Q19928 - 2711-NC21 and 2711-NC22 cables for the PanelView Last Modified: 07/16/2002 Previously Released as #13911 The 2711-NC21 and NC22 cables are 9 pin to 8 pin mini-din cables designed originally to connect a PV300 Keypad or a xxx5, xxx9 or xxx16 terminal directly to a ML1000, 1200 or 1500 processor. They only differ by the length: The NC21 is 16.4ft (5 meter) The NC22 is 49 ft (15 meter) The pinout of this cable is: PV AIC+, ML1000 9 pin 8 pin (Rt. Angle) DCD 1 -------- 5 DCD TXD 2 -------- 4 RXD RXD 3 -------- 7 TXD GND 5 -------- 2 GND 4 ---| 6 ---| RTS 7 -------- 3 RTS ; RTS/CTS are not crossed. They must be crossed when used with a Belden network. CTS 8 -------- 6 CTS Problem: The problem is when the NC21/NC22 is connected to an AIC+ and a Belden cable is also connected. The handshaking pins are required in this setup and the handshaking pins not crossed. They are required to be crossed for handshaking to occur with the Belden cable. If Belden is not used, the handshaking pins are not required. Alternatives: Use a 1761-CBL-PM02 or a 2711-CBL-PM05 with a null modem adapter. Or, add a 9 to 9 pin adapter to the NC21 cable with pins 7 and 8 crossed. But don't re- cross pins 2 and 3, they are already crossed. May 2002: New cables that correct the handshaking pins are available as Ser A Rev B. Documentation General Category: s EOI Product(s): PanelView Catalog #: 2711ND3 Series / Revision: Subject (Keyphrases): Summary of Technote Information: Page 1 of 2 Documentation Technote: 2711-NC21 and 2711-NC22 cables for the PanelView 6/29/2006 http://domino.automation.rockwell.com/applications/kb/RAKB.nsf/0/A4350EB6186504DF852...

Upload: abel524572144

Post on 27-Oct-2015

67 views

Category:

Documents


15 download

DESCRIPTION

ConfigurCION DE CABLE 2711 NC 21/22

TRANSCRIPT

Page 1: 2711 NC21 and 2711 NC22 Cables for the PanelView

Q19928 - 2711-NC21 and 2711-NC22 cables for the PanelView

Last Modified: 07/16/2002

Previously Released as #13911

The 2711-NC21 and NC22 cables are 9 pin to 8 pin mini-din cables designed originally to

connect a PV300 Keypad or a xxx5, xxx9 or xxx16 terminal directly to a ML1000, 1200 or

1500 processor.

They only differ by the length: The NC21 is 16.4ft (5 meter) The NC22 is 49 ft (15 meter)

The pinout of this cable is: PV AIC+, ML1000 9 pin 8 pin (Rt. Angle) DCD 1 -------- 5 DCD TXD 2 -------- 4 RXD RXD 3 -------- 7 TXD GND 5 -------- 2 GND 4 ---| 6 ---| RTS 7 -------- 3 RTS ; RTS/CTS are not crossed. They must be crossed when used with a

Belden network. CTS 8 -------- 6 CTS

Problem: The problem is when the NC21/NC22 is connected to an AIC+ and a Belden cable is also

connected. The handshaking pins are required in this setup and the handshaking pins not

crossed. They are required to be crossed for handshaking to occur with the Belden cable.

If Belden is not used, the handshaking pins are not required.

Alternatives: Use a 1761-CBL-PM02 or a 2711-CBL-PM05 with a null modem adapter.

Or, add a 9 to 9 pin adapter to the NC21 cable with pins 7 and 8 crossed. But don't re-

cross pins 2 and 3, they are already crossed.

May 2002: New cables that correct the handshaking pins are available as Ser A Rev B.

Documentation

General Category: s EOIProduct(s): PanelViewCatalog #: 2711ND3

Series / Revision:Subject

(Keyphrases):Summary of

Technote Information:

Page 1 of 2Documentation Technote: 2711-NC21 and 2711-NC22 cables for the PanelView

6/29/2006http://domino.automation.rockwell.com/applications/kb/RAKB.nsf/0/A4350EB6186504DF852...

Page 2: 2711 NC21 and 2711 NC22 Cables for the PanelView

The new pinout of this cable is: PV AIC+, ML1000 9 pin 8 pin (Rt. Angle) DCD 1 -------- 5 DCD TXD 2 -------- 4 RXD RXD 3 -------- 7 TXD GND 5 -------- 2 GND 4 ---| 6 ---| RTS 7 -------- 6 CTS ; RTS/CTS are now crossed with a Ser A Rev B cable. CTS 8 -------- 3 RTS

Related Links:

DISCLAIMER This knowledge base web site is intended to provide general technical information on a particular subject or subjects and is not an exhaustive treatment of such subjects. Accordingly, the information in this web site is not intended to constitute application, design, software or other professional engineering advice or services. Before making any decision or taking any action, which might affect your equipment, you should consult a qualified professional advisor. ROCKWELL AUTOMATION DOES NOT WARRANT THE COMPLETENESS, TIMELINESS OR ACCURACY OF ANY OF THE DATA CONTAINED IN THIS WEB SITE AND MAY MAKE CHANGES THERETO AT ANY TIME IN ITS SOLE DISCRETION WITHOUT NOTICE. FURTHER, ALL INFORMATION CONVEYED HEREBY IS PROVIDED TO USERS "AS IS." IN NO EVENT SHALL ROCKWELL BE LIABLE FOR ANY DAMAGES OF ANY KIND INCLUDING DIRECT, INDIRECT, INCIDENTAL, CONSEQUENTIAL, LOSS PROFIT OR DAMAGE, EVEN IF ROCKWELL AUTOMATION HAVE BEEN ADVISED ON THE POSSIBILITY OF SUCH DAMAGES. ROCKWELL AUTOMATION DISCLAIMS ALL WARRANTIES WHETHER EXPRESSED OR IMPLIED IN RESPECT OF THE INFORMATION (INCLUDING SOFTWARE) PROVIDED HEREBY, INCLUDING THE IMPLIED WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE, MERCHANTABILITY, AND NON-INFRINGEMENT. Note that certain jurisdictions do not countenance the exclusion of implied warranties; thus, this disclaimer may not apply to you.

Copyright © 2006 Rockwell Automation. All rights reserved.

Close Print this Page

Page 2 of 2Documentation Technote: 2711-NC21 and 2711-NC22 cables for the PanelView

6/29/2006http://domino.automation.rockwell.com/applications/kb/RAKB.nsf/0/A4350EB6186504DF852...