8/6/2019 3. VRF Refrigerant Cycle Ok
1/34
-
8/6/2019 3. VRF Refrigerant Cycle Ok
2/34
Contents ni dung
D3 R410A system h thng D3 R410A
V4 R410A system h thng V4 R410A
-
8/6/2019 3. VRF Refrigerant Cycle Ok
3/34
-
8/6/2019 3. VRF Refrigerant Cycle Ok
4/34
D3 system 1.Internal structure cu toAuxiliary 4-way valve
Van o chiu ph
Oil balance pipe between compressorsng cn bng du gia cc my nn
2 EXVs van tit lu
Gas-liquid separatorBnh tch lng
Gas pipeng thp p
Digital compressorMy nn k thut s
Liquid pipeng cao p
Gas balance pipe 1ng cn bng gas1
Gas balance pipe 2ng cn bng gas2
Constant compressorMy nn c nh
Constant compressorMy nn c nh
Liquid accumulatorBnh cha lng
Outdoor unitMy ngoi
Main 4-way valve
Van o chiu chnh
-
8/6/2019 3. VRF Refrigerant Cycle Ok
5/34
D3 system 2.Cooling cycle qu trnh lm lnh
Liquid side
Gas sideng thp p
Gas balance 2Cn bng gas2
Gas balance 1Cn bng gas1
Cooling cycleQu trnh lm lnh
Heat exchanger (Condenser)trao i nhit (dnngng)
Main 4-way valveVan o chiu
chnh
Gas-liquid separatorBnh tch lng
Liquid accumulatorbnh cha lng
OS OS OS
D F1 F2
-
8/6/2019 3. VRF Refrigerant Cycle Ok
6/34
Liquid sideng thp p
Gas side
Gas balance 2cn bng gas2
Gas balance 1cn bng gas1
D3 system 3.Heating cycle qu trnh lm nhitHeating cycle
Qu trnh lm nhit
Heat exchanger (Evaporator)trao i nhit(dn ngng)
Main 4-way valveVan o chiu chnh
Gas-liquid separatorbnh tch lng
Liquid accumulatorbnh cha lng
OS OS OS
D F1 F2
-
8/6/2019 3. VRF Refrigerant Cycle Ok
7/34
D3 system 4.Key components thnh phn chnh
From indoor
Gas balance 2cn bng gas2
Gas balance 1cn bng gas1
Gas-liquid separatorbnh tch lng
SV2
SV5
To indoor
Liquid accumulatorbnh cha lng
SV6 SV1
EXV
Oil separatorsbnh tch du
Compressorsmy nn
SV3
Heat exchangertrao i nhit
ST1 ST2
-
8/6/2019 3. VRF Refrigerant Cycle Ok
8/34
D3 system 5.Oil Control iu khin du
Part 1 phn 1
Oil separatorsbnh tch du
Compressorsmy nn
-
8/6/2019 3. VRF Refrigerant Cycle Ok
9/34
D3 system 5.Oil Control iu khin du
Oil Separator is used to separate oil from
high pressure & temperature gas refrigerant
that is pumped out from compressor. Bnh
tch du c dng tch lng du
nhit cao v p sut cao c ln vi hi gas
t my nn nn ra .
The separation efficiency is up to 99%, it
makes the oil return back to each compressor
very soon. Hiu qu c tch ln n 99%
,n lm cho lng du v my nn rt sm .
Oil separator
bnh tch duOutlet u ra
Oil return pipe
ng hi du
Inlet u vo
-
8/6/2019 3. VRF Refrigerant Cycle Ok
10/34
D3 systemOil separators
tch du
CompressorsMy nn
5.Oil Control iu khin du
High pressure & temperatureliquid
Dch nhit v p sut cao
Low pressure & temperaturegas
Gas p sut v nhit thp
Refrigerant oilgas du
Oil balance between compressorsCn bng du gia cc my nn
Oil separationtch du
Oil balanceCn bngdu
Oil returnHi du
Oil balancecn bng du
-
8/6/2019 3. VRF Refrigerant Cycle Ok
11/34
D3 system 5.Oil Control iu khin du
The oil return program starts when the system has continued operating for 4 hours. Chng
trnh hi du bt u khi h thng hot ng c lin tc trong 4 ting .
The program will last for 3 minutes. Chng trnh hi du s t nht l 3 pht
All the outdoor EXV open to 480 pulse and SV6 is on. Tt c van EXV ca my ngoi m 480
v van SV6 l m
Action of indoor Fan and EXV: hnh ng ca qut my trong v EXV
Indoor units that is in standby mode or fan mode:my trong ch ch hay ch qut
Indoor EXV action: Open to 300 pulse Van EXV my trong hnh ng : m 300
Indoor units that is in operating mode: My trong hot ng ch Keep fan speed and EXV open degree unchanged gi tc qut v m van EXV
khng thay i
Indoor fan action: Low speed in cooling, anti-cold air mode in heating mode Hnh
ng qut my trong : tc thp ch lm lnh , chng ch m ch lm nhit
Oil Return program (Auto) chng trnh hi du(t ng)
-
8/6/2019 3. VRF Refrigerant Cycle Ok
12/34
SV3
Heat exchangertrao i nhit
ST2ST1
D3 system 6.Heat-exchanger control i u khi ntrao i nhitPart 2 phn 2
-
8/6/2019 3. VRF Refrigerant Cycle Ok
13/34
Main 4-way valve (ST1): van o chiu chnh (ST1) :
Use to switch the system to cooling mode or heating
mode. S dng chuyn i h thng qu trnh
lm lnh hay qu trnh lm nhit
D3 system 6.Heat-exchanger control i u khi ntrao i nhit
Auxiliary 4-way valve (ST2): van o chiu ph(ST2):
Use to shut off half of the heat exchanger for the
part load condition. Dng tt mt na dn
trao i nhit cho cc iu kin ti phn
ST1 and ST2
-
8/6/2019 3. VRF Refrigerant Cycle Ok
14/34
-
8/6/2019 3. VRF Refrigerant Cycle Ok
15/34
To indoor unitFrom compressorTo indoor unitti my trong
From compressorT my nn ti
D3 system 6.Heat-exchanger control i u khi ntrao i nhitCooling mode: FULL LOAD condition
Ch lm lnh : iu kin y ti
Refrigerant directionHng mi cht i
4-way valve (ST2) OFFVan o chiu (ST2) tt
Solenoid valve (SV3) OFFVan in t (SV3) tt
-
8/6/2019 3. VRF Refrigerant Cycle Ok
16/34
To indoor unitFrom compressor
D3 system 6.Heat-exchanger controlCooling mode: LOW LOAD conditionCh lm lnh : iu kin ti thp
Refrigerant directionhng mi cht i
To indoor unitti my trong
From compressorT my nn ti
In cooling modetrong ch lm lnh
When the indoor unit capacity demand is less than 12, ST2 turns ON to Shut off half of the heat exchanger. Khi m my trong c cng
sut di 12, ST2 m lt tt mt na dn trao i nhit
4-way valve (ST2) ONVan o chiu (ST2) m
Solenoid valve (SV3) OFFVan in t (SV3) tt
-
8/6/2019 3. VRF Refrigerant Cycle Ok
17/34
From indoorunit
To compressorFrom indoorunit t my
trong ti
To compressorti my nn
D3 system 6.Heat-exchanger controlHeating mode: FULL LOAD condition
Ch lm nhit : iu kin y ti
Refrigerant directionHng mi cht i
4-way valve (ST2) OFFVan o chiu (ST2) tt
Solenoid valve (SV3) ONVan in t(SV3) m
In heating modetrong ch lm nhit
SV3 is open when the average temperature of all indoor coils is less than 46. SV3 c m ra khi nhit trung
bnh ca tt c my trong nh hn 46.
-
8/6/2019 3. VRF Refrigerant Cycle Ok
18/34
From indoorunit
To compressorFrom indoorunit t my
trong ti
To compressorTi my nn
D3 system 6.Heat-exchanger control i u khi ntrao i nhitHeating mode: LOW LOAD condition
Ch lm nhit : iu kin ti thp
Refrigerant directionHng mi cht i
In heating modetrong ch lm nhitWhen the average temperature of all indoor coils is up to 52, SV3 turns OFF to Shut off half of the heat exchanger. Khi nhit
trung bnh ca tt c cun dy my trong ln n 52th SV3 tt lt tt mt na dn trao i nhit .
4-way valve (ST2) OFFVan o chiu(ST2) tt
Solenoid valve (SV3) OFFVan in t (SV3) tt
-
8/6/2019 3. VRF Refrigerant Cycle Ok
19/34
D3 system 7.Refrigerant control
Liquid accumulatorbnh cha lng
SV6 SV1
EXV
To indoor timy trong
Part 3 phn 3
-
8/6/2019 3. VRF Refrigerant Cycle Ok
20/34
D3 system 7.Refrigerant control i u khi n micht lnh
By adopting double outdoor EXVs, the systems refrigerant flow volume can be precisely regulated, and the regulation accuracy
is up to 960 degree. The discharge temperature of compressor can be controlled to maximize the efficiency of the compressor. Bng
vic p dng 2 van EXV vi my ngoi , khi lng lu lng mi cht lnh c khng ch chnh xc ,v c khng ch
chnh xc ln n 960 ,nhit nn ca my nn c th c iu khin ti a ha hiu qu ca my nn
When the outdoor unit is power on, the two EXVs firstly close with 700 pulse, then they open with 350 pulse and then standby,
but two EXVs action are not at the same time. Khi mays ngoi m ngun in th 2 van EXV trc ht ng vi 700 ,sau
chng m 350 v sau ch ,nhng 2 van EXV khng phi hnh ng cng 1 lc
Double EXVs
Double EXVs2 van EXV
Double EXVs 2 van EXV
-
8/6/2019 3. VRF Refrigerant Cycle Ok
21/34
D3 system 7.Refrigerant control i u khi n micht lnh
SV6 SV1
SV1: When the outdoor unit is startup, the SV1 opens immediately. When the outdoor unit stops , the SV1
closes immediately. Khi my ngoi khi ng ,van in t SV1 s m ra ngay . Khi my ngoi dng ,van in
t SV1 v ng ngay
SV6 is used for protecting the compressors. SV6 c dng bo v my nn
It opens only when the compressors discharge temperature is over-high. N ch m khi nhit nn
ca my nn l qu cao
Closes when the unit is standby or system is in heating mode. N ng khi h thng ang ch ch
hay ch lm nhit
SV1 and SV6
-
8/6/2019 3. VRF Refrigerant Cycle Ok
22/34
D3 system 7.Refrigerant control
It is used to store the overmuch liquid refrigerant. N dng lu tr mi cht c qu lnh thnh
lng .
Comparing with the gas-liquid separator: so snh vi bnh tch lng
Liquid accumulator accumulates unwanted liquid refrigerant. Bnh cha lng cha mi cht
khng mong mun .
Gas-liquid separator is used to store the liquid refrigerant for protecting the compressor from liquid
hammer. Bnh tch lng dng cha cht lng bo v my nn ,khng cho lng trc tip t dn
bay hi a v my nn .
Liquid accumulator bnh cha lng
Liquid accumulator
-
8/6/2019 3. VRF Refrigerant Cycle Ok
23/34
D3 system 7.Refrigerant control
Gas-liquid separatorBnh tch lng
SV2
SV5
From indoorT mytrong ti
Gas balance 2Cn bng
gas2
Gas balance 1Cn bng
gas1
Part 4 phn 4
-
8/6/2019 3. VRF Refrigerant Cycle Ok
24/34
D3 system 7.Refrigerant control
Connect the gas-liquid separators by a communicating pipe between modules and the pressure of system will help refrigerant
equal distribution, guarantee safety operation. Kt ni bnh tch lng vi 1 ng ng cn bng gas 2 (ni gia bnh tch lng
ca my ny vi bnh tch lng ca my kia.) s gip cn bng mi cht lnh ,m bo an ton hot ng .
It is used to store the liquid refrigerant. N dng lu tr mi cht lnh
From indoor
To compressor
Gas balance pipe 2
Gas-liquid separator
INOUT
Gas-liquid separator bnh tch lng
-
8/6/2019 3. VRF Refrigerant Cycle Ok
25/34
D3 system 7.Refrigerant control
From indoor From compressor
To compressor
Gas balance pipe
SV2
SV5
SV5:
It opens after the outdoor unit start heating 5 minutes, for lifting the suction pressure. N m ra sau khi my ngoi khi
ng ch lm nhit 5 pht ,dng tng p sut htIt is used in defrost mode, for making the defrosting process more quickly. N dng trong ch x , n lm cho qu
trnh x nhanh hn
SV2: It is used to regulate the discharge temperature, when the discharge temperature is higher than 105, SV2 opens
immediately. N dng iu tit nhit nn ,khi nhit nn ln cao hn 105,SV2 s m ra ngay
About defrost cycle:v chu k x
It starts when any modules condenser temp.
(T3) < 0, last for 40minutes. N bt u khi c
bt k nhit dn ngng no (T3)
-
8/6/2019 3. VRF Refrigerant Cycle Ok
26/34
D3 system 8.Refrigerant balance cn bng gas
Gas balance pipe 1
Cn bng gas1
Gas balance pipe 2Cn bng gas2
Between compressorsNi gia cc my nn vi nhau
Between gas-liquid separatorsNi gia cc bnh tch lng vi
nhau
Gas balance pipe
ng cn bng gas
-
8/6/2019 3. VRF Refrigerant Cycle Ok
27/34
V4 R410A systemV4 R410A systemH thng V4 R410AH thng V4 R410A
VRF refrigerant cycle system
-
8/6/2019 3. VRF Refrigerant Cycle Ok
28/34
V4 system Difference between V4&D3Khc nhau gia V4&D3D3
-
8/6/2019 3. VRF Refrigerant Cycle Ok
29/34
V4 system Difference between V4&D3Khc nhau gia V4&D3
To indoorti my trong
From indoorT my trong
Gas balanceCn bng gas
Oil balanceCn bng du
1 Oil separator
Tch du 1
2
SV44
3
V4
CompressorsMy nn 1
-
8/6/2019 3. VRF Refrigerant Cycle Ok
30/34
V4 system 1.DC inverter compressorMy nn bin tn DC
Discharge pipeng nn
Suction pipe
ng ht
PWM valve
Discharge Pipe
ng nn
Suction Pipe
ng ht
Compressors of V4 and D3
V4 DC inverter compressor
(Hitachi)
D3 digital scroll compressor
(Copeland)
Oil return pipeng hi du
-
8/6/2019 3. VRF Refrigerant Cycle Ok
31/34
-
8/6/2019 3. VRF Refrigerant Cycle Ok
32/34
V4 system 3.Oil balance
Oil balance pipeng cn bng du
Gas balance pipeng cn bng gas
Between oil separatorsGia cc bnh tch du vi nhau
Between gas-liquid separatorsGia cc bnh tch lng vi nhau
Oil balance pipe
ng cn bng du
-
8/6/2019 3. VRF Refrigerant Cycle Ok
33/34
V4 system 4.SV4 valve
SV4: Oil return valve. Van hi du
Opens when the inverter compressor is running for 5 minutes and then closes 15 minutes later. (For the
system has only one outdoor unit) m ra khi my nn bin tn m ra chy c 5 pht,v ng li sau 15
pht (dng cho h thng ch c 1 my ngoi )
Every 20 minutes, SV4 of each outdoor unit opens for 3 minutes. (For the system has more than one
outdoor units) v mi 20 pht ,van SV4 ca my ngoi m ra 3 pht (dng cho h thng nhiu hn 1 my
ngoi )
Gas balanceCn bng gas
Oil balanceCn bng du
SV4
SV4
-
8/6/2019 3. VRF Refrigerant Cycle Ok
34/34