1.ew 655139 engineering change notice/67531/metadc742248/...i i 1. ecn (use no. from pg. 1) page 2...

62
ENGINEERING CHANGE NOTICE PW.lOfJ 2. ECN Category (mark one) Direct Revision @ Supplemental 0 Change ECN 0 Temporary 0 Standby 0 Supersedure 0 CancelNoid 0 1.EW 655139 ........................ . . . . . . . . . . . . . . I 3. Originator's Name, Organization. MSIN, and Telephone No. 14. USQ Required? 15. Date MG Cantaloub, WRAP Engineering, T4-52, 372-2122 @Yes ONo 02/25/00 I WRAP Facilitv/AJ60 I I 9. Document Numbers Changed by vlis ECN (indudes 10. Related ECN No(s). sheet no. and rev.) 11. Related PO No. 1°F-4051, Rev. 3, All I N/A I N/A - 12a. Modification Work 0 Yes (fill out Blk. 12b) 0 No NABlks 12b. ~ZC, 12d) 12b. Work Package No. 12c. Modification Work Completed 12d. Restored lo Ori inal Condition (Temp. or Standby ECds only) N/A N/A N/A -. jete Bite Design AuthoritylCo Engineer Signature 8 Design AuthoritylCo Engineer Signature 8 13a. Description of Change 13b. Design Baseline Document? 0 Yes @ No l4a. Justification (mark one) Criteria Change 0 This document is being revised in it's entirety. All IPAN information has been added back into this document. 14b. Justification Details - Design verification not required Facilitate Const. 0 Const. ErrorlOmission 0 Design ErrorlOmission 0 Additions made in response to WIPP audit comments Design Improvement Environmental This document is being revised in it's entirety. USQ WRP-00-050 Facility Deactivation As-Found See attached distribution sheet

Upload: others

Post on 03-Mar-2020

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: 1.EW 655139 ENGINEERING CHANGE NOTICE/67531/metadc742248/...I I 1. ECN (use no. from pg. 1) Page 2 of L ENGINEERING CHANGE NOTICE 16. Design Verification 17.Cost Impact Required ENGINEERING

ENGINEERING CHANGE NOTICE P W . l O f J

2. ECN Category (mark one)

Direct Revision @ Supplemental 0

Change ECN 0 Temporary 0 Standby 0 Supersedure 0 CancelNoid 0

1 . E W 655139 ........................ . . . . . . . . . . . . . .

I 3. Originator's Name, Organization. MSIN, and Telephone No. 14. USQ Required? 15. Date

MG Cantaloub, WRAP Engineering, T4-52, 372-2122

@Yes O N o 02/25/00

I WRAP Facilitv/AJ60 I I 9. Document Numbers Changed by vlis ECN (indudes 10. Related ECN No(s).

sheet no. and rev.) 11. Related PO No.

1°F-4051, Rev. 3, All I N/A I N/A - 12a. Modification Work

0 Yes (fill out Blk. 12b)

0 No NABlks 12b. ~ Z C , 12d)

12b. Work Package No. 12c. Modification Work Completed 12d. Restored lo Ori inal Condition (Temp. or Standby ECds only)

N/A N/A N/A

-. j e t e B i te Design AuthoritylCo Engineer Signature 8 Design AuthoritylCo Engineer Signature 8

13a. Description of Change 13b. Design Baseline Document? 0 Yes @ No

l4a. Justification (mark one)

Criteria Change 0

This document is being revised in it's entirety. All IPAN information has been added back into this document.

14b. Justification Details - Design verification not required

Facilitate Const. 0 Const. ErrorlOmission 0 Design ErrorlOmission 0

Additions made in response to WIPP audit comments Design Improvement

Environmental

This document is being revised in it's entirety.

USQ WRP-00-050 Facility Deactivation

As-Found

See attached distribution sheet

Page 2: 1.EW 655139 ENGINEERING CHANGE NOTICE/67531/metadc742248/...I I 1. ECN (use no. from pg. 1) Page 2 of L ENGINEERING CHANGE NOTICE 16. Design Verification 17.Cost Impact Required ENGINEERING

I I 1. ECN (use no. from pg. 1)

Page 2 of L ENGINEERING CHANGE NOTICE

16. Design Verification 17. Cost Impact Required ENGINEERING CONSTRUCTION

ECN-655139

18. Schedule Impact (days)

0 Yes Additional 0 $ N/A Additional 0 $ N/A Improvement 0 N/A

@ No Savings 0 $ N/A Savings 0 S N/A Delay O N / A - - 19. Cnange Impact Review' In0 a l e tne re alea docJmentS (ouler than tne en neei n docdmcnrs iocnt fed on S.de 1) tnat w:li be aifected by

tne cnanae oesuibeo in E ock 13. Enter Ine aiidcleo docLme-.l n.moer in$ ock 261 - SDDlDD 0 Functional Design Criteria 0 Operating Specification 0 Criticality Specification 0 Conceptual Design Report 0 Equipment Spec. 0 Const. Spec. CI Procurement Spec. U Vendor Information 0 OM Manual 0 FSAWSAR 0 Safety Equipment List 0 Radiation Work Permit 0

Environmental Report

Environmental Impact Statement 0

SeismidStress Analysis 0 StresslDesign Report 0 Interface Control Drawing 0 Calibration Procedure 0 InstallaOon Procedure 0 Maintenance Procedure 0 Engineering Procedure 0 Operating Instruction 0 Operating Procedure 0

iEFD Drawing

Cell Arrangement Drawing 0

Fac. Proc. Samp. Schedule 0 Inspection Plan 0

Operational Safety Requirement 0

Essential Material Specification 0

Tank Calibration Manual 0 Health Physics Procedure

Spares Multiple Unit Listing 0

Component Index 0 ASME Coded Item 0

Computer Software 0 Electric Circuit Schedule 0 ICRS Procedure 0

Process Flow Chart 0 Purchase Requisition 0 Tickler File

None [x1

Test ProceduresISpecification 0

Human Factor Consideration 0

Process Control ManuaVPlan 0

Environmental Permit 0 Inventory Adjustment Request 0 0 !O. Other,Affected Documents: (NOTE: Documents listed below will not be revised by this ECN.) Signatures below indicate that the signing

organization has been notified of other affected documents listed below. Document NumberIRevision Document NumberIRevision Document NumberIRevision

None

!l. Aoorovals r . ~ ~ ~ ~

Signature Date

- Safety

Environ.

Other MG Cantaloub

SQAO JL Maupin

Signature Date

Design Agent

PE

OA

Safety

Design

Environ.

Other

PEPARTMENT OF ENERGY

Signature or a Control Number that tracks the Approval Signature

ADDITIONAL

A-7900-013-3 (10197)

Page 3: 1.EW 655139 ENGINEERING CHANGE NOTICE/67531/metadc742248/...I I 1. ECN (use no. from pg. 1) Page 2 of L ENGINEERING CHANGE NOTICE 16. Design Verification 17.Cost Impact Required ENGINEERING

HNF-4051 Revision 4

Quality Assurance Objectives For Nondestructive Assay at The Waste Receiving and Processing Facility

Prepared for the U.S. Department of Energy Assistant Secretary for Environmental Management

Project Hanford Management Contractor for the U.S. Department of Energy under Contract DE-AC06-96RL13200

P.O. Box 1000 Richland, Washington

Fluor Hanford

Approved for public release; further dissemination unlimited

Page 4: 1.EW 655139 ENGINEERING CHANGE NOTICE/67531/metadc742248/...I I 1. ECN (use no. from pg. 1) Page 2 of L ENGINEERING CHANGE NOTICE 16. Design Verification 17.Cost Impact Required ENGINEERING

HNF-4051 Revision 4

TRADEMARK DISCLAJMER Reference nerein to any specfc commemal p r w 4 process or service of lraae name, Irademam man.facl.rer, or OlheMISe. does not necessar ly consltbte or mply IS endorsement. rewmmendal on. or favor ng by me Jn led States Government of any agency thereof or (1s contractors or subcontractors .

This report has been reproduced from the best available wpy.

Page 5: 1.EW 655139 ENGINEERING CHANGE NOTICE/67531/metadc742248/...I I 1. ECN (use no. from pg. 1) Page 2 of L ENGINEERING CHANGE NOTICE 16. Design Verification 17.Cost Impact Required ENGINEERING

HNF-4051 Revision 4

Quality Assurance Objectives For Nondestructive Assay at The Waste Receiving and Processing Facility

MG Cantaloub Flour Hanford

EDTIECN: ECN-655139

Registered Trademarks:

Total Pages: 5- 4

* Genie PC is a registered trademark of Digital Euipment. Corp., Huston, TX.

Release Stamp

Date Published March 2000

Prepared for the U.S. Department of Energy Assistant Secretary for Environmental Management

Fluor H anford P.O. Box 1000 Richland, Washington

Approved for public release; further dissemination unlimited

Page 6: 1.EW 655139 ENGINEERING CHANGE NOTICE/67531/metadc742248/...I I 1. ECN (use no. from pg. 1) Page 2 of L ENGINEERING CHANGE NOTICE 16. Design Verification 17.Cost Impact Required ENGINEERING

1 (1) Document Number I RECORD OF REVISION

1 Page - HNF-4051

Quality Assurance Objectives for Non-Destructive Assay at the WRAP Facility

(3) Revision

0

Authorized for Release

(5 ) Cog Engr I (6) Cog Mgr Date (4) Descripbon of Change - Replace Add, and Delete Pages

(7) Initial Release, dated 03/03/99 on EDT-623514

1

1 -A

2

I I 3 1 Complete revision per ECN-655134

Complete Revision per ECN-651723

Page change for WRAP QAO NDA Replace page iii of the Table of Contents Replace page 4 per ECN-651724 Complete revision per ECN-651739

4

A-7320-005 (10/97)

Complete revision per ECN-655139 MG Cantalob J ~ W d k

Page 7: 1.EW 655139 ENGINEERING CHANGE NOTICE/67531/metadc742248/...I I 1. ECN (use no. from pg. 1) Page 2 of L ENGINEERING CHANGE NOTICE 16. Design Verification 17.Cost Impact Required ENGINEERING

HNF-405 1 , Revision 4

Quality Assurance Objectives for Nondestructive Assay at the Waste Receiving and Processing Facility

Craig Wills and Michael G. Cantaloub, Fluor Hanford Inc

Page 8: 1.EW 655139 ENGINEERING CHANGE NOTICE/67531/metadc742248/...I I 1. ECN (use no. from pg. 1) Page 2 of L ENGINEERING CHANGE NOTICE 16. Design Verification 17.Cost Impact Required ENGINEERING

HNF 405 1 Rev. 4

Executive Summary

The Waste Receiving and Processing (WRAP) facility, located on the Hanford Site in southeast Washington, is a key link in the certification of transuranic (TRW waste for shipment to the Waste Isolation Pilot Plant (WIPP). Waste characterization is one of the vital functions performed at WRAP, and nondestructive assay (NDA) measurements of TRU waste containers is one of two required methods used for waste characterization. The Waste Acceptance Criteria for the Waste Isolation Pilot Plant, DOEMPP-069 (WIPP-WAC) delineates the quality assurance objectives which have been established for NDA measurement systems. Sites must demonstrate that the quality assurance objectives can be achieved for each radioassay system over the applicable ranges of measurement.

Thls report summarizes the validation of the WRAP NDA systems against the radioassay quality assurance objectives or QAOs. A brief description of the each test and significant conclusions are included. Variables that may have affected test outcomes and system response are also addressed.

Page 9: 1.EW 655139 ENGINEERING CHANGE NOTICE/67531/metadc742248/...I I 1. ECN (use no. from pg. 1) Page 2 of L ENGINEERING CHANGE NOTICE 16. Design Verification 17.Cost Impact Required ENGINEERING

HNF-4051 REV 4

Table of Contents

Executive Summary ....._.._... Table of Contents ...............

...................................................... . .......................................... . ........ .. 11 ... ........................................................................................................ 111

Introduction . . .. . . . . . . . . . . . . . . ................................................................................................................. 1 Descnption of Tests .... ................................................................................................................ 4 Summary of GEA A Tests - Accurancy, Precision and Bias ......................................................... 6 Summary of GEA A Tests - Minimum Detectable Concentration ................................................ 7 Discussion of Results ..................................................................................................................... 9 Appendices ......................................... .._.__.............. . . . . . . . . ........................................ . . . . . . . . . . . . . .. 13 Appendix A - Individual Assay Results .................................................................................... . .. . Appendix B - Source Certificates ..........................

. .

. . . . . . . . . . . . . . . . . . . . . . . . , . . . . . . . . . . . . . . . . . . .

Page 10: 1.EW 655139 ENGINEERING CHANGE NOTICE/67531/metadc742248/...I I 1. ECN (use no. from pg. 1) Page 2 of L ENGINEERING CHANGE NOTICE 16. Design Verification 17.Cost Impact Required ENGINEERING

HNF4051 Rev.4

Introduction

The WRAP facility has four primary NDA systems: two imaging passivdactive neutron (IPAN) systems and two gamma energy assay (GEA) systems. The two IPAN units are identical, as are the GEA units, thus the systems are designated as follows: IPAN A, IPAN B, GEA A, and GEA B. This report documents the conformance of GEA-A to the precision and accuracy radioassay QAOs, and reports the minimum detectable concentration (MDC). The QAOs were demonstrated for 55-gallon (208 L) waste containers only. A separate document, HNF-4050 addresses the total measurement uncertainty (TMU) for the GEA system while HNF-5148 addresses system calibration.

WPP sets forth four nominal testing points for NDA which are in alpha curies and grams of weapons grade (WG) Pu. Due to the nature of available sources, WRAP used the nominal WG Pu gram quantities for testing. This report documents testing of the GEA-A system at the 0.1 g, 1.0 g, 10 g, and 160 g levels for the QAOs with system calibration established in December of 1999, and a supplemental transmission calibration in March of 2000.

‘lhe MDC was determined as a h c t i o n of waste density and Pu-239 transitions of particular interest. Five drums containing non-interfering matrix material covering a density range of 0.046 to 1.56 kg/L were assayed. The MDC reflects the best sensitivity for a particular assay system and specific assay conditions (is. count time, sample configuration) when no added radioactivity is present. As such, no radioactive sources were required for the MDC determination. As with the accuracy and precision QAOs, the MDC is valid for 55-gallon waste containers only. The assay data for the MDC calculations was obtained from December 1999 into early January 2000. The instrument response and the documented results are applicable to the current waste stream undergoing analysis at WRAP.

Precision and Accuracy

To comply with QAO requirements, facilities must determine precision and accuracy values obtained for 15 replicate measurements of appropriate-size mock waste containers containing nominal test quantities of TRU isotopes distributed in a non-interfering matrix. This must be done for each system which is to be certified. The equations used to determine these values, tabulated later in this report, are listed below.

Equation 1 calculates precision as the percent relative standard deviation (%RSD) of the distribution of 15 replicate measurements:

S % RSD= = * 100

Y

where

%RSD = percent relative standard deviation; s = standard deviation; y = mean of the replicate measurements. -

Equation 2 determines the standard deviation:

I

- ... . ...

Page 11: 1.EW 655139 ENGINEERING CHANGE NOTICE/67531/metadc742248/...I I 1. ECN (use no. from pg. 1) Page 2 of L ENGINEERING CHANGE NOTICE 16. Design Verification 17.Cost Impact Required ENGINEERING

HNF-405 1 REV 4

where s = standarddeviation; - yi = the measured value of the i" replicate measurement; y = the mean of the replicate measurements; n = the number of replicate measurements.

Equation 3 determines the accuracy as percent recovery for replicate measurements:

% R = - c," * 100 C ,

where

%R = percent recovery; C, = average result of 15 replicate determinations; C, = known value for the isotope standard used in the replicate measurements

Minimum Detectable Concentration

The WIPP-WAC defines the MDC as that radioactivity concentration which, if present, yields a measured value greater than the critical level with 95% probability, where the critical level is defined as that value which measurements of the background will exceed with 5% probability. No value is specified for the MDC. TRU waste destined for WIPP must have a TRU alpha activity concentration greater than 100 nCi/g. The MDC for the waste stream and the assay conditions must be less than the TRU alpha concentration determined in the waste container. Instruments performing TRUAow-level waste discrimination measurements must effectively have an MDC of 100 nCi/g or less. This sets an effective 'minimum' MDC of 100 nCi/g.

Equation 4 gives the base expression used for determining the MDC:

MDC=K,(2.71+4.65*s6)

where

KI = proportionality constant relating the detector response (counts) to activity concentration. KI incorporates factors such as the detection efficiency and branching ratio for the gamma ray under consideration, the collection live time, waste weight and conversion factors. The magnitude of KI is expected to change depending on the characteristics of the waste matrix (e.g. density) as this affects detection efficiency.

Sb = the standard deviation or uncertainty of the background.

With respect to equation 4, the standard deviation of the background is determined as

2

Page 12: 1.EW 655139 ENGINEERING CHANGE NOTICE/67531/metadc742248/...I I 1. ECN (use no. from pg. 1) Page 2 of L ENGINEERING CHANGE NOTICE 16. Design Verification 17.Cost Impact Required ENGINEERING

HNF-405 1 REV 4

where

counts CR Tc = count time (real time) for the assay (second).

= the total counts acquired in the region of interest for a photon of energy E; = count rate in the region of interest for a photon of energy E (cps);

Substituting terms appropriate for gamma spectroscopy (GEA) into K1 yields a final equation (Equation 5) for representing the MDC for the GEA system:

where

CR(E.,) =

Tc e(&) =

I(%) = M = 37 =

count rate in the region of interest for a photon of energy E (cps); count time for the assay (second); the detection efficiency for the photon of energy E (counts/photon); yield or intensity for the photon of energy Efjhotodsecond); mass of the drum waste matrix (g); conversion factor relating decays per second to nCi (dpshci).

- -

While equation 5 is the base equation for MDC calculations, it was not explicitly evaluated in determining the assay MDC values. The GEA system software suite (Canberra Genie PC) calculates and reports a minimum detectable activity (MDA) for nuclides listed in the analysis library, but not identified in the sample spectrum. If a specified peak exceeds the decision level inherent in equation 5, the software reports the nuclide, otherwise the MDA for the nuclide is reported. The system operating manual (Genie-PC Volume Two, Algorithms Appendix B) describes the analysis algorithm. The MDA value reported is determined from expressions identical to equation 4 and 5.) As configured at WRAP, the software report provides an MDA (in pCi) for all 'undetected' radionuclides listed in the search library. The system reported MDA can be converted to a MDC by use of the appropriate waste matrix mass and conversion factor as shown in equation 6:

MDA(E,)*1000 M * 1000

MDC(E, ) =

where:

MDC(EJ = minimum detectable concentration for a specific nuclide based upon emission of a photon of energy E (nCi/g);

3

Page 13: 1.EW 655139 ENGINEERING CHANGE NOTICE/67531/metadc742248/...I I 1. ECN (use no. from pg. 1) Page 2 of L ENGINEERING CHANGE NOTICE 16. Design Verification 17.Cost Impact Required ENGINEERING

HNF-4051 REV 4

MDAK) =

- - M 1000/1000 =

system reported minimum detectable activity for the specified nuclide photon of energy E (pCi); mass of the waste matrix (kg); conversion factor relating nCi to pCi and kg to grams -1000 nCi/pCi; 1000 g per kg (nCi kg/pCi g).

Description of Tests

Precision and Accuracy

For testing of the NDA systems against the WIPP QAO requirements, the PDP “empty” matrix drum was loaded with sources to approximate the nominal test points. The previous QAO demonstration (HNF-4051 REV 2 and REV 3) utilized the PDP “combustibles” matrix drum. The table below shows the specific sources used in each test configuration and their arrangement within the drum. The test arrangement number (e.g., QAO-AI) is shown in the next section where individual test results are tabulated.

Table 1. QAO sample configuration for January and March 2000 tests.

The “T” and “P” references are to tube number and pin height, respectively. Tube 1 is centered in the drum, while tube 2 is located about halfway between the center and the outer wall of the drum. Tube 3 is located near the outer wall of the drum, opposite tube 2. The pin numbers refer to height (in inches) above the bottom of the drum at which the source is placed. The sources are composed of Pu dispersed in diatomaceous earth, doubly enclosed in concentric stainless steel cylinders. They are nine inches long and about two inches in diameter. The nominal Pu-239 content is 94% for all sources. All the sources were ‘WRAP’ sources, purchased by WRAP for NDA (GEA and IPAN) operations. The sources were not part of the PDP cycle. All assays were performed using the WRAP GEA

4

Page 14: 1.EW 655139 ENGINEERING CHANGE NOTICE/67531/metadc742248/...I I 1. ECN (use no. from pg. 1) Page 2 of L ENGINEERING CHANGE NOTICE 16. Design Verification 17.Cost Impact Required ENGINEERING

HNF-4051 REV 4

operating procedure (W1-OP-0906). Two QAO tests were performed. QAO testing was conducted Jaunary 5 - 12 following calibration of the GEA-A unit. The second QAO evaluation was performed March 6 - 9 as a result of the transmission source recalibration of GEA-A. The same test configurations were used in both tests, with the March configurations designated with an ‘A’ sufiix (Le. QAO-MA). Only three nominal QAO points were assayed. The 0.1 g WP Pu point (QAO-AI) was not reevaluated as the transmission calibration was not expected to impact system performance or the system results at this point.

The GEA system MDC was determined from replicate measurements of drums over a matrix density of 0.046 to 1.56 k g L (g/cm3). The drum matrix was uniform and contained no distributed radioactive sources or interfering components. Additionally, no radioactive sources were added to the drums. Data was acquired for 15 replicate assays at three different drum densities using a nominal (5 minute) counting time. Additionally, two 60-minute assays were performed on the same set of drums. The system reported MDA values ($i) were converted to MDC values through equation 6 and the appropriate drum mass. As above, all assays conducted for the MDC determination were performed in accordance with the WRAP GEA operating procedure (WRP1-OP-0906).

OAO Results

Results for the GEA-A system are presented in summary tables for the precision and accuracy QAOs, followed by the MDC determinations. Table 2 gives the precision and accuracy QAO results from the January tests while Table 3 contains the results from early March. The same samples were used in both evaluations. Results are given for the ‘Sum Segments’ and ‘Combine All’ algorithms for each ofthe nominal evaluation points usingthe 414 keV (Pu-239B) and 129 keV (Pu-239A) emissions of Pu-239. The January results appear first, followed by the March evaluations. Finally, data for the 160 g WG Pu sample includes results with and without the detector shields (collimator per manufacturer’s terminology) in place. Data for the 15 replicates runs for each of the QAO assays is contained in Appendix A.

5

Page 15: 1.EW 655139 ENGINEERING CHANGE NOTICE/67531/metadc742248/...I I 1. ECN (use no. from pg. 1) Page 2 of L ENGINEERING CHANGE NOTICE 16. Design Verification 17.Cost Impact Required ENGINEERING

HNF-405 1 REV 4

Summarv of Januarv GEA A Tests - Accuracv and Precision

I Nominal Point Pu Mass Sum Segments I Combine All

Precision Accuracy I Precision Accuracy

... . I (Attenuator) I IPu-239A I 3.76 7.53 I 6.04 19.82 All listed data are the average from 15 replicate assays

Table 2. GEA-A QAO results for January 2000.

Summarv of March GEA A Tests - Accuracv and Precision

Nominal Point Pu Mass

was not conducted. Results from the January tests are applicable. Table 3. GEA-A QAO results for March 2000.

6

Page 16: 1.EW 655139 ENGINEERING CHANGE NOTICE/67531/metadc742248/...I I 1. ECN (use no. from pg. 1) Page 2 of L ENGINEERING CHANGE NOTICE 16. Design Verification 17.Cost Impact Required ENGINEERING

HNF-405 1 REV 4

Summary of GEA A Tests -Minimum Detectable Concentration

Figure 1 shows MDC determinations as a function of a non-interfering matrix density for Pu-239B (414 keV) and Pu-239A (129 keV). Each data point represents the average, software ‘sum segments’ MDA value for 15 replicate measurements, adjusted per equation 6 to yield an MDC. The smooth curves are power function fits of the data points. The MDC determined using the lightest matrix

~~~

0.00 0.20 0.40 0.60 0.80 1 .oo 1.20 1.40 1.60 1 Drum matrix density (kglL)

I I

Figure 1. Minimum Detectable Concentration (MDC) as a function of drum matrix density based on Pu-239A (129 keV) and Pu-239B (414 keV) peaks. Data is the average sum segment from 15 replicate measurements at a nominal count time of five minutes.

I I

(0.046 kg/L -first data point) is 40 nCilg for the 129 keV peak of Pu (Pu-239A) and 130 nCilg for the 414 keV Pu-239 emission (Pu-239B). It is worth noting that the MDC determined from the 129 keV data is in excellent agreement with the 39 f 2 nCgg value reported in revision 2 of this document. The 100 nCi/g effective lower limit for the MDC would clearly be met for all waste densities for assay results based upon the 129 keV Pu-239 emission. For the 414 keV peak, the data indicates that the 100 nCiig minimum MDC would be met for all but the lightest density waste. Based upon the displayed regression, a waste density of 0.068 or - 0.07 kg/L yields a 100 nCi/g, TRU-low level waste MDC cutoff criteria. Based upon a review of over 100 waste stream drums assayed at WRAP, the average waste density is 0.24 kg/L, with a minimum observed density of 0.094 k&. More than 95% of the waste drums assayed to date had waste densities greater than 0.10 kg/L.

Page 17: 1.EW 655139 ENGINEERING CHANGE NOTICE/67531/metadc742248/...I I 1. ECN (use no. from pg. 1) Page 2 of L ENGINEERING CHANGE NOTICE 16. Design Verification 17.Cost Impact Required ENGINEERING

HNF-405 I REV 4

Using the actual waste densities and the power function determined in Figure I , the expected MDCs for the current waste stream utilizing the Pu-239B and Pu-239A lines (414 and 129 keV respectively) can be determined. Figure 2 shows this data. The largest MDC of 80 nCiig would occw at an observed waste density of 0.094 k g L For 98% of the waste drums assayed at WRAP to date, the maximum MDC would be 66 and 21 nCi/g as determined from the 414 keV and 129 keV Pu-239 lines respectively.

I 0 0 MDC = 15.84(Den~ity)'~~'

Pu-239A (129 keV line)

0.00 0.20 0.40 0.60 0.80 1.00 1.20 1.40 1.60

Measured Drum Waste Density (kg/L) I

i

Figure 2. Minimum detectable concentrations for Pu-2396 (414 keV) & Pu-239A (129 keV) calculated for processed waste densities using the derived MDC function for 5 minute assays.

8

.- - . .. -

Page 18: 1.EW 655139 ENGINEERING CHANGE NOTICE/67531/metadc742248/...I I 1. ECN (use no. from pg. 1) Page 2 of L ENGINEERING CHANGE NOTICE 16. Design Verification 17.Cost Impact Required ENGINEERING

HNF-4051 REV 4

Discussion of Results

The following table, taken fiom Table E-1 of HNF-2600, Hanford Site Transuranic Wuste Certification Plan, gives the precision and accuracy QAO validation requirements.

Nominal Parameter compliance

Range of waste Point Precision' Accuracy" activity in a-Curiesa (%RSD) (%R) a-Curiesa (g WG Pu)~ 0 to 0.02 0.008 - <20 70-130

(0.1)

(1 .O)

(1 0)

(160)

>0.02 to 0.2 0.08 - c15 70-130

>0.2 to 2.0 0.8 - <IO 70-1 30

>2.0 12.8 - c5 70-1 30

a Applicable range of TRU activity in a 208-L (55-gal.) waste container to which the QAOs apply, units are Curies of alpha-emitting TRU isotopes with half-lives greater than 20 years.

The nominal activity (or weight of Pu) used to demonstrate that QAOs can be achieved for the corresponding range in column 1 . Values in parentheses are the appropriate equivalent weights of weapons grade plutonium (WG Pu) 15 years afier purification; for purposes of demonstrating QAOs, "nominal" means within *50 percent, except for the highest range, where "nominal" means f25 percent.

f One standard deviation based on 15 replicate measurements of a noninterfenng matrix. The calculated standard deviation is compared with the mean measured value of the QAO source to obtain the %RSD.

Percent recoveiy(%R) determined from the ratio of measured to known values based on the average of 15 replicate measurements of a noninterfering matrix.

b

It should be noted that a noninterfering matrix is a virtual impossibility. For this QAO test, the empty PDP drum was used. While the interference of this matrix is non existent, the test sources themselves provide interference, particularly for the 129 keV gamma of Pu-239. The two walls of stainless steel surrounding the Pu source material does attenuate gamma flu. The primary energy line used for gamma detection of Pu-239 is 414 keV, but at extremely low mass levels (such as 0.lg) the yield fraction of the 414 keV gamma is too low to be consistently detectable. At these mass values, the primary energy line becomes 129 keV, since it has a significantly higher yield fraction than the 414 keV line. This relatively low (129 keV) energy line can be easily attenuated by the encapsulating steel walls of the source.

Precision and Accuracy

Table 4. provides a comparison of the January QAO results with the required performance. As before (HNF-405 1 Rev 3) the GEA-A system satisfied the 1 g and 10 g test points for the 'Combine All' and 'Sum Segment' results using either the 129 keV or 414 keV Pu-239 transition. Neither the Sum Segments nor Combine All results satisfy the QAO requirements at the 0.1 gram nominal point using the 414 keV emission., however both algorithms satisfy the requirements utilizing the 129 keV

9

Page 19: 1.EW 655139 ENGINEERING CHANGE NOTICE/67531/metadc742248/...I I 1. ECN (use no. from pg. 1) Page 2 of L ENGINEERING CHANGE NOTICE 16. Design Verification 17.Cost Impact Required ENGINEERING

HNF-405 1 REV 4

peak. As mentioned above, this is a direct result of the high yield fraction for the 129 keV transition. The affect of the stainless steel encapsulation is evident in the lower percent recovery determined from the 129 keV emission in comparison to the recovery determined using the 414 keV emission.

The QAO requirements can not be satisfied at the 160 gram point utilizing the 129 keV emission for either ‘Sum Segments’ or ‘Combine All’. The QAO is satisfied, however, ifthe 414 keV gamma is used in either the Combine All or Sum Segments algorithms at this mass. Use of the sum segments algorithm at the 160 gram point requires assaying with the collimator (detector shield) in place for best performance.

Table 4. GEA-A QAO results for January 2000.

The QAO tests performed in March were a direct result of system maintenance and establishing a new system transmission calibration. The transmission information is used in the Combine All algorithm. Table 5 gives the QAO results for the 1 .O, 10 and 160 gram nominal points which were identical to the January QAOs. The 0.1 nominal Pu mass QAO was not reassayed. The March results are very similar to those obtained in January, though some points are worth mentioning. For the 10 gram point, the ‘Sum Segment’ results obtained fiomthe 129 keV emission fail the accuracy QAO. Table 3 shows a recovery of 71 YO from the January evaluation and 67% for

Nominal Point Pu Mass Sum Segments 1 Combine All

Precision % Accuracy I Precision % Accuracy (g WG Pu) Range (9) Emission

Table 5. GEA-A QAO results for March 2000.

IO

RSD % R RSD % R

Page 20: 1.EW 655139 ENGINEERING CHANGE NOTICE/67531/metadc742248/...I I 1. ECN (use no. from pg. 1) Page 2 of L ENGINEERING CHANGE NOTICE 16. Design Verification 17.Cost Impact Required ENGINEERING

HNF-4051 REV 4

the same sample in March.

Overall, the J a n w and March 2000 QAO test results agree with the previous reported QAO results (HNF-4051 Rev 3). The GEA ‘Combine All’ results failed at the 0.1 g level for both the empty and combustible PDP drum. For GEA A, the ‘Combine All Results’ algorithm is preferred at the lower gram levels; at approximately 5.0 g Pu the ‘Combine All’ algorithm is preferred.

All testing was performed using the WRAP GEA operating procedure (WRPl-OP-0906). The standard operating software for the system was used to acquire data and report results. Testing was performed for 55-gallon (208 liter) waste drum configurations only and the QAO results, are therefore, only valid for 55-gallon (208 liter) waste packages.

For these results to be valid, full independence of source materials must be maintained. The QAO tests were performed using plutonium sources, each with its own pedigree and documentation. GEA calibration utilizedmixed sources containing Co-60. Ba-133, (3-137, and Am-241. No sources used in calibration were or are used in QAO validation. Appendix B contains the certificates for the sources used in the January and March QAO validation.

Minimum Detectable Concentration

The MDC curves presented in Figure 1 and Figure 2 demonstrate the effect of matrix density on the

I + MDC (nCiIg) - 5 minute count (routine) t

\ /’ /’

0.00 0.20 0.40 0.60 0.80 1.00 1.20 1.40 1.60

Drum Matrix Density (kg/L)

Figure 3. Minimum Detectable Activity (MDA) and MDC as a function of waste density for the 414 keV Pu-239 emission.

~~~~~~~~ ~~~~~ ~ ~~ ~~~ ~ ~ ~~~ ~~~ ~~~~~ ~~ ~ ~ ~~~

Page 21: 1.EW 655139 ENGINEERING CHANGE NOTICE/67531/metadc742248/...I I 1. ECN (use no. from pg. 1) Page 2 of L ENGINEERING CHANGE NOTICE 16. Design Verification 17.Cost Impact Required ENGINEERING

HNF-4051 REV 4

minimum detectable concentration (equation 5 and 6). Figure 3 shows minimum detectable activity (MDA - determined and reported directly by the system software) and calculated MDC data for Pu- 239B (414 keV) as determined from the ‘sum spectrum’ or ‘sum segments’ algorithm. The three data points and power function trend line (MDC - 5 minute count) are the data points from Figure 1. The additional data are a result of 60-minute assays conducted on the three ‘original’ chums (Figure 1 j and two additional drums. The two additional density points at 0.43 and 0.65 kgiL were assayed to better cover the factor of 20 “gap” in the 0.046 to 0.86 kg/L density interval. The data points are the average value from two, 1-hour assays. The additional points re-enforce the previously developed power function trend line.

The curves in figure 3 are consistent with the expected instrument response and equations 5-6 for MDC and MDA. Plotting the MDA (@) values along with the MDC for the one-hour assays illustrates several important factors. From the MDC plot, one might conclude that assay sensitivity increases with increasing matrix density. The MDA plot in Figure 4 demonstrates the true response. As drum density increases, the magnitude of the measured MDA increases; which is equivalent to a decrease in assay sensitivity. This is consistent with the factors contributing to MDC and MDA. The first is the drop in detector efficiency with increased matrix density. Efficiency appears in the denominator of equation 5. The detection efficiency drops as a result of increased attenuation by the sample matrix necessitating an increase in the MDA. In other words, more activity is required for the true signal to be reliably recognized as a true signal.

The increase in waste density also contributes to a loss in assay sensitivity as result of increased background. Sources of background at WRAP include the natural radiation in the building materials, including the detector, and materials around the facility. Radiation from manmade radionuclides originating from adjacent waste drums may also contribute to this background. The increase in matrix density does not change the background radiation flux at the detector. Rather, having a more dense matrix increases the probability of these emissions interacting with the matrix and being detected as either discrete lines or contributing to the detector continuum.

The combined effect of increased interactions of the background radiation and the decreased efficiency associated with a more dense matrix, results in the loss of measurement sensitivity. This is illustrated by the increase in MDA values with density. Yet, the MDC decreases with matrix density. This is a direct result of the MDC being defined as a concentration, having mass (grams) as its basis. Waste mass is directly proportional to waste density, with the net effect being the decrease in the MDC with increasing waste mass despite the loss of assay sensitivity. The power function regressions in figure 1 help illustrate the effect. If the MDC were solely a function of sample density ( i t detection efficiency and background were independent of density) the regression formulae would show an x‘’ or k g L ’ [l/(kgiL)] dependence.

One final comment on MDC for the GEA systems is prudent. It must be remember that the minimum detectable concentration value is an apriori estimate of the minimum activity that would result in a net signal that could be reliably quantified by the GEA system. It is dependent on both the samples being analyzed, and the parameters of the assay (e.g. count time), and is thus specific for the particular assay condition.

. ..

Page 22: 1.EW 655139 ENGINEERING CHANGE NOTICE/67531/metadc742248/...I I 1. ECN (use no. from pg. 1) Page 2 of L ENGINEERING CHANGE NOTICE 16. Design Verification 17.Cost Impact Required ENGINEERING

HNF-4051 Revision 4

GEA A QAO-AI 0.lg WG Pu in Empty Matrix Pu-239A

GEA A QAO-A1 0.lg WG Pu Empty Matrix (129keV)

0 2 4 6 8 10 12 14 16

Rim S . .-.. . .

. - + - -Sum Segments +Combine All

Appendix A

Page 23: 1.EW 655139 ENGINEERING CHANGE NOTICE/67531/metadc742248/...I I 1. ECN (use no. from pg. 1) Page 2 of L ENGINEERING CHANGE NOTICE 16. Design Verification 17.Cost Impact Required ENGINEERING

HNF-4051 Revision 4

GEA A QAO-A1 0. lg WG Pu in Empty Matrix

GEA A QAO-A1 0.lg WG Pu Empty Matrix (414keV)

200 180 160

0 2 4 6 8 10 12 14 16

Run #

1 - - + - -Sum Seements +Combine All I

Appendix A

Page 24: 1.EW 655139 ENGINEERING CHANGE NOTICE/67531/metadc742248/...I I 1. ECN (use no. from pg. 1) Page 2 of L ENGINEERING CHANGE NOTICE 16. Design Verification 17.Cost Impact Required ENGINEERING

HNF-4051 Revision 4

120

100

80

60

40

20

0

-

GEAA QAO-A2 1.Og WGPu Empty Matrix (129keV)

0 2 4 6 8 10 12 14 16

Run # - - + - -Sum Segments +Combine All

Page 25: 1.EW 655139 ENGINEERING CHANGE NOTICE/67531/metadc742248/...I I 1. ECN (use no. from pg. 1) Page 2 of L ENGINEERING CHANGE NOTICE 16. Design Verification 17.Cost Impact Required ENGINEERING

HNF-4051 Revision 4

GEA A QAO-A2 1.Og WG Pu in Empty Matrix

.-

GEA A QAO-A2 1.Og WG Pu Empty Matrix (414keV)

0 2 4 6 8 10 12 14 16

Run #

- - + - -Sum Segments +Combine All ~~

AppendixA

Page 26: 1.EW 655139 ENGINEERING CHANGE NOTICE/67531/metadc742248/...I I 1. ECN (use no. from pg. 1) Page 2 of L ENGINEERING CHANGE NOTICE 16. Design Verification 17.Cost Impact Required ENGINEERING

HNF-4051 Revision 4

Summed Segments 129keV

Activity (uCi) Mass (6) Mass

Detected Detected % Actual

GEA A QAO-A3 1O.Og WG Pu in Empty Matrix

Combine All Results 12YkeV

Activity (UCi) Mass (9) Mass

Detected Detected %Actual

GEA A QAO-A3 1O.Og WG h Empty Matrix (129keV)

0 2 4 6 8 10 12 14 16

Run #

I - . + ~ . Sum Seaments --b Combine All 1

Page 27: 1.EW 655139 ENGINEERING CHANGE NOTICE/67531/metadc742248/...I I 1. ECN (use no. from pg. 1) Page 2 of L ENGINEERING CHANGE NOTICE 16. Design Verification 17.Cost Impact Required ENGINEERING

HNF-4051 Revision 4

Precision Accuracy

GEA A QAO-A3 1 0 . 0 ~ WG eU in Empty Matrix Pu-239B

I Summed Semnents 414keV I Combine All Results 414keV I

standard deviation = 1.15E-01 = 9.76E-02 standard

deviation

%RSD = 1.07 (Pass) %RSD = 1.07 (P-4 % R = 97.37 (Pass) % R = 114.13 (Pass)

Detected Detected %Actual Detected Detected %Actual I Activity (uCi) I Mass (9) I Maw I Activity (UCi) I Mass (9) I Mass I

TotalBias(%) 95.93 to 99.83 112.88 to 116.95

GEAA QAO-A3 1O.Og WGPu Empty Matrix (414keV)

120

110

100

90

80

70

60

0 2 4 6 8 10 12 14 I6

R i m #- I - - + - -Sum Seements +Combine All I

Appendix A

Page 28: 1.EW 655139 ENGINEERING CHANGE NOTICE/67531/metadc742248/...I I 1. ECN (use no. from pg. 1) Page 2 of L ENGINEERING CHANGE NOTICE 16. Design Verification 17.Cost Impact Required ENGINEERING

I

Summed Segments 120keV

HNF-4051 Revision 4

Comhine All Results IZ!JkeV

GEA A QAO-A4 16O.Og WG Pu in Empty Matrix - Unattenuated

Precision Accuracy

= 1.30E+Q0 standard deviation = 6.27E+03 standard

deviation

%RSD = 202.90 (Fail) %RSD = 1.67 (P-4 % R = 2059.10 (Fail) % R = 51.62 (Fail)

Detected %Actual Detected Detected % Adual Detected I Activity(uCi) I Mass (g) I Mass I Activity(uCi) I Mass@) I Mass I

Total Bias (%) 40.47 to 10233.02 m i to 53.81

GEA A QAO-A4 160.0g WG Pu Empty Matrix (129keV)

0 2 4 6 8 10 12 14 16

Run #

1 - - + - -Sum Segments +Combine All 1

Appendix A

Page 29: 1.EW 655139 ENGINEERING CHANGE NOTICE/67531/metadc742248/...I I 1. ECN (use no. from pg. 1) Page 2 of L ENGINEERING CHANGE NOTICE 16. Design Verification 17.Cost Impact Required ENGINEERING

HNF-4051 Revision 4

Summed Segments 414keV

Activity (uCi) Mass (6) Mass

Detected Detected %Actual

Combine All Results 414keV

Activity (uCi) Mass (8) M*S

Detected Detected %Actual

Total Bias (%) 89.30 to 22245.69 102.01 to 108.05

GEA A QAO-A4 160.0g WG Pu Empty Matrix (414keV)

I l(1

I no

90

80

70

60

0 2 4 6 8 i n 12 14 16

Run #

1 - - + - -Sum Segments +Combine All 1

Appendix A

Page 30: 1.EW 655139 ENGINEERING CHANGE NOTICE/67531/metadc742248/...I I 1. ECN (use no. from pg. 1) Page 2 of L ENGINEERING CHANGE NOTICE 16. Design Verification 17.Cost Impact Required ENGINEERING

HNF-4051 Revision 4

GEA A QAO-A4 160.0g WG Pu in Empty Matrix -- Attenuated Pu-239.4

Summed Segments lZYkeV I Combine All Results IZ!JkeV

GEAA QAO-A4 160.0g WGPu Empty Matrix (129keV)

60

50

40

30

20

10

0 0 2 4 6 8 10 12 14 16

Run #

1 - - *. - -Sum Segments +Combine All 1

Appendix A

Page 31: 1.EW 655139 ENGINEERING CHANGE NOTICE/67531/metadc742248/...I I 1. ECN (use no. from pg. 1) Page 2 of L ENGINEERING CHANGE NOTICE 16. Design Verification 17.Cost Impact Required ENGINEERING

HNF-4051 Revision 4

Summed Segments 414keV

Activity (uCi) Mass (6) MUS

Detected Detected % Achlal

Combine All Results 414keV

Activity (uCi) Mass (6) M a 3

Detected Detected %Actual

Average

Precision

8.36E4-06 1.33Ei-02 8.86Ei-01 1.04E4-07 1.6634-02 l.llEi-02

= 7.34E+OO standard standard deviation deviation

%RSD = 0.34 /Pass) %RSD = 4.42 fPosS)

= 4.56E-01

GEA A QAO-A4 160.0g WG Pu Empty Matrix (414keV)

ToialBias(%) 88.14 to 8909

I20

I IO

I vu 31)

80

70

GO

103.28 to 118.64

0 2 4 6 8 10 12 14 16

Run #

1 - - + ~ ~ Sum Segments +Combine All I

1

Appendix A

Page 32: 1.EW 655139 ENGINEERING CHANGE NOTICE/67531/metadc742248/...I I 1. ECN (use no. from pg. 1) Page 2 of L ENGINEERING CHANGE NOTICE 16. Design Verification 17.Cost Impact Required ENGINEERING

I

Summed Segments 414keV Detected Detected %Actual

Activity (uCi) Mass (9) M a s

HNF-4051 Revision 4

Combine All Results 414keV Detected Detected %Actual

Activity (uCi) Mass (8 ) Mnss

~ o t d Bias ( 89.15 to 100.85

Average I 5.64EM4 8.963-01 9.563+011 6.753+04 1.07EW0 1.14EM2 standard rleui.tinn

= 4.02E-02 sitandud = 3.43E-02

Ae"irti,>n

106.44 to 123.05

IPrecision I %RSD = 3.X2 /Puss) I %RSD = 3.15 /Puss) I

GEA A QAO-AlA 1.Ug WG Pu Empty Matrix (414keV)

0 2 4 6 8 10 12 14 I6

Run #

- - + - -Sum SegmrntS -Combine All

Appendix A

.- ._I___--

Page 33: 1.EW 655139 ENGINEERING CHANGE NOTICE/67531/metadc742248/...I I 1. ECN (use no. from pg. 1) Page 2 of L ENGINEERING CHANGE NOTICE 16. Design Verification 17.Cost Impact Required ENGINEERING

HNF-4051 Revision 4

Summed Segments 12YkeV Detected Detected %Actual

Activity (UCi) Mass (8 ) Mass

GEA A QAO-MA 1.Og WG Pu in Empty Matrix Pm-239A

Combine All Results 12YkeV Detected Dete&d % A d d

Activity (uCi) Mass (8 ) Mass

I I standard . -. I s

I

Average I 4.3!JE+ll4 6.Y8E-01 7.41EHlll 6.1I6EHM Y.63E-01 1.03E-42 standard deviation = 1.91E-02

Precision I %RSD = 2.74 (Pass) Accuracy %R = 74.41 (Pass) TotalBias ( 72.37 to 78.30

standard = 3.00E-02 deviation

%RSD = 3.11 (Pass) %R = 102.64 (Pass) 98.14 to 107.46

= 1.YIE-UZ deviation

Precision I %RSD = 2.74 (Pass) Accuracy %R = 74.41 (Pass) TotalBias ( 72.37 to 78.30

dLllOLIYll

%RSD = 3.11 (Pass) %R = 102.64 (Pass) 98.14 to 107.46

GEA A QAO-MA 1.Og WG Pu Empty M a t r i x (129keV)

120

100

80

60

40

20

0

0 2 4 6 R 10 12 14 16

Run #

1;- 4 - -Sum Segments +Combine All I

Appendix A

Page 34: 1.EW 655139 ENGINEERING CHANGE NOTICE/67531/metadc742248/...I I 1. ECN (use no. from pg. 1) Page 2 of L ENGINEERING CHANGE NOTICE 16. Design Verification 17.Cost Impact Required ENGINEERING

HNF-4051 Revision 4

Precision I %RSD = 0.74 (Pass) Accuracy % R = 92.93 (Pass) TotalBias( 91.36 to 94.24

%RSD = 0.86 (Pass) %R = 118.04 (Pass)

116.27 to 119.66

GEA A QAO-A3A 10 .0~ WG Pu Empty Matdr (414keV)

120

1 10

100

90

80

70

60 0 2 4 6 8 10 12 14 16

Run U I - - + . -Sum S & r i

Appendix A

Page 35: 1.EW 655139 ENGINEERING CHANGE NOTICE/67531/metadc742248/...I I 1. ECN (use no. from pg. 1) Page 2 of L ENGINEERING CHANGE NOTICE 16. Design Verification 17.Cost Impact Required ENGINEERING

HNF-4051 Revision 4

Summed Segments 12YkeV Detected Detected %Actual

Activity ("Ci) Mass (9 ) Mass

Combine All Results 12YkeV Detected Detected %Actual

Activity (uCi) Mass (9) Mass

Average I 3.YSE4lS 6.28EtUO 6.6YEMlll S.63E4-05 X.YSE+OU Y.51EMI1 standard deviation = 4.65E-02

Precision I %RSD = 0.74 (Pass) Accuracv % R = 66.95 (Fail)

standard deviation = 1.55E-01

%RSD = 1.13 (Pass) % R = 95.38 (Pass)

Total Bias ( 65.93 to 67.80

~

GEA A QAO-MA 1O.Ug WG Pu Empty Matrix (129kev)

92.88 to 98.81

LOO

90

80

70

60

50

40

0 2 4 6 8 10 12 14 16

Run #

- - + - -Sum Segments +CombineAll

AppendixA

Page 36: 1.EW 655139 ENGINEERING CHANGE NOTICE/67531/metadc742248/...I I 1. ECN (use no. from pg. 1) Page 2 of L ENGINEERING CHANGE NOTICE 16. Design Verification 17.Cost Impact Required ENGINEERING

HNF-4051 Revision 4

Precision I %RSD = 364.90 (Fail) Accuracy I % R = 1552.74 (Fail) TotalBias (%) 89.09 to 22033.82

%RSD = 1.47 (Pass) % R = 108.54 (Pass)

105.93 to 112.29

GEA A QAO-A4A 160.0g WG Pu Empty Matrix (414keV)

0 2 4 6 8 IO 12 14 16

Run #

1 - - + - -Sum Segments +Combine All 1

Appendix A

-.

Page 37: 1.EW 655139 ENGINEERING CHANGE NOTICE/67531/metadc742248/...I I 1. ECN (use no. from pg. 1) Page 2 of L ENGINEERING CHANGE NOTICE 16. Design Verification 17.Cost Impact Required ENGINEERING

HNF-4051 Revision 4

Summed Segments 129keV

Activity (uCi) Mass (9) Mass

Detected Detected % Actual

Combine All Results 129keV

Activity (uCi) Mass (9) Mass

Deteded Detected %Actual

Average

Precision Accuracy

GEAA QAO-A4A 160.0g WGPu Empty Matrix (129keV)

6.753+07 1.07Ei-03 7.153+02 5.12Ei-06 8.14EW1 5.43Ei-01 standard deviation = 1.29E+00 = 3.92E+03 standard

deviation

%RSD = 364.95 (Fail) %RSD = 1.59 (Pus) % R = 715.06 (Fail) % R = 54.25 (Fail)

120 I I t 1 101)

XU 70 60

40

2 0

90

5 0

30

Total Bias (%) 40.36 to 10148.27

0 2 4 6 8 i n 12 14 16

Run A'

1- - + - -Sum Seements +Combine All 1

52.65 to 55.93

Appendix A

Page 38: 1.EW 655139 ENGINEERING CHANGE NOTICE/67531/metadc742248/...I I 1. ECN (use no. from pg. 1) Page 2 of L ENGINEERING CHANGE NOTICE 16. Design Verification 17.Cost Impact Required ENGINEERING

HNF-4051 Revision 4

Precision Accuracy

GEA A QAO-A4A 160.0g WG Pu in Empty Matrix - Attenuated Pu-239B

Summed Segments 414keV Combine All Results 414keV Detected Detected %Actual Detected Detected % Actual

Activity (uCi) MUS Activity (uCi) Mass (9) Mass

= ~ . ~ O E + O O standard deviation

%RSD = 3.47

= 6.87E-01 standard deviation

(Pass) %RSD = 0.51 ( P 4 % R = 89.02 (Pass) % R = 113.42 (Pass)

I I

Average I 8.40EW6 3.343+02 8.90EW1 I 1.07EH7 1.70EW2 1.13EW2

TotalBias (%) 88.24 to 89.62 108.05 to 125.00

GEAA QAO-A4A 160.0g WGPu Empty Matrix (414keV)

0 2 4 6 n 10 12 14 16

Run #

I ~ - + . -Sum Seernents + C o r n G Z K

Appendix A

Page 39: 1.EW 655139 ENGINEERING CHANGE NOTICE/67531/metadc742248/...I I 1. ECN (use no. from pg. 1) Page 2 of L ENGINEERING CHANGE NOTICE 16. Design Verification 17.Cost Impact Required ENGINEERING

HNF-4051 Revision 4

Summed Segmentu 129keV

GEA A QAO-A4A 160.0g WG F'u in Empty Matrix - Attenuated P..-779A

Cumhine All Results 1WkeV Detected Detected % Adual Detected Detected %Actual I Activity(uCi) I Mass (9) I Mass I Activity (uCi) I M a s k ) I M-3

GEAA QAO-A4A 160.0g WG PU Empty Matrix (129keV)

0 2 4 6 8 1 0 12 14 16

Run #

1 - - + - -Sum Segments +Combine All I

Appendix A

.. ... ~. . . .

Page 40: 1.EW 655139 ENGINEERING CHANGE NOTICE/67531/metadc742248/...I I 1. ECN (use no. from pg. 1) Page 2 of L ENGINEERING CHANGE NOTICE 16. Design Verification 17.Cost Impact Required ENGINEERING

IMF-405 1 Rev 4

Los Alamos National Laboratory Certificate of Content anb QikateaWtp

Pu02-Diatomaceous Earth Standard WRAPlOOMGPU

This NDA standard contains high purity plutonium dioxide dispersed io diatomaceous earth. Quantitative information and uncertainties on the nuclear content of this WRM are listed below. Complete information regarding the Pu and Am content, P u . isotopic ratios, chemical composition, elemental impurities, containment, and fabrication procedures a r e retained in files by the Los Alamos National Laboratory CMR Analytical Chemistry Group. . .

NUCLEAR MATERIAL CONTENT

The nuclear material content and total alpha activity for this standard are listed below. Also listed are overall uncertainty estimates a t 95% confidence intervals (CI) for each component.

. .

Component Quantity or Value 95 % CI P u Q In standard 0.11064 grams i O.OOOOS grams ('1

Pu in standard 0.09710 grams i O.OOO~I grams ('1

Am Assay 1128.9 pglg PuO1* * 0:3 pg/g (dl

"'Am in standard 0.110 mg* * 0.001 mg")

P u Assay 87.761 % of PuO1* * 0.081.% ')

'241

Isotopic Weight,Fraction*

0.00014

0.93809

0.05939

0.00185

0.00054

rt 0.000005 ('

h 0.000015 ('

f 0.000007 (0

h 0.000009 (0

f 0.000003 (O

Total Alpha Activity in standard 6.635 mCi** 2.4553+08 Bq

I- 0.017 mCi (e)

i 6E+05 Bq @)

*Decay corrected value on 1/21/99 ** Effective 1/21/99

A

&,J2 Robert S. Marshall, Proiect Ma@& . - NDA WRM Production

Appendix B

Page 41: 1.EW 655139 ENGINEERING CHANGE NOTICE/67531/metadc742248/...I I 1. ECN (use no. from pg. 1) Page 2 of L ENGINEERING CHANGE NOTICE 16. Design Verification 17.Cost Impact Required ENGINEERING

MEASUREMENT METHOD AND TRACEABJLm

The nucleaf contents of this standard were characterized and qnantified using the following methods with traceability to the National h t i t u t e of Standards and Technology OyIST) or New Brunswick Laboratory (NBL) standards.

Measurement Measurement Method Reference Material

Weighing 5 place analytical balance NISI traceable weights PU Assay Controlled Potential Coulometry Am Assay Isotope Dilution Mass Spectrometry

NBL (SRM # 126

NBL CRM # 128

P u Isotopic Total Evaporation Mars Spectrometry NBLCRM# 128 Alpha Activity Calculated fromPu and Am mas, and

isotope alpha specific activities listed below. Pu tIn as stated for NLST SRM946

Am tm as stated for NLST SRM4322B .

Y O 139 The stated Alpha Activity was calculated using the following isotope half lives (in years): 24,119; ""Pu: 6,560; PU. 14.34; Pu: 387,000; and Am: 432.2.

Pu: 87.74; PU: 241 2.n 1 4 1

Random and systematic e r ror terms were combined and reported as 95% confidence internalp. E r r o r terms include estimates of the following:

(a) Balance precision, buoyancy, standard weight bias, and transfer loss. (b) Long and short term precision, control check bias weighing precision and bias. (c) Above weighing and assay terms, and transfer loss (d) Long and short term precision, and bias. (e) Ahove weighing terms, Am assay terms, and transfer loss. (0 Long and short term prcrision, and blas. (g) Based on propagated uncertainties on the Pu mass, '"Am mass and Pu isotopic uncertainties listed

above. No half-life uncertainty components are inclnded and it is recommended that all facilities participating in the NDA PDP program USE the bnlf-lives listed above to preclude bcL!.ity-t*ficility error terms introduced by using different half life values.

Appendix B

Page 42: 1.EW 655139 ENGINEERING CHANGE NOTICE/67531/metadc742248/...I I 1. ECN (use no. from pg. 1) Page 2 of L ENGINEERING CHANGE NOTICE 16. Design Verification 17.Cost Impact Required ENGINEERING

€Ih'1:-405 1 Rev 1

Los Alamos National Laboratory aetrtifitate of Content anb Z!LrateabiIitp

PuOZ-Diatomaceous Earth Standard WRAP-1 SOOMGPU

This NDA standard contains high purity plutonium dioxide dispersed in diatomaceous earth. Quantitative information a n d uncertainties on the nuclear content of this WRM are listed below. Complete information regarding the Pu and Am content, Pu isotopic ratios, chemical composition, elemental impurlties, containment, and fabrication procedures are retained in files by the Los Alamos National Laboratory CMR Analytical Chemistry Group.

PUCLEAR MATERIAL CONTENT

The nuclear material content and total alpha activity for this standard are listed below. Also listed are overall uncertainty esti.mates a t 95% confidence intervals (CI) for each component

Component PuOl in standard

P u Assay . Pu in standard

'"Am Assay '"Am in standard

Isotopic Weight Fraction*

=8Pu

'39Pu

l"oPu

'"PU

'r'Pu

Quantitv or Value 0.57920 grams

0.50831 grams 1128.9 p u g PuOt*

0.574 mg*

87.761 Yo of PuOl*

0.00014

0.93809

0.05939

0.00185

0.00054

Total Alpha Activity in standard 34.73 mCi** 1.285E+09 Bo

*Decay corrected value on ll21199 * * Effective 1/21/99

95 % CI * O . O O O O ~ grams ('1

zt 0.081 % (b)

* 0.00051 grams (') * 0.3 pglg (a)

f 0.004 mg

* 0.000005 (O

* 0.000015 (' * 0.000007 (' * 0.000009 VI

* 0.000003 ('

rt 0.09 mCi (E' It 3E+06 Bq

q o b e r t LL,/*,JY S. Marshall, Project Manag

NDA WRM Production

Appendix B

Page 43: 1.EW 655139 ENGINEERING CHANGE NOTICE/67531/metadc742248/...I I 1. ECN (use no. from pg. 1) Page 2 of L ENGINEERING CHANGE NOTICE 16. Design Verification 17.Cost Impact Required ENGINEERING

MEASUREMENT METHOD AND TRACEABILITY

The nuclear C O d t e d t S of this standard were characterized an4 quantified wing the following methods with traceability to the National Institute of Standards and Technology (NET) or New BNoswick Laboratory W L ) standards.

Measurement Measurement Method Reference Material

Weighing 5 place analytical balance NIST traceable weights Pu Assay Controlled Potential Coulometry NBL CRM # 126 Am Assay Isotope Dilution Mass Spectrometry NBL CRM # 128

Pu Isotopic Total Evaporation Mass SpectrQrnetry NBL CRM # 128 Alpha Activity Calculated fromPu and Am mass, and

isotope alpha specific activities listed below. Pu tm as stated for NLST SW946

Am tm as stated for NIST SRM4322B .

218 The stated Alpha Activity was calculated using the following isotope half lives (in years): 24,119; Pu: 6,560; "'?hr: 14.34; Pu: 387,000; and Am: 432.2.

PU: 87.74; "'Pu: a40 141 341

Random and systematic e r ror terms were comblned and reported as 95% confidence intervals. E r ro r terms ioclude estimates of the following:

(a) Balance precision, buoyancy, standard wcight bias, and transfer loss. (b) Long and short term precbion, control check Vis, weighing precision and bias (c) Above weighing and assay terms, and transfer loss (d) Long and short term precision, and bias. (e) Above weighing terms, Am assay terms, and transfer loss. (0 Long and short term precision, and bias. (g) Based on propagated uncertainties on the Pu mass, "'Am mass and Pu isotopic uoeertninties listed

above. No half-life uncertainty components are included and it is recommended that all facilities participating in the ND.4 PDP program use the half-lives listed above to preclude facllity-to-facility cfror terms introduced by using different half life values.

Appendix B

Page 44: 1.EW 655139 ENGINEERING CHANGE NOTICE/67531/metadc742248/...I I 1. ECN (use no. from pg. 1) Page 2 of L ENGINEERING CHANGE NOTICE 16. Design Verification 17.Cost Impact Required ENGINEERING

HNF-105 1 Rev 4

Los Alamos National Laboratory amtifitate of aCotrtetrt atrb QJrateabilitp

PuOZ-Diatomaceous Earth Standard WRAP-2 500MGPU

This NDA standard contains high purity plutonium dioxide dispersed in diatomaceous earth. Quantitative information and uncertainties on the nuclear content of this WRM are listed below. Complete information regarding the Pu and Am content, Pu isotopic ratios, chemical composition, elemental impurities, containment, and fabrication procedures a r e retained in files by the Los Alamos National Laboratbry CMR Analytical Chemistry Group.

NUCLEAR MATERIAL CONTENT

The nuclear material content and total alpha activity for this standard are listed below. Also listed a r e overall uncertalnty estimates a t 95% confidence intervals (CT) for each component

Cornvonent Quantitv o r Value 95 Yo C I PuO, in standard 0.58708 grams * 0.00006 grams ('I

P u Assay 87.761 Yo ofPuO,* * 0.081 % @)

P u in standard 0.51522 grams i 0.00051 grams (') "'Am Assay ll28.9 pglgPu02* i 0.3 pglg (dl

Am in standard 0.582 mg* i 0.004 mg W 111

Isotopic Weight Fraction*

P u ua

U9Pu

2roPu

"'Pu

"2Pu

0.00014

0.93809

0.05939

0.00185

0.00054

i 0.000005 Io

-I 0.000015 lo

i 0.000007 lo

* 0.000009 & 0.000003

Total Alpha Activity in standard 35.21 mCi'* 1.303Et09 Bq i 3E+06 Bq

j: 0.09 m c i (0)

*Decay corrected value on 1/21/99 ** Effective 1121199

t

~

Robert S. Marshall. Project M a n a w d &IR Analytical Chemistry

. . . NDA WRbl Production

Appendix B

Page 45: 1.EW 655139 ENGINEERING CHANGE NOTICE/67531/metadc742248/...I I 1. ECN (use no. from pg. 1) Page 2 of L ENGINEERING CHANGE NOTICE 16. Design Verification 17.Cost Impact Required ENGINEERING

HNF-4051 Rev 4

b E A W R E M E N T METHOD ANDTRACEABILITY

The nuclear C O r t t c d k of this standard were characterized and quantified wing the following methods with traceability to the National Institute of Standards and Tcchnology (MST) or New Brunswick Laboratory 0yI)L) standards.

Measurement Measurement Method Reference Material

Weighing 5 place analytical balance NISI traceable weights Pu Assay Controlled Potential Coulometry Am Assay Isotope Dilution Mass Spectrometry

NBL CRM # 126

NBL CRM # 128

Pu Isotopic Total Evaporation Mass Spectrqmetry NBL CRM # 128 Alpha Activity Calculated nom Pu and Am mas, and

isotope alpha specific activities listed below. Pu tln as stated for NIST SRM946

Am tm as stated for NET SRM4322B .

a38 339 The stated Alpha Activity was calculated using the following isotope half lives (in years): 24,119; Pu: 6,560; "'PIX 14.34; Pu: 387,000; and Am: 432.2.

Pu: 87.74; PU: 140 141 141

Random and systematic error t e r m were combined and reported as 95% confidence intervals. Error terms include estimates of the following:

(a) Balance precision, buoyancy, standard weight bias, and transfer loss. (b) Long and short term precision, control check bias, weighing precision and bias ( c ) Above weighing and assay terms, and transfer loss (d) Long and short term precision, and bias. (e) Above weighing terms, Am assay terms, and transfer loss. ( f ) Long and short term precision, and bias. (g) Based on propagated uncertainties on the PU mass, "'Am mass and Pu isotopic uncertainties listed

above. No half-life uncertainty components a re inclnded and it is recommended that all facilities participating in the NDA PDP program w the half-lives listed above to preclude fncility-to-facility error t e r m introduced by using different half life values.

Appendix B

Page 46: 1.EW 655139 ENGINEERING CHANGE NOTICE/67531/metadc742248/...I I 1. ECN (use no. from pg. 1) Page 2 of L ENGINEERING CHANGE NOTICE 16. Design Verification 17.Cost Impact Required ENGINEERING

IMF-405 1 Rev 4

Los Alamos National Laboratory Certifitate of Content anb aratea'biritp

PuOz-Diatomaceous Earth Standard WRAP-I 5.OGPU

This NDA standard contains high purity plutonlum di0xid.e dispersed In diatomaceous earth. Quantitative information and uncertainties on the nuclear content of this WRM are listed below. Complete information regarding the Pu and Am content, Pu isotopic ratios, chemica) composition, elemental impurities, containment, and fabrication procedures are retained in files by the Los Alamos National Laboratory CMR Analytical Chemistry Group.

NUCLEAR MATERIAL CONTENT

Thenuclear material content and total alpha activity for this standard are listed below. A k a listed a r e overall uncertainty estimates a t 95% confidence intervals (CI) for each component.

Comuonent PuO, in standard

Pu Assay Pu in standard

"'Am Assay '"Am in standard

Isotopic Weight Fraction*

2J8Pu

u 9 p U

Z4OPU

'"Pu '4'PU

Quantitv o r Value 5.74627 grams

. 5.04298 grams 1128.9 pg/g Pu02*

5.69 mgf

87.761 % of PuO,"

0.00014

0.93809

0.05939

0.00185

0.00054

95 Yo CI f O.OOO~O grams

* 0.081 % f 0.00474 grams (')

* 0.3 pg/g (dl

f 0.04 mg

' =t 0.000005 VI

f 0.000015 (0

f 0.000007 (O

f 0.000009 (O

f 0.000003 (O

Total Alpha Activity in standard 344.6 mCi** 1.275E+10 Bq f 3E+07 Bq

f 0.9 mCi (e)

*Decay corrected value on 1/21/99 ** Effective 1/21/99 /7

/4%L422 d e Kobert S. Marshall, Project Manager a- NDA WRM Production

Appendix B

-I__. . ~- -

Page 47: 1.EW 655139 ENGINEERING CHANGE NOTICE/67531/metadc742248/...I I 1. ECN (use no. from pg. 1) Page 2 of L ENGINEERING CHANGE NOTICE 16. Design Verification 17.Cost Impact Required ENGINEERING

MEASCJRF.MJINT METHODANDTRACEABIJATY

The nucleat contents c this standard were chracterized and quantzed wiog the ,Ilowing methods with traceability to the National bst i fute of Stsndards and Technology (NIST) or New Brunvwick Laboratoly (NBL) standards.

Measurement Measurement Methcd Reference Materisl

Weighing 5 place analytical balance MST traceable weights Pu Assay Controlled Potential Coulometry NBL CRM # 126 Am Assay Isotope Dilution Mass Spectrometry NBL CRM # 128 Pu lsotopic Total Evaporation Mass Spectrometry hBL CRM # 128

Alpha Activity Calculated f romPu and Am ma%, and isotope alpha specific activities listed below.

Pu tln a8 stated for NIST SRM946 Am tm as slated for NIST

SRM4322B .

Y 8 139 The stated Alpha Activity was calculated using the following isotope half lives (in years): 24,119; "'Pu: 6,560; PU. 14.34; Pu: 387,000; and Am: 432.2.

Pu: 87.74; PIX 141 142 141

Random and systematic error terms were combhed and reported as 95% confidence intervah. Error terms include estimates of the following:

(a) Balance precision, buoyancy, standard weight bias, and transfer loss. (b) Long and short term precision, control check bias, weighing precision and bias (c) Above we igh ig and assay terms, and transfer lass (d) Long and short term precision, and bias. (e) Above weighing terms, Am assay terms, and transfer loss. ( f ) Long and short term precision, and bias. (g) Based on propagated uncertainties on the Pu mass, "'Am mass and Pu isotopic unce r t ab t i a listed

above. No half-life uncertainty components a re included and it is recommended that all facilities participating in the NDA PDP program use tbe half-lives listed above to preclude fncU@-iwfacaD' crror terms introduced by using different half life values.

Appendix B

Page 48: 1.EW 655139 ENGINEERING CHANGE NOTICE/67531/metadc742248/...I I 1. ECN (use no. from pg. 1) Page 2 of L ENGINEERING CHANGE NOTICE 16. Design Verification 17.Cost Impact Required ENGINEERING

HNF-405 i Rev 4

%os Marnos National Laboratory

- . PuOz-Diatomaceous Earth Standard '1yRAp-2 5.OFPU , .

.This NDA s tandard contains high puri ty plutonium dioxide dispersed in diatomaceous ear th . Quantiiative information and uncertainties on the huclear content of this %'A are listed below. Co'mpiete Information regarding the P u a n d A m content, Pu isotopic ratios, chcmical composition, elkmental Impurities, containment, a n d fabrication procedures are retained& files by the Los Alamos National Laboratory CbGR Analytical Chemistry Group.

NUCLEAR M A T E R ~ A L CONTENT

The nuclear material content a n d total alpha aclivity for thisstandard are listed below. Also listed areoverali uncertainty estimates a t 95% conQdence intervals (CI) for each component.

Cornponenl g u a a r i t v or Value 95 % CI PuO, i n s t a n d a r d 5.71060 grams * O . O O O ~ I grams (')

Pu,in s t a n d a r d 5.01168 grams rt 0.00372 grams(" Pu Assay . ' 87.761 %'ofPuOl* t 0.081 %

l4'Arn Assay . . 1128.9 jlg/gpuo,* i 0.3 pg/g (d)

'"Am i n s tandard 5.66 mg* , i 0.04 mg+)

Isotopic Weight Fraction"

'lsPu 0.00014 .10.000005(o

"sPu 0.93809 t0 .000015(o

0.05939 t 0.000007(q ""u J4IPu 0.00185 z t 0.000009 (0

""pu 0:00051 & 0.000003 ('

iO.9 rnCi'I' Total Alpha Activity in s tandard 342.5 rnCih* ' 1.267E-PlO Bq 13E+07 Bq'"

'Decay corrected value on 1/21/99 + * Effective 1/21/99

Robert S. Marshall, Project M a n a g e r P;DA lVRM Production

Appendix B

Page 49: 1.EW 655139 ENGINEERING CHANGE NOTICE/67531/metadc742248/...I I 1. ECN (use no. from pg. 1) Page 2 of L ENGINEERING CHANGE NOTICE 16. Design Verification 17.Cost Impact Required ENGINEERING

MNF-4051 Rcv 4

MEASUREMENT METHOD AND TRACEABILITY

The nucleat contents of t h h standard were characterized and quantified m h g the following methods with t h c e a b a t y to the National Institute of Standards and Technology (EnsT) or New Bnrnswick Laboratory (NBL) standards.

Measurement Measurement Method Reference Material

Wcighing 5 place analytical balance '. MST traceable weights NBL CRM # 126 Pu &say Controlled Potential Coulometry

AmArsay Isotope Dilution M a s Spectrometry NBL CRM # 128 Pu Isotopic Total Evaporation Mass Spedi$rnett$ NBLCRM#128

. .

Alpha Activity Calculated from Pu and Am mas, and isotope alpha specific activities listed below.

Pu tln as stated for NJST SRM946 Am tin as stated for NIST

SRM4322B

ud 139 The stated Alpha Activity was calculated using the following isotope half lives (in years): 24,119; Pu: 6,560; PU: 14.34; Pu: 387,000; and"'Am: 432.2.

PU: 87.74; Pu: 310 241 143

m S

Random and systematic error terms were combined and reported as 95% confideoce intervalr. Er ror terms include estimates of the following:

(a) Balance precision, buoyancy, standard wcight bias, sod transfer loss. (b) Long and short t e rm prec'uion, control check bias, weighing precision and bias. (c) Above weighing a n d assay terms, and transfer loss. (d) Long and short t e rm precision, and bias. (e) Above weighing terms, Am assay terms, and transfer loss. (0 Lone and short t e rm precision, and bias. (s) Based on propagated uncertaintics on the Pu mass, "'Am mass and Pu isatopic uncertainties listed

above. No half-life uncertainty components a r e included and it is recommended tha t all facilities participating in tbc ND.4 PDP p r e r a m use the half-lives listed above t o preclude ficW'-to-fac~tY error t c r m introduced by using different half Life vallies.

Appendix B

Page 50: 1.EW 655139 ENGINEERING CHANGE NOTICE/67531/metadc742248/...I I 1. ECN (use no. from pg. 1) Page 2 of L ENGINEERING CHANGE NOTICE 16. Design Verification 17.Cost Impact Required ENGINEERING

HNF-4051 Rev4

Lss Marnos National. Laboratory

Pu02-Diatomaceous Earth Standard WRAP-3 5.OGPU

This N D A standard contains high purity plutonlum dioxide dispersed In diatomaceous earth. Quantitative information and uncertainties on the nuclear content or thls WRM a re listed below. qdmplele information regarding the P u and Am content, Pu isotopic ratios, chemical composition, clemental impurities, , containment, and fabrication procedures are retainedih files by the Los Alamos Nalional Laboratory CMR Analytical Chemistry Group.

NUCLEAR hlATERIAL CONTENT

The nuclear mathrial content and total alpha activily for this standard a r e listed below. Also listed a re overall uncertainty estimates a t 95% confidence intervals (CI) for each component.

Component Quantity or Value 95 O h CI PuO, i n standard 5.69429.grams * 0.00031 grams (*)

P u Assay 87.761 % ofPuQ,* i: 0.081 % (b)

Pu in standard ' 4.99736 grams + 0.00476 grams ('I

"'Am Assay . 1128.9 pg/g PuOl*' t 0.3 pg!g "'Am in standard 5.64 mg* -L 0.04 mg

Isotopic Weight Fraction*

~'JPU 0.00014

PU 0.93809 a w

'%I 0.05939 '

Y U 0.00185

Z'ZPU 0.00054

-L 0.000005

6z 0.000015

t 0.000007 "

-L 0 . 0 0 0 0 0 9 ' ( ~

i 0.000003 ('

Total Alpha Activity i n standard 311.5 mCi** 50.9 mCi (') I I 1.263E+10 Bq i: 3Et07 Bq

'Decay cor'rccled value on 1121199 **Effective 1/21/99

obert S. NDA WRM Production

Appendix B

Page 51: 1.EW 655139 ENGINEERING CHANGE NOTICE/67531/metadc742248/...I I 1. ECN (use no. from pg. 1) Page 2 of L ENGINEERING CHANGE NOTICE 16. Design Verification 17.Cost Impact Required ENGINEERING

1~Ih'F-405 1 Rev 4

MEASZTREMENT METHOD AND TRACEABILITY

Thc nucleic contents of this standard were characterized nnd quantified wing the followin,o methods with traceability to the National h t i t u t e of Standards and Technology (NIST) or New Brunswick Laboratory W L ) standards.

Measurement yeasurement Method Reference Material

Weighing 5 place analytical balance NISI traceable weights Pu Assay Controlled Patential Coulometry

A m b Y Isotope Dilution M a s Spectrometry NBLCRM#126 NBL CRM # 128

Pu Lsotopic Total Evaporation Mass Spedroinetry NBL CRM # 128 Alpha Activity Calculated from Pu and Am mass, and

isotope alpha specific aetivities listed below. Pu t l n as stated for h7ST SRM946

Am tm as stated for NLST SRM4322B

ud aa) The stated Alpha Activity was calculated using the following isotope half lives (in years): 24,119; Pu: 6,560; PU: 14.34; "bu: 387,000; and Am: 432.2.

Pu: 87.74; PIX 140 Y1 1 4 1

NOTES

Random and systematic error t e r m were combloed and reported as 95% confidence interval$. Error terms include estimates of the following:

(a) Balance precision, buoyancy, standard weight bias, and transfer Icss. (b) Long and short term precision, control check bias, weighing precision and bias (c) Above weighing and assay terms, and transfer loss. (d) Long and short term precbion, and bias. (e) Above weighmg terms, Am assay terms, and transfer loss. (r) Long and short term precision, and bias. (9, Based on propagated unccrtaintics on thc Pu mass, "'Am mass and Pu Atopic uncertainties listed

above. No balf-life uncertainty components a r e idcladed and it is recommended that all facilities participating in tbc ND.4 PDP program use the half-lives listed above to preclude facility-twfacility error terms introduced by using different half life vallies.

Appendix B

Page 52: 1.EW 655139 ENGINEERING CHANGE NOTICE/67531/metadc742248/...I I 1. ECN (use no. from pg. 1) Page 2 of L ENGINEERING CHANGE NOTICE 16. Design Verification 17.Cost Impact Required ENGINEERING

HNF-405 1 Rev 4

Los ABamos National Laboratory

PuOZ-Diatomaceous Earth Standard WRAPlOGPU

This NDA standard contains high purity plutonium dioxide disperscd in diatomaceous ealth. Quantitativc 'information a n d uncertainties on the nuclear content of thls W i I a re listed below. Cohpletc information regarding the Pu a n d Am content, Pu isotopic ratios, chemical composition, elekental impurities, containment, and fabrication procedures a t e retained i j files by the Los Alamos National Laboratory CMR Analytical Chemistry Group.

a ' NUCLEAR MATERIAL CONTENT

The nuclear material content a n d total alpha activity for this standard a re listed below. Also listed a r e overall uncertainty estimates a t 95% confidence intervals (CI) for each component.

Componcnt PuO, in standard

Pu Assay P u i n standard

"'Am Assay ,2''Am'in standard

Isotopic Weight Fraction"

l J a P U

='PU lroPu

"'PU 14?pu

Quantitv or Valuc 11.40156 grams

10.00612.grarns 1128.9 pg/gPuOl*

11.30 mg"

87.761 % of PuO>*

0.00014

0.93803

0.05939

0.00165

0.00054

-L-o.ooooo~ (0

10.000015 (O

:t 0.000007

j: 0.000009

i 0.000003

Total Alpha Activity i n standard 2.530E-1-10 Bq 5 7Ei07 Bq

*Decay corrcctcd value on 1/21/99 Effective 1/21/99

N D A WYRM Production

Appendix B

Page 53: 1.EW 655139 ENGINEERING CHANGE NOTICE/67531/metadc742248/...I I 1. ECN (use no. from pg. 1) Page 2 of L ENGINEERING CHANGE NOTICE 16. Design Verification 17.Cost Impact Required ENGINEERING

HNF-4051 Rev 4

MXASUREMENI METHOD ANDTRACEABILITY

The nuclear contcn.ts of thb standard were characterized and quantilied ming the following methods with traceability to the National Institute of Standard3 and Techpology (MST) or New Bnrnswick Labon to ry (NBL) standards.

Measurement Measurement Method Reference Material

Weighing 5 place analytical balance '. NIST traceable weights NBLCRM#126 Pu h s a y Controlled Potential Coulometry

Am A G y Isotope Dilution M a s Spectrometry NBL CRM # 128 . .

Pu Isotopic Total Evaporation Mass Spedro ine tG NBL CBM #/ 128 Alpha Activity Calculated from Pu and Am mas, and

isotope alpha specific activities listed below. Pu tln as stated for NLST SRM946 .

Am tm as stated for NIST SRii4322B

m 239 The stated Alpha Activity was calculated using the fallowing isotope half lives (in years): 24,119; 140Pu: 6,560; Pu: 14.34; Pu: 387,000; and "'Am: 432.2.

Pu: 87.74; PU: MI 14).

Random and systematic error t e r m were comblned and reported as 95% contidence intervah Error terms include estimates of the following:

(a) Balance preckion, buoyancy, standard wcight bias, and tran3fer loss. (b) Long and short t e rm preckion, control check bias, weighing precision and bias (c) Above weigbing and assay terms, and transfer loss (d) Long and short term precision, and bias. (e) Above wcigbing t e r m , Am assay t e r m , and transfer loss. (0 Long and short term preckion, and bias. (s) Based on propagated uncertainties on the Pu m a s , "'Am mass and Pu Atopic uncertainties listed

above. No balf-life uncertainty components a re included and it is recommended that all facilitiM participating in the ND.4 PDP program w the half-lives Lirted above to preclude facZW-tO-hCaQ' crror t e r m introduced by using different half Life vallies.

Appendix B

Page 54: 1.EW 655139 ENGINEERING CHANGE NOTICE/67531/metadc742248/...I I 1. ECN (use no. from pg. 1) Page 2 of L ENGINEERING CHANGE NOTICE 16. Design Verification 17.Cost Impact Required ENGINEERING

HNF-4051 Rev4

Los Allamos National Laboratory

Pu02-Diatomaceous Earth Standard WRAP20GPU

This NDA standard contains hlgh purity plutonium dioxide dispersed In diatomaceous ehrth. Quantitaiive Information and.unccrtaintis~ on thenuclear content or.this WRM are listed below. Cdmplete information regarding the Pu and Am contcnt, Pu isotopic ratios, chemical composition, . c l k n t a l impurities, containment, and fabrication procedures a te retained Jn files by the Las Alamos National Laboratory CMR Analytical Chemistry Group.

NUCLEAR MATERIAL CONTENT

The nuclear material content and total alpha activity for Lhls standard a r e listed below. Also listed a r e overall uncertainty estimates at 95% confidence intervals (CI) for each component.

Cornponeot Puo, in standard .

P u Assay

'"Am Assay "tAm in standard

Pu lns t anda td . .

Isotopic Weight Fraction*

l IJp , ' .

a " P u 1ropu

'%I

'J?pu

Total Alpha Activity i n standard

Quantity or Value 22.79925 grams

87.761 % ofPuO,* 20.00884 grams

1128.9 pz/g PuOlx 22.59 mg*

0.00014

0.93809

0.05939

0.00185

0.00054

1361 mCi*'

rt 0.00062 grams ('I t 0.081 % 0)

I0.01875 grams ('I t 0.3 pg/g (d)

t 0:17 mg (4

5 059EilO Bq j: 1Et08 Bq (')

*Decay corrcctcd value on 1R1199 * * Effective 1121199

n

NDx WRM Production

Appendix B

Page 55: 1.EW 655139 ENGINEERING CHANGE NOTICE/67531/metadc742248/...I I 1. ECN (use no. from pg. 1) Page 2 of L ENGINEERING CHANGE NOTICE 16. Design Verification 17.Cost Impact Required ENGINEERING

IlNf?-4051 Rev 4

MEASLmEMEKT METHOD AND TRACEABLLITY

The nuclear contcnb of thh standard were characterized and quantified using the following methods with traceability to the National Incititute of Standards and Technology (NLSr) or New Bruoswick Labontory (NJilL) standards.

Measurement Measurement Method Reference Material

Weighing 5 place analytical balance NIST traceable weights Pu Assay Controlled Potential Coulometry NBLCRM#126 A m b Y Isotope Dilution Maw Spechometry NBL CRM # 128

Pu Isotopic Total Evaporation Mass Spedio'metty NBLcRM#128 Alpha Activity Calculated from Pu and Am mas, and

isotope alpha specific activities listed below. Pu t ln a9 stated for NIST SRM946

Am tul as stated for NIST SRM4322B

J a 119 The stated Alpha Activity wag calcula!ed using the following isotope balf lives (in years): 24,119; Pu: 6,560; PU: 14.31; "'Pu: 387,000; and"'Am: 432.2.

Pu: 87.74; Pu: 140 241

Rnndom and systematic crror terms were combined and reported as 95% confidence intervals. Error terms include e s tha t e s of the following:

(a) Balance prcckion, buoyancy, standard weight bias, and transfer loss. (b) Long and short term precision, control check bias, weighing precision and bias. (c) Above weigbing and assay terms, and transfer loss. (d) Long and short term precision, and bias. (e) Above weigbing terms, Am assay terms, and transfer loss. (Q Long and short term precision, and bias. (g, Based on propagated uncertainties on thc PU mass, "'Am mass and PU isotopic uncertninties listed

above, No half-life uncertainty components a r e included and it is recommended that all tacilitiea participating in the ND.4 PDP program use the half-lives listed above to preclude f ic f iWtO-fEC~V crror t erm introduced by usiag different half life vatues.

Appendix B

Page 56: 1.EW 655139 ENGINEERING CHANGE NOTICE/67531/metadc742248/...I I 1. ECN (use no. from pg. 1) Page 2 of L ENGINEERING CHANGE NOTICE 16. Design Verification 17.Cost Impact Required ENGINEERING

INF-405 1 Rev 4

Los Alamos National Laboratory Qertifitate of VContent anb llCrarteabiIitp

Pu02-Diatomateous Earth Standard WRAP30GPU

This NDA' standard contains high purity plutonium dioxide dispersed in diatomaceous earth. Quantitative information and uncertainties on the nuclear content of this WFW a r e listed below. Complete information regardlng the Pu, a n d Am content, Pu isotopic . ratios, chemical composition, elemental impurities, containmenf and fabrication procedures are retained & files by the JAS Alamos National Laboratory CMR Analytical Chemistry Group.

NUCLEAR MATERIAL CONTJZNT

The nuclear material content and total alpha activity for this standard a r e listed below. Also listed are overall uncertainty estimates a t 95% conpdence Intervals (CI) for each component.

Comuonent guantity or Value 95 Yo CI PuO, in standard 34.19337 grams * 0.~0101 grams (*)

Pu Assay 87.761 Yo oIPuO~' * 0.081 % (b) Pu in standard 30.00842 grams * 0 . 0 ~ 8 1 ~ grams ('1

'"Am Assay 1128.9 pglg P u O ~ * * 03 pg/g (d)

"'Am in standard 33.88 mg* A 0.26 mg

Isotopic Weight Fraction* I 0.00014

0.93809

0.05939

0.00185

0.00054

* 0.000005 It)

t 0.000015 "

& 0.000007

i 0.000009 (O

* 0.000003 ('

Total Alpha Activity in standard 2051 mCi'* * 5 mCi '0 7.587E+10 Bq * 2E+08 Bq

*Decay carrectcd value on 1/21/99 ** Effective 1/21/99

n

NDA WRM Production

Appendix B

7

Page 57: 1.EW 655139 ENGINEERING CHANGE NOTICE/67531/metadc742248/...I I 1. ECN (use no. from pg. 1) Page 2 of L ENGINEERING CHANGE NOTICE 16. Design Verification 17.Cost Impact Required ENGINEERING

ITNF-4051 Rev 1

MEASLmE MEW METHOD AND TRACZABILW

The nuclear contcnL4 of thi, standard were characterucd and quantXed wing the following methods with traceability to the National Institute of Standards and Techqology (MST) or New Brunswick Laboratory OyBL) standards.

Measurement Measurement Method Reference Material

Weighing 5 place analytical balance NIST traceable wei$ts PU Assay Controlled Potential Coulometry NBL CRM # 126 A m h Y Isotope Dilution Mass Spectrometry NBL CRM # 128 Pu Isotopic Total Evaporation Mass Speciioinet& MlLcILM#128

Alpha Activity Calculated from Pu and Am mass, and isatape alpha specific activities listed below.

Pu tln as stated for NJST SRM946 Am tm as stated for NIST

SRM4322B

aM 1a9 The stated Alpha Activity was calculated using the following isotope half lives (io years): 24,119; pu: 6.,560; PU: 14.34; Pu: 387,000; and ’“Am: 432.2.

Pu: 87.74; PIX 140 a41 14’

Random and systematic error t e r m wcre combhed and reported as 95% contidence interval% Er ro r terms include estimates of the following:

(a) Balance precision, buoyancy, standard weight bias, end transfer loss. (h) Long and short term prechion, control check bias, weighing precision and bias (c) Above weighing and assay terms, and transfer loss (d) Long and short t e rm precision, and bias. (e) Above wcigbiag terms, Am assay terms, and transfer loss. (I) Long and short term precision, and bias. @ Based on propagated uncertainties on the Pu m a s , ’“Am mass and Pu isotopic uncertainties listed

above. No half-life uncertainty components are inclnded and i t is recommended that all hcilities participating i n the ND.4 PDP program use the half-lives listed above t o preclude h c ~ V - t w f i C x V errar tcrms introduced by using different half Life values.

Appendix B

Page 58: 1.EW 655139 ENGINEERING CHANGE NOTICE/67531/metadc742248/...I I 1. ECN (use no. from pg. 1) Page 2 of L ENGINEERING CHANGE NOTICE 16. Design Verification 17.Cost Impact Required ENGINEERING

KNF-1051 Rev 4

Los Alamos National Laboratory Certificate of UContent anb '(2CrateabiIitp

Pu02-Diatomaceous Earth Standard WRAP40GPU

Thls NDA standard contalns high purity plutonium dioxide dispersed i n diatomaceous earth. Quantitative information and uncertainties on the nuclear content o f t h i s WRM are listed below. Complete information regarding 'the Pu and Am content, Pu isotopic ratios, chemical composition, elemental impurities, containment, and fabrication procedures are retained .hi files by the Los Alamor National Laboratory CMR Analytical Chemistry Group.

NUCLEAR MATERIAL CONTENT

The nuclear material content and total alpha activity for this standard are listed below. Also listed a r e overall uncertainty estimates a t 95% confidence intervals (CQ for each component.

Component Quantitv or Value 95 % CI PuO, instandard 45.58093 grams i0.00111 grams(')

Pu in standard. 40.00226 grams i 0.03740 grams (4 Pu Assay 87.761 % of PuOl' i 0.081 % (b)

"'Am Assay 1128.9 pg/g PUOI* I 0.3 vg/g (d)

"'Am in standard 45.16 mg* I 0.35 mg

Isotopic Weight Fraction*

0.00014

0.93809

0.05939

0.00185

0.00054

i O.OOOOO5

& 0.000015 ('

* 0.000007 ('

I 0.000009

i 0.000003 ('

Total Alpha Activity in standard 2733 rnCi'* I 7 mCi W . I .OlIE+ll Bq I 3Et08 Bq

*Decay corrected value on 1/21/99 ** Effective 1121199

€ $ l U cKerley, G&dp Leader kMR Analytical Chemistry

Appendix B

( - $ a & , J g obert S. Marshall, Project Manag

NDA WRM Production

Page 59: 1.EW 655139 ENGINEERING CHANGE NOTICE/67531/metadc742248/...I I 1. ECN (use no. from pg. 1) Page 2 of L ENGINEERING CHANGE NOTICE 16. Design Verification 17.Cost Impact Required ENGINEERING

HNP-405 1 Rev 4

MEASUREMENT METHOD AND TRACEABILITY

The nuclear ContcnLS of thh standard were characterized and quanthied using the following methods with traceability to the National h t i t u t e of Standards and Technology (NET) or New BNoswick Laboratory (NFJL) standards.

Measurement Measurement Method Reference Material

Weighing 5 place analytical balance MST traceable weights Pu Assay Controlled Potential Coulometry NBLCRM#126 A m h Y Isotope Dilution Mass Spectrometry NBL CRM # 128

Pu Isotopic Total Evaporation Mass Spectrometry NBL CRM # 128 Alpha Activiry Calculated from Pu and Am mu, and

isotope alpha specific activities listed below. Pu tln as stated for NIST SRM946

Am tn as stated for NIST SRM4322B

yd 2J4 The stated Alpha Activity was calculated using the following isotope half lives (in years): 24,119; Pu: 6,560; PU: 14.34; '"Pu: 387,000; andl"Am: 432.2.

Pu: 87.74; PU: 140 241

Random and systematic crror t e r m were comblned and reported as 9.5% confidence intervak. Error terms include estimates of the following:

(a) Balance precision, buoyancy, standard weight bias, and transfer loss. (b) Long and short t e rm precuion, control check bias, weighing precision and bias (c) Above weighingand assay terms, and transfer loss. (d) Long and short term precision, and bias. (e) Above wcigbing terms, Am assay terms, and transfer loss. ( f ) Long and short term preckion, and bias. (9, Based 00 propagated uncertaintics on the Pu mass, '"Am m s s and Pu htopic uncerfainties listed

above. No half-lie uncertain;y components a re included and it is recommended tha t all (acilities participating in tbe ND.4 PDP program use the half-lives Listed above to preclude facfitS;-to-faC~tY crror tcrms introduced by wing different half Life vallies.

Appendix B

Page 60: 1.EW 655139 ENGINEERING CHANGE NOTICE/67531/metadc742248/...I I 1. ECN (use no. from pg. 1) Page 2 of L ENGINEERING CHANGE NOTICE 16. Design Verification 17.Cost Impact Required ENGINEERING

HNF-405 1 Rev 1

Los Alamos National Laboratory Certifitate of QContelrt anb IEraceabiIitp

PuOZ-Diatomaceous Earth Standard WRAPSOGPU

This NDA standard contains high purity plutonium dioxide dispersed in diatomaceous earth. Quantitative information and uncertainties on the nuclear content of this WRM a r e listed below. Complete information regarding the Pu and Am content, Pu isotopic ratios, chemical composition, elemental impurities, containment, and fabrication procedures are retained $ files by the Los Alamos National Laboratory CMR Analytical Chemistry Group.

NUCLEAR MATERTAL CONTENT

The nuclear material content and total alpha activitv for this standard are listed below. Also listed are overall uncertainty estimates a t 95% confidence intervals (CI) for each component

Componeot Pu02 in standard

Pu Assay Pu in standard

'"Am Assay "'Am in standard

Quantity or Value

56.99360 grams 87.761 % Of PuOI*

50.01813 grams I 0.04661 grams

56.47 mg* -L 0.43 mg

95 % CI i 0.001 12 grams ('1

IO.081 % @)

1128.9 pg/g PUOl* .L 0.3 pg/g (d)

Isotopic Weight Fraction*

='PU

'39Pu

""PU

'''Pu

"1PU

Total Alpha Activity in standard

0.00014

0.93809

0.05939

0.00 i 85

0.0 0 0 5 4

3418 mCi"

i 0.000005

-L 0.000015(0

& 0.000007 ('

.L 0.000009 (0

-I 0.000003 ('

t 9 mCi

I 1.265EilI Bq rc. 3Ec08 Bq"

'Decay corrected value on 1RI199 +* Effective 1/21/99

Bi .b& Kerley, C r o a e a d e r C k Analytical Chemistry NDA WRM Production

Appendix B

__

Page 61: 1.EW 655139 ENGINEERING CHANGE NOTICE/67531/metadc742248/...I I 1. ECN (use no. from pg. 1) Page 2 of L ENGINEERING CHANGE NOTICE 16. Design Verification 17.Cost Impact Required ENGINEERING

1-INF-4051 Rev4

MEASURE MEW METHOD AND TRACEABKLm

The nuclear con'tcn.ts of tbh standard were characterized and quantified Oshg the following methods with traceability to the National h t i t u t c of Standards and Tcchpology (NIST) or New Brunswick Laboratory (NBL) standards.

Measurement Measurement Method Reference Material

Weighing 5 p b c e analytical balance NIST traceable wei$ts Pu h a y Controlled Potential Coulometry NFJLCRM#126 b h Y Isotope Dilution M a s Spectrometry Pu Isotopic Total Evaporation Mass Speciroinetry

NBL CRM # 128

NBL CRM # 128

Alpha Activity Calculated from Pu and Am mass, and isbtope alpha specific activities listed below.

h tln as stated for NlST SRM946 . Am tm as stated for NIST

SRM4322B

m 139 The stated Alpba Activity was calculated using the following isotope half lives (in years): 24,119; Pu: 6,560; 14.34; Pu: 387,000; and"'Am: 432.2.

PU: 87.74; PU: 140 I,>

NOTES

Random and systematic error terms wcre comblned and reportcd as 95% confidence interval% Error t e r m include estimates of the following:

(a) Balance prccbion, buoyancy, standard wcight bias, and transfer loss. (b) Lo% and short term precision, control check bias, weighing precision and bias. (c) Above weighing a n d assay terms, and transfer loss. (d) Long and short te rm precision, and bias. (e) Above wcigbing terms, Am assay terms, and transfer loss. ( f ) Long and short te rm precision, and bias. @ Based on propagated uncertainties on the Pu m a s , '"Am mass and Pu isotopic uncertaintics listed

above. No half-life uncertainty components are included and i t is recommended tha t all facilities participating i n the ND.4 PDP program we the half-lives listed above to preclude facility-t*fiCxQ' crror tcrms introduced by using different half Life valiies.

Appendix B

Page 62: 1.EW 655139 ENGINEERING CHANGE NOTICE/67531/metadc742248/...I I 1. ECN (use no. from pg. 1) Page 2 of L ENGINEERING CHANGE NOTICE 16. Design Verification 17.Cost Impact Required ENGINEERING

DISTRIBUTION SHEET

HNF-4051, Rev. 4, Quality Assurance Objectives for NDA at the WRAP Facility

To From Page 1 of 1 Distribution Proiect Titleiwork Order Date 02/25/00

EDTNo. NJA

ECN No. ECN-655139

Name

MG Cantaloub

WG Jasen

Attach” EDT/ECN Text With All Text Only Appendix

Only MSlN Attach. Only

T4-52 X

T4-05 X

JK Kersten T4-52 X

A-6000.135 (10197)

JL MauDin T4-06 X

MA Purce11

WR Thackaberry

CE Taylor

~

T6-50 X

T4-52 X

T4-52 X

JR Weidert

CE Wills

DOEjRL Reading Room

Engineering Files

T4-52 X

T4-52 X

H2-53 X

B1-07 X