21-ht ele & panel boq with cost

Upload: tceterex

Post on 08-Aug-2018

232 views

Category:

Documents


1 download

TRANSCRIPT

  • 8/22/2019 21-Ht Ele & Panel Boq With Cost

    1/32

    Date : 25th SEPTMBER 2011

    Project : TOWER C Prestige Shantiniketan .

    Consultanc : Sripeksha Engineering Consultancy Services Pvt. Ltd., Bangalore

    Subject : Electrical Work - SUMMARY

    Sl. No Description Amount

    I PART -A

    1 H T WORKS 14514660

    II PART -B

    1 Internal Electrification Work 23005275

    II PART -C

    1 Bus Bar Trunking and Bus Duct 18515500

    IV PART-D

    1 M V PANELS 14405100

    TOTAL 70,440,535

    Add WC Tax @ . . . %

    Grand total

    Note ED exemption for HT panel, LT panel

    Transformer, BBT and Capcitor banks

    Import option for BBT, HT and LT switchgears

    Signature & Seal of Tenderer

    130 S E C S P L

  • 8/22/2019 21-Ht Ele & Panel Boq With Cost

    2/32

    Subject : Eectrica Wor - Part - A H T wor s

    Note :

    a All materials & work shall be as per relevant

    standards, EB, Electrical Inspectorate and

    local approving agency's rules, requirementand local practice of BESCOM/KPTCL.

    b The vendor to submit detailed shop drawings

    for approval BEFORE manufacturing

    Processing for H T RMU / Metering cubical,

    HT switchgear cubical,Transformer and MV Panel.

    Working Dwg., Cable Routing, wiring, rising main,

    earthing etc., to be submitted.

    C For Detail Refer schematic dwg

    D BESCOM/ CEIG sanction/approval for the entire electrical

    installation is to be included and the work

    shall be executed accordingly.

    e The rate to exclude Civil Works such as construction of

    f The rate shall include for civil works such as for

    cable laying, fence, etc. are to be INCLUDED

    whether explicitly mentioned or not under the

    respective item.

    g Customs Duty benefit for imported items like

    BBT and Switch gear.

    h ED benefit for cables, HT & LT panel, BBT

    and DBs

    i The clients reserve the right to supply major

    equipment such as Trr., RMU, CABLE , Light

    fixtures, etc and thecontractor shall install the

    same at the erection rates quoted by him.

    Sl. No Description Unit Rate Qty Amount

    1.0.0 11kV HT PANELS

    Supply, transport to Site, Loading / unloading

    testing and commissioning of 11kV, 500MVA,

    50Hz, Outdoor / Indoor, extensible type HT

    switchgear as per detailed BOQ, enclosed

    specification & data sheet and relevant

    standards. The rate shall include providing necessaryreadymade cable trench and ISMC channels for

    erecting panel

    1.1.1 RMU panel-1 as per specifications & data sheet

    VCB type Main RMU Panel 1 & 2 HT RMU 500

    MVA 11kV SF6/Vaccum Circuit Breaker

    extendable OUTDOOR Weather Proof Cubicle

    type. VCB shall be draw-out type

    Locn. : RMU yard

    Incoming Panels (OD) - 2 Nos. each

    Outgoing Panels (VL) - 1 Nos.each :

    Supply Sets 800000 1 800000

    Errection Sets 20000 1 20000

  • 8/22/2019 21-Ht Ele & Panel Boq With Cost

    3/32

    1.2.0 HT METERING CUBICLE ( OUT DOOR TYPE)

    S I T & C of 11kV Metering Cubicle as per Bescom

    rules /requirements (In case the Metering C ubcle

    supplied by BESCOM , the same shall be erected at

    the erection rate quoted below). The panel shall

    be outdoor type made out of 14/16G CRCA sheet

    with sealing and viewing arrangements. Thecubicle shall comprise of 400/5A 11kV 500MVA CTs

    and 11000/110V 100VA Potential Transformer, 25 x

    6mm sleeved Cu bus bar, terminals and trivector

    meter. The CTs, PTs and the meters shall be

    calibrated by authorised agency

    1.2.1 11kV Metering Cubicle

    Supply Sets 125000 1 125000

    Erection Sets 15000 1 15000

    1.2.2 H T PANEL - 1 ( 3 Panel OUT DOOR type)

    Locn. : At Metering Yard

    Incomer - 1 nos As per Annexture-1

    Out going - 2nos As per Annexture-1 Supply Sets 1600000 1 1600000

    Erection Sets 25000 1 25000

    1.2.3 HT EB/DG PANEL - 2 ( 9 Panel OUT DOOR type)

    Locn. : At Metering Yard

    Incomer - 4 nos As per Annexture-1

    Out going - 4nos As per Annexture-2

    Bus-coupler- 1nos As per Annexture-1

    Supply Sets 4500000 1 4500000

    Erection Sets 50000 1 50000

    1.3.0 11kV HT XLPE U/g CABLE

    Supply, installation, testing and

    commissioning of 11kV XLPE Al condr.armoured u/g cable. The rate shall exclude

    excavation providing brick/ tile and sand

    protection, back filling, compacting &

    levelling the surface for cables laid outdoor

    1.3.1.1 3c x 400 sqmm. Al conductor A2XFY

    Supply Mts 1500 2000 3000000

    Erection Mts 100 2000 200000

    1.3.1.2 3c x 240 sqmm. Al conductor A2XFY

    Supply Mts 1150 150 172500

    Erection Mts 90 150 13500

    1.3.1.3 3c x 185 sqmm. Al conductor A2XFy

    Supply Mts 860 RO

    Erection Mts 80 RO

    1.3.2 XLPE Cable Joints/ End Termination

    Supply and making HT-A2XFY heat shrink

    able Raychem cast UG cable termination

    for the above cables with suitable copper

    heavy duty lugs all as per the manufacture

    details & as per BESCOM specification

    complete

    1.3.2.1 Pot outdoor type -3C x 400 sqmm.

    Supply Sets 16500 2 33000

    Erection Sets 2100 2 4200

  • 8/22/2019 21-Ht Ele & Panel Boq With Cost

    4/32

    1.3.2.2 Pot Indoor type -3C x 400 sqmm.

    Supply Sets 15550 14 217700

    Erection Sets 2000 14 28000

    1.3.2.3 Pot Indoor type - 3C x 240 sqmm.

    Supply Sets 10000 6 60000

    Erection Sets 1750 6 10500

    1.3.2.4 Pot Indoor type - 3C x 185 sqmm.

    Supply Sets 8000 RO

    Erection Sets 1450 RO

    2.2.0 POWER TRANSFORMER

    S,T,C of 2500 kVA, oil filled type, 11000 / 415 V,

    DyN 11 distributionTransformer with COPPER

    WINDING along with OLTC and allaccessories as

    per enclosed specifications. The rate shall include

    necessary SSM foundation including PCC at the top

    and bottom and railing.

    2.2.1 2500 kVA

    Erection Sets 25000 3 75000

    3.0.0 EARTHING

    EARTH STATIONS

    S I T & C of earth station as per IS3043, with

    proper earth lead connection arrangements. Rate

    shall include all materials, excavation, refilling and

    compacting providing 450 x 450 x 600mm brick

    masonry GI funnel, salt and charcoal, 6mm thick

    hinged type chamber cover with frame etc.,

    complete. The GI funnel and tapping connection

    shall not be greater than 10" from the finished

    floor level

    3.1.1 With 600 x 600 x 3mm COPPER plate electrode SET 11500 6 69000

    3.1.2 With 100 dia CI Pipe electrode SET 6900 8 55200

    3.2.0 EARTH STRIPS

    Supply and laying earth strips 0.3M below ground/

    exposed including connections by welding /BRASSING/

    The Joint Shall Be treated with anti corressive paint.

    Cu. Flat

    3.2.1 75 X 10mm Cu flat Mts 2875 10 28750

    3.2.2 50 X 6mm Cu flat Mts 1610 500 805000

    3.2.5 50 X 6mm braided Cu flexible with end terminal Mts 2500 4 10000

    3.3.0 2mm PVC sleeve for

    3.3.1 75 X 10mm Cu flat . Mts 46 10 460

    3.3.2 50 X 6mm Cu flat . Mts 35 500 17500

    3.4.0 GI Flat

    3.4.1 100 X 10 mm GI flat . Mts 450 500 225000

    3.4.2 50 X 6mm GI flat . Mts 250 100 25000

    4.1.0 Fencing

    Providing 12G GI chain link fence of 2.5M high withnecessary MS angle, 1 no. 1.2 M wide gate, 100

  • 8/22/2019 21-Ht Ele & Panel Boq With Cost

    5/32

    mm gravel, brick pedestal for inter mittent angle

    support, etc., complete for HT yard & Transformer

    yard. The entire job shall be to the requirements

    of Electrical Inspectorate

    4.1.1 For TFR yard. Metering and rmu yard. Mts 4100 120 492000

    5.1.0 SAFETY ITEMS

    5.1.1 1M wide with ISI mark 11kV grade rubber mat. Mts 920 8 7360

    5.1.2 Shock and First Aid charts in T/W frame. Nos 350 2 700

    5.1.3 Danger Board 4" X 6" 11kV /415vgrade . Nos 170 4 680

    5.1.4 Rubber Gloves 11kV rated . Nos 860 4 3440

    5.1.5 Sand filled fire marked buckets with stand. Nos 1850 2 3700

    5.1.6 11kV marked CI cable route marker with 450mm

    long angle pedestal. The unit shall be grouted in

    the earth with concrete Nos 510 30 15300

    5.1.7 CI Earth marker with angle pedestal. The unit

    shall be grouted in the earth with concrete Nos 290 14 4060

    5.1.8 Drawing Display board suitable for AO size of

    Drawing with Lamination Sets 2900 1 2900

    5.1.9 AS BUILT' drawings of the total work executed,using AutoCAD-R14, on CDs and 4 sets of

    blue prints on 1:50 scale, and 1 set of plots ontracing cloth Sets 25000 1 25000

    5.2.0 L T Control Cables

    Supply, laying, testing & commissioning of below

    listed PVC insulated, PVC sheathed steel

    armoured copper control cable. The rate shall

    exclude eath excavation and brick protection.

    5.2.1 4C x 4 sqmm Mts 170 500 85000

    5.2.2 4C x 2.5 sqmm Mts 170 500 85000

    5.2.2 6C x 2.5 sqmm Mts 170 600 102000

    5.2.2 12C x 2.5 sqmm Mts 350 500 175000

    5.2.2 14C x 2.5 sqmm Mts 350 750 262500

    5.2.3 16C x 2.5 sqmm Mts 400 500 200000

    5.2.4 24C x 2.5 sqmm Mts 510 750 382500

    5.3.0 End termination of below listed cables using

    . brass gland copper lugs

    5.3.1 4C x 4 sqmm MtS 150 10 1500

    5.3.2 4C x 2.5sqmm MtS 140 10 1400

    5.3.3 4C x 2.5 sqmm Mts 170 10 1700

    5.3.4 6C x 2.5 sqmm Mts 170 10 1700

    5.3.5 12C x 2.5 sqmm Mts 350 10 3500

  • 8/22/2019 21-Ht Ele & Panel Boq With Cost

    6/32

    5.3.6 14C x 2.5 sqmm MtS 350 10 3500

    5.3.7 16C x 2.5 sqmm MtS 400 10 4000

    5.3.8 24C x 2.5 sq mm MtS 520 8 4160

    6.0 CIVIL WORK FOR CABLE LAYINGExcavation, refilling, consolidating,

    compacting of earth excluding in hard rock

    upto a depth as listed below. Consolidation

    shall be carried out in layer by sufficcient

    watering and allowing sufficient time for

    settelment

    6.1.1 Earth excavation upto a depth of 1.0 M for

    cable / pipe, refilling, consolidating,

    compacting, brick and sand protection for

    cables. Bricks and sand protections. Cmt. 250 200 50000

    61.2 Earth excavation upto a depth of 1.0 M for

    cable / pipe, refilling, consolidating and

    compacting Cmt. 350 60 21000

    6.1.3 Supply and laying of following size NP2 RCC

    Hume pipes with collars, cementing of joints,

    etc.

    6.1.3.1 150mm dia Mts 265 150 39750

    6.1.3.2 300mm dia Mts 500 200 100000

    7 Professional Fee for liasion work

    7.1.1 Preparation of drawing for getting approvals duly

    interacting with consultants, statutory boards CEIG/EB

    and local authority for getting power in Phase wise on

    supply from EB. the charges shall include preparation

    of drawing, filing application, getting the power

    sanction, clearence approval of drawings on HT side

    from BESCOM arranging site visit, getting the

    installation service. All statutory deposits / fees shall

    be paid by client L/s 250000 1 250000

    GRAND -TOTAL OF HT WORK 14514660

  • 8/22/2019 21-Ht Ele & Panel Boq With Cost

    7/32

    Subject : Electrical Work - Part - B Internal Electrification Work

    SL.NO. DESCRIPTION UNIT RATE Qty AMOUNT

    NOTE :

    1) All materials & work shall be as per IS

    standards, EB and Inspectorate rules & local

    practice

    2) Final shop floor drawings to be prepared by

    the vendor before execution of the work &

    approval to be taken from the consultant /

    client

    3) Colour conduits should be used for data, raw

    power, UPS & access control as listed raw

    power, UPS & access control as listed below

    coding

    a) Data - Gray

    b) Raw Power - Blue

    c) UPS - Black

    d) Fire Alarm - Red

    e) CCTV, Access Control - White

    Clients reserve the right to supply items such

    as light fittings, etc. for which the Contractor

    shall under take erection at the rates quoted

    by him in the tender below.

    1 MV CABLES

    ALUMINIUM CABLES

    Supplying, laying, testing and commissioning of

    XLPE/PVC insulated FRLS PVC sheathed/PVC

    sheathed, Al/CU. conductor steel armoured 1100V

    grade cable. The cable shall be laid under ground / on

    wall / in pipe / trench as required. For cables laid

    underground - the rate shall exclude earth excavation,

    providing brick and sand protection. refilling,

    compacting etc. For cables laid on wall / on tray /

    inpipe / trench - the rate shall including necessary

    clamping arrangements.

    Standards applicable For below cable

    A2XFY/2XFY/2XWY - IS 6098 PART II

    YY/YFY/AYFY/YWY - IS 1554 PART I

    1.1.1 3.5c x 300 sqmm A2XFY cable.Supply M 850 3000 2550000

    Laying M 60 3000 180000

    1.1.2 3.5c x 240 sqmm A2XFY cable.

    Supply M 600 550 330000

    Laying M 50 550 27500

    1.1.3 3.5c x 120 sqmm A2XFY cable.

    Supply M 400 350 140000

    Laying M 40 350 14000

    1.1.4 3.5c x 35 sqmm A2XFY cable.

    Supply M 160 RO

    Laying M 20 RO

  • 8/22/2019 21-Ht Ele & Panel Boq With Cost

    8/32

    SL.NO. DESCRIPTION UNIT RATE Qty AMOUNT

    1.1.5 4c x 16sqmm A2XFY cable .

    Supply M 65 2500 162500

    Laying M 15 2500 37500

    1.2.0 Armoured type Copper cables

    1.2.1 1c x 240 sqmm 2XWY CU cable .Supply M 800 2000 1600000

    Laying M 35 2000 70000

    1.2.2 1c x 16 sqmm 2XWY CU cable .

    Supply M 120 1300 156000

    Laying M 10 1300 13000

    1.2.3 3c x 185 sqmm YFY CU cable

    Supply M 1100 500 550000

    Laying M 30 500 15000

    1.2.3 3c x 50 sqmm YFY cable

    Supply M 800 1300 1040000

    Laying M 25 1300 32500

    1.2.4 3c x 35 sqmm YFY cable

    Supply M 600 RO

    Laying M 25

    1.2.5 3c x 10 sqmm YFY cable

    Supply M 325 2100 682500

    Laying M 20 2100 42000

    1.2.6 3c X 6sqmm 2XWY CU cable .

    Supply M 180 RO

    Laying M 15 RO

    1.3.0 Armoured Cu. Conductor Control cable

    1.3.1 4c x 4 sqmm YWY cable

    Supply M 160 200 32000

    Laying M 12 200 2400

    1.3.2 4c x 2.5 sqmm YWY FRLS cable

    Supply M 150 800 120000

    Laying M 8 800 6400

    1.3.3 6c x 2.5 sqmm YWY cable

    Supply M 160 200 32000

    Laying M 10 200 2000

    1.3.4 12c x 2.5 sqmm YWY cable

    Supply M 161 60 9660Laying M 15 60 900

    1.3.5 16c x 2.5 sqmm YWY cable

    Supply M 320 30 9600

    Laying M 20 30 600

    1.3.6 24c x 2.5 sqmm YFY cable

    Supply M 460 30 13800

    Laying M 20 30 600

    1.3.6 4c x 2.5 sqmm YWY cable Shielded

    Supply M 150 400 60000

    Laying M 20 400 8000

    1.4.0 PVCA CABLE END TERMINATION

  • 8/22/2019 21-Ht Ele & Panel Boq With Cost

    9/32

    SL.NO. DESCRIPTION UNIT RATE Qty AMOUNT

    Providing and termination for the below listed

    cross section cable with single compression

    brass glands, solderless tinned long barrel Cu

    crimping type lugs, gland earthing, etc.,

    complete.

    ALUMINIUM CABLES/COPPER CABLEA2XFY/2XY/YFY

    1.4.1 3.5c x 300 sqmm A2XFY cable. Nos. 900 220 198000

    1.4.2 3.5c x 240 sqmm A2XFY cable. Nos. 500 36 18000

    1.4.3 3.5c x 185 sqmm A2XFY cable. Nos. 500 16 8000

    1.4.4 3.5c x 120 sqmm A2XFY cable. Nos. 500 10 5000

    1.4.5 3c x 50 sqmm A2XFY/YFY cable Nos. 230 50 11500

    1.4.6 3.5c x 35 sqmm A2XFY/YFY cable. Nos. 210 RO

    1.4.7 4c x 16sqmm A2XFY cable . Nos. 140 40 5600

    1.4.8 3c x 10 sqmm A2XFY/YFY cable. Nos. 95 90 8550

    1.4.9 3c x 6 sqmm A2XFY/YFY cable. Nos. 80 4 320

    1.5.0 Armoured Cu. Conductor cable

    2XFY/YFY Using double compression

    gland

    1.5.1 1c x 240 sqmm 2XWY CU cable . Nos. 350 90 31500

    1.5.2 1c x 16 sqmm 2XWY CU cable . Nos. 200 60 12000

    1.6.0 Armoured Cu. Conductor Control cable

    1.6.1 4c x 4 sqmm YWY cable Nos. 80 12 960

    1.6.2 4c x 2.5 sqmm YWY cable Nos. 60 40 2400

    1.6.3 6c x 2.5 sqmm YWY cable Nos. 80 12 960

    1.6.4 12c x 2.5 sqmm YWY cable Nos. 250 8 2000

    1.6.5 16c x 2.5 sqmm YWY cable Nos. 280 4 1120

    1.6.6 24c x 2.5 sqmm YFY cable Nos. 350 4 1400

    1.6.6 4c x 2.5 sqmm YWY cable Shielded Nos. 60 4 240

    Sub - Total of MV Cables 8248010

    2 Distribution Boards

    S I T & C of surface mounting / flush mounting 10kA

    phase segregated TPN MCB distribution boards (MCB

    DB). The DB shall be made out of 1.2 mm CRCA

    sheet steel enclosure and powder coated complete

    with cable gland plate with knock out at the top &

    bottom. The DB shall have double door with hinged

    lock able external door.The DB's shall be phase

    segregated type and shall have 4 PMCB / MCB isolator

    as incomer, DP RCCB / RCBO as phase incomer andSP MCB as outgoing with the rating as specified. The

  • 8/22/2019 21-Ht Ele & Panel Boq With Cost

    10/32

    SL.NO. DESCRIPTION UNIT RATE Qty AMOUNT

    busbar shall be tinned copper; Insulated fork type for

    phases, Independent neutral bus for each phase

    including inter connecting wiring & earth bus on

    insulatation mount.

    Note

    The RCCB / RCBO shall be Hpi / Si series &MCBs shall be 'D' Curve for UPS DBs

    (UDB) and 'C' Curve for other application.

    2.1 Lighting /RawPower DBS

    2.1.1 8way TPN MCB DB similar to Legrand type

    4 Tier with 40A TP+N MCB

    Isolator as incomer, 40A 100mA DP RCBO

    as phase incomer and 24 nos. 6/10/16A

    SP MCB as outgoings. (LDBs & RDBS) Nos. 11500 6 69000

    2.1.2 6way TPN MCB DB similar to Legrand type

    4 Teir with 40A TP+ N MCB

    Isolator as incomer, 40A 100mA DP RCBO

    as phase incomer and 18 nos. 6/10/16A

    SP MCB as outgoings. ( LDBs & RDBS) Nos. 10200 6 61200

    2.1.3 6 way VTPN MCB DB similar to Legrand type

    with Double c door, 40A 4P 300MA ELMCB as

    incomer and 40A/25/16 TP MCB 2nos , &

    32/25/16/10A SP MCB 9nos, as outgoings. Nos. 18000 4 72000

    2.1.4 8 way VTPN MCB DB similar to Legrand type with

    Double c door,80A TP+NL MCCB as incomer

    and 40A/25/16 TP MCB 2nos , &

    32/25/16/10A sp MCB 18nos, as outgoings. Nos. 25000 1 25000

    2.1.5 12way SPN MCB DB similar to Legrand type606622 with Acrylic door, 40A RCBO

    100mA as incomer and 10nos. 5/10A SP

    MCB as outgoings. Nos. 4000 4 16000

    2.2.0 Emergency DBS

    2.2.1 12way SPN MCB DB similar to Legrand type

    606622 with Acrylic door, 40A RCBO

    100mA as incomer and 10nos. 5/10A SP

    MCB as outgoings. (ELDB) Nos. 4200 10 42000

    2.2.2 8way TPN MCB DB similar to Legrand type

    4 Teir with 63A TP+NL MCB Isolator

    as incomer, 40A 300mA DP RCBO SISERIES/A-S TYPE as phase incomer and 24

    nos. 6/10/16A SP MCB as outgoings. Nos. 11500 4 46000

    2.2.3 6way TPN MCB DB similar to Legrand type

    4 Teir with 63A TP+NL MCB Isolator

    as incomer, 40A 300 mA DP RCBO SI

    SERIES/A-Sas phase incomer and 18 nos.

    6/10/16A SP MCB as outgoings.(UDBs) Nos. 10200 7 71400

    2.2.4 Fabrication and providing 16swg Wire

    way/drawbox/raceways for DBS sides etc.,

    usingsheet steel complete with powder

    coatedpainting hardware, etc., as per site

    requirements. Sqft 250 200 50000

  • 8/22/2019 21-Ht Ele & Panel Boq With Cost

    11/32

    SL.NO. DESCRIPTION UNIT RATE Qty AMOUNT

    Sub Total of DBs 452600

    3 Sub Mains / Circuit Mains :

    Supply and laying of sub/ circuit mains

    using 2mm thick FRLS PVC conduit,

    accessories like bends, junction boxes, GIcleat and saddles etc., 660/ 1100V grade

    FRLS flexible copper wires and wiring

    accessories, terminating wires on either

    ends by providing copper lugs and carrying

    out surface / concealed wiring. Most of the

    area have false ceiling and conduits shall

    run exposed above false ceiling.

    The rate shall include grooving of walls,

    floors chipping, rough plastering, providing

    MS brackets for conduit suspension. Circuit

    mains shall be measured from DB to switch

    board and looping from switch board to

    switch board

    3.1.1 2 x 1.5 + 1 x 1.5 sqmm in 19mm dia

    conduit (for emergency lighting) M 48 3000 144000

    3.1.2 2 x 2.5 + 1 x 1.5 sqmm in 19mm dia

    conduit M 60 2500 150000

    3.1.3 4 x 2.5 + 2 x 1.5 sqmm in 25mm dia

    conduit M 105 1500 157500

    3.1.4 2 x 2.5 + 1 x 1.5 sqmm through sleeves

    in Existing Raceway / Conduit. M 50 600 30000

    Sub Total for Sub Mains and Circuit Mains 481500

    4.1.0 Point Wiring

    Supplying and carrying wiring for light, fan

    and dependent socket points by using 2mm

    thick FRLS conduit of required dia as per

    IS632, MS conduit accessories, PVC

    reinforced flexible conduit with couplers for

    drops with accessories, 2 x 1.5 +1 x1.5

    sqmm. 660/1100V grade HFFR flexible

    copper wires approved 5A modular type

    switches and sockets, GI / PVC boxes, and

    other point wiring accessories and carring

    outsurface / concealed conduit system of

    wiring.

    All points shall be earthed with 1.5 sqmm

    HFFR flexible copper wire. Wires shall be

    terminated at light fixtures with ferrules,

    15A 4 way connector; wire ends shall not be

    loose / bare.

    The rate shal include necessary civil works

    for embedding conduits and boxes

    Note: Ceiling height is 3.5mt. Point wiring

    shall not be measured on RM basis

    4.1.1 1 light point controlled by a 6A switch Nos. 300 500 150000

  • 8/22/2019 21-Ht Ele & Panel Boq With Cost

    12/32

    SL.NO. DESCRIPTION UNIT RATE Qty AMOUNT

    4.1.2 2 light points controlled by 6A switch Nos. 425 250 106250

    4.1.3 3 light points controlled by 6A switch Nos. 565 200 113000

    4.1.4 4 light points controlled by 6A switch No. 625 200 125000

    4.1.5 5 light points controlled by 6A switch No. 850 100 85000

    4.1.6 6 light points controlled by 6A switch No. 1000 80 80000

    4.1.7 6-10 light points controlled by 6A switch No. 1550 20 31000

    4.1.8 3 light points controlled by Existing 6A/10A MCB Nos. 500 40 20000

    4.1.9 4 light points controlled by Existing 6A/10A MCB No. 575 40 23000

    4.1.10 5 light points controlled by Existing 6A/10A MCB No. 680 30 20400

    4.1.11 6 light points controlled by Existing 6A/10A MCB No. 800 20 16000

    4.1.12 6-10 light points controlled by Existing 6A/10A MC No. 950 20 19000

    Sub Total of wiring for Lighting 788650

    5.1.0 Sub Mains / Circuit Mains for Raw Power

    Spec as per Sub mains & LTG CKT Mains

    5.1.1 2 x 2.5 + 1 x 1.5sqmm in 19mm dia

    conduit (RP) M 60 3500 210000

    5.1.2 4 x 2.5 + 2 x 1.5sqmm in 25mm dia

    conduit (RP) M 105 2000 210000

    5.1.3 2 x 2.5 + 1 x 1.5sqmm through PVC

    sleeve in Existing Raceway / Conduit (RP) M 50 750 37500

    5.1.4 4 x 2.5 + 2 x 1.5 sqmm through PVC

    sleeve in Existing Raceway / Conduit (RP) M 90 750 67500

    5.1.5 2 x 4 + 1 x 2.5 sqmm in 19mm dia conduit

    (RP) M 100 1500 150000

    5.1.6 4 x 4 + 2 x 2.5 sqmm in 25mm dia conduit

    (RP) M 145 2000 290000

    Sub Total for Circuit Mains / Raw Power 965000

    6.1.0 Units In MS Enclosure

    S I T & C of the following components like

    approved make / type switches, socket etc,.

    housed in MS / GI enclosure, duly wired &

    painted. All the switch sockets are without

    boxes since the same is covered under

    different item

    6.1.0 Raw power socket

    6.1.1 1 nos 5/15A combined socket controlled by

    1nos 16A Sp switch with cover plate but with

    out box . Nos 200 640 128000

    6.1.2 1 nos 5A multi pin universal socketcontrolled by 1nos 6A Sp switch with cover

  • 8/22/2019 21-Ht Ele & Panel Boq With Cost

    13/32

    SL.NO. DESCRIPTION UNIT RATE Qty AMOUNT

    plate but with out box . Nos 155 100 15500

    6.1.3 2 nos 5/15A combined socket controlled by

    1nos 16A Sp switch with diffferent cover

    plate but with out box . Nos 350 50 17500

    6.1.4 2 nos 5/15A combined socket controlled by2nos 16A Sp switch with diffferent cover

    plate but with out box . Nos 425 50 21250

    6.1.5 4 nos 5/15A combined socket controlled by

    2nos 16A Sp switch with diffferent cover

    plate but with out box . Nos 650 20 13000

    6.2.0 Industrial socket

    6.2.1 250V 16A, 2p+E 1ph 3pin Industrial PC socket

    with plug & socket,16A DP 'RCBO

    control with PC enclosure similar to Legrand

    Tempra 056661 ( IP 66) Nos. 2800 20 56000

    6.2.2 250V 32A, 2p+E 1ph 3pin Industrial PC socket

    with plug & socket,32A RCBO

    control with PC enclosure similar to legrand

    Tempra 056669 (IP 66) Nos. 3400 10 34000

    6.2.3 415V 32A, 3P+N +E 3Ph 5pin Industrial PC socket

    with plug & socket, 32A 4P RCBO

    control with PC enclosure similar to legrand

    056664 ( IP66) Nos. 4000 10 40000

    6.2.4 415V 63A, 3P+N +E 3Ph 5pin Industrial PC socket

    with plug & socket, 32A 4P RCBO

    control with PC enclosure similar to legrand

    056299 ( IP 66) Nos. 8500 10 85000

    6.2.5 80A TPN MCB Isolator in 450 x 300 x200 MS

    box Nos. 1100 2 2200

    6.2.6 63A TP MCB Isolator in 450 x 300 x200 MS

    box Nos. 1100 2 2200

    6.2.7 32A TPN MCB Isolator in 300 x 300 x200 MS

    box Nos. 830 2 1660

    6.2.8 16A TP MCB Isolator in 200 x 300 x200 MS

    box Nos. 600 2 1200

    6.2.9 100A 4P switch (MCCB) type LoadBreakSwitchrequired, Busbar, terminal,

    powder coated MSenclosure, cable entry

    box with angle ironframework for support.

    (PACUNIT) .

    Supply No. 10000 2 20000

    Erection No. 200 2 400

    6.2.10 125A 4P switch (MCCB) type Load

    BreakSwitchrequired, Busbar, terminal,

    powder coated MSenclosure, cable entry

    box with angle ironframework for support.

    (PACUNIT) .

    Supply No. 13000 2 26000

    Erection No. 200 2 400

  • 8/22/2019 21-Ht Ele & Panel Boq With Cost

    14/32

    SL.NO. DESCRIPTION UNIT RATE Qty AMOUNT

    6.2.11 1/2M MS GI Coated Box Nos. 30 15 450

    6.2.12 3M MS GI Coated Box Nos. 40 800 32000

    6.2.13 4M MS GI Coated Box Nos. 60 20 1200

    6.2.14 6M MS GI Coated Box Nos. 65 40 2600

    6.2.15 8M MS GI Coated Box Nos. 85 50 4250

    6.2.16 3M PVC Coated Box Nos. 53 100 5300

    6.2.17 6M PVC Coated Box Nos. 100 50 5000

    6.2.18 8M PVC Coated Box Nos. 120 20 2400

    6.3.0 Starter panel for AC units. With 25KA

    MCCB for Below starter

    6.3.1 DOL Starter panel for 1-5 HP, 3 Phase Motor,

    comprising of 32A MCCB incomer Powercontactors with auxiliary contacts ON / OFF

    luminous push buttons, terminals over load

    relay, Auto/ Manual SS, Local / remote SS

    etc. all housed in poweder coated MS

    enclosure (Indoor type) .

    Supply Nos 9000 10 90000

    Erection Nos 500 10 5000

    6.3.2 DOL Starter panel for 1-5 HP, 3 Phase Motor,

    comprising of MCCB incommer, Power

    contactors with auxiliary contacts ON / OFF

    luminous push buttons, terminals over load

    relay, Auto/ Manual, Local / remote SS etc. all

    housed in powder coated MS enclosure With

    inter locking contractor selector Space

    provision for VFD (indoor type).

    Supply Nos 11000 20 220000

    Erection Nos 500 20 10000

    6.3.3 Star Delta Starter panel for 6 to 15 HP, 3

    Phase Motor, comprising of MCCB incommer ,

    Power contactors with auxiliary contacts ON

    / OFF luminous push buttons, terminals over

    load relay, Auto/ Manual, Local / remote SS

    etc. all housed in MS enclosure With inter

    locking contractor selector & Space provision

    for VFD (indoor type).

    Supply Nos 20000 36 720000

    Erection Nos 500 36 18000

    6.3.4 UPS Lighting change over panel comprising of

    auto / manual selector switch, 63A TP MCCB

    I/c with 2 nos Power contactor with 2 NO+2NC

    Auxiliary contacts, 2No 10A Auxiliary

    contactor, 3Nos.63A semi conductor fuse

    set, set of terminals, as incomer, 6Nos. 32/25/16A

    DP MCB, with 2set Auto manual selector Switch

    timer etc all Enclosed in MS Enclosure goings

    (Emergency Lighting )

    Supply Nos. 25000 1 25000

    Erection Nos. 650 1 650

    6.3.5 Push Button Station

  • 8/22/2019 21-Ht Ele & Panel Boq With Cost

    15/32

    SL.NO. DESCRIPTION UNIT RATE Qty AMOUNT

    6.3.6 ON / OFF Push button station lockable with

    key at OFF position (for AHUs) Nos. 1000 40 40000

    6.3.7 8 Way 10A Terminals in Weather Proof

    Thermo plastic box with 2Nos. cable gland

    suitable for 4cx 16 Sqmm PVCA cable

    similar to Hensel Make Nos. 650 50 32500

    Sub total of units in MS 1678660

    7 Light and Fan Fixture

    7.1 Fluorescent Light Fixture

    Supply, installation, testing & commissioning

    of light fixture complete with Electronic

    ballast for cold start, holders, Mirror optic

    reflectors, louvers, inter connecting wires,

    terminals, lamps, etc., complete Erection

    rate shall include necessary supporting /

    suspending hardware.

    7.1.1 Surface mounting 4' Box type fluorescent

    lightfixture, with different colour tube 1 x

    28W T5 tube similar to PHILPS TMS 1XTL528HF.

    Supply Nos 260 1000 260000

    Erection Nos 50 1000 50000

    7.1.2 Surface mounting 2', Box type fluorescent

    lightfixture, patti type WITH 1 x 14W T5 tube

    similar to PHILPS TMS 1099/114 HF

    Supply Nos 260 100 26000

    Erection Nos 50 100 5000

    7.1.3 Surface mounting 4' Patti type fluorescent

    lightfixture, patti type With different

    colour tube 2 x 28W T5 tube , with Open type

    Reflectors

    similar to PHILPS TMS 2XTL528HF.

    Supply Nos 650 100 65000

    Erection Nos 50 100 5000

    7.1.4 Surface mounting fluorescent light fixture,

    1 x28W tube similar to

    similar to PHILPS TMS206 1XTL528 hf

    Supply Nos 320 100 32000

    Erection Nos 50 100 5000

    7.1.5 Recessed mounting indirect lighting

    luminaire 2 x 28W T5 light fixure with allaccessories for fixing similar to

    PHILPS TBX310 2x TL5 28W

    Supply Nos 1200 20 24000

    Erection Nos 50 20 1000

    7.2 Spot Light Fixture

    7.2.1 Recessed mounting circular CFL light fixture

    with frosted glass,Wth 1 x 13W PL Lamp

    similar to Phillps FBH 145M x 1xPLC 2P13W HF

    Supply Nos 950 200 190000

    Erection Nos 30 200 6000

    7.2.2 Recessed mounting circular CFL light fixturewith frosted glass,Wth 1 x 18W PL Lamp

  • 8/22/2019 21-Ht Ele & Panel Boq With Cost

    16/32

    SL.NO. DESCRIPTION UNIT RATE Qty AMOUNT

    similar to Phillps FBH 145M x 1xPLC 2P18W HF

    Supply Nos 1000 1000 1000000

    Erection Nos 30 1000 30000

    7.2.3 Same of above item no -8.2.5 but with

    Electronic Dimmable blast

    Supply Nos 1350 20 27000Erection Nos 45 20 900

    7.2.4 Recessed mounting circular CFL light fixture

    with frosted glass,Wth 2 x 18W PL Lamp

    similar to Phillps FBH 145M x 2xPLC 2P18W HF

    Supply Nos 1500 500 750000

    Erection Nos 30 500 15000

    7.2.5 Same of above item no -8.2.5 but with

    Electronic Dimmable blast

    Supply Nos 3500 25 87500

    Erection Nos 45 25 1125

    7.2.6 Wall bracket type decorative light fitting

    with 1 x 13 W PL Lamp, as per Arch. Choice

    Supply Nos 6000 65 390000

    Erection Nos 150 65 9750

    7.2.7 Mirror light fitting with 1 x 28 W PL Lamp, as per

    Arch. Choice For Hand wash Area

    Supply Nos 2500 250 625000

    Erection Nos 30 250 7500

    7.2.8 Only 11/13/18 W PL lamps with ballast

    Supply Nos 125 100 12500

    Erection Nos 15 100 1500

    7.2.9 450mm(900 RPM) heavy duty exhaust fan Exhaust

    Fan with Metal Louvers

    Supply Nos 1200 40 48000

    Erection Nos 100 40 4000

    Sub Total of Light fixtures 3678775

    8.1.0 EXTERNAL LIGHTING

    SIT&C of swaged type tubular pole as per

    sketch. The Pole shall be provided with

    10mm thick MS base plate, weather proof

    polycarbonate box housing 5A MCB, 8way6A terminal, etc, Concrete pedestal upto 300

    mm above ground, PCC plinth, internal wiring

    from marshalling box upto the lamp using

    2Cx2.5 sqmm PVC flexible Cu cable.

    The rate shall include earth excavation, civil

    foundation, 2 nos. 50mm dia 1 Mtr. Long GI

    pipe with bend for cable entry / exit and GI

    Spiral earthing

    Light Fixtures will be supplied by

    Client)

    8.1.1 0.8 Mtrs. Integral Bollard in die cast

    aluminium construction with 500mm high

    extruded aluminium mounting coloumn withloop-in loop-out box similar to WIPRO

  • 8/22/2019 21-Ht Ele & Panel Boq With Cost

    17/32

    SL.NO. DESCRIPTION UNIT RATE Qty AMOUNT

    FBP 34118 / 31118

    Supply Nos 3500 100 350000

    Erection Nos 300 100 30000

    8.1.2 9.5 Mtrs. Long single-cross arm 4.5mm thick

    street light pole without light fixure of pressure

    die cast Aluminium housing toughned curvedglass, including 3 phase loop-in loop-out box

    similar to WIPRO WSH 80250. The rate shall

    include earth excavation upto 1.5 mtrs deep

    and concrete pedestal

    Supply Nos 10000 30 300000

    Erection Nos 1800 30 54000

    8.1.3 9.5 Mtrs. Long two-cross arm street light

    pole without light fixure

    of pressure die cast Aluminium housing

    toughned curved glass, including 3 phase

    loop-in loop-out box similar to WIPRO WSH

    80250. The rate shall include earth excavation

    upto 1.5 mtrs deep and concrete pedestalSupply Nos 12000 10 120000

    Erection Nos 2000 10 20000

    8.1.4 3/4 Mtrs. Long street light post suitable for

    mounting 1no. of post top lantern complete

    with single phase loop-in and loop-out box,

    base plate, earth terminal and required

    accessories similar to WIPRO FPS 41061.

    Supply Nos 7800 10 78000

    Erection Nos 600 10 6000

    8.1.5 Gate light / compound light with 1m high GI

    pipe of suitable dia and fixture similar to FPH

    61060 with 60W MH lamp

    Supply Nos 4500 4 18000

    Erection Nos 250 4 1000

    8.1.6 Walkover / driveover integral light fixture similar

    to Wipro FDQ 45050 with 50W halogen lamp

    Supply Nos 3500 50 175000

    Erection Nos 150 50 7500

    Sub total - Street lighting 1159500

    9.1.0 EARTHING

    Designing, S I T & C of earthstation as per

    IS 3043, with proper earth lead connection

    arrangements. Rate shall include allmaterials, excavation, refilling, compacting,

    providing 2'dia / 450 x450mm 9" thick brick

    masonry, GI funnel, salt and charcoal,

    hinged cover fabricated out of angle iron

    frame and 6mm thick chequered plate etc.,

    complete. The GI funnel and tapping

    connection shall not be greater than 10"

    from the FFL

    9.1.1 With 600 x 600 x 3mm Copper plate

    electrode Nos 10500 4 42000

    9.1.2 With 100mm dia 3M long CI Pipe electrode Nos 6000 10 60000

    9.1.3 With 32mm dia 3M long GI Pipe electrode Nos 3000 20 60000

  • 8/22/2019 21-Ht Ele & Panel Boq With Cost

    18/32

    SL.NO. DESCRIPTION UNIT RATE Qty AMOUNT

    9.1.4 With 50mm dia 20M long GI pipe electrode

    with bentonite soil including drilling of rock for

    20m deep. Nos 20000 RO

    9.2 MAT EARTHING

    9.2.1 3M x 2M Mat made out of 50 x 6 GI strips

    mesh at 300mm distance equal interval . Set 35000 1 35000

    9.2.2 3M x 2M Mat made out of 50 x 6 Cu strips

    mesh at 300mm distance equal interval. Only

    flat outer shall be 50 x 6 and internal Mesh

    shall be 25x6mm copper flat. Set 160000 1 160000

    9.2.3 450x450x450mm earthing chambers with

    1000mm long, 50mm dia G.I pipe with funnel /

    Cu earth bus for Earth Matt Set 6500 4 26000

    9.3 EARTH STRIPS

    Supply and laying of earth strips at 0.3m

    below ground / exposed in tray / trench

    including connections by bolting / riveting /

    welding as required

    9.3.1 100 X 10 mm GI flat M 400 500 200000

    9.3.2 65 X 10 mm GI flat M 325 100 32500

    9.3.3 50 X 6mm GI flat M 200 2000 400000

    9.3.4 25 X 6mm GI flat M 450 600 270000

    9.3.5 65 X 6mm Cu flat M 2100 20 42000

    9.3.6 50 X 6mm Cu flat M 1550 50 77500

    9.3.7 25 X 6mm Cu flat M 990 100 99000

    9.3.8 25 X 3mm Cu flat M 400 100 40000

    9.3.9 8 SWG GI wire M 18 2000 36000

    9.3.10 8 SWG Cu wire M 65 650 42250

    9.3.11 14 SWG Cu wire M 120 100 12000

    9.3.12 Sleeve suitable for 65 X 6mm earth flat M 43 20 860

    9.3.13 Sleeve suitable for 50 X 6mm earth flat M 31 50 1550

    9.3.14 Sleeve suitable for 25 X 6mm earth flat M 33 100 3300

    9.3.15 Sleeve suitable for 25 X 3mm earth flat M 33 100 3300

    9.4 CI COVER PLATE FOR EARTH STATIONS

    9.4.1 600mm dia, 65Kg. Weight CI frame and

    cover Nos. 1600 20 32000

    9.4.2 600mm dia, 100Kg. Weight CI frame and

    cover Nos. 3000 20 60000

    Sub Total of Earthing 1735260

  • 8/22/2019 21-Ht Ele & Panel Boq With Cost

    19/32

    SL.NO. DESCRIPTION UNIT RATE Qty AMOUNT

    10 EMPTY CONDUITS

    Supply and fixing of 2mm thick FRLS PVC

    conduit of various dia., exposed or

    concealed, with all accessories and fish wire.

    10.1 25mm dia MS conduit. M 32 40 1280

    10.2 32mm dia MS conduit. M 46 40 1840

    10.3 19mm dia GI flexible conduit. M 20 100 2000

    10.4 25mm dia GI flexible conduit. M 30 200 6000

    10.5 50mm dia GI reinforced flexible conduit. M 80 100 8000

    10.6 65mm dia GI reinforced flexible conduit. M 110 RO

    10.7 100mm dia GI reinforced flexible conduit. M 150 RO

    Sub total - Empty conduits 19120

    11 SAFETY ITEMS

    Providing and laying / fixing the below

    mentioned safety items

    11.1 1M wide 10 mm thick ISI mark 11000V

    grade rubber mat Sqm 1500 20 30000

    11.2 1M wide 10 mm thick ISI mark 1100V

    grade rubber mat Sqm 650 80 52000

    11.3 Shock and First Aid charts in T/W frame Nos. 500 35 17500

    11.4 415V 150mm x 150mm enamel type

    danger board Nos. 180 35 6300

    11.5 Drawing display board suitable for A1ize of

    drawing with lamination of one copy of As built Nos. 1000 2 2000

    dwg .

    Sub Total of SAFETY ITEMS 107800

    12 LIGHTENING PROTECTION

    12.1.1 Design, supply, erection, testing and

    commissioning of Early Streamer Emission

    type lightniing protection system comprising

    of Air terminals or Dynasphere, down

    conductor, event counter, Nos. 125000 1 125000

    12.1.2 With 100mm dia 3M long CI Pipe electrode Nos 18500 RO

    12.1.3 With 32mm dia 3M long GI Pipe electrode Nos 5000 1 5000

    12.2 EARTH STRIPS

    12.2.1 25 X 3mm Cu flat M 400 500 200000

    12.2.2 Test link for lightning protection system M 250 2 500

    Total For Safty Items 330500

    13 CABLE TRAYSupply and fixing of pre fabricated factory

  • 8/22/2019 21-Ht Ele & Panel Boq With Cost

    20/32

    SL.NO. DESCRIPTION UNIT RATE Qty AMOUNT

    made ladder / perforated folded type cable

    tray. The tray shall be fabricated out of

    2.5mm thick pre galvanised for indoor and

    hot dip galvanised steel sheet conforming to

    IS1069:1963 and IS513: 1994. The ladder

    type tray shall comprise of 'C' type side

    runners, bolted slotted rungs at 300mminterval. The tray shall be in standard length

    of 2.5m.

    13.1 150mm W x 60mm D ladder type M 340 150 51000

    13.2 300mm W x 60mm D ladder type M 385 500 192500

    13.3 450mm W x 60mm D ladder type M 450 400 180000

    13.4 600mm W x 60mm D ladder type M 665 1500 997500

    13.5 750mm W x 60mm D ladder type M 690 500 345000

    13.6 Tray accessories llike Tees, bend, reducers,etc suitable for above trays KGS 100 650 65000

    13.7

    300mm W x 40mm H powder coated

    13.8 perforated cable tray. M 563 50 28150

    13.9 600mm W x 40mm H powder coated

    perforated cable tray. M 1200 100 120000

    13.10 Tray accessories llike Tees, bend, reducers,

    etc suitable for above trays KGS 100 50 5000

    Sub - Total for satety, Cable tray 1984150

    14 MISCELLANEOUS ITEMS

    14.1 Temporary lighting within the building with

    supply of 5/15A sockets, 1ph. Industrial

    socket, Distribution Boards with ELCB, MCB /

    fuse cutouts, wiring, light fixture etc.,

    complete Job 65000 RO

    14.2 Fabrication and providing MS items, like

    angles, channels, plates and flats with

    hardware, duly painted/ powder coated etc., Kg. 75 10000 750000

    14.3 Supply and erection of Hitech make GI M

    10 / M8 size suspenders Mtrs 30 650 19500

    14.4 Supply and erection of Hitech make 2mm

    thick 25mm wide GI 'C' type slotted rail Mtrs 65 650 42250

    14.5 Supply and erection of M10 Anchor fasteners

    suitable for above said suspenders. Nos 12 23000 276000

    14.6 415V marked CI cable route marker with 450

    mm long angle pedestal. The unit shall be

    grouted in the earth with concrete Nos 150 20 3000

    14.7 CI Earth pit marker with angle pedestal. The

    unit shall be grouted in the earth with concrete Nos 150 20 3000

    14.8 Floor chipping for conduits and raceway usingmachine and rough plastering Sq.M 450 RO

  • 8/22/2019 21-Ht Ele & Panel Boq With Cost

    21/32

    SL.NO. DESCRIPTION UNIT RATE Qty AMOUNT

    14.9 Supply, installation, testing and commissioning

    of 415V 3 ph. input, 3ph Output.20kVA

    Inverter output with 30 min smf battary

    backup

    Supply Nos 280000 1 280000

    Erection Nos 2000 12000

    Sub-total of Miscellaneous 1375750

    Summary

    1 MV Cables

    2 Distribution Boards

    3 Sub Mains / Circuit Mains for Lighting

    4 Point Wiring

    5 Sub Mains / Circuit Mains for Raw Power

    6 Units in MS Enclosure

    7 Light and Fan Fixtures

    8 External lighting

    9 Earthing

    10 Empty Conduits

    11 Safety Items

    12 Lightening Protection

    13 Cabletray and Raceway

    14 Miscellaneous

    Sub Total Internal Electrification Work

    Add WC Tax @ . . . %

    Grand Total Internal Electrification Work

    1678660

    330500

    107800

    3678775

    23005275

    1984150

    1375750

    481500

    1735260

    19120

    1159500

    788650

    965000

    Amount

    8248010

    452600

  • 8/22/2019 21-Ht Ele & Panel Boq With Cost

    22/32

    Subject : Electrical Installation Work - PART -C Bus Bar Trunking and Bus Duct

    NOTE :

    I All materials & work shall be as per

    standards, EB and Inspectorate rules &

    MSEB local practice

    II Final shop floor drawings to be prepared

    by the vendor before execution of the

    work & approval to be taken from the

    consultant / client

    III All tap unit shall have minimum of 300mm

    space between terminal of MCCB spreader

    and gland plate of Tap Unit for Cable

    termination / Cable extention BOX .

    IV All End feed unit shall minimum of 500MM

    space between terminal of MCCBs

    spreader/ terminals and gland plate of

    Tap Unit for Cable termination.

    V All End feed unit shall have Extention box,

    extention busbar with adequate no of

    terminal fortermination no runs of cable as

    per site condition.

    VI All MCCB End feed / tap of box unit shall

    have Spreaded extention terminal with

    phase barrier

    VII The vendor shall be responsible for

    coordination with Panel vendor and DG

    vendor, etc for installation and termination

    of BBT and BD with respective

    equipments.

    VIII All End feed unit and Tap Of unit shall be

    earthed using proper size Braided Copper

    wires

    IX The vendor Shall subimit during Bidding

    Technical specification sheet with brochures /

    catalogues and Detailed specification sheet for

    all auxiliary ,components giving material

    specifications,make/model, etc.

    X Clients reserve the right to supply items

    such as MCCBS, etc. for which the

    Contractor shall under take erection at the

    rates quoted by him in the tender below.

    SL.NO. DESCRIPTION UNIT RATE QTY AMOUNT

    1.1.0 Bus Bar Trunking system

    Supply, installation, testing and commissioning

    of 1000V,Sandwich type Bus Bar trunking

    system for Rising Main application. The

    enclosrue shall be made of CRCS with

    148 SECSPL

  • 8/22/2019 21-Ht Ele & Panel Boq With Cost

    23/32

    SL.NO. DESCRIPTION UNIT RATE QTY AMOUNTanti-corrosive electrolytic coating and finally

    epoxy polyester powder coating. The BBT shall

    be with Aluminium conductor, as

    mentioned in below with PVC sleeving,

    complete with mounting accessories etc.. As

    per enclosed specification .

    The bus bar trunking run horizontally

    suspended from celing appox 1.5mts from

    celing the rate shall inculde nesscessary rigid

    support and accessories for BBT and tap off

    unit complete installation .

    1.1.1 2000A 65kA 3P+N, with Aluminium conductor

    neutral rated fo 50% and The earth flat shall beof Al and run external surface of Enclosure

    through out the length on eitheir side.

    Supply Rmts 14000 160 2240000

    Erection Rmts 2200 160 352000

    1.1.2 1000A 65kA 3P,2N, with copper conductor

    neutral rated for 200% and With additional

    ground bus bar runing entire length of enclosure

    ( for UPS power distrubtion )

    Supply Rmts 36000 160 5760000

    Erection Rmts 2000 160 320000

    1.2.0 Adopter box End connection with braided

    copper flexible. At panel End

    1.2.1 2000A Aluminium BBT

    Supply Set 36000 RO

    Erection Set 2400 RO

    1.2.2 1000A Copper BBT

    Supply Set 25000 RO

    Erection Set 2000 RO

    1.3.0 Horizontal Bend /ELBOW

    1.3.1 FOR 2000A Aluminium BBT .

    Supply Nos. 22000 4 88000

    Erection Nos. 2100 4 8400

    1.3.2 FOR 1000A copper BBT .

    Supply Nos. 25000 4 100000

    Erection Nos. 1800 4 7200

    1.4.0 Vertical Bend /ELBOW

    1.4.1 FOR 200A Aluminium BBT .

    Supply Nos. 25000 4 100000

    Erection Nos. 2100 4 8400

    1.4.2 FOR 1000A copper BBT .

    Supply Nos. 28000 4 112000

    Erection Nos. 1800 4 7200

    149 SECSPL

  • 8/22/2019 21-Ht Ele & Panel Boq With Cost

    24/32

    SL.NO. DESCRIPTION UNIT RATE QTY AMOUNT

    1.5.0 Vertical TEE

    1.5.1 FOR 2000A Aluminium BBT .

    Supply Nos. 26000 2 52000

    Erection Nos. 1800 2 3600

    1.5.2 FOR 1000A copper BBT .

    Supply Nos. 28000 2 56000

    Erection Nos. 1600 2 3200

    1.6.0 End covers(for above rasing mains)

    1.5.1 FOR 2000A BBT

    Supply Nos. 2000 2 4000

    Erection Nos. 250 2 500

    1.6.1 FOR 1000A copper BBT .

    Supply Nos. 1500 2 3000

    Erection Nos. 200 2 400

    1.7.0 Thrust pad (for above rasing mains)

    1.7.1 FOR 2000A BBT

    Supply Nos. 3500 2 7000

    Erection Nos. 1800 2 3600

    1.7.2 FOR 1000A BBT

    Supply Nos. 2500 2 5000

    Erection Nos. 1500 2 3000

    2.1.0 End feed Unit .

    The unit shall have adequate space forterminating cables With Cable extenstion

    Box, Extenstion Bus bar terminal for

    termination of cables.

    2.1.1 2500A End feed Unit .

    2500A, 430V, 50Hz. 3P+2NL Manually operated

    Draw out type ACB.

    Type of release =Micro Processor type

    Icu =Ics=Icm =65kA For 1 sec .

    Instantanous Short Circuit setting Ii - (1.5

    -10) In.

    Short time delay Short Circuit setting Isc -

    (1.5 -10) In.

    Over load Setting I L = 40 - 100% In.

    Earth Fault Setting 10 - 40% In

    Shunt trip and Auxillary Contacts.

    Supply Nos. 300000 2 600000

    Erection Nos. 6000 2 12000

    2.1.2 1000A End feed Unit .

    1000A, 430V, 50Hz. 3P+2NL Manually operated

    Fixed type MCCB.

    Type of release =Micro Processor type

    150 SECSPL

  • 8/22/2019 21-Ht Ele & Panel Boq With Cost

    25/32

    SL.NO. DESCRIPTION UNIT RATE QTY AMOUNTIcu =Ics=Icm =50kA For 1 sec .

    Instantanous Short Circuit setting Ii - (1.5

    -10) In.

    Short time delay Short Circuit setting Isc -

    (1.5 -10) In.

    Over load Setting I L = 40 - 100% In.Earth Fault Setting 10 - 40% In

    Shunt trip and Auxillary Contacts.

    Supply Nos. 125000 2 250000

    Erection Nos. 4000 2 8000

    1.8.0 MCCB Tap Off unit .

    The unit shall have adequate space for

    terminating cables With Cable extenstion

    Box, Extenstion Bus bar terminal for

    termination of cables.

    1.6.1 630A TAP off Unit .

    630A, 430V, 50Hz. 3P+N link Manually

    operated Fixed type MCCB.Type of release =Micro Processor type.

    Icu =Ics=Icm =35kA For 1 sec .

    Instantanous Short Circuit setting Ii - (1.5

    -10) In.

    Short time delay Short Circuit setting Isc -

    (1.5 -10) In.

    Over load Setting I L = 40 - 100% In.

    Shunt trip and Auxillary Contacts.

    With 630A/5A CT and PEM with serial port

    similar Electix FLEMTO 2T 96

    The unit shall have adequate space for

    terminating cables With Cable extenstion

    Box, Extenstion Bus bar terminal for

    termination of cables.

    Supply Nos. 40000 ROErection Nos. 1000 RO

    1.6.2 320A TAP off Unit .

    320A, 430V, 50Hz. 3P+N link Manually

    operated Fixed type MCCB.

    Type of release =Micro Processor type.

    Icu =Ics=Icm =35kA For 1 sec .

    Instantanous Short Circuit setting Ii - (1.5

    -10) In.

    Short time delay Short Circuit setting Isc -

    (1.5 -10) In.

    Over load Setting I L = 40 - 100% In.

    Shunt trip and Auxillary Contacts.

    With 320A/5A CT and PEM with serial port

    similar Electix FLEMTO 2T 96

    The unit shall have adequate space for

    terminating cables With Cable extenstion

    Box, Extenstion Bus bar terminal for

    termination of cables.

    Supply Nos. 30000 RO

    Erection Nos. 900 RO

    1.6.2 250A TAP off Unit .

    250A, 430V, 50Hz. 3P+N link Manually

    151 SECSPL

  • 8/22/2019 21-Ht Ele & Panel Boq With Cost

    26/32

    SL.NO. DESCRIPTION UNIT RATE QTY AMOUNToperated Fixed type MCCB.

    Type of release =Micro Processor type.

    Icu =Ics=Icm =35kA For 1 sec .

    Instantanous Short Circuit setting Ii - (1.5

    -10) In.

    Short time delay Short Circuit setting Isc -(1.5 -10) In.

    Over load Setting I L = 40 - 100% In.

    Shunt trip and Auxillary Contacts.

    With 320A/5A CT and PEM with serial port

    similar Electix FLEMTO 2T 96

    The unit shall have adequate space for

    terminating cables With Cable extenstion

    Box, Extenstion Bus bar terminal for

    termination of cables.

    Supply Nos. 26000 RO

    Erection Nos. 700 RO

    1.6.2 160A TAP off Unit .

    160A, 430V, 50Hz. 3P+N link Manuallyoperated Fixed type MCCB.

    Type of release =Micro Processor type.

    Icu =Ics=Icm =35kA For 1 sec .

    Instantanous Short Circuit setting Ii - (1.5

    -10) In.

    Short time delay Short Circuit setting Isc -

    (1.5 -10) In.

    Over load Setting I L = 40 - 100% In.

    Shunt trip and Auxillary Contacts.

    With 320A/5A CT and PEM with serial port

    similar Electix FLEMTO 2T 96

    The unit shall have adequate space for

    terminating cables With Cable extenstion

    Box, Extenstion Bus bar terminal for

    termination of cables.Supply Nos. 16000 36 576000

    Erection Nos. 750 36 27000

    1.7.2 400A TAP off Unit .

    630A, 430V, 50Hz. 3P+2N link Manually

    operated Fixed type MCCB.

    Type of release =Micro Processor type.

    Icu =Ics=Icm =35kA For 1 sec .

    Instantanous Short Circuit setting Ii - (1.5

    -10) In.

    Short time delay Short Circuit setting Isc -

    (1.5 -10) In.

    Over load Setting I L = 40 - 100% In.

    Shunt trip and Auxillary Contacts.

    The unit shall have adequate space for

    terminating cables With Cable extenstion

    Box, Extenstion Bus bar terminal for

    termination of cables.

    Supply Nos 35000 RO

    Erection Nos 800 RO

    1.7.3 200A TAP off Unit .

    200A, 430V, 50Hz. 3P+2N link Manually

    operated Fixed type MCCB.

    152 SECSPL

  • 8/22/2019 21-Ht Ele & Panel Boq With Cost

    27/32

    SL.NO. DESCRIPTION UNIT RATE QTY AMOUNTType of release =Micro Processor type.

    Icu =Ics=Icm =35kA For 1 sec .

    Instantanous Short Circuit setting Ii - (1.5

    -10) In.

    Short time delay Short Circuit setting Isc -

    (1.5 -10) In.Over load Setting I L = 40 - 100% In.

    Shunt trip and Auxillary Contacts.

    The unit shall have adequate space for

    terminating cables With Cable extenstion

    Box, Extenstion Bus bar terminal for

    termination of cables.

    Supply Nos RO

    Erection Nos RO

    1.7.4 125/100A TAP off Unit .

    125/100A, 430V, 50Hz. 3P+2N link Manually

    operated Fixed type MCCB.

    Type of release =Micro Processor type.

    Icu =Ics=Icm =35kA For 1 sec .

    Instantanous Short Circuit setting Ii - (1.5-10) In.

    Short time delay Short Circuit setting Isc -

    (1.5 -10) In.

    Over load Setting I L = 40 - 100% In.

    Shunt trip and Auxillary Contacts.

    With 320A/5A CT and PEM with serial port

    similar Electix FLEMTO 2T 96

    The unit shall have adequate space for

    terminating cables With Cable extenstion

    Box, Extenstion Bus bar terminal for

    termination of cables.

    Supply Nos 12000 36 432000

    Erection Nos 500 36 18000

    Sub Total of Supply & Erection of BBT 11,167,500

    2.1.0 BUS DUCT

    S I T& C of three phase 4 wire Aluminium

    Sandwitch Type. Busducts with necessary

    ,straight runs, bends,Risers,brackets The

    Busduct shall be properly supported through

    proper MS brackets and clamps etc. The

    support shall be such that the weight of

    busduct does not bear on TFR,DG and

    ACBS ETC.

    2.1.1 4000A 65kA Aluminium Three phase 50 Hz 4 wire,

    Sandwitch typ busduct as per enclosed

    specification

    The earth flat shall be of copper and run

    external surface of Enclosure through out

    the length on eitheir side.

    I Out door (IP-56) M 25000 50 1250000

    ii Horizontal bend ( IP 56) Set 20000 6 120000

    iii vertical bend ( IP56) Set 30000 6 180000

    iv End connections with cu. Flexible (IP56) Set

    aAdopter box at TFR. End with copper flexible

    153 SECSPL

  • 8/22/2019 21-Ht Ele & Panel Boq With Cost

    28/32

    SL.NO. DESCRIPTION UNIT RATE QTY AMOUNT

    connection ( IP56) Set 83000 3 249000

    bAdopter box at D G End with copper flexible

    connection ( IP56) Set RO

    same as above but at panel end Set 83000 3 249000

    iX Wall frame assembly Set 10000 1

    ii In door M 25000 200 5000000

    iii Horizontal bend Nos. 20000 6 120000

    vi vertical bend Nos. 30000 6 180000

    v End connections with cu. Flexible

    a

    Adopter box at TFR. End with copper flexible

    connection Nos. RO

    b

    Adopter box at D G End with copper flexible

    connection Nos. 83000 RO

    c same as above but at panel end Nos. 83000 6

    vi Wall frame assembly lot 10000 1

    Sub Total of Supply & Erection BUS DUCT 7348000

    Grand Total of BBT & BUS DUCT 18,515,500

    154 SECSPL

  • 8/22/2019 21-Ht Ele & Panel Boq With Cost

    29/32

    Subject : Electrical Work - Part - D M V PANEL

    PART - D- MV PANELS

    Note :- All materials and workmanship

    shall be to standards to consultantsapproval and shall comply with TNEB

    & CEIG requirements.

    Part - D - MV Panels

    Supply , installation , testing and

    commissioning ( SIT & C ) of the following

    extensible dust and vermin proof cubicle type

    floor mounted switchboard. The panels shall

    be Compartmentalised in construction. The

    panel frame shall be made out of 3mm

    folded sheet /angle iron frame, doors and

    body of 14/ 16 G MS sheet. All the sheet

    metal work shall follow rigorous cleansing

    process before it is painted / powder coated

    of approved colour. The panel in generalshall comply with relevant standards,

    enclosed specification and annexures

    All the SFUs shall be provided with HRC

    fusesof rating as shown in schematic.

    All the ACB/MCCB's shall have adjustable

    over current setting. Pad locking, door

    interlock with defeat facility.

    Sl.No Description Unit Rate Qty AMOUNT

    1.1.1 LT MSB-1 & 2

    as per Annexure -A

    Supply Set 2500000 2 5000000Erection Set 30000 2 60000

    1.1.2 MSB -1 & 2

    as per Annexure -B

    Supply Set 1276000 2 2552000Erection Set 20000 2 40000

    1.1.3 AC SMSB -1 (FRESH AIR FAN PNL)

    as per Annexure -C

    Supply Set 340000 1 340000Erection Set 8000 1 8000

    1.1.4 AC SMSB -02 (CHILLER PNL1)

    as per Annexure -D

    Supply Set 1140000 1 1140000Erection Set 15000 1 15000

    1.1.5 AC SMSB -03(CHILLER PNL 2)

    as per Annexure -E

    Supply Set 1160000 1 1160000Erection Set 15000 1 15000

    1.1.6 AC SMSB -4 (COND,CO TOWER )

    as per Annexure -F

    Supply Set 340000 1 340000Erection Set 6000 1 6000

    1.1.7 AC SMSB -5 (COND,CO TOWER )

    as per Annexure -G

    Supply Set 340000 1340000Erection Set 6000 1 6000

    1.1.8 APFCR PANEL-1

  • 8/22/2019 21-Ht Ele & Panel Boq With Cost

    30/32

    Sl.No Description Unit Rate Qty AMOUNT

    1.1.9 APFCR PANEL-2

    as per Annexure -I

    Supply Set 1010000 1 1010000Erection Set 4000 1 4000

    1.1.10 UTILITY PANEL-1

    as per Annexure -J

    Supply Set 250000 1 250000Erection Set 3500 1 3500

    1.1.11 UTILITY PANEL-2

    as per Annexure -K

    Supply Set 275000 1 275000Erection Set 3500 1 3500

    1.1.12 EMERGENCY PANEL

    as per Annexure -L

    Supply Set 85000 1 85000Erection Set 2500 1 2500

    1.1.13 Battery charger panel

    Locn. : Electrical room

    Supply Sets 350000 1 350000

    Erection Sets 5000 1 5000

    1.1.14 Lift control panelas per Annexure -M

    Supply Sets 35000 10 350000

    Erection Sets 1200 10 12000

    1.1.15 800A, 430V, 50Hz. TP+N Manually

    operated Fixed type Load Break Switch in

    powder coated MS enclosure with Bus bar

    terminal etc

    Supply Sets 35000 3 105000

    Erection Sets 1200 3 3600

    Tota or Supp y

    Total for Erection

    Grand Total of MV Panels 14,405,100

  • 8/22/2019 21-Ht Ele & Panel Boq With Cost

    31/32

    MAKES OF MATERIALS

    1 FRLS PVC CONDUIT : VIP / PRECISION

    2 MS CONDUIT (16G) : BI / GUPTA

    3 PVC/ MS CONDUIT ACCESSORIES : PEW / HOMELITE/GUPTA/BI

    4 PVC HFFR COPPER WIRES : FINOLEX / RR CABLE/ POWERFLEX

    6 MODULAR SW. / SOC 5/15A. : WIPRO

    7 MCB / MCB DB : MG/ HAGER/ABB/LEGRAND

    8 ELCB : MG/ HAGER /ABB /LEGRAND

    9 HT / MV CABLE : POLYCAB / RAVIN / TORANTO

    10 METAL CLAD SOCKET : LEGRAND / CLIPSAL / NEPTUNE

    11 CABLE TRAY 2mm tk. : STORAC/INDIANA/PROFAB

    12 EXHAUST FAN : CGL / GEC

    13 LIGHTNING ARRESTOR : INDELEC / ERRICO / NIMBUS / LPI

    14 LIGHT FITTINGS : WIPRO / Phillps

    15 HT VCB RMU : MEI

    15 HT VCB change over PANEL : MEI/ Semiens /CGL /Pragathi

    16 TRANSFORMER : KIRLOSKAR ELECTRIC/ VOLTAMP/RAYCHEM RPG

    17 ACB : MG / ABB / SIEMENS

    18 MCCBs : ABB/ SCHNEIDER (MG)/SIEMENS

    19 CONTRACTOR AND O L RELAY : ABB/ SCHNEIDER (MG)

    20 DIGITAL METERS : CIRUTOR / ELECTREX / AVR / ENERCON

    21CAPACITOR ALL PP / HEAVY DUTY MPP

    :UNIVERSAL / MEHER /ASIAN / SIEMENS

    22 CTs & PTs : KAPPA/ INDCOIL/ SIEMENS /INDCOIL

    291

  • 8/22/2019 21-Ht Ele & Panel Boq With Cost

    32/32

    23 CONTROL SWITCHES : KAYCEE/GEC/ALSTOM/SIEMENS

    24 ELR / EARTH FALUT RELAY : ALSTOM/ PROK DIVS

    25 PROTECTVE RELAY : ALSTTOM / AVKC

    26 PUSH BUTTOM : SIEMENS/ TECHNIC

    27 INDICATING LAMPS (LED TYP ) : SIEMENS/ TECHNIC

    28 LUGS / GLANDS : DOWELLS/SMI

    29 TERMINALS : ELMEX /ESSEN-FINGER TOUCH PROOF

    30 FERRULES : MAYFAIR

    31 BBT : MEGADUCT/ C&S.

    32 BUS BAR SUPPORTS : POWERMAT

    33 PANEL FABRICATOR : PRAGATHI / ELINS / DYNAM .

    34 ANY OTHER ITEMS : TO CONSUTANTS / CLIENTS APPROVAL