . . . . . .53Figure 35: Types DS and DSL Circuit Breakers with DIGITRIP RMS

    Trip Units Typical Long Delay and Short Delay Time-PhaseCurrent Characteristic Curve (LS) . . . . . . . . . . . . . . . . . . . . 54

    Figure 36: Types DSII and DSLII Circuit Breakers with DIGITRIP RMSTrip Units Typical Instantaneous Time-Phase CurrentCharacteristic Curve (l) . . . . . . . . . . . . . . . . . . . . . . . . . . . .55

    Figure 37: Types DSII and DSLII Circuit Breakers with DIGITRIP RMSTrip Units Typical Long Delay Time-Phase CurrentCharacteristic Curve (LS) . . . . . . . . . . . . . . . . . . . . . . . . . . 56

    LIST OF FIGURES

  • 8/9/2019 6035-510A Instruction Manual

    6/72

    DIGITRIP

    RMS Trip Units Bulletin No. 6035-510A

    List of Figures November 1998

    1998 Square D All Rights Reserved

    iv

    Figure 38: Types DS/DSL and DSII/DSLII Circuit Breakers withDIGITRIP RMS Trip Units Typical Time-Ground CurrentCharacteristic Curve (G) . . . . . . . . . . . . . . . . . . . . . . . . . . .57

    Figure 39: POWERLOGIC DIGITRIP RMS 810D Trip Unit and DS Circuit

    Breaker Schematic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .58

    Figure 40: POWERLOGIC DIGITRIP RMS 810D Trip Unit and DSII Cir-

    cuit Breaker Schematic . . . . . . . . . . . . . . . . . . . . . . . . . . . .60

    http://6035-510atext%287%29appe.pdf/http://6035-510atext%287%29appe.pdf/http://6035-510atext%287%29appe.pdf/
  • 8/9/2019 6035-510A Instruction Manual

    7/72

    Bulletin No. 6035-510A DIGITRIP

    RMS Trip Units

    November 1998 List of Tables

    v

    1998 Square D All Rights Reserved

    Table 1: Trip Unit Types of Protection . . . . . . . . . . . . . . . . . . . . . . . . 4

    Table 2: DIGITRIP RMS Trip Units Functional Summary. . . . . . . . . . 5

    Table 3: Rating Plug Comparison 800 A and 1600 A. . . . . . . . . . . . . 9

    Table 4: Rating Plug Catalog Numbers . . . . . . . . . . . . . . . . . . . . . . 11

    Table 5: Ground Fault Current Pickup Settings . . . . . . . . . . . . . . . . 17

    Table 6: DIGITRIP RMS 610 Information Functions . . . . . . . . . . . . 21

    Table 7: DIGITRIP RMS 610 Message Codes. . . . . . . . . . . . . . . . . 22Table 8: POWERLOGIC DIGITRIP RMS 810D

    Information Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26

    Table 9: POWERLOGIC DIGITRIP RMS 810D Message Codes. . . 29

    Table 10: POWERLOGIC DIGITRIP RMS 810D Communications . . 36

    Table 11: Replacement Batteries . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44

    LIST OF TABLES

  • 8/9/2019 6035-510A Instruction Manual

    8/72

    DIGITRIP

    RMS Trip Units Bulletin No. 6035-510A

    List of Tables November 1998

    1998 Square D All Rights Reserved

    vi

  • 8/9/2019 6035-510A Instruction Manual

    9/72

    DIGITRIP

    RMS Trip Units Bulletin No. 6035-510A

    Introduction November 1998

    1996 Square D All Rights Reserved

    1

    The DIGITRIP

    RMS 510, DIGITRIP RMS 610, and POWERLOGIC

    DIGITRIP RMS 810D trip units are ac devices with microprocessor-basedtechnology. They provide true root mean square (RMS) current sensing forproper correlation with thermal characteristics of conductors and equipment.The primary function of the trip unit is overcurrent protection. The deviceanalyzes the current signals received from the circuit breaker current

    sensors. It initiates trip signals to the circuit breaker trip actuator whenpredetermined current levels and time delay settings are exceeded. Inaddition to the basic overcurrent protection, all DIGITRIP RMS trip unitmodels provide information and integral test functions.

    This bulletin provides operation and maintenance instructions for theDIGITRIP RMS 510, DIGITRIP RMS 610, and POWERLOGIC DIGITRIPRMS 810D trip units installed in Types DS/DSL and DSII/DSLII low voltage

    circuit breakers. Because trip units are installed in circuit breakers at thefactory, no installation procedures are included in this manual. Refer to LowVoltage Circuit Breakers, Types DSII and DSLII instruction bulletin, 44021-

    996-01

    for installation, operation, and maintenance of circuit breakers. SeeDS/DSL and DSII/DSLII Voltage Power Circuit Breaker Replacement Partscatalog, 6035CT9801 for spare parts for these circuit breakers. RequestCD-ROM 0110TC9601R11/98 for a set of trip curves.

    The DIGITRIP RMS 510 is the basic model in this product line. The DIGITRIPRMS 610 includes all features of the 510, plus some enhancements. At the

    top of the line is the POWERLOGIC DIGITRIP RMS 810D trip unit. Itperforms all the functions of the DIGITRIP RMS 610. In addition, it has moreinformation displays as well as POWERLOGIC communications capabilities.To reduce repetition, the information in this manual is presented in thefollowing manner:

    BASIC OPERATION

    covers operations that are common to DIGITRIPRMS 510, DIGITRIP RMS 610, and POWERLOGIC DIGITRIP RMS 810Dtrip units.

    PROTECTION SETTINGS covers the available protection settingsdepending on the type of tr ip unit. All three models come in six

    different types.

    DIGITRIP RMS 610 OPERATION covers operations that are beyond thescope covered in BASIC OPERATION

    .

    POWERLOGIC DIGITRIP RMS 810D OPERATION covers operationsthat are beyond the scope covered in BASIC OPERATION.

    TRIP UNIT COMMUNICATIONS: POWERLOGIC DIGITRIP RMS 810Dcovers POWERLOGIC network communications of the POWERLOGICDIGITRIP RMS 810D trip unit.

    POWER/RELAY MODULE describes the Power/Relay module thatcomes with the DIGITRIP RMS 610 and POWERLOGIC DIGITRIP RMS

    810D trip units.

    AUXILIARY POWER MODULE,TEST PROCEDURE,

    MAINTENANCE, CIRCUIT BREAKER APPLICATION,andAPPENDIX Aapply to all three models of DIGITRIP RMS trip units.

    APPENDIX Bexplains how to interpret display codes after a circuitbreaker trips. This information pertains only to the DIGITRIP RMS 610and POWERLOGIC DIGITRIP RMS 810D trip units.

    APPENDIX C has trip curves for reference.

    APPENDIX D is a schematic for the POWERLOGIC DIGITRIP RMS

    810D trip unit and DS circuit breaker.

    APPENDIX E is a schematic for the POWERLOGIC DIGITRIP RMS810D trip unit and DSII circuit breaker.

    INTRODUCTION

    Organization of this Manual

  • 8/9/2019 6035-510A Instruction Manual

    10/72

    DIGITRIP

    RMS Trip Units Bulletin No. 6035-510A

    Safety Precautions November 1998

    1996 Square D All Rights Reserved

    2

    The trip units are already installed in DS and DSII circuit breakers at the

    factory. Refer to the Low Voltage Circuit Breakers instruction bulletin forreceiving, handling, and storage procedures.

    SAFETY PRECAUTIONS

    HAZARD OF ELECTRIC SHOCK, BURN OR EXPLOSION

    Do not attempt to install or perform maintenance on equipment whileit is energized. Verify that no voltage is present before proceeding

    with the task. Follow accepted safety procedures. Square DCompany is not liable for the improper application or installation of itsproducts.

    Observe all recommendations, warnings, and cautions concerningthe safety of personnel and equipment, as well as all general andlocal safety laws, codes, and procedures.

    The recommendations and information in this bulletin are based onSquare D Company experience and judgment. However, they cannotcover every application or circumstance that may arise. If you haveany questions or need further information or instructions, please

    contact Square D Field Services at (800) 634-2003.

    Failure to follow these instructions will result in death or serious

    injury.

    DANGER

    RECEIVING, HANDLING, ANDSTORAGE

  • 8/9/2019 6035-510A Instruction Manual

    11/72

    Bulletin No. 6035-510A DIGITRIP

    RMS Trip Units

    November 1998 DIGITRIP RMS Trip Units Description

    3

    1996 Square D All Rights Reserved

    The DIGITRIP RMS 510, DIGITRIP RMS 610, and POWERLOGICDIGITRIP RMS 810D trip units are components that are mounted within adrawout circuit breaker, which is part of metal enclosed switchgear. When thecircuit breaker is closed, no external power is required for the protectionsystem. The trip unit derives power to operate from current signal levels andcurrent sensors integrally mounted in the circuit breaker. DIGITRIP

    RMS 510, DIGITRIP RMS 610, and POWERLOGIC DIGITRIP RMS 810Dtrip units are UL Listed for use in Types DS/DSL and DSII/DSLII low voltagecircuit breakers.

    The DIGITRIP RMS 510 trip unit performs the basic functions covered inBASIC OPERATION on page 6. Protection settings describedinPROTECTION SETTINGS on page 12 are available depending on thetype of trip unit. Figure 1depicts a typical DIGITRIP RMS 510 trip unit.

    The DIGITRIP RMS 610 trip unit performs all the functions of the DIGITRIPRMS 510 trip unit. In addition, it has a four character display, three phase andone ground (when supplied) current pointer LEDs, and a Step pushbutton forchanging information displays.Figure 2 depicts a typical DIGITRIP RMS 610trip unit.

    Figure 2: DIGITRIP RMS 610 Trip Unit

    DIGITRIP RMS TRIP UNITSDESCRIPTION

    DIGITRIP RMS 510

    DIGITRIP RMS 610

    6035-9801

    Figure 1: DIGITRIP RMS 510 Trip Unit

    6035-9802

  • 8/9/2019 6035-510A Instruction Manual

    12/72

    DIGITRIP

    RMS Trip Units Bulletin No. 6035-510A

    DIGITRIP RMS Trip Units Description November 1998

    1996 Square D All Rights Reserved

    4

    The POWERLOGIC DIGITRIP 810D trip unit (Figure 3) performs all thefunctionsof the DIGITRIP RMS 610 trip unit with the addition of peakdemand, present demand, and energy consumed LEDs. It also has a peakdemand Reset pushbutton.

    The trip unit displays information and also has remote communications via aPOWERLOGIC communication network signal link. When used in a circuit

    breaker equipped with the spring release option, the unit allows remotetripping and closing of the circuit breaker by POWERLOGIC communicationsignals.

    All three models of trip units are available in six different types. Each trip unitmay be equipped with a maximum of five phase and two ground (time-current) adjustments to meet specific application requirements. Table 1liststhe protection provided by each available type.

    Figure 3: POWERLOGIC DIGITRIP RMS 810D Trip Unit

    Table 1: Trip Unit Types of Protection

    Protection Provided Type

    Long Time/Instantaneous LI

    Long Time/Short Time LS

    Long Time/Short Time/Instantaneous LSI

    Long Time/Instantaneous/Ground LIG

    Long Time/Short Time/Ground LSG

    Long Time/Short Time/Instantaneous/Ground LSIG

    POWERLOGIC DIGITRIP RMS

    810D

    Available Protection Types

    6035-9803

  • 8/9/2019 6035-510A Instruction Manual

    13/72

    Bulletin No. 6035-510A DIGITRIP

    RMS Trip Units

    November 1998 DIGITRIP RMS Trip Units Description

    5

    1996 Square D All Rights Reserved

    X = Standard

    OPT. = Optional

    NOTES:

    Use of zone interlocking is optional with circuit breaker wiring modification.

    Supplied if INST protection is omitted.

    Supplied only when trip unit is equipped with ground fault protection option.

    Table 2: DIGITRIP RMS Trip Units Functional Summary

    DIGITRIP RMS Type 510 610POWERLOGIC

    810D

    Long Delay Setting X X X

    Long Delay Time X X X

    Long Time Memory Powered X X X

    Overtemperature X X X

    Short Delay Pick-Up OPT. OPT. OPT.

    Short Delay Time OPT. OPT. OPT.

    Flat/I

    2

    T Response X X X

    Zone Interlocking See Note

    See Note

    See Note

    Instantaneous Pick-Up OPT. OPT. OPT.

    DIScriminator Disable Switch See Note

    See Note

    See Note

    Ground Fault Pick-Up OPT. OPT. OPT.

    Ground Fault Time OPT. OPT. OPT.

    Flat/l

    2

    t Response X X X

    Ground Time Memory X X X

    Zone Interlocking See Note

    See Note

    See Note

    Interchangeable Rating Plug X X X

    Auto Lockout After Trip X X

    Mode of Trip LEDs X X X

    Battery - for Mode of Trip LEDs X X X

    Battery Status LED (Green) X X X

    Battery Test Pushbutton X X X

    Power/Relay Module X X

    Remote Signal Contacts

    High Load Alarm X X

    Long Delay Trip X X

    Short Circuit Trip X X

    Ground Fault Trip See Note

    See Note

    Integral Test Provisions X X X

    Trip Unit Status Indication LED X X X

    4 Digit Display X X

    A Current X X

    B Current X X

    C Current X X

    Ground See Note

    See Note

    Potential Transformer Module X

    PTM Disconnect Plug for DielectricTesting of Circuit Breaker

    X

    Energy Monitoring and

    Communications X

  • 8/9/2019 6035-510A Instruction Manual

    14/72

    DIGITRIP

    RMS Trip Units Bulletin No. 6035-510A

    Basic Operation November 1998

    1996 Square D All Rights Reserved

    6

    This section covers basic operation that is common to all of the DIGITRIPRMS trip unit models. DIGITRIP RMS 510 trip unit operation is covered in itsentirety in this section. See DIGITRIP RMS 610 OPERATION on page 19for additional operating instructions for the DIGITRIP RMS 610 trip unit.Refer toPOWERLOGIC DIGITRIP RMS 810D OPERATION on page 23and to TRIP UNIT COMMUNICATIONS: POWERLOGIC DIGITRIP RMS

    810D on page 31for additional operating instructions for the POWERLOGICDIGITRIP RMS 810D trip unit.

    DIGITRIP RMS trip units are designed for use in industrial environments

    where the ambient temperature ranges from 4 F (20 C) to 185 F (85 C)and rarely exceeds 167 F (75 C). Because temperatures outside this rangemay adversely affect performance, trip units have a built-in protection featurethat is factory set to trip the circuit breaker if the microcomputer chiptemperature exceeds 95 C (203 F). If high temperature trips the circuitbreaker, the Long Delay Time LED comes on.

    The trip unit has a custom-designed integrated circuit that includes amicrocomputer to perform numeric and logic functions. Figure 4is a blockdiagram for the DIGITRIP RMS 510 tr ip unit. SeeFigure 17 on page 19for ablock diagram for the DIGITRIP RMS 610 trip unit. See Figure 19 on page 24

    for a block diagram for the POWERLOGIC DIGITRIP RMS 810D.

    BASIC OPERATION

    General

    CurrentSensors

    AuxCTs

    BridgeCircuits

    PowerSupply

    Auxiliary Power Module Input(When Used)

    Battery+3 V

    RatingPlug

    Pushbuttonturns green LEDon if battery OK

    4-bitLatchChip

    AnalogOverrideTrip Circuit

    FET

    IntegralTestPanel

    Input Protection Function SettingBy Switches And Pushbuttons

    Trip UnitOperating StatusIndicator (FlashingGreen Indicates OK)

    ZoneInterlockCircuitry

    IN

    OUT

    T

    RatingPlugConnectors

    Typical Phase Or GroundCalibration Resistor

    Custom-DesignedIntegrated Circuit Chip

    N1 2 3

    DTA

    6035-98149

    Figure 4: DIGITRIP RMS 510 Block Diagram with Circuit Breaker Interface

    In the DIGITRIP RMS trip units, all sensing and tripping power required forthe protection function is derived from the current sensors in the circuitbreaker. The secondary currents from these sensors provide the correctinput information for the protection functions, as well as tripping power,whenever the circuit breaker is carrying current. These current signalsdevelop analog voltages across the appropriate calibrating resistorsincluding:

    phase currents

    ground current (when supplied)

    rating plug

    The resulting analog voltages are digitized by the integrated circuits.

  • 8/9/2019 6035-510A Instruction Manual

    15/72

    Bulletin No. 6035-510A DIGITRIP

    RMS Trip Units

    November 1998 Basic Operation

    7

    1996 Square D All Rights Reserved

    The microcomputer, in cyclic fashion, repeatedly scans the voltage valuesacross each calibrating resistor and enters these values into random accessmemory (RAM). This data is used to calculate true RMS current values.These values are repeatedly compared with the protection function settingsand other operating data stored in read only memory (ROM). The softwareprogram determines whether to initiate protection functions, including

    tripping the circuit breaker through the low energy trip device (flux transfershunt trip or direct trip actuator) in the circuit breaker.

    For Type LS or LSG DIGITRIP RMS trip units are not equipped with an

    adjustable instantaneous setting, the override analog trip circuit is factorypreset to a value no greater than the short-time withstand current rating ofthe circuit breaker in which the trip unit is installed.

    Zone selective interlocking (or zone interlocking) is available for DIGITRIPRMS trip units having short delay or ground fault protection or both. Zoneinterlocking provides the fastest possible tripping for faults within the zone ofprotection of the circuit breaker, and provides positive coordination among allcircuit breakers in the system (mains, ties, feeders, and downstream circuitbreakers) to limit the outage to the effected part of the system only. When

    zone interlocking is enabled, a fault within the zone of protection of the circuitbreaker will cause the DIGITRIP RMS trip unit to:

    1. Trip the effected circuit breaker instantaneously, and, at the same time,

    2. Send a signal to upstream RMS DIGITRIP trip units to restrain them fromtripping immediately. The restraining signal causes upstream circuitbreakers to follow their set coordination times so that disruptions areminimized while the fault is cleared in the shortest time possible.

    This signal requires only a pair of wires from the output terminals of the tripunit in the circuit breaker downstream to the input terminals of the trip unit inthe circuit breaker upstream.

    NOTE: If circuit breaker #1 receives a zone interlocking signal from circuit

    breaker #2, and the fault current level is less than the trip unit setting for #1,

    the signal from #2 will not cause #1 to trip.

    For standard time-delay coordination only (without zone interlocking),

    connect the zone interlocking terminals with jumper wires according to theconnection diagram for the circuit breaker. The time-delay settings providethe intended coordination. The jumper wires ensure time coordination, whichprotects the equipment from nuisance tripping. For an example of how zoneselective interlocking may be used, see APPENDIX A on page 48.

    NOTE: Zone Interlocking is possible only with other DS/DSL or DSII/DSLII

    circuit breakers equipped with Digitrip RMS trip units. It is not available on

    circuit breakers not equipped with Digitrip RMS trip units.

    Time-current curves are depicted on the face of the tr ip unit. After anautomatic trip, the reason for the trip is identified by the segment of the time-

    current curve where the LED illuminates (Figure 5 on page 9). A backupbattery continues to supply power to the LEDs after an automatic trip.

    A green Unit Status LED (Figure 5 on page 9) indicates the operational statusof the trip unit. Once the load current through the circuit breaker exceedsapproximately 10% of the frame/current sensor rating, the LED flashes onceeach second, indicating that the trip unit is energized and operating properly.If the LED stays on steadily (does not flash), the trip unit is not ready toperform its circuit protective functions. If the LED continues to stay onsteadily, check the tr ip unit for proper operation. Refer to TEST

    PROCEDURE on page 40.

    Fixed Instantaneous Override

    Zone Interlocking

    Trip and Operation Indicators

  • 8/9/2019 6035-510A Instruction Manual

    16/72

    DIGITRIP

    RMS Trip Units Bulletin No. 6035-510A

    Basic Operation November 1998

    1996 Square D All Rights Reserved

    8

    Type LS or LSG DIGITRIP RMS trip units do not have an adjustableinstantaneous protection setting. Instead, they have a making currentrelease, or discriminator circuit. This circuit stops the circuit breaker frombeing closed and latched-in on a faulted circuit. The nonadjustable release ispreset at 11 times the installed rating plug current (I

    n

    ).

    The discriminator is enabled only for the first 10 cycles after an initial circuit

    breaker closing, provided the load current exceeds approximately 10% of thecircuit breaker current sensor rating. If the load current through the circuitbreaker drops to less than the 10% value, the release will reset. Once reset,the release remains enabled until the load current passing through the circuitbreaker exceeds the 10% value for 10 cycles. The discriminator trips thecircuit breaker instantaneously.

    If the circuit breaker is intended to close (but not trip out) into a circuit wherecurrent could initially be higher than 11 x I

    n

    , it is possible to deactivate thediscriminator. If the circuit breaker closes onto a fully rated fault current whenthe discriminator is deactivated, the circuit breaker will wait for the full short-time delay setting before it trips. To deactivate the discriminator, turn theOverride setting switch (next to the bottom edge of the trip unit) from the DISposition until the window is blank.

    This switch has eight positions. Seven of them show DIS in the window. Onlyone position displays a blank window. When the Override window is blank,the only fast-acting high short-circuit protection available is the Override

    (Fixed Instantaneous). Refer to Fixed Instantaneous Override on page 7.

    The Frame Rating of a circuit breaker is the maximum RMS current it cancarry continuously. The maximum short-circuit current ratings of the circuitbreaker are related to the frame rating as well.

    It is often advisable to designate a current value (I

    n

    ) that is less than the full

    frame rating as the basis for the coordination of the circuit breaker protectionfunctions. For the DIGITRIP RMS trip units, the maximum continuous current(I

    n

    ) is set by the rating plug or current sensors or both.

    The (Current) Sensor Rating is the maximum RMS current the circuit breakercan carry with the specified current sensors installed. The sensor rating maybe the same or less than the frame rating, but not greater.

    The Rating Plug (Figure 5 on page 9) fits into a special cavity to complete thetrip unit.

    Discriminator (Making Current Release)

    Frame Rating, Sensor Rating,

    and Rating Plugs

    HAZARD OF PERSONAL INJURY OR EQUIPMENT DAMAGE

    Installing a rating plug that does not match the circuit breaker type andframe rating (or sensor rating, if applicable) can cause miscoordinationor failure of the protection system. Before putting the rating plug into thetrip unit, verify that the circuit breaker type and frame rating (or sensor

    rating, if applicable), matches what is on the rating plug face.Failure to follow this instruction can result in death or serious

    injury.

    WARNING

  • 8/9/2019 6035-510A Instruction Manual

    17/72

    Bulletin No. 6035-510A DIGITRIP

    RMS Trip Units

    November 1998 Basic Operation

    9

    1996 Square D All Rights Reserved

    Figure 5: Trip Unit Face

    The rating plug sets the I

    n value, the basis for the trip unit current protectionsettings. Each circuit breaker frame rating represents the maximum currentit can carry continuously. However, for proper coordination of overcurrentprotection, it is often advisable to choose different levels of I

    n

    for differentcircuit breakers of the same frame rating. An assortment of rating plugs withdifferent I

    n

    values is available for each breaker frame rating to allow flexibilityto change the value of I

    n

    without having to change the primary currentsensors on the breaker. Refer to Table 4 on page 11for rating plug catalognumbers. By changing the rating plug, the range of current protectionsettings can be changed without having to remove the circuit breaker from itsenclosure.

    For example, if a circuit designated to carry 600 A initially is to be uprated to1200 A in the future, 1600 A cables and a 1600 A breaker frame could beinstalled with a trip unit with a rating plug for which I

    n

    = 800 A. Later on whenthe additional load is ready to come on line, the rating plug can be exchangedfor one for which I

    n

    = 1600 A, without having to remove the breaker from itsenclosure. As shown in Table 3, the available settings would offer thefollowing choices:

    NOTE: Rating plugs from DIGITRIP models 500/600/700/800 cannot be

    used with model DIGITRIP RMS 510, DIGITRIP RMS 610, or

    POWERLOGIC DIGITRIP RMS 810D trip units. The connection pins are

    located in different positions.

    Table 3: Rating Plug Comparison 800 A and 1600 A

    I

    r

    = I

    n

    x .5 .6 .7 .8 .85 .9 .95 1.0

    I

    n

    = 800 A

    LDPU I

    r = (in amperes)

    400 480 560 650 680 720 760 800

    I

    n

    = 1600 A

    LDPU I

    r

    = (in amperes)

    800 960 1120 1280 1360 1440 1520 1600

    Rating Plug

    Typical LED for indicating thecause of a circuit breaker trip

    Trip Reset Pushbutton

    Unit Status LED

    6035-9601

  • 8/9/2019 6035-510A Instruction Manual

    18/72

    DIGITRIP

    RMS Trip Units Bulletin No. 6035-510A

    Basic Operation November 1998

    1996 Square D All Rights Reserved

    10

    Rating plugs for the DIGITRIP RMS trip units are marked for both50 and 60 Hz systems and may be applied to either system.

    Rating plugs have two current ratings listed on their covers:

    The Must be used with Sensor Rated current value

    I

    n

    (Rated I) = current value.

    I

    n

    is the base value for the trip unit current settings:

    The Instantaneous and Ground Fault Current Settings (if applicable) aremultiples of I

    n

    . See Instantaneous Setting on page 16 andGround FaultSetting on page 17.

    The Long Delay Current Setting, Ir, is a multiple of In.

    Long Delay Current Setting = Ir = LD x In. SeeLong Delay Setting onpage 13.

    The Short Delay Current Setting (if provided) is a multiple of Ir, which inturn is a multiple of In.

    The Short Delay Current Setting = SD x Ir= SD x LD x In. See Short DelaySetting on page 15.

    If the rating plug is removed from the trip unit while the circuit breaker isclosed, the circuit breaker will trip. Therefore, securely tighten the rating plugbefore operating the circuit breaker.

  • 8/9/2019 6035-510A Instruction Manual

    19/72

    Bulletin No. 6035-510A DIGITRIPRMS Trip Units

    November 1998 Basic Operation

    11 1996 Square D All Rights Reserved

    Table 4: Rating Plug Catalog Numbers

    Rated Current

    (A) In

    Sensor Ratings

    (A)

    Catalog Number

    50/60 Hz

    100200

    RP6D02A010

    200 RP6D02A020

    200

    300

    RP6D03A020

    250 RP6D03A025

    300 RP6D03A030

    200

    400

    RP6D04A020

    250 RP6D04A025

    300 RP6D04A030

    400 RP6D04A040

    300

    600

    RP6D06A030

    400 RP6D06A040

    600 RP6D06A060

    400

    800

    RP6D08A040

    600 RP6D08A060

    800 RP6D08A080

    600

    1200

    RP6D12A060

    800 RP6D12A080

    1000 RP6D12A1001200 RP6D12A120

    800

    1600

    RP6D16A080

    1000 RP6D16A100

    1200 RP6D16A120

    1600 RP6D16A160

    1000

    2000

    RP6D20A100

    1200 RP6D20A120

    1600 RP6D20A160

    2000 RP6D20A200

    1600

    2400

    RP6D24A160

    2000 RP6D24A200

    2400 RP6D24A240

    1600

    3200

    RP6D32A160

    2000 RP6D32A200

    2400 RP6D32A2403000 RP6D32A300

    3200 RP6D32A320

    3200 RP6D32A320S

    2000

    4000

    RP6D40A200

    2400 RP6D40A240

    3200 RP6D40A320

    4000 RP6D40A400

    3200

    5000

    RP6D50A320

    4000 RP6D50A400

    5000 RP6D50A500

  • 8/9/2019 6035-510A Instruction Manual

    20/72

    DIGITRIPRMS Trip Units Bulletin No. 6035-510A

    Protection Settings November 1998

    1996 Square D All Rights Reserved12

    Before authorizing the use of any circuit breaker, verify that each trip unitprotection setting is set to the values specified for the installation. Whateveradjustments are required, if any, depend on the type of protection theparticular model is designed to provide. Types of protection available varydepending on the type of trip unit.

    To change settings, use a small screwdriver to turn the slotted head on arotary switch. As shown in Figure 6, settings are indicated in a rectangularviewing window above the rotary switch.

    The rating plug installed into the unit determines the maximum continuouscurrent rating (In) of the circuit breaker. Instantaneous and ground currentsettings are defined in multiples of In.

    Time-current curves on the trip unit face plate illustrate the effect of eachprotection curve setting. The rotary switch for each setting is beside to theportion of the simulated time-current curve it controls. If an automatic tripoccurs (as a result of the current exceeding the pre-selected value), the LEDin the appropriate segment of the simulated time-current curve illuminates,indicating the reason for trip.

    Figures 10through 15illustrate the available settings and the effect ofchanging the settings.

    Figure 6: Changing Settings

    PROTECTION SETTINGS

    Changing Settings

    To change a setting,turn the slotted headon the rotary switchbelow the indicator.

    6035-9601

  • 8/9/2019 6035-510A Instruction Manual

    21/72

    Bulletin No. 6035-510A DIGITRIPRMS Trip Units

    November 1998 Protection Settings

    13 1996 Square D All Rights Reserved

    Eight long delay current settings are possible as shown in Figure 7. Each Irsetting is expressed as a multiple (ranging from 0.5 to 1) of the rating plugcurrent In.

    NOTE: Iris also the basis for the short delay current setting. See Short Delay

    Setting on page 15.

    Figure 7: Long Delay Current Settings

    Eight long delay time settings are possible, ranging from 2 to 24 seconds.

    Refer to Figure 8for available settings. The long delay time (LDT) is the totalclearing time when the current value equals six times Ir.

    Figure 8: Long Delay Time Settings

    In addition to standard long delay protection, the DIGITRIP RMS trip unit has

    long time memory (LTM), which protects load circuits from the effects ofrepeated overload conditions. If a circuit breaker is reclosed soon after a longdelay trip, and the current again exceeds the long delay setting (Ir), the LTMautomatically reduces the time to tr ip. This allows for the higher-than-normalload circuit temperature, which is a result of the previous overload condition.Each time an overload condition is repeated, the LTM causes the circuit

    breaker to trip in a time progressively earlier than the long delay time setting.When the load current returns to normal, the LTM begins to reset. After about10 minutes, it is fully reset. The next long delay trip time will again be thesetting value.

    Units are shipped from the factory with the LTM function inactive. In certainapplications, it is desirable to enable the LTM function. To enable the LTMfunction:

    Long Delay Setting

    6035-98150A

    Long Delay Setting Ir

    X In= Ir1

    Ir

    Available Settings.5, .6, .7, .8,.85, .9, .95, 1.0

    In multiples of ratingplug amperes (In)

    Ir

    Long Delay Time

    6035-98151A

    Available Settings2, 4, 7, 10,12, 15, 20, 24

    seconds at 6 timesLong Delay Setting(Ir)

    6 X Ir

    Long Delay Time

    Sec. At6 X Ir

    4

    Long Time Memory

  • 8/9/2019 6035-510A Instruction Manual

    22/72

    DIGITRIPRMS Trip Units Bulletin No. 6035-510A

    Protection Settings November 1998

    1996 Square D All Rights Reserved14

    1. Open the circuit breaker.

    2. Open the cover on the rating plug. See Figure 9.

    Figure 9: Typical Rating Plug

    3. Loosen the screw in the rating plug. SeeFigure 10.

    Figure 10: Removing the Rating Plug

    4. Pull the rating plug out.

    5. Using a small screwdriver, pry the LTM jumper out of the inactive positionand move it to the active position. See Figure 11.

    Figure 11: Long Time Memory (LTM) Jumper

    This edge flips down.

    6035-9601

    6035-98152A

    Loosen this screw

    SCK3

    SCK2

    SCK1

    SCK3

    SCK2

    SCK1

    6035-98153

    Standard from Factory LTM Inactive LTM active

    Rating Plug Cavitiy Rating Plug Cavitiy

  • 8/9/2019 6035-510A Instruction Manual

    23/72

    Bulletin No. 6035-510A DIGITRIPRMS Trip Units

    November 1998 Protection Settings

    15 1996 Square D All Rights Reserved

    Consider the action of the LTM when performing multiple Long Delay Timetests. See Preparation for Testing, page 40.

    When the circuit breaker is closed, the Long Delay Trip LED can erroneouslyindicate that an LDT has occurred. This can happen when an overloadcurrent momentarily exceeds the long delay current setting, Ir, so that theLong Delay LED flashes to indicate the overload condition. If, at the exact

    moment that the LED is on, the load current drops to a value less than 10%of the circuit breaker current sensor rating, then the trip unit stops functioningwhile the 4-bit latch chip is set and the LED remains lit. If the current againincreases to a value above the long delay current setting, Ir, and then returnsto normal, the LDT will reset itself. To manually clear the LDT or any other tripindication at any time, press the red Trip Reset pushbutton.

    Eight short delay current settings are possible (see Figure 12). Six settingsare in the range from 2 to 6 times Ir. The other two settings are S1or S2timesIr. Iris the long delay current setting. S1equals 8 and S2equals 10 for DS andDSII circuit breakers. S1and S2are both specified on the rating plug face.

    Figure 12: Short Delay Current Settings

    Two different short delay time curve shapes are availablefixed time (flat)and I2t response. Refer to Figure 13 on page 16. The shape selecteddepends on the type of selective coordination chosen. The I2t response

    provides a longer time delay in the low end of the shor t delay current rangethan will the flat response.

    Five flat (.1, .2, .3, .4, .5 second) and three I2t (.1*, .3*, .5* second) responsetime delay settings are possible. The asterisk (*) appearing in the viewingwindow identifies the I2t response settings. The I2t response is applicable tocurrents less than eight times Ir, the long delay setting. For currents greaterthan eight times Ir, the I

    2t response reverts to the flat response.

    Short Delay Setting

    6035-98154

    Available Settings

    2, 2.5, 3, 4, 5, 6, S1, S2

    In multiples ofLong Delay Setting(Ir)

    Short DelaySetting

    S1and S2values are specified on the rating plugDSII circuit breakers: S1= 8, S2= 10

    5 X Ir

    Short Delay Time

  • 8/9/2019 6035-510A Instruction Manual

    24/72

    DIGITRIPRMS Trip Units Bulletin No. 6035-510A

    Protection Settings November 1998

    1996 Square D All Rights Reserved16

    Figure 13: Short Delay Time Settings

    Eight instantaneous current settings are possible as shown in Figure 14.Sixsettings range from two to six times In, the rating plug value, and the othertwo settings are M1or M2times In. M1equals 8 and M2equals 12 for DSII

    circuit breakers. M1and M2are both specified on the rating plug face.

    NOTE: LS and LSG type trip units do not have an instantaneous setting.

    Instead, they have a making current release, or discriminator. See

    Discriminator (Making Current Release) on page 8, and Fixed

    Instantaneous Override on page 7, for available fast-acting high short-circuit

    protection.

    Figure 14: Instantaneous Current Settings

    6035-98155A

    Available Settings.1, .2, .3, .4, .5seconds with flat response

    Short Delay Time

    .4 Sec.

    I2t shape returns to flat response atcurrents higher than 8 x Ir

    seconds with I2t shape

    .1*, .3*, .5*

    8 x Ir

    * in viewing window indicates I2t shape

    Instantaneous Setting

    Available Settings2, 2.5, 3, 4, 5, 6, M1, M2

    In multiples of rating plugamperes (In)

    InstantaneousSetting

    6 X In

    M1and M2values are specified on the rating plugDSII circuit breakers: M1= 8, M2= 12 6035-98156A

  • 8/9/2019 6035-510A Instruction Manual

    25/72

  • 8/9/2019 6035-510A Instruction Manual

    26/72

    DIGITRIPRMS Trip Units Bulletin No. 6035-510A

    Protection Settings November 1998

    1996 Square D All Rights Reserved18

    As illustrated in Figure 16, two different ground fault curve shapes areavailable fixed time (flat) and I2t response. The shape selected depends onthe type of selective coordination chosen. The I2t response provides a longertime delay in the low end of the ground fault current range than does the flatresponse.

    Figure 16: Ground Fault Time Delay Settings

    Five flat (0.1, 0.2, 0.3, 0.4, 0.5 seconds) and three I2t (0.1*, 0.3*., 0.5*seconds) response time delay settings are possible. The asterisk (*)appearing in the viewing window, identifies I2t response settings. The I2tresponse applies to currents less than 0.625 times the ampere rating of theinstalled rating plug (In). For currents greater than 0.625 x In, the I

    2t responsereverts to the flat response.

    Ground Fault Time

    6035-98158A

    Available Settings.1, .2, .3, .4, .5

    seconds with flat response

    Ground Fault Time

    .3 Sec.

    I2t shape returns to flat responses atapproximately 0.625 In

    seconds with I2t shape

    .1*, .3*, .5*

    * in viewing window indicates I2t shape

  • 8/9/2019 6035-510A Instruction Manual

    27/72

    Bulletin No. 6035-510A DIGITRIPRMS Trip Units

    November 1998 DIGITRIP RMS 610 Operation

    19 1996 Square D All Rights Reserved

    This section covers DIGITRIP RMS 610 operation that is beyond the scopeof the basics covered in BASIC OPERATION on page 6. SeePROTECTION SETTINGS on page 12 for protection settings availabledepending on the type of unit. In addition to all the features that the DIGITRIPRMS 510 has, the DIGITRIP RMS 610 also has:

    Local four-digit alphanumeric display for

    Amperes

    Mode of trip

    Service trip messages

    Options available:

    Local high load indication

    Remote signal contacts for high load and mode of trip (via the auxiliarytrip relay-ATR)

    The trip unit uses a custom-designed integrated circuit, which includes amicrocomputer to perform numeric and logic functions. Figure 17is a blockdiagram for the DIGITRIP RMS 610 trip unit.

    The four-digit alphanumeric display window (Figure 18 on page 20) servestwo basic purposes: instrumentation and mode of trip and trouble indication.The information displayed in the window is listed inTable 6 on page 21.

    DIGITRIP RMS 610 OPERATION

    General

    Four Character Information DisplayWindow

    CurrentSensors

    AuxCTs

    BridgeCircuits

    PowerSupply

    Auxiliary Power Module Input(When Used)

    Battery+3 V

    RatingPlug

    Pushbuttonturns green LEDon if battery OK

    4-bitLatchChip

    AnalogOverride

    Trip Circuit

    FET

    IntegralTestPanel

    Input Protection Function SettingBy Switches And Pushbuttons

    Trip UnitOperating StatusIndicator (FlashingGreen Indicates OK)

    ZoneInterlockCircuitry

    IN

    OUT

    T

    RatingPlugConnectors

    Typical Phase Or GroundCalibration Resistor

    Custom-DesignedIntegrated Circuit Chip

    Short Circuit Trip Alarm Contact

    High Load Alarm Contact

    Long Delay Trip Alarm Contact

    Ground Fault Trip Alarm Contact orNeutral Overcurrent Alarm Contact

    Alarm Common

    120 Volt50/60 HertzControl Power

    Front Panel Alpha-NumericDisplays and Pointer LEDs

    Power/RelayModule

    DTA

    N1 2 3

    6035-98159

    Figure 17: DIGITRIP RMS 610 Block Diagram with Circuit Breaker Interface

  • 8/9/2019 6035-510A Instruction Manual

    28/72

    DIGITRIPRMS Trip Units Bulletin No. 6035-510A

    DIGITRIP RMS 610 Operation November 1998

    1996 Square D All Rights Reserved20

    Figure 18: DIGITRIP RMS 610 Trip Unit

    The alphanumeric display window provides current values under normalservice conditions and coded messages after an alarm condition or after an

    overcurrent trip operation. Four LEDs below the display window indicatewhich value of current appears in the display window. Press the Step

    pushbutton to view the value of the next parameter. See Figure 18.

    During the normal service conditions, with the circuit breaker closed, theDigitrip RMS 610 serves as an ammeter, displaying the individual phasecurrents (IA, IB, IC) and ground current (IG) or the fourth pole (neutral) current(ID), provided the circuit breaker is set up for ground or fourth pole protection.Current values are displayed in kA. The value displayed is current in the pole(or ground) indicated by the LED that is on. Press the Step pushbutton toview the values of current in the other phases. The range, accuracy, andwave shape parameters for current values displayed are:

    RANGE: 5% to 100% of (Current) Sensor Rating for Type DS andDSII circuit breakers.

    ACCURACY: +2% of (Current) Sensor Rating for Type DS and DSIIcircuit breakers.

    WAVE SHAPE: Sinusoidal, reference IEC 947-2 Appendix F (Harmoniccontent included for True RMS reading).

    Display Window

    LEDs that indicate whichvalues are displayed

    Trip Reset Pushbutton

    Step Pushbutton

    6035-9602

    Value Displayed During Normal Service

    Current Values

  • 8/9/2019 6035-510A Instruction Manual

    29/72

    Bulletin No. 6035-510A DIGITRIPRMS Trip Units

    November 1998 DIGITRIP RMS 610 Operation

    21 1996 Square D All Rights Reserved

    After an alarm condition or circuit breaker trip operation occurs, one of thecoded messages listed in Table 7 on page 22appears in the display window,provided control power is still available for the Power/Relay Module (SeePOWER/RELAY MODULE on page 38 for information on the Power/RelayModule). When an ALARM condition occurs, the operator has time to takeaction, such as reducing the load, to correct the situation. The message

    remains in the display window until the Step pushbutton is pressed. Then themessage disappears and the values of currents (kA) at the moment can beviewed in the window.

    NOTE: Press the Step pushbutton several times to verify that the values of all

    the currents appear. The first value displayed may not be the highest.

    Following a circuit breaker TRIP operation, the display window indicates thereason for trip, using coded messages such as INST (Instantaneous Trip),LDT (Long Delay Trip), and so forth. As with the alarm function, pressing theStep pushbutton clears the reason for trip message. The display window thenshows the values of current at the time of trip. The values remain in memory,and the LED indicating the reason for trip stays on until the trip unit is resetby pressing the red Trip Reset pushbutton (Figure 18).

    NOTE: Record all values of interest, and note which LEDs are lit before

    resetting the trip unit. Correct the cause of the overload or fault before

    resetting the trip unit.

    The LOCKOUT after trip feature requires that the trip unit be reset before thebreaker can be closed again.

    For examples of how to interpret the display after an overload and after ashort circuit, see APPENDIX B on page 51.

    Table 6: DIGITRIP RMS 610 Information Functions

    Trip Unit Type

    LI LSI LS LIG LSG LSIG

    4-Character LED Display x x x x x x

    Current Values:

    Phase A Current (Ia) (kA) x x x x x x

    Phase B Current (Ib) (kA) x x x x x x

    Phase C Current (Ic) (kA) x x x x x x

    Ground Current (Ig) (kA) x x x

    Message Codes:

    DISC = DISCriminator Trip x x

    GNDT = GrouND Trip x x x

    HILD = High LoaD Alarm x x x x x x

    INST = INStantaneous Trip x x x x

    LDPU = Long-Time Delay Pickup x x x x x x

    LDT = Long-Time Delay Trip x x x x x x

    ORNG = OverRaNGe Trip x x x x x x

    PLUG = Rating PLUG Problem x x x x x x

    SDT = Short-Time Delay Trip x x x x

    TEMP = OverTEMPerature Trip x x x x x x

    TEST = TEST Ready to Begin x x x x x x

    Messages Displayed After Alarm or Trip

  • 8/9/2019 6035-510A Instruction Manual

    30/72

    DIGITRIPRMS Trip Units Bulletin No. 6035-510A

    DIGITRIP RMS 610 Operation November 1998

    1996 Square D All Rights Reserved22

    If the rating plug is missing or not well connected, PLUG appears in thedisplay and the instantaneous/override LED is on. If the circuit breaker isclosed, it will tr ip. If it is open, it will remain trip-free, as long as 120 Vaccontrol power is available to the Power/Relay Module. See POWER/RELAYMODULE on page 38for more information. Even if control power is lost, andthe breaker is reclosed before the rating plug condition is corrected, the trip

    unit will trip the breaker again. A backup battery provides power for LEDswhen external control power to the Power/Relay Module is not available.

    NOTE: The battery only supplies the power for LEDs. It has no part in the

    protection function of the trip unit, and it does not light the display window.

    Notes: In the case of a high-level fault condition where fast tripping is desirable, the trip unit will

    operate before a complete RMS current value can be calculated. For this reason, thedisplayed value may be less than the actual RMS fault current.

    In the case of a very high fault current (greater than 28 x In), the message ORNG(indicating over range) appears because the trip unit cannot determine the actual value ofthe fault current.

    Table 7: DIGITRIP RMS 610 Message Codes

    Message Meaning Comment

    DISC DISCriminator Trip(High Initial Current Release)

    Breaker tripped instantaneously becausephase current exceeded 11 x rating plugcurrent InValue.

    GNDT GrouND-fault Trip Breaker tripped because ground currentexceeded Ground Fault protection settings.

    HILD HIgh LoaD Alarm

    ALARM: NearingOverload Condition

    Phase current has exceeded 85% of Long-

    Time Current Setting for more than 40seconds.

    INST INStantaneous Trip Breaker tripped instantaneously becausephase current exceeded instantaneousprotection setting.

    LDPU Long-Time Delay Pick-UpALARM: Overload Condition inProgress

    Phase current has exceeded Long-Timecurrent setting. Trip unit is timing to tripbreaker.

    LDT Long-Time Delay Trip(Overload Trip)

    Breaker tripped because phase currentexceeded Long-Time protection settings.

    ROM ERROR Nonfatal memory error Protection functions stil l operate, but may beup to 12% out of tolerance. Replace trip unitat first opportunity.

    ORNG Over RaNGe Trip(Current too high to measure.)

    Breaker tripped instantaneously becausephase current (or ground current) exceeds28 x rating plug current Invalue.

    PLUG Rating PLUG Problem Rating Plug is missing, damaged or not wellconnected. If breaker is closed, it will trip, andthe instantaneous/override LED will light. Ifbreaker is open, it will not close.

    SDT Short-Time Delay Trip Breaker tripped because phase currentexceeded Short-Time Delay protectionsettings.

    TEMP OverTEMPerature Trip Breaker tripped because ambienttemperature of 95 C exceeded.

    TEST TEST and trip breaker is readyto begin.

    Trip unit will begin as soon as you release thepush to test button and TEST message willdisappear. The breaker will trip, and thecause of trip is displayed.

    (blank) Test (without tr ipping breaker) isready to begin.

    Trip unit test begins as soon as you releasepush to test button, and the display shows theelapsed time of test.

    or

    Trip unit not ON Control power is out.

    Rating Plug Missing or Disconnected

    Indication

  • 8/9/2019 6035-510A Instruction Manual

    31/72

    Bulletin No. 6035-510A DIGITRIPRMS Trip Units

    November 1998 POWERLOGIC DIGITRIP RMS 810D Operation

    23 1996 Square D All Rights Reserved

    This section covers POWERLOGIC DIGITRIP RMS 810D operation that isbeyond the scope of the basics covered in BASIC OPERATION on page 6.See PROTECTION SETTINGS on page 12 for protection settings availabledepending on the type of unit. In addition to all the features that the DIGITRIPRMS 510 has, the DIGITRIP RMS 810D also has:

    Local four-digit alphanumeric display for

    Amperes

    Mode of trip

    Service trip messages

    Energy and power monitoring:

    Peak demand

    Present real power

    Energy consumption

    Direct communications link to the POWERLOGIC Power Monitoring andControl System:

    Amperes

    Energy and demand information Remote breaker operation

    Service and trip messages

    Options available:

    Local high load indication

    Remote signal contacts for high load and mode of trip (via the auxiliarytrip relay-ATR)

    The trip unit uses a custom-designed integrated circuit which includes amicrocomputer to perform numeric and logic functions. Figure 19is a blockdiagram for the DIGITRIP RMS 810D tr ip unit.

    The four-digit alphanumeric display window (Figure 20 on page 25) servestwo basic purposes: instrumentation and mode of trip and trouble indication.The information displayed in the window is listed inTable 8 on page 26.

    The alphanumeric display window displays current, power or energy valuesunder normal service conditions and displays coded messages after analarm condition or after an overcurrent trip operation. The four LEDs left andbelow the display window (Figure 20 on page 25) identify which current (kA)value is being displayed. Options are: phase A current (IA), phase B current(IB), phase C current (IC), ground current (IG) if the unit is equipped with theground fault protection option. The three LEDs on the right identify which

    Demand value is being displayed. Options are: Peak Power Demand (MW),Present Power Demand (MW or Energy Demand (MWh). Press the Steppushbutton to view the value of the next parameter. Details about values andmessages follow in this section.

    During the normal service conditions, with the circuit breaker closed, theDIGITRIP 810D serves as an ammeter, displaying the individual phasecurrents.

    POWERLOGIC DIGITRIP RMS 810DOPERATION

    General

    Four Character Information DisplayWindow

    Values Displayed During Normal Service

    Current Values

  • 8/9/2019 6035-510A Instruction Manual

    32/72

    DIGITRIPRMS Trip Units Bulletin No. 6035-510A

    POWERLOGIC DIGITRIP RMS 810D Operation November 1998

    1996 Square D All Rights Reserved24

    Figure 19: POWERLOGIC DIGITRIP RMS 810D Block Diagram with Circuit Breaker Interface

    CurrentSensors

    AuxCTs

    BridgeCircuits

    PowerSupply

    Auxiliary Power Module Input(When Used)

    Battery+3 V

    RatingPlug

    Pushbuttonturns green LED onif battery OK

    4-bitLatchChip

    AnalogOverride

    Trip Circuit

    FET

    IntegralTestPanel

    Input Protection Function SettingBy Switches And Pushbuttons

    Trip UnitOperating StatusIndicator (FlashingGreen Indicates OK)

    ZoneInterlockCircuitry

    IN

    OUT

    T

    RatingPlugConnectors

    Typical PhaseOr GroundCalibration Resistor

    Custom-DesignedIntegrated Circuit Chip

    Short Circuit Trip Alarm Contact

    High Load Alarm Contact

    Long Delay Trip Alarm ContactGround Fault Trip Alarm Contact orNeutral Overcurrent Alarm Contact

    Alarm Common

    120 Volt50/60 HertzControl Power

    Front Panel Alpha-NumericDisplays and Pointer LEDs

    Power/RelayModule

    PT Module

    Energy and Power Monitor

    POWERLOGICCommunicationCircuit

    RS-485POWERLOGICSY/MAXCommunication

    Close

    DisconnectPlug

    DTA

    N1 2 3

    6

  • 8/9/2019 6035-510A Instruction Manual

    33/72

    Bulletin No. 6035-510A DIGITRIPRMS Trip Units

    November 1998 POWERLOGIC DIGITRIP RMS 810D Operation

    25 1996 Square D All Rights Reserved

    Figure 20: POWERLOG DIGITRIP RMS 810D Trip Unit

    (IA, IB, IC) and ground current (IG), provided the circuit breaker is set up forground fault protection. Current values are displayed in kA. The value

    displayed is current in the pole (or ground) indicated by the LED that is on.Press the Step pushbutton to view the values of current in the other phases.

    The range, accuracy, and wave shape parameters for current valuesdisplayed are:

    RANGE: 5% to 100% of (Current) Sensor Rating for Type DS andDSII circuit breakers.

    ACCURACY: 2% of (Current) Sensor Rating for Type DS and DSIIcircuit breakers.

    WAVE SHAPE: Sinusoidal, (Refer to IEC 947-2 Appendix F; Harmoniccontent included for True RMS reading.)

    6035-9603

    Display Window

    Reset Pushbutton

    LEDs that indicate whichpower or energy value isdisplayed

    LEDs that indicate whichpower or energy value isdisplayed

    Step Pushbutton

    Trip Reset Pushbutton

  • 8/9/2019 6035-510A Instruction Manual

    34/72

    DIGITRIPRMS Trip Units Bulletin No. 6035-510A

    POWERLOGIC DIGITRIP RMS 810D Operation November 1998

    1996 Square D All Rights Reserved26

    The DIGITRIP RMS 810D trip unit displays power and energy values. Byusing the circuit breaker current sensors and an integrally mounted PotentialTransformer Module (see Potential Transformer Module on page 30) powerand energy values are computed and displayed in the four-digit displaywindow on the face of the trip unit.

    The power and energy parameter values displayed in the window on the face

    of the trip unit are:

    Peak Demand in MW (Megawatts)

    Present Real Power in MW (Megawatts)

    Energy (Consumed) in MWh (Megawatt-hours)

    Three LEDs as shown indicate which power or energy value is displayed. The

    same Step pushbutton for changing the displayed values of current is alsoused to change the displays of power and energy values.

    Table 8: POWERLOGIC DIGITRIP RMS 810D Information Functions

    Trip Unit Type

    LI LSI LS LIG LSG LSIG

    4-Character LED Display x x x x x x

    Current Values:

    Phase A Current (Ia) (kA) x x x x x x

    Phase B Current (Ib) (kA) x x x x x x

    Phase C Current (Ic) (kA) x x x x x x

    Ground Current (Ig) (kA) x x x

    Power and Energy Values:

    Peak Power Demand (MW) x x x x x x

    Present Real Power x x x x x x

    Reverse Power Flow x x x x x x

    Energy Consumption (MWh) x x x x x x

    Reverse Energy Consumption x x x x x x

    Local Messages:

    DISC = DISCriminator Trip x x

    EXTT = EXTernal Trip x x x x x x

    GNDT = GrouND Trip x x x

    HILD = High LoaD Alarm x x x x x x

    INST = INStantaneous Trip x x x x

    LDPU = Long-Time Delay Pickup x x x x x x

    LDT = Long-Time Delay Trip x x x x x x

    NPOW = Negative POWer Flow x x x x x x

    ORNG = OverRaNGe Trip x x x x x x

    PLUG = Rating PLUG Problem x x x x x x

    SDT = Short-Time Delay Trip x x x x

    TEMP = OverTEMPerature Trip x x x x x x

    TEST = TEST Ready to Begin x x x x x x

    Power and Energy Values

  • 8/9/2019 6035-510A Instruction Manual

    35/72

  • 8/9/2019 6035-510A Instruction Manual

    36/72

    DIGITRIPRMS Trip Units Bulletin No. 6035-510A

    POWERLOGIC DIGITRIP RMS 810D Operation November 1998

    1996 Square D All Rights Reserved28

    After an alarm condition or circuit breaker trip operation occurs, one of thecoded messages listed in Table 9appears in the display window, providedcontrol power is still available for the Power/Relay Module. SeePOWER/RELAY MODULE on page 38. When an alarm condition occurs, the operatorhas time to take action, such as reducing the load, to correct the situation.The message remains in the display window until the Step pushbutton is

    pressed. Then the message disappears and the values of currents (kA) at themoment can be viewed in the window.

    NOTE: Press the Step pushbutton several times to verify that the values of all

    the currents appear. The first value displayed may not be the highest.

    Following a circuit breaker trip, the display window indicates the reason fortrip, using coded messages such as, INST (Instantaneous Trip), LDT (LongDelay Trip), and so forth. As with the alarm function, pressing the Steppushbutton clears the reason for trip message. Then the display windowshows the values of current at the time of trip. The values remain in memory,and the LED indicating the reason for trip stays on until the trip unit is resetby pressing the red Trip Reset pushbutton.

    NOTE: Record all values of interest, and note which LEDs are lit before

    resetting the trip unit. Correct the cause of the overload or fault beforeresetting the trip unit.

    The LOCKOUT after trip feature requires the trip unit to be reset before thebreaker can be closed again.

    For examples of how to interpret the display after an overload and after ashort-circuit, see APPENDIX B on page 51.

    If the rating plug is missing or not well connected, PLUG appears in thedisplay and the instantaneous/override LED is on. If the circuit breaker isclosed, it will tr ip. If it is open, it will remain trip-free, as long as 120 Vaccontrol power is available to the Power/Relay Module. Even if control poweris lost, and the circuit breaker is reclosed before the rating plug condition iscorrected, the trip unit will trip the circuit breaker again. A backup battery

    provides power for LEDs when external control power to the Power/Relaymodule is not available.

    NOTE: The battery only supplies power to the LEDs. It has no part in the

    protection functions of the trip unit, and it does not light the display window.

    Messages Displayed after Alarm or Trip

    Rating Plug Missing or Disconnected

    Indication

  • 8/9/2019 6035-510A Instruction Manual

    37/72

    Bulletin No. 6035-510A DIGITRIPRMS Trip Units

    November 1998 POWERLOGIC DIGITRIP RMS 810D Operation

    29 1996 Square D All Rights Reserved

    Notes:

    In the case of a high-level fault condition where fast tripping is desirable, the trip unit willoperate before a complete RMS current value can be calculated. For this reason, thedisplayed value may be less than the actual RMS fault current.

    In the case of a very high fault current (greater than 28 x In), the message ORNG(indicating over range) appears because the trip unit cannot determine the actual value ofthe fault current.

    Table 9: POWERLOGIC DIGITRIP RMS 810D Message Codes

    Message Meaning Comment

    DISCDISCriminator Trip(High Initial Current Release)

    Breaker tripped instantaneously because phasecurrent exceeded 11 x rating plug current InValue.

    EXTT EXTernal Trip Breaker tripped due to external communicationscontrol signal for example from POWERLOGIC.

    GNDT GrouND-fault TripBreaker tripped because ground current exceededGround Fault protection settings.

    HILDHIgh LoaD AlarmALARM: NearingOverload Condition

    Phase current has exceeded 85% of Long-TimeCurrent Setting for more than 40 seconds.

    INST INStantaneous TripBreaker tripped instantaneously because phasecurrent exceeded instantaneous protectionsetting.

    LDPULong-Time Delay Pick-UpALARM: OverloadCondition in Progress

    Phase current has exceeded Long-Time currentsetting. Trip unit is timing to trip breaker.

    LDTLong-Time Delay Trip(Overload Trip)

    Breaker tripped because phase current exceededLong-Time protection settings.

    NPOW Negative POWer flowNet power is flowing into load side (bottom) ofbreaker, and out from line side (top) of thebreaker.

    ORNGOver RaNGe Trip (Current too high tomeasure.)

    Breaker tripped instantaneously because phasecurrent (or ground current) exceeds 28 x ratingplug current Invalue.

    PLUG Rating PLUG Problem

    Rating Plug is missing, damaged or not wellconnected. If breaker is closed, it will trip, and theinstantaneous/override LED will light. If breaker isopen, it will not close.

    SDT Short-Time Delay TripBreaker tripped because phase current exceededShort-Time Delay protection settings.

    TEMP OverTEMPerature TripCircuit breaker tripped because ambienttemperature of 95 C exceeded.

    TESTTEST and trip breaker isready to begin.

    Trip unit will begin as soon as you release the pushto test button and TEST message will disappear.The circuit breaker will trip, and the cause of tripis displayed.

    (blank)Test (without trippingbreaker) is ready to begin

    Trip unit test begin as soon as you release push totest button, and the display shows the elapsedtime of test.

    or

    Trip unit not ON Control power is out.

  • 8/9/2019 6035-510A Instruction Manual

    38/72

    DIGITRIPRMS Trip Units Bulletin No. 6035-510A

    POWERLOGIC DIGITRIP RMS 810D Operation November 1998

    1996 Square D All Rights Reserved30

    The Potential Transformer Module (PTM) is also separate from thePOWERLOGIC DIGITRIP RMS 810D trip unit and is not required for the tripunit to perform its protection functions. The Potential Transformer Moduleprovides three-phase primary voltage information necessary for the trip unitto calculate power and energy values.

    The Potential Transformer Module primary terminals are suitable for all

    system voltage ratings up through 600 V 50/60 Hz, and are connected to theprimary phase conductors inside the circuit breaker. The PTM providesstepped down voltage signals to input terminals VA, VB, VC, and VNon therear of the POWERLOGIC DIGITRIP RMS 810D trip unit housing.

    The primary voltage connection to the Potential Transformer Module is madethrough a disconnect plug that can be located either on the module, asshown in Figure 21, or on the side of the circuit breaker.

    The Communication Power Module supplies an isolated voltage for theRS-485 communications circuitry. It is housed in an enclosure identical tothat of the Power Relay Module and mounted on the DS/DSL and DSII/DSLIIbreaker adjacent to the trip unit. It is not required for the trip unit to performits protective functions.

    Figure 21: Potential Transformer Module

    Potential Transformer Module

    Communication Power Module

    Disconnect Plug

    6035-9605

  • 8/9/2019 6035-510A Instruction Manual

    39/72

    Bulletin No. 6035-510A DIGITRIPRMS Trip Units

    November 1998 Trip Unit Communications: POWERLOGIC DIGITRIP RMS 810D

    31 1996 Square D All Rights Reserved

    The POWERLOGIC DIGITRIP RMS 810D trip unit can be a fully integratedpart of the POWERLOGIC Power Monitoring and Control Systemmanufactured by Square D. The trip unit is equipped with RS-485communications for connection to the POWERLOGIC system. Over thiscommunications link, a wide variety of metering and trip data can becommunicated to aid facility operation. In addition, users can remotely reset

    and operate the circuit breaker by commands sent over the communicationnetwork.

    There is a wide variety of networking options available when designing acommunications network for the POWERLOGIC system with POWERLOGICDIGITRIP RMS 810D trip units. The options range from simple, shielded, twotwisted pairs of wire to fiber optic and wireless Ethernet. Contact yourSquare D representative for more information about communications

    options.

    The trip unit can be connected by the communication network to any numberof display and control devices. Examples include:

    The POWERLOGIC System Display, a compact and versatile data displayunit ideal for installation in the switchgear or electrical room.

    Using the system display, a user can observe a wide variety of trip unitdata from up to 32 circuit breakers. The data includes: phase currents,

    power, energy, demand, protective settings, cause of trip, and more. Inaddition, resets can be done from the system display.

    Personal computers running POWERLOGIC software, such asSystem Manager.

    This versatile software, written by Square D expressly for powermonitoring, is a powerful tool for display, alarming, graphics, and more.The software makes it easy to pull together data and control for a wholeelectric plant in one spot and in real time.

    Programmable Logic Controllers (PLCs), which are often used when

    automatic control sequences are desired.

    PLCs can be programmed to read information from trip units or circuit

    monitors, make decisions, and initiate control actions. The PLCs can bothread data from the trip units and send open and close commands over thecommunication network. Automatic control can be used for tasks such asdemand control, load shedding, emergency power transfer, power factorcontrol, and others.

    Each POWERLOGIC DIGITRIP RMS 810D trip unit must be given a unique

    network address so that data can be properly routed over the communicationnetwork. Also, the trip unit can communicate at any of the five following baudrates: 1200, 2400, 4800, 9600, and 19,200 baud. The baud rate must be setthe same as all other trip units and devices on the network to successfullysend and receive data. The default address is 1, and the default baud rate is9600. These can be easily changed by the user in the field.

    To change the trip unit address or baud rate:

    NOTE: The circuit breaker need not be open and may be carrying current.

    TRIP UNIT COMMUNICATIONS:POWERLOGIC DIGITRIP RMS 810D

    Trip Unit Address and Baud Rate

  • 8/9/2019 6035-510A Instruction Manual

    40/72

    DIGITRIP RMS Trip Units Bulletin No. 6035-510A

    Trip Unit Communications: POWERLOGIC DIGITRIP RMS 810D November 1998

    1996 Square D All Rights Reserved32

    1. Determine present settings by pressing and holding the red Trip Resetpushbutton. After about five seconds the kA, MW, or MWh valuedisappears. In its place, a letter appears on the left side of the display anda number appears on the right side. Letters correspond to thesebaud rates:

    A 1200 baud

    B 2400 baud

    C 4800 baud

    D 9600 baud

    E 19,200 baud

    The number is the network address of the trip unit.

    2. Change the trip unit address or baud settings as follows:

    Higher address To change the address to a higher number, press theblack Reset pushbutton near the display window while holding the red TripReset pushbutton. The address increases by one unit each time the Resetpushbutton is pressed. Pressing and holding the black Reset pushbutton

    increases the address continuously, slowly at first, and then faster.

    Lower address To change the address to a lower number, press the Steppushbutton near the display window while holding the red Trip Resetpushbutton. The address decreases by one each time the Steppushbutton is pressed. Pressing and holding the Step pushbuttondecreases the address continuously, slowly at first, and then faster.

    Baud rate To change the baud rate, press the Test pushbutton whileholding the red Trip Reset pushbutton. The letter corresponding to thebaud rate steps up alphabetically each time the Test pushbutton ispressed.

    3. When the address and baud rate code in the display window are correct,

    release the red Trip Reset pushbutton to save the values into thenonvolatile memory of the trip unit. The kA, MW, or MWh value will thenreturn to the display window. If control power is lost, the trip unit will retainits (new) address and baud rate.

    NOTE: If control power is lost while the address or baud rate is being

    changed, that is, while the red Trip Reset pushbutton is still being held in, the

    display goes blank. When control power is restored, the trip unit retains the

    previous address and baud rate values, as though there had been no attempt

    to change them.

    NOTE: Because trip units and circuit breakers of the same rating are

    interchangeable, if more than one has been withdrawn for maintenance at the

    same time, it is critical that each be returned to its correct cell location so that

    the circuit has the correct address. For example, if two identical breakers (one

    with a trip unit address of 1 and the other with an address of 10) were

    switched, there would be confusion. Information coming from the 1 trip unit,

    as well as commands going to the 1 trip unit, will actually involve the 10

    circuit, and vice versa.

  • 8/9/2019 6035-510A Instruction Manual

    41/72

    Bulletin No. 6035-510A DIGITRIPRMS Trip Units

    November 1998 Trip Unit Communications: POWERLOGIC DIGITRIP RMS 810D

    33 1996 Square D All Rights Reserved

    A personal computer can be used as a POWERLOGIC workstation simply byinstalling POWERLOGIC software and connecting to the same data networkbeing used by the POWERLOGIC DIGITRIP RMS 810D tr ip units. For smallnetworks (up to 32 trip units and a single computer), the network can beconnected to the computer serial port with an inexpensive RS-232/485converter. The computer can be connected to larger networks by installing a

    SY/LINK

    communication card in a free ISA compatible slot on the computer.The SY/LINK has a communications coprocessor that unloads thecomputers microprocessor and permits network speeds of up to 500 kbaud.

    Figure 22: POWERLOGIC with Personal Computer Workstation

    A system display (must be model SD-300 or SD-320) can be installed in thesame switchgear with the circuit breakers, or at a remote location, to monitor

    the information from any of the POWERLOGIC DIGITRIP RMS 810D tripunits. The connections in the network are made by twisted pair cable. Thebaud rate must be set the same for all trip units and the system display.

    Figure 23: System Display Model SD-300

    Personal Computer Workstations

    DB-9M connection to MCA-485 and SY/LINK card. Shielding is grounded at the computer only through the SY/LINK card.

    Where devices are daisy-chained, interconnect shielding, but do not ground the connection. MCT-485 termination device required on last circuit breaker or POWERLOGIC device.

    D 1 0 0 D 1 0 1

    Typical IBM (or IBM compatible) computer

    Belden 8723Twisted Pair

    3 DigitSY/MAXaddress

    Baud rateand

    Typical circuitbreaker withDIGITRIP RMS810D trip unit

    SY/LINK Card

    6035-98162A

    6035-98163

  • 8/9/2019 6035-510A Instruction Manual

    42/72

    DIGITRIP RMS Trip Units Bulletin No. 6035-510A

    Trip Unit Communications: POWERLOGIC DIGITRIP RMS 810D November 1998

    1996 Square D All Rights Reserved34

    Figure 24: System Display Connections

    A virtually unlimited number of personal computers and system displays canbe connected to the power monitoring network. Each has equal access todata from any POWERLOGIC DIGITRIP RMS 810D trip unit connected tothe network. Network Interface Modules (NIMs) or SY/LINK cards (forcomputers) are used to connect to the network.

    Figure 25: POWERLOGIC Network with Personal Computer Workstation and

    System Display

    D 0 0 1

    Note: Ok to mix circuit monitors, POWERLOGIC DIGITRIP 810D Trip Units, and otherPOWERLOGIC devices.

    Shielding is grounded at the computer only through the SY/LINK card.Where devices are daisy-chained, interconnect shielding, but do not ground the connection.

    MCT-485 termination device required on last circuit breaker or POWERLOGIC device.

    Belden 8723Twisted Pair

    3 DigitSY/MAXaddress

    Baud rateand

    Circuit Monitor

    SystemDisplay

    6035-98164

    Personal Computer Workstations and

    System Display Combination

    D O O I D O O 2

    Shielding as is accomplished through the Network Interface Module.Where devices are daisy-chained, interconnect shielding, but do not ground the connection.

    DB-9M connection to MCA-485 and Network Interface Module.

    Typical IBM(or IBM compatible)

    computer

    Belden 8723Twisted Pair

    3 DigitSY/MAXaddress

    Baud rateandTypical DS circuit

    breakers withPOWERLOGICDIGITRIP RMS 810Dtrip units

    SY/LINK Card

    6035-98165A

    SystemDisplay

    NetworkInterfaceModule

    Belden 9463

    To otherPOWERLOGICDIGITRIP 810Dtrip units(max. of 32units total)

  • 8/9/2019 6035-510A Instruction Manual

    43/72

    Bulletin No. 6035-510A DIGITRIPRMS Trip Units

    November 1998 Trip Unit Communications: POWERLOGIC DIGITRIP RMS 810D

    35 1996 Square D All Rights Reserved

    POWERLOGIC communications are based on, and are compatible with, theSY/MAXcommunications system. This system was developed and hasbeen used for critical factory automation applications for many years. ThePOWERLOGIC system uses two levels of communication.

    At the field device level, used by trip units and system displays, an RS-485protocol is used. RS-485 is a very commonly used physical protocol, which

    allows easy connection to a variety of commercially available modems.Typically, a twisted pair cable (Belden 8723 or equivalent) is used at this level.The cable connects devices in a daisy chain fashion. A termination device isinstalled at the final device on the daisy chain (MCT-485). Transmission ratesof up to 19.2 kbaud and distances of up to 10,000 feet are supported.

    A high-speed LAN is used as the backbone of the POWERLOGICcommunication system. Typically, this LAN is the SY/NETnetwork.Square D developed SY/NET especially for rugged industrial environmentsand features high resistance to noise and deterministic access by allconnected devices. Up to 100 NIMs or computers can be connected directlyto the LAN. In addition, several networks can be interconnected. This extendstotal connected device counts into the millions. The cable used mostcommonly is Belden 9463 (or equivalent) twinax cable. Speeds of up to

    500 kbaud and distances of up to 15,000 feet are supported.As an alternative, Square D has pioneered the use of Ethernet in powermonitoring systems. Ethernet can be used in place of SY/NET, and Ethernet

    network interface modules are used in placed of conventional NIMs andSY/LINK cards. Ethernet has the advantages of being faster and morecommonly found in facilities. On the other hand, it was not designed forindustrial use, communications access is non-deterministic, and maximumrun lengths are often shorter. However, Ethernet is a useful option for someusers.

    The DIGITRIP RMS 810D uses microprocessors to measure electricalparameters, continuously ascertain the need for protective action, and meterand communicate circuit values to the outside world. Values for electricalquantities are continually updated and stored in local memory. The values in

    memory can be read and displayed by a variety of devices convenient toplant engineers, electricians, and operators. Display devices include thesystem displays and personal computers described above.

    Information available for remote display includes:

    Status of circuit breaker: closed, open, or tripped

    All protection settings (See PROTECTION SETTINGS on page 12)

    All information displayed in the trip unit window

    Phase and ground or neutral current values

    Power and energy demand parameter values

    The information available through the SY/MAX communication system isgreater than that available locally through the trip unit display. For example,at a system display or personal computer, it is possible to view the presentsystem power factor, the time of trip event, and trip event counter, eventhough these values are not available for local display in the trip unit window.

    Network Connections

    Information Communicated by the

    POWERLOGIC DIGITRIP RMS 810D

  • 8/9/2019 6035-510A Instruction Manual

    44/72

    DIGITRIP RMS Trip Units Bulletin No. 6035-510A

    Trip Unit Communications: POWERLOGIC DIGITRIP RMS 810D November 1998

    1996 Square D All Rights Reserved36

    LEGEND:x = Function included.r = This information can be viewed only remotely by POWERLOGIC.* = Requires optional electrical close or spring release option with circuit breaker, and the trip

    unit may have to be reset before the circuit breaker can close.

    Table 10: POWERLOGIC DIGITRIP RMS 810D Communications

    LI LSI LS LIG LSG LSIG

    REMOTE INFORMATION via Communications Link x x x x x x

    View Circuit Breaker Status:

    OPEN/CLOSED/TRIPPED x x x x x x

    Address Register & Baud Rate x x x x x x

    View Trip Event Values:

    Trip Event Time r r r r r r

    Trip Event Counter r r r r r r

    View Protection Settings:

    Long Time Delay:

    Current Setting (Pickup) x x x x x x

    Time Delay Setting x x x x x x

    Short Time Delay:

    Current Setting (Pickup) x x x x

    Time Delay Setting x x x x

    Opt. I squared T Curve Shape x x x x

    Instantaneous:

    Current Setting (Pickup) x x x x

    DISCriminator (11 x) IN or OUT x x

    Ground Fault:

    Current Setting (Pickup) x x x

    Time Delay Setting x x x

    Opt. I squared T Curve Shape x x x

    View Current Values:

    Phase A Current (Ia) (kA) x x x x x x

    Phase B Current (Ib) (kA) x x x x x x

    Phase C Current (Ic) (kA) x x x x x x

    Ground Current (Ig) (kA) x x x

    Neutral Current (Id) (kA) n n n

    View Power/Energy Values:

    Peak Power Demand (MW) x x x x x x

    Present Power Demand (MW) x x x x x x

    Reverse Power Flow x x x x x x

    Energy Consumption (MWh) x x x x x x

    Reverse Energy Consumption x x x x x x

    View Power Factor Value: r r r r r rView Remote Messages:

    DISC = DISCriminator Trip x x

    EXTT = EXTernal Trip x x x x x x

    GNDT - GrouND Trip x x x

    HILD = High LoaD Alarm x x x x x x

    INST = INStantaneous Trip x x x x

    LDPU = Long-Time Delay Pick-Up x x x x x x

    LDT = Long-Time Delay Trip x x x x x x

    NORM = Normal r r r r r r

    NPOW = Negative POWer Flow x x x x x x

    ORNG = OverRaNGe Trip x x x x x x

    PLUG = Rating PLUG Problem x x x x x x

    SDT = Short-Time Delay Trip x x x x

    NRES = Communications Failure r r r r r r

    TEMP = OverTEMPerature Trip x x x x x xTEST = TEST Ready to Begin x x x x x x

    Remote control via POWERLOGIC commun. x x x x x x

    TRIP (OPEN) Circuit Breaker Command x x x x x x

    CLOSE Circuit Breaker Command * * * * * *

    RESET TRIP UNIT Command x x x x x x

    RESET Demand, Energy, Trip Event x x x x x x