Programmable Logic Controllers( Definition according to NEMA standard ICS3-1978)
A digitally operating electronic apparatus which uses a programming memory for the internal storage of instructions for implementing specific functions such as logic, sequencing, timing, counting and arithmetic to control through digital or analog modules, various types of machines or process.
Apr 19, 2023 2
Advantages of PLCs
• Less wiring.• Wiring between devices and relay contacts are done in the PLC program.• Easier and faster to make changes.• Trouble shooting aids make programming easier and reduce downtime.• Reliable components make these likely to operate for years before failure.
INTRODUCTION TO PLCS
Apr 19, 2023 3
Major Components of a Common PLC
PROCESSOR
POWERSUPPLY
I MN O P D U UT L E
O M U OT DP UU LT E
PROGRAMMING DEVICE
From SENSORS
Pushbuttons,contacts,
limit switches,etc.
ToOUTPUT
Solenoids, contactors,
alarmsetc.
Apr 19, 2023 4
The Microprocessor or CPU Module• Is the brain of a PLC system.
• It consists of the microprocessor, memory integrated circuits, and circuits necessary tostore and retrieve information from memory.
• It also includes communications ports to other peripherals, other PLC's or programmingterminals.
• Today's processors vary widely in their capabilities to control real world devices.
• Some control as few as 6 inputs and outputs (I/O) and others 40,000 or more.
• One processor can control more than one process or manufacturing line.
• Processors are often linked together in order to provided continuity throughout the process.
• The number of inputs and outputs PLCs can control are limited by the overall capacity ofthe PLC system hardware and memory capabilities.
• The job of the processor is to monitor status or state of input devices, scan and solve the logic of a user program, and control on or off state of output devices.
Apr 19, 2023 5
RAM• Random Access Memory is a volatile memory that would lose it's information if power
were removed.This is why some processor units incorporate a battery back up.
• The type of RAM normally used is CMOS or Complementary Metal Oxide Semiconductor.
• CMOS RAM is used for storage of the user's program (ladder logic diagrams) and storage memory.
ROM or Read Only Memory is a non-volatile type of memory. • This means you don't need an external power source to keep information. • In this type of memory, information can be read, but not changed. • For this reason the manufacture sometimes calls this firmware. • It is placed there for the internal use and operation of processor units.
EEPROM or Electrically Erasable Programmable Read Only Memory• Is usually an add-on memory module that is used to back up the main program in
CMOS RAM of the processor. • In many cases, the processor can be programmed to load the EEPROM's program
to RAM if RAM is lost or corrupted.
Apr 19, 2023 6
Input Module• There are many types of input modules to choose from. • The type of input module used is dependent upon what real world input to the PLC is
desired. • Some examples of inputs are limit switches, electric eyes, and pushbuttons.• DC inputs, such as thumbwheel switches, can be used to enter integer values to be
manipulated by the PLC.• DC input cards are used for this application. • Since most industrial power systems are inherently noisy, electrical isolation is
provided between the input and the processor. • Electromagnetic interference (EMI) and Radio Frequency Interference (RFI) can
cause severe problems in most solid state control systems. • The component used most often to provide electrical isolation within I/O cards is
called an optical isolator or Opto-coupler. • The wiring of an input is not complex. • The object is to get a voltage at a particular point on the card. • Typically there are 8 to 32 input points on any one input module. • Each point will be assigned a unique address by the processor. • Analog input modules are special input cards that use analog to digital conversion
(A to D) to sense variables such as temperature, speed, pressure, and position. • The external device normally is connected to a controller (transducer) producing an
electrical signal the analog input card can interpret. • This signal is usually (4 to 20) mA or a (0 to 10) volt signal.
Apr 19, 2023 7
Output Module
Output modules:• can be used for ac or dc devices such as solenoids, relays, contractors,
pilot lamps, and LED readouts. • Output cards usually have from 6 to 32 output points on a single module. • The output device within the card provides the connection from the user
power supply to the load. • Usually silicon controlled rectifiers (SCR), triac, or dry contact relays are use
for this purpose. • Individual outputs are rated most often at 2 to 3 Amperes. • Output cards, like input cards have electrical isolation between the load
being connected and the PLC.• Analog output cards are a special type of output modules that use digital to
analog conversion (D to A). • The analog output module can take a value stored in a 12 bit file and
convert it to an analog signal. • Normally this signal is (0 -10) volts dc or (4 to 20) m A.• This analog signal is often used in equipment such as motor operated
valves and pneumatic position control devices.
Apr 19, 2023 8
Apr 19, 2023 9
Apr 19, 2023 10
Apr 19, 2023 11
Apr 19, 2023 12
NAND Gate
Apr 19, 2023 1313
NOT OPERATION
In the rung above, it can be seen that if input A is be true (1),then the output C is true (0) or when A is (0), output C is 1.
RungA
C
Apr 19, 2023 14
Apr 19, 2023 15
Apr 19, 2023 16
INPUTS
• These are the physical connections from the real world to the PLC.
• They can be limit switches, push buttons, sensors, anything
that can "switch" a signal on or off.
• The voltage of these devices are usually, but not always, 24 Volt DC.
• PLC Manufacturers make inputs that can accept a wide range of voltages both ac and dc.
• It should be remembered that an input will be ON, "status 1", when the voltage is present at the input connection and OFF, "status 0", when the voltage is no longer present at the input connection.
Apr 19, 2023 17
OUTPUTS
• These are the connections from the PLC to the real world. They are used to switch solenoids, lamps, contactors, etc. ON and OFF.
• Again they are usually 24 Volt DC, either relay or transistor, but can also be 115/220 Volt AC.
Apr 19, 2023 1818
I/O Module• The I/O interface section of a PLC connects it to external field devices.
• The main purpose of the I/O interface is to condition the various signals received from or sent to the external input and output devices.
• Input modules converts signals from discrete or analog input devices to logic levels acceptable to PLC’s processor.
• Output modules converts signal from the processor to levels capable of driving the connected discrete or analog output devices.
Apr 19, 2023 19
Common Industrial Hardware Representing the Binary Concept
Apr 19, 2023 2020
I/O Module
DC INPUT MODULE
OPTO-ISOLATOR
IS NEEDED TO: Prevent voltage transients from damaging the processor.Helps reduce the effects of electrical noise
CurrentLimitingResistor
FROM INPUTDEVICE
USE TO DROP THE VOLTAGE TO LOGIC LEVEL
Buffer, Filter, hysteresis Circuits
TOPROCESSOR
Apr 19, 2023 2121
I/O Module
AC INPUT MODULE
OPTO-ISOLATOR
IS NEEDED TO: Prevent voltage transients from damaging the processor.Helps reduce the effects of electrical noise
Rectifier,ResistorNetwork
FROM INPUTDEVICE
CONVERTS THE AC INPUT TO DC AND DROPS THE VOLTAGE TO LOGIC LEVEL
Buffer, Filter, Hysteresis Circuits
TOPROCESSOR
Apr 19, 2023 2222
Apr 19, 2023 2323
Apr 19, 2023 2424
PLC
INPUTS
OUTPUTS
MOTOR
LAMPCONTACTOR
PUSHBUTTONS
Apr 19, 2023 2525
L1 L2
P. B SWITCH
INPUT MODULE
WIRING DIAGRAM
LADDER PROGRAM
I:2
0
I= Input Moduleslot # in rack
ModuleTerminal #
Allen-Bradley 1746-1A16
Address I:2.0/0
Apr 19, 2023 2626
Discrete Input
A discrete input also referred as digital input is an input that is either ON or OFF are connected to the PLC digital input. In the ON condition it is referred to as logic 1 or a logic high and in the OFF condition maybe referred to as logic o or logic low.
Normally Open PushbuttonNormally Closed Pushbutton
Normally Open switch
Normally Closed switch
Normally Open contact
Normally closed contact
Apr 19, 2023 2727
OUT
PLC
AnalogOutputModule
An analog output is an output signal that has a continuoussignal. Typical outputs may vary from 0 to 20mA, 4 to 20mAor 0 to10V.
Analog Output
EP
Pneumatic control valve
Supply air
Electric to pneumatic transducer
0 to 10V
Apr 19, 2023 2828
PLC Operation
Basic Function of a Typical PLC
Read all field input devices via the input interfaces, execute the user program stored in application memory, then, based on whatever control scheme has been programmed by the user, turn the field output devices on or off, or perform whatever control is necessary for the process application.
This process of sequentially reading the inputs, executing the program in memory, and updating the outputs is known as scanning.
Apr 19, 2023 2929
While the PLC is running, the scanning process includes the following four phases, which are repeated continuously as individual cycles of operation:
PHASE 2Program
Execution
PHASE 3Diagnostics/
Comm
PHASE 4Output
Scan
PHASE 1Read Inputs
Scan
Apr 19, 2023 3030
PHASE 1 – Input Status scan
A PLC scan cycle begins with the CPU reading the status of its inputs.
PHASE 2– Logic Solve/Program Execution
The application program is executed using the status of the inputs
PHASE 3– Logic Solve/Program Execution Once the program is executed, the CPU performs diagnostics and communication tasks
Apr 19, 2023 3131
PHASE 4 - Output Status Scan •An output status scan is then performed, whereby the stored output values are sent to actuators and other field output devices. The cycle ends by updating the outputs.
Apr 19, 2023 32
Selecting a PLC
Criteria
• Number of logical inputs and outputs.• Memory• Number of special I/O modules• Scan Time• Communications• Software
Apr 19, 2023 33
A Detailed Design Process
1. Understand the process2. Hardware/software selection3. Develop ladder logic4. Determine scan times and memory requirements
Apr 19, 2023 3434
Specifications
OUTPUT-PORT POWER RATINGS
Each output port should be capable of supplying sufficient voltage and current to drive the output peripheral connected to it.
SCAN TIME
This is the speed at which the controller executes the relay-ladder logic program. This variable is usually specified as the scan time per 1000 logic nodes and typically ranges from 1 to 200 milliseconds.
Apr 19, 2023 35
PLC Status Indicators
•Power On
•Run Mode
•Programming Mode
•Fault
Apr 19, 2023 36
Examples of PLC Programming Software:
1. Allen-Bradley – Rockwell Software RSLogix5002. Modicon - Modsoft3. Omron - Syswin4. GE-Fanuc Series 6 – LogicMaster65. Square D- PowerLogic6. Texas Instruments – Simatic6. Telemecanique – Modicon TSX Micro
Apr 19, 2023 37
What is a PLC?
A special computer for logic controls using ladder logic programming.
Apr 19, 2023 38
PLC a Real World Relay Replacement
Real world Parts:
• Switch
• Bell
• Relay
Switch controlling AC circuit or bell
Relay
Apr 19, 2023 39
Example of a Motor Control
STARTSTOP
output
START STOP
output
EQUIVALENT DIAGRAMS
Normally Open Contact
NormallyClosed Contact
Apr 19, 2023 40
How to program PLCs?
• Using a specialized Ladder Logic Software– Allen-Bradley uses RsLogix 500 software to program
SLC, Micrologix and so on
– Omron uses Cx Programmer software for its SYSMAC PLCs
• Other manufacturers has their own software
Apr 19, 2023 41
Ladder Logic
• Ladder logic is a method of drawing electrical logic schematics
• A graphical language popular for PLCs Controllers
• Invented to describe logic made from relays• Language resemble ladders, with two vertical
"rails" and a series of horizontal "rungs" between them
• Rule-based language, rather than a procedural language
• Executed sequentially by software, in a loop
Apr 19, 2023 42
Examples
Relay Logic
Ladder Logic
Apr 19, 2023 43
Binary Data Representation
• We communicate to others using groups of letters arranged into words.
• The PLC uses groups of bits called words.
• Different bit patterns represent different information.
Apr 19, 2023 44
PLC Words
• One measure of a computer’s capabilities is the length of the data words on which it can operate.
• Current PLCs use 16-bit words.
• Newer PLCs use 32-bit words.
• SLC 500 family PLCs are 16-bit computers.
Apr 19, 2023 45
Information Represented as Combinations of Bits
Apr 19, 2023 46
Parts of a 16-Bit Word
Apr 19, 2023 47
Bytes, Nibbles, and Bits
Apr 19, 2023 48
16-Point Module’s I/O Points Represented in a
Word
Apr 19, 2023 49
Physical Input Conditions and the Corresponding Input Data
Word
Apr 19, 2023 50
8-Point Input Module Represented in a Word
Apr 19, 2023 51
24-Point I/O Module Represented in Two Words
Apr 19, 2023 52
Two Words Representing Inputs for a 32-Bit Module
Apr 19, 2023 53
Data Table Format
• Words are 16 bits.– Bits 0 through bit 15
• First word or bit is always 0.
• SLC 500 data tables can contain up to 256 words (0 to 255).
Apr 19, 2023 54
Words Arranged in a Data Table
Apr 19, 2023 55
Input Data File (1 of 2)
• Each input screw terminal has one memory location to store on or off status.
• Input data is stored in the input data file. – Also called the input status file
• Input status file holds input status information, which is used to solve ladder program.
Apr 19, 2023 56
Input Data File (2 of 2)
• Identified as an I-type data file
• Only one input status file allowed per project
• Only has words created for actual modules in system
Apr 19, 2023 57
Output Data File (1 of 3)
• Each output screw terminal has one memory location to store on or off status.
• Output data is stored in the output data file, also called the output status file.
Apr 19, 2023 58
Output Data File (2 of 3)
• Output status file holds output status information to update outputs
• Is the result of solving the ladder program.
• Output data sent to modules during output update portion of scan
Apr 19, 2023 59
Output Data File (3 of 3)
• Identified as an O-type data file
• Only one output status file allowed per project
• Only has words created for actual modules in system