3.takeo to kampot

Upload: ratana-kem

Post on 07-Jul-2018

215 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/18/2019 3.Takeo to Kampot

    1/2

    ELECTRICITE DU CAMBODGE CORPORATE PLANNING AND PROJECT DEPARTMENT TECHNICAL O

    From Bus = TAKEO To Bus = KAMPOT

    From Bus Code = 0 To Bus Code = 0

    CT Ration = 1200/1 VT Ratio = 230/Ö3 : 110/Ö3

    System KV = 230 Distance (km) = 73 No. Circuit = 2  No. Conductor /Ø = 1

    Current Currying Capacity (A) = 842 MW/ Circuit (PF=0.95) = 319

    Conductor Name = DRAKE Arrester Name = GJ-100

    Conductor Type = ACSR  Arrester Type = G.S.W

    Stranding (mm) = 26/4.442 - 7/3.454 Stranding (mm) = 7/4.115

    Total Area (mm²) = 468.6 Total Area (mm²) = 119.73

    Total Diameter (mm) = 28.13 Total Diameter (mm) = 12.35

    GMR = 0 GMR = 0W/km 20 °c = 0.07167 W/km 20 °c = 1.603608118

    XL Ω/km = 0 XL Ω/km = 0

    XC Ω/km = 0 XC Ω/km = 0

    OPGW Name = OPGW 90 Insulator type = Aluminum Polimenia

    OPGW Type = ACS No. of Disc / String = U120BP x 16

    Stranding (mm) = 8/3.7 - 1/6.0 Total Length (mm) = 2336

    Total Area (mm²) = 105.6

    Total Diameter (mm) = 11.59GMR = 0

    W/km 20 °c = 0.8030

    XL Ω/km = 0

    XC Ω/km = 0

    Conductor Conductor

    Ultimate Strenght = * Ultimate Strenght = *

    Maximum Working Tension = * Max. Working Tension = *

    Sage (m) = 13 Sage (m) = *

    arrester wire arrester wire

    Ultimate Strenght = * Ultimate Strenght = *

    Maximum Working Tension = * Max. Working Tension = *

    Sage (m) = 10.4 Sage (m) = *

    %SAG match = * %SAG match = *

    TENSION AND SAG 30 °C TENSION AND SAG 90 °C

    Transmsmission line Parameter Calculation

    TAKEO TO KAMPOT

    TYPE OF CONDUCTOR ARRESTER WIRE

    OPGW INSULATOR  

    SUBSTATION SECTION 3/31/

  • 8/18/2019 3.Takeo to Kampot

    2/2

    ELECTRICITE DU CAMBODGE CORPORATE PLANNING AND PROJECT DEPARTMENT TECHNICAL O

    OPGW OPGW

    Ultimate Strenght = * Ultimate Strenght = *

    Maximum Working Tension = * Max. Working Tension = *

    Sage (m) = 10.4 Sage (m) = *

    %SAG match = * %SAG match = *

    R1 (W) = * X1 (W) = *

    R0 (W) = * X0 (W) = *

    B1 (S) = * B0 (S) = *

    Y1 = 26 X1A = 4.6

    Y2 = 31.5 X1B = 4.6

    Y3 = 37 X1C = 4.6

    Y4 = 42.5 X1G = 4.6

    X2A = 4.6

    X2B = 4.6

    X2C = 4.6

    X2G = 4.6

    LINE CONSTANT PARAMETER 

    TOWER CONFIGURATION

    G1

    Y1

    Y2

    Y3

    X1A

    X1B

    X1C

    X1G

    X2C

    X2A

    X2B

    X2GY4

    OPGW

    SUBSTATION SECTION 3/31/