2013.01.09 - aci appendix d - updates for aci 318-11
DESCRIPTION
aci DTRANSCRIPT
ACI Appendix D – Updates for ACI 318-11
By Mark Bartlett, PE
RLG Consulting Engineers
SE University, January, 2013 www.LearnWithSEU.com
Topics to be covered
Review of Appendix D (ACI 318-02, 05, 08) Very brief review
Major 2011 Updates to Appendix D Adhesive Anchors Adhesive Anchors Seismic Revisions Installation and Inspection of Anchors
What does IBC 2009 say about anchors?
How to correctly specify post-installed anchors
2
REVIEW OF APPENDIX D
(ACI 318-02, 05, 08)
ACI Appendix D – Updates for ACI 318-11
3
Appendix D – D.2.2
Strength design method for anchorage to concrete
CIP anchors CIP anchorsHeaded bolts, Hooked bolts, Headed studs,
4
Appendix D – D.2.2
Post-installed anchorsUndercut anchors, Expansion anchors
(Sleeve anchors and Wedge anchors) and Adhesive anchors (new in 2011)Adhesive anchors (new in 2011)
Post-installed Anchors must undergo pre-qualification testing ACI 355.2 for mechanical anchors
ACI 355.4 for adhesive anchors
5
Appendix D – D.2.2 Anchors not covered
Specialty inserts
Through-bolts
Screw-type anchorsScrew-type anchors
Multiple anchors connected to a single plate at the embedded end of the anchors
Grouted anchors (not the same as adhesive anchors)
Powder or pneumatic actuated nails
6
ACI 318 - Appendix D
Strength design method for anchorage to concrete (i.e. Nu ≤ ΦNn or Vu ≤ ΦVn)
Nu & Vu – Ultimate capacities determined from service loads multiplied by load factorsservice loads multiplied by load factors
Nn & Vn – Nominal capacities determined from equations
Φ – Strength reduction factor based on factors such as failure mode, supplemental reinforcement and anchor category
7
Appendix D Design Equations & Failure Modes
Design equations check multiple failure modes Steel capacity (Tension and Shear)
Concrete breakout capacity (Tension and Concrete breakout capacity (Tension and Shear)
Pullout/Pull-through capacity (Tension)
Concrete Pryout (Shear)
Concrete side-face blowout (Tension for CIP anchors only)
Bond Strength (Tension for Adhesive Anchors only)
8
Tension Equations
Steel (D.5.1)Nsa = nAse,N futa
Concrete Breakout (D.5.2)Ncbg = ANc/ANco(Ψec,N Ψed,N Ψc,N Ψcp,N Nb)Ncbg = ANc/ANco(Ψec,N Ψed,N Ψc,N Ψcp,N Nb)
Pullout/Pull-through (D.5.3)Npn = Ψc,P Np
Concrete Side-face Blowout (D.5.4)Nsb = (160ca1√Abrg)λ√f’c
Bond Strength (D.5.5)Nag = ANa/ANao Ψec,Na Ψed,Na Ψcp,Na Nba
9
Shear Equations
Steel (D.6.1)Vsa = n 0.6 Ase,V futa
Concrete Breakout (D.6.2) Concrete Breakout (D.6.2)Vcbg = AVc/AVco (Ψec,V Ψed,V Ψc,V Ψh,V Vb)
Concrete Pryout (D.6.3)Vcpg = kcp Ncb
10
Effects of Reinforcement
Anchor Reinforcement (D.4.2.1) Where anchor reinforcement is provided in
accordance with D.5.2.9 and D.6.2.9, calculation of the concrete breakout strength in accordance with the concrete breakout strength in accordance with D.5.2 and D.6.2 is not required.
Refer to sections D.5.2.9, RD.5.2.9, D.6.2.9 and RD.6.2.9 for specific requirements
11
Effects of Reinforcement
Supplemental Reinforcement (D.4.2.1) Configuration and placement similar to anchor
reinforcement
Not specifically designed to transfer the full design Not specifically designed to transfer the full design load from the anchors into the structural member (ex. stirrups for shear reinforcement)
Condition A – with supplemental reinforcement
Condition B – without supplemental reinforcement
Explicit design of supplemental reinforcement is not required (RD.4.3)
12
Phi (Φ) factors- Section D.4.3Failure Mode
CIP
0.75CIPSide Face Blowout
Brittle
0.75Use Condition B
DuctileSteel
ShearTension ShearTension
Condition BCondition AФ Factor
Anchor Property
0.75
0.75 0.75
0.65
0.65 0.60
0.70 0.70
0.70 0.70
13
Pryout
Pullout
Cat. 3Cat. 2
Cat. 1
CIP
Breakout
Cat. 3Cat. 2
Cat. 1
CIP
Cat. 3Cat. 2
Cat. 1
CIP
0.75 0.75
0.75 0.75
0.65 0.75
0.55 0.75
Use Condition B
Use Condition B
0.70 0.70
0.65 0.70
0.55 0.70
0.45 0.70
0.70 0.70
0.65 0.700.55 0.70
0.45 0.70
0.70 0.70
0.65 0.70
0.55 0.70
0.45 0.70
What about Bond Failure?
Post-Installed Anchor Category
Category 1 Low sensitivity to installation and high reliability
Category 2 Medium sensitivity to installation and medium
reliability
Category 3 High sensitivity to installation and lower reliability
Determined from testing per ACI 355.2 Mechanical anchors only
14
Interaction of Tension and Shear - Section D.7
15
Interaction of Tension and Shear - Section D.7
If Vua ≤ 0.2ΦVn full tension allowed
If Nua ≤ 0.2ΦNn full shear allowedIf Nua ≤ 0.2ΦNn full shear allowed
OtherwiseNua Vua
ΦNn ΦVn
+ < 1.2
16
MAJOR 2011 UPDATESADHESIVE ANCHOR ADDITION
ACI Appendix D – Updates for ACI 318-11
17
Biggest Change to Appendix D
Like mechanical anchors, you still need input from manufacturers
Adhesives in Appendix D
from manufacturers
More than just design equations Assumptions regarding installation conditions
Installation by trained personnel
18
Section D.2.2Minimum concrete age of 21 days at the time
of anchor installation
Adhesives in Appendix D
of anchor installation Moisture issue, not strength
Cover this information in your general notes and specs
Common that anchors are installed prior to 21 days
19
Section D.3.5Horizontal or upwardly inclined installations
and anchors subjected to sustained tension
Adhesives in Appendix D
and anchors subjected to sustained tension loading must satisfy D.4.1.2 (45% capacity reduction) Satisfy Installer certification and inspection
requirements per D.9.2.2 – D.9.2.4
These installations will be more expensive
20
Section D.3.640% reduction in lightweight concrete (20% for
expansion and 0% for CIP and undercut)
Adhesives in Appendix D
Section D.3.7 f’c < 10,000 psi for CIP f’c < 8,000 psi for Post-installed
Difficulty of expanding wedge type anchors in very high strength concrete (VHSC)
Adhesive bond strength negatively affected in VHSC
21
Section D.4.1.2Adhesive anchors resisting sustained tension
loads 0.55 ФNba > Nua,s
Adhesive in Appendix D
0.55 ФNba > Nua,s
Nba : Basic bond strength in tension per D.5.5.2
Nua,s: Factored sustained tension load
Sustained tension loads (hanging loads) are especially critical
22
Section D.5.5: Bond strength of adhesive anchor in tension
N = A /A Ψ Ψ N (D-18)
Adhesives in Appendix D
Na = ANa/ANao Ψed,Na Ψcp,Na Nba (D-18) Single Anchor
Nag = ANa/ANao Ψec,Na Ψed,Na Ψcp,Na Nba (D-19) Group of anchors
23
ANa: Influence area for a group of adhesive anchors
Adhesives in Appendix DNag = ANa/ANao Ψec,Na Ψed,Na Ψcp,Na Nba
anchors
ANao: Influence area for a single anchor ANao= (2cNa)2
cNa = 10da√(τuncr/1100)
da = anchor diameter
τuncr: bond stress (per testing / manuf.)
24
Ψec,Na : Modification for eccentric loading
Adhesives in Appendix DNag = ANa/ANao Ψec,Na Ψed,Na Ψcp,Na Nba
Ψed,Na : Modification for edge effects
Ψcp,Na : Modification for adhesive anchors designed for uncracked concrete without supplementary reinforcement to control splitting
25
Adhesives in Appendix DNag = ANa/ANao Ψec,Na Ψed,Na Ψcp,Na Nba
26
Manufacturer’s InfoPermitted Embedment Depth Range
27
Minimum Concrete ThicknessCritical and Minimum
Edge DistanceMinimum Anchor Spacing
Manufacturer’s InfoSteel Strength in Tension
28
Concrete Breakout Strength in Tension
Temperature Range during service life (interior or exterior conditions)
29
Continuous or Periodic Inspection
Dry or Water-saturated Concrete
Strength reduction factors (Φ factor)
Software
Use itSimpson
Hilti
PowersPowers
Free downloads
30
MAJOR 2011 UPDATESSEISMIC REVISIONS
ACI Appendix D – Updates for ACI 318-11
31
Appendix D Seismic
Section D.3.3.1Additional requirements if Seismic Design
Category is C, D, E or F
Section D.3.3.2 Section D.3.3.2Appendix D does not apply for anchors
located in a plastic hinge
Section D.3.3.3Post-installed anchor must pass simulated
seismic testing
32
Appendix D Seismic
Section D.3.3.4.1 If seismic forces are less than 20% of total
tensile force, the extra requirements of section D.3.3.4.3 are not necessaryD.3.3.4.3 are not necessary
Section D.3.3.4.2 If seismic forces are more than 20% of total
tensile force, the extra requirements of section D.3.3.4.3 are necessary
33
Appendix D Seismic
Section D.3.3.4.3 Without reading the commentary, this section
is hard to followis hard to follow
Anchors and their attachments must satisfy one of options (a) through (d)
This section is trying to prevent brittle failures from occurring during a seismic event
34
Appendix D Seismic
Section D.3.3.4.3 (a)Transmit tensile loads via a ductile steel
element.Upset
element.
35
Upset Threads
Appendix D Seismic
Section D.3.3.4.3 (b) Ductile yielding of the attachment
Section D.3.3.4.3 (c) Anchor capacity limited by a non-yielding attachment
like a wood sill plate
Section D.3.3.4.3 (d) Anchors designed for maximum tension obtained
from design load combinations that include E with Eincreased by Ωo
36
Appendix D Seismic
Section D.3.3.4.4 25% reduction to anchor
tensile strength for all failure modes (except steel) given modes (except steel) given in table D.4.1.1
Assume concrete is cracked unless demonstrated that it remains uncracked
37
Appendix D Seismic
Section D.3.3.4.5When anchor reinforcement is provided, no
reduction in anchor tensile strength is reduction in anchor tensile strength is required
D.5.2.9 requires a 25% reduction in the design of the anchor reinforcement
38
Appendix D Seismic
Section D.3.3.5.1 If seismic forces are less than 20% of total
shear force, the extra requirements of section D.3.3.5.3 are not necessaryD.3.3.5.3 are not necessary
Section D.3.3.5.2 If seismic forces are more than 20% of total
shear force, the extra requirements of section D.3.3.5.3 are necessary
39
Appendix D Seismic
Section D.3.3.5.3 Shear “ductile” requirements similar to the ones for
tension loads
(a) ductile yield mechanism in the attachment (a) ductile yield mechanism in the attachment
(b) anchors designed for the maximum shear that can be transmitted to the anchors by a non-yielding attachment
(c) Anchors designed for maximum shear obtained from design load combinations that include E with Eincreased by Ωo
40
Appendix D Seismic
Section D.3.3.5.4 When anchor reinforcement is provided, no reduction
in shear strength is required
Section D.3.3.6 Section D.3.3.6 Anchors subject to both tension and shear shall be
designed to satisfy D.7 (interaction equation) with tensile strength calculated from D.3.3.4.4 (25% reduction)
Section D.3.3.7 Anchor reinforcement must be ASTM A615 Grades
40 and 60 or ASTM A706 Grade 60 41
Appendix D Seismic
Section D.3.4 Adhesive anchors installed horizontally or upwardly
inclined shall be tested per ASTM 355.4 for sensitivity to installation directionto installation direction
Section D.3.5 For adhesive anchors subjected to sustained tension
loading, D.4.1.2 (45% reduction) shall be satisfied
Installer certification and inspection requirements shall be in accordance with D.9.2.2 through D.9.2.4
42
Appendix D Seismic
Section D.3.6 Modification factor for lightweight concrete
CIP and undercut anchor concrete failure – 1.0λ
Expansion and adhesive anchor concrete failure - 0.8λ Expansion and adhesive anchor concrete failure - 0.8λ
Adhesive anchor bond failure – 0.6λ
Section D.3.7 f’c max is 10,000 psi for CIP and 8,000psi for PI
43
MAJOR 2011 UPDATESINSTALLATION AND INSPECTION
OF ANCHORS
ACI Appendix D – Updates for ACI 318-11
44
Appendix D Section D.9
Section D.9.1 Anchors shall be installed by qualified
personnel in accordance with the contract documents.contract documents.
The contract documents shall require installation of post-installed anchors in accordance with the Manufacturer’s Printed Installation Instructions (MPII).
Installation of adhesive anchors shall be performed by personnel trained to install adhesive anchors. 45
Appendix D Section D.9
Section D.9.2 Installation of anchors shall be inspected in
accordance with section 1.3 (Inspection) and accordance with section 1.3 (Inspection) and the general building code.
Adhesive anchors shall be subject to the following additional requirements (sections D.9.2.1 through D.9.2.4)
46
Appendix D Section D.9
Section D.9.2.1 The contract documents shall specify proof loading
where required in accordance with ACI 355.4.
The contract documents shall also specify all The contract documents shall also specify all parameters associated with the characteristic bond stress used for the design including:
minimum age of concrete
concrete temperature range
moisture condition of concrete at time of installation
type of lightweight concrete (if applicable)
requirements for hole drilling and preparation
47
Appendix D Section D.9
Section D.9.2.2 For horizontal and upwardly inclined adhesive
installations, the installer shall be certified by an ACI/CRSI Adhesive Anchor Installer Certification ACI/CRSI Adhesive Anchor Installer Certification Program or equivalent.
Section D.9.2.3 Acceptability of other certifications is the responsibility
of the licensed design professional.
48
Appendix D Section D.9
Section D.9.2.4Horizontal and upwardly inclined installations
require continuous special inspectionrequire continuous special inspection
Inspector shall be specially approved for that purpose by the building official
49
IBC 2009 SECTION 1912
ACI Appendix D – Updates for ACI 318-11
50
IBC 2009 Section 1912
Anchorage to Concrete – Strength DesignCIP anchors, expansion anchors and
undercut anchors “shall be designed in undercut anchors “shall be designed in accordance with Appendix D of ACI 318”
“The strength design of anchors that are not within the scope of Appendix D of ACI 318…shall be in accordance with an approved procedure.” Concrete screws, specialty inserts, etc.
51
Poll Question
Where do you currently specify the requirements for post-installed concrete anchors?
A. Specifications onlyA. Specifications only
B. General Notes only
C. Details only
D. Specs and Details
E. General Notes and Details
F. Specs, General Notes and Details
52
HOW TO PROPERLY SPECIFY
CONCRETE ANCHORS
ACI Appendix D – Updates for ACI 318-11
53
Specifying Concrete Anchors
SpecificationsAdd a dedicated section for concrete anchors
Include both CIP and PI anchors Include both CIP and PI anchors
Sample specs can be downloaded from either Simpson or Hilti Download both and use the best parts of each one
Useful for legal reasons, but how practical is the information?
54
Specifying Concrete Anchors
General NotesAdd a dedicated section for concrete anchors
Include both CIP and PI anchors Include both CIP and PI anchors
Sample general notes can be downloaded from either Simpson or Hilti These will probably not include the requirements
called out in Appendix D section D.9.2.1 minimum age of concrete, concrete temperature range,
moisture condition of concrete at time of installation, etc.
55
Specifying Concrete Anchors
Details If possible, stay generic; If not, be very
specific about the anchorspecific about the anchor
Refer back to the general notes or specifications for additional information
Create a standard “anchor detail” and refer to it when possible
56
Specifying Concrete Anchors
Good Term
Torque-Controlled Anchor A little wordy, but accurate
Adhesive Anchor
Bad Term
Expansion Anchor / Exp. Bolt Too generic
Epoxy Anchor Referenced in App. D;
includes rod and adhesive
Structural Adhesive Threaded rod separate
Threaded Rod Refer to General Notes for
ASTM designation
Not all adhesives are epoxies; not all epoxies are structural
Epoxy Grout or Grout Grouted anchors are different
Bolt Too generic; bolts are not fully
threaded
57
Specifying Concrete Anchors
58
Specifying Concrete Anchors
59
Specifying Concrete Anchors
60
Specifying Concrete Anchors
61
Specifying Concrete Anchors
Type of threaded rod is not called out
GC may feel that he can GC may feel that he can determine the “Or Equal” alternative
62
Specifying Concrete Anchors “Drill & Epoxy Grout” is too
open ended
Older adhesives have not been tested per ACI 355.4 and are not allowed
63
not allowed Simpson SET and AT
Hilti HY 150 and RE 500
Powers Power-Fast
Acceptable versions Simpson SET-XP & AT-XP
Hilti HY150 MAX-SD & RE500-SD
Powers PE1000+ and AC100+ Gold
Specifying Concrete Anchors 8” embed. is too deep
“Exp. Bolt” is too generic
Older “Exp. Bolts” not tested per ACI 355.2 and
64
are not allowed per code Simpson Wedge-All
Hilti Kwik Bolt 3
Powers Power-Stud
Acceptable versions Simpson Strong-Bolt 2
Hilti Kwik Bolt TZ
Powers Power-Stud+ SD1
Specifying Concrete Anchors
“Exp. Bolt” again Not a big deal here
¾” Exp. Bolt gets:
65
¾” Exp. Bolt gets: ≈ 5,000 lbs. tension
≈ 18,000 lbs. shear
Overkill ½” anchor acceptable
Summary
Adhesive Anchors added to Appendix D
Seismic provisions re-written
New installation and inspection New installation and inspection requirements
Proper anchor specifying is critical
Fix that stair stringer detail
66
Questions
67
ACI Appendix D – Updates for ACI 318-11
By Mark Bartlett, PE
RLG Consulting Engineers
SE University, January, 2013 www.LearnWithSEU.com
ACI Appendix D – Updates for ACI 318-11