16715-voice & data cabling

Upload: uddinnadeem

Post on 02-Apr-2018

219 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/27/2019 16715-Voice & Data Cabling

    1/16

    SECTION 16715

    VOICE AND DATA COMMUNICATION CABLING

    00000000PART 1 - GENERAL

    1.1 DESCRIPTION:

    A. The Work shall consist of furnishing and installation of voice and datacommunication cabling as shown on the drawings and specified herein.

    B. Basic Criteria:

    A complete structured cabling system shall be designed based on ISO/IEC11801 2002, EIA/TIA 568A, B. and EIA/TIA 569. The system shall be unified andsupports telephone, data, video and others. The system shall support Ethernetas defined by IEEE 802.3 standard and shall be open to any new applicationsthat require an ISO/IEC 11801.

    Structured cabling system shall be installed, tested certified and guaranteed byan authorized supplier/contractor. The warranty shall provide performanceguarantee for 20 years.

    The system shall support IEEE 802.3 10GBASE-T 10 Giga speed (CAT 6A)component, and shall be configured in star configuration with full redundancyusing fiber optic as back bone and UTP category 6A horizontal cable to eachcommunication outlets

    The system shall include, but not limited to:

    Backbone Cabling (dual 12 core Fiber optic cables)

    Horizontal cabling (UTP)

    Telecommunication face plates and outlets

    Patch Panels

    Patch Cords and connection cords

    Equipment Racks

    Modular rack-mounted UPS

    Pathways

    All the component of the structured cabling system shall be as required by IHG-IT specs and as per the requirement of CAT 6a (Class Ea) as per EIA/TIA 568A,B and ISO/IEC 11801 and. and shall meet the following minimum requirement:

    C. BackboneCabling:

    The intra building cabling system shall be designed to support 10 Gbps Ethernetbased converged networking to ANSI, TIA and EIA standards with all networkendpoints designed to support 10/100/1000 Mbps.Dual 12 core Tight-buffered multimode fiber optic 50/125 cables will provideconnectivity between the main telecom room and each comm. room. Thistopology will allow for redundant connectivity to both Guest and Admin network

    active equipment, the implementation of future technologies and ensurescapability to implement a 10 Gbps Ethernet backbone throughout the hotel.

    ITCC in RiyadhResidential ComplexJ10-13300

    16715-1Voice & Data Communication

    Cabling

  • 7/27/2019 16715-Voice & Data Cabling

    2/16

    The backbone fiber cables will be terminated with either SC or LCconnectors and housed in rack mounted optical fiber patch panels.All cables will be Low Smoke Zero Halogen (LSZH) sheathing materialthat does not give off toxic fumes in case of fire.Single mode fiber optic cables shall be used to cover long distances.

    D. Horizontal Cabling:

    The horizontal cabling shall be 4 pairs Unshielded Twisted Pairs (UTP) category6a.

    The cable shall have solid conductor of 0.55mm diameter. Cable shall be PVCinsulated and twisted and shall be LSZH (low smoke Zero Halogen).Performance and twisting shall be guaranteed to meet or exceed the ISO/IEC11801 standard

    Each Telecommunication outlet shall have two cables in general

    Fiber optic cables can be used for the horizontal cabling if the distancesbetween telecommunication outlet and patch panel communication cabinetexceeds 90m.

    Telecommunication Outlets (Faceplates):

    As recommended by the ISO/IEC 11801 standard at least 2 RJ45 outlets perTelecommunication outlet.

    Connection shall be provided for data services to a PC, network printer,or network computing equipment including antennas for wireless IP LANapplications, Voice over IP telephone outlets, P.O.S. outlets, IPTV / HiTV

    outlets, High Speed Internet Access outlets and Digital Signage outlets.Data cables (horizontal data, copper data patch cables and interfacecables) shall be terminated using standard RJ-45 plugs or sockets asappropriate.

    For back of house offices Telecommunication Outlets shall follow the furniturelayout i.e. one telecommunication outlet for each workstation or minimum oneoutlet for each 10 m2 of usable workspace where there is no recommendation orfurniture layout.

    Every back of house office shall have a minimum of one Telecommunicationoutlet (one faceplate with 2 RJ45 outlets)A minimum of four RJ45 outlets shall be provided in meeting rooms fortelephone, TV and other services.RJ45 outlets shall be provided in front of house areas where telephone, TV,workstations and network printers are planed to be located.A minimum of five RJ45 outlets shall be provided for guest room. These will beused for:

    3x Telephone handsets

    1x In room Entertainment (IPTV and Hi TV system)

    1x RJ45 for future use

    The wall-mounted faceplate shall match the wiring devices finishes and shapeand it shall accept modular type RJ45 outlets (2 or 4 as required)

    ITCC in RiyadhResidential ComplexJ10-13300

    16715-2Voice & Data Communication

    Cabling

  • 7/27/2019 16715-Voice & Data Cabling

    3/16

    E. Patch Panels:

    Copper patch panels must have 19 to fit in the standard 19 cabinet, rack orbay. Patch panels must be modular, and have RJ45 connectors. A typical 1HUhigh patch panel shall have 24 port modular snap-in RJ45 connectors

    Performance and specification shall meet or exceed CAT 6a ISO/IEC 11801The optical fiber patch panel must have 19 to fit in the standard 19 cabinet,rack or bay. The patch panel shall support the ST or SC connector type.

    All patch panels, patch cord and accessories shall be CAT 6a rated.F. Pathways:

    The Containment Pathways comprise conduit, riser openings, cable traysystems and containment for the vertical and horizontal cabling. Thevolume of the pathways required to support each area will be calculated

    using standards based criteria of the project.

    Current and future requirements will be considered in the design of thepathways for this project with sufficient additional capacity provided inorder to accommodate future moves, add, and changes to the systems.All pathways and support systems will be sized for an installed capacityof 50% i.e. no trunking or cable tray shall be more than 50% occupied oninstallation.

    The pathways linking the main telecom room, comm. rooms and Outletswill consist of dedicated vertical and horizontal cable trays and conduits.Cable Trays shall be of hot dip galvanized steel, to provide physicalprotection from a service-level environment, and electrical protection from

    EMI/RFI and other signaling interferences.

    All pathway routes shall be coordinated with other building services(electrical, mechanical, plumbing, etc.) to assure proper clearance andaccess, as well as to avoid impact from heat, electro-magneticinterference or leakage from other building services. A separation of300mm between parallel runs of telecommunications and electricalcabling shall be maintained.

    Backbone copper and optical fiber cabling will follow the vertically andhorizontally aligned routes to carry the backbone cables to theirrespective termination equipment.

    For horizontal cabling, 25mm conduit shall be provided from the trayinfrastructure to each telecommunications outlet location.

    1.2 REFERENCES:

    A. SASO - Saudi Arabian Standards Organization .

    ITCC in RiyadhResidential ComplexJ10-13300

    16715-3Voice & Data Communication

    Cabling

  • 7/27/2019 16715-Voice & Data Cabling

    4/16

    SASO 1357 Electrical installation of buildings Part 7: Requirementsfor special installation or locations Section 707:Earthing Requirements for the installation of dataprocessing equipment.

    B. ISO International Standards Organization

    ISO/IEC 11801 Information Technology Generic Cabling for CustomerPremises

    ISO/IEC TR 14763-1 Information technology Implementation and operationof customer premises cabling Part 1: Administration

    ISO/IEC TR 24750 Information Technology Assessment of installedbalanced cabling channels in order to support 10GBASE - T

    C. IEC - International Electrotechnical Commission

    IEC 60603-7 Connectors for Electronic Equipment Part 7-1 & 7-7

    IEC 60793 All parts relevant to these Specifications

    IEC 60794 All parts relevant to these Specifications

    IEC 61156-1 to 6 Multicore and symmetrical pair/quad cables for digitalcommunications Part 1 to 6

    IEC 61935-1 & 2 Generic cabling systems Specification for the testing of

    balanced communication cabling in accordance withISO/IEC 11801 Part 1 & 2

    IEC 60332 Test on electric cables under fire conditions

    IEC 60754 Test on Gases Evolved During Combustion of Materialfrom Cables

    D. EIA - Electronic Industries Association

    RS-453 Dimensional, Mechanical and Electrical CharacteristicsDeferring Phone Plugs and Jacks

    EIA 310 Racks, Panels and Associated Equipment

    EIA/TIA 492AAAA Detail Specification for 62.5-UM Core Diameter/125-UMCladding Diameter Class 1A Graded-Index MultimodeOptical Fibers

    EIA/TIA 526-14-A Optical Power Loss Measurements of Installed MultimodeFiber Cableplant - OFSTP-14a

    EIA/TIA 568 A Commercial Building Telecommunications WiringStandard

    EIA/TIA 568-B.1 Commercial Building Telecommunications Cabling

    ITCC in RiyadhResidential ComplexJ10-13300

    16715-4Voice & Data Communication

    Cabling

  • 7/27/2019 16715-Voice & Data Cabling

    5/16

    Standard, Part 1: General Requirements (ANSI)

    EIA/TIA 568-B.2 Commercial Building Telecommunications CablingStandard, Part 2: Balanced Twisted-Pair CablingComponents (ANSI)

    EIA/TIA 568-B.3 Optical Fiber Cabling Components (ANSI)

    EIA/TIA 569 Commercial Building Standard for TelecommunicationsPathways and Spaces

    EIA/TIA 606-A Administration Standard for theTelecommunications Infrastructure of CommercialBuildings

    EIA/TIA 607 Commercial BuildingGrounding/Bonding/Requirement Standard

    EIA/TIA TSB 67 Transmission Performance Specifications for Field Testingof UTP Cabling Systems

    EIA/TIA TSB 155 Additional Guidance for 4 Pair 100 ohms Category 6Cabling for 10 GBASE-T Application

    E. IEEE - Institute of Electrical and Electronic Engineers

    IEEE 802.3 AN 10 GBASE T Standards 2006

    F. ICEA - Insulated Cable Engineers Association

    ICEA S-80-576 Category 1 & 2 Individually Unshielded Twisted Pair Indoor Cables for Use in Communications WiringSystems

    ICEA S-83-596 Standard for Fiber Optic Premises Distribution Cable

    G. CFR - Code Of Federal Regulations

    47 CFR 68 Connection of Terminal Equipment to the TelephoneNetwork

    H. NFPA - National Fire Protection Association

    NFPA 70 National Electric Code

    NFPA 78 Lightning Protection Code

    I. NEMA - National Electric Manufacturer Association

    NEMA 250 Enclosures for Electrical EquipmentNEMA WD 6 Wiring Device - Dimensional Requirements

    J. UL - Underwriters Laboratories Inc.

    ITCC in RiyadhResidential ComplexJ10-13300

    16715-5Voice & Data Communication

    Cabling

  • 7/27/2019 16715-Voice & Data Cabling

    6/16

    UL 50 Enclosures for Electrical Equipment

    UL 1863 Standard for Safety, Communications CircuitAccessories

    1.3 SUBMITTALS:

    A. Product Data: Include data on features, ratings, and performance for eachcomponent specified.

    B. Shop Drawings: Include dimensioned plan and elevation views of each individualcomponent. Show equipment assemblies, method of field assembly, workspacerequirements, and access for cable connections.

    C. Wiring Diagrams: Show typical wiring schematics including workstation outlets,jack and jack assemblies, patch cords, patch panels, fiber-optic boxes and otherequipments.

    D. Samples: For workstation outlets (TO), jacks, jack assemblies, and faceplatesfor color selection and evaluation of technical features.

    E. Switches specification and data sheet (if applicable).

    1.4 TRANSPORTATION, HANDLING AND STORAGE:

    A. Deliver equipment and components in factory-fabricated containers or wrappings,which properly protect equipment from damage.

    B. Store equipment and components in original packaging. Store inside in a well-ventilated space protected from weather, moisture, soiling, humidity, and extremetemperatures.

    C. Handle equipment and components carefully to prevent damage, breaking, andscoring of finishes. Do not install damaged units or components; replace with new.

    1.5 WARRANTY:

    A. The manufacturer must guarantee to the End User that the products referencedwithin the specific Warranty Modules (Class E System) when correctly installed inaccordance with installation guidelines:

    Will be free from product defects in materials and workmanship

    Are guaranteed to exceed the Class E Channel and Permanent Link

    requirements as specified in ISO/IEC 11801:2002

    Supports the following application (not limited):

    10BASE T Ethernet 100BASET Fast Ethernet 1000BASE TX Gigabit Ethernet 10GBASE-T 155Mbit ATM 1000Mbit ATM (CB1G)

    10 GBASE-T For a duration of 20 years

    ITCC in RiyadhResidential ComplexJ10-13300

    16715-6Voice & Data Communication

    Cabling

  • 7/27/2019 16715-Voice & Data Cabling

    7/16

    B. All components including the patch cords have to be produced by the samecabling system manufacturer to ensure warranted performances and applicationsagainst the standards.

    1.6 QUALITY ASSURANCE:

    A. Manufacturer's Qualifications: The items provided under this contract will be frommanufacturers that have a minimum of 5 years experience in producing the typesof systems and equipment specified.

    B. Installer Qualifications: Specialist subcontractor with at least 5 years of successfulinstallation experience with projects utilizing data system similar to that required forthis project. Subcontractor shall be subject to approval of Engineer.

    C. Materials and installation shall comply with the specified Codes and Standards.

    D. Single Source Responsibility: All components and accessories shall be product ofsingle manufacturer except for cables.

    1.7 ENVIRONMENTAL REQUIREMENTS:

    A. Connecting hardware shall be rated for operation under ambient conditions of 0to 60 degrees C and in the range of 0 to 95 percent relative humidity, non-condensing.

    PART 2 - PRODUCTS

    2.1 SYSTEM DESCRIPTION:

    A. The voice and data communication cabling shall consist of horizontal andbackbone cables and connecting hardware to transport data (includingLAN/WAN) and voice (telephone) system signals between related as shown ondrawings. Numbers of outlets shall be as shown on drawings and documents.The Data Local Area Network (LAN) Sub-Contractor shall coordinate his workwith telephone equipment Sub-Contractor.

    The system shall support CATEGORY 6A 10GBASE -T

    2.2 GENERAL:

    A. Materials and equipment shall be the standard products of amanufacturer regularly engaged in the manufacture of the products and shall beof latest technology/version available at the time of installation, and has been insatisfactory use for at least 1 year prior to installation. Materials and equipmentshall conform to the respective publications and standards specified herein andto the applicable requirements of ISO/IEC 11801,2002 EIA/TIA 568 and to alladditional requirements of IEEE 802.3 AN and TIA TSB 155 and ISO/IEC TR24750 to support the 10 GBASE-T application over 100 meters channel.

    2.3 HORIZONTAL CABLING:

    A. Horizontal Distribution Cable: Horizontal distribution cable shall be 10 G (UTP)Category 6A. The cable shall be a four, thermoplastic-insulated, individually

    ITCC in RiyadhResidential ComplexJ10-13300

    16715-7Voice & Data Communication

    Cabling

  • 7/27/2019 16715-Voice & Data Cabling

    8/16

    twisted pairs of copper conductors; No.24 AWG, color-coded; enclosed in PVCjacket or a material that does not give off toxic fumes (Low Smoke Zero Halogen- LSZH) in case of fire and offer flame propagation retardant properties. Cableshall be designed to support the IEEE 802.3 1000Base.T (Gigabit Ethernet),potentially 1.2 Gbps ATM and 2.4 Gpbs ATM as well as analogue broadbandvideo up to 550 MHz. Cable shall meet or exceed attenuation and NEXTrequirements in ISO/IEC 11801, CENELEC EN50173 and EIA/TIA 568A. All pairsmust have impedance of 100 Ohms, with a tolerance of +/- 15 Ohms. In theconstruction of the cable cross-talk performance shall be maintained using a C3

    (Central dielectric Cross-talk Cancellation) member set between the 4 pairs.Insulators in standard Blue/White, Orange/White, Green/White, Brown/Whitecolors must cover the conductors. Cable shall be of latest technology/speedmanufactured and available at the installation time. This cable shall be used forhorizontal run between data, voice (telephone), clock and security system outletsand floor communicable cabinet.

    B. Telecom Outlets (TO): Telecom outlets shall be CAT 6A (UTP) RJ45. Eachconnector shall provide both T568A and T568B color code identification for thepins at the rear of the connector. The punch down is to be in accordance with theT568B color code. Reassignment of pairs is forbidden. All conductors from theCAT6A 4 pair cable shall be terminated on the respective contacts. To avoidinstallation errors, the wire organizer of the snap-in connector must be identifiedby the same standard color coding as the wires. All CAT 6A (UTP) RJ45connectors shall be fully compliant with the ISO/IEC 11801:2002 standard. Thepresentation of the outlet shall provide for labeling and identification. Atransparent window shall protect the labeling tag. All outlets shall be equippedwith shutters.

    Snap-in Format (Where required): The dimensions of the Snap-in format

    connectors shall be H x W x D: 19.5 mm x 16.8 mm x 35.7 mm. The same formatconnectors (unscreened) shall be used on each link. The connector fits in specificstructural hardware for Snap-in format of third parties. If not available, the Snap-in connector can be used in combination with a keystone clip and specificstructural hardware for keystone connectors.

    .C. Copper Patch Panels (RJ45): Patch panels must have 19 equipment practice

    dimensions to permit mounting in standard cabinets, racks or bays. Provide 24port Snap-in format (Modular) patch panels equipped with a cable managementmechanism that provides strain relief, earthing and grounding features. Thepresentation of the Patch Panel shall provide for labeling using a printednumbering system. The connector shall provide both T568A and T568B colour

    code identification for the pins at the rear of the connector. Patch panel outletsmust have each Category 6A (UTP) RJ45 connector, connected separately. Thepunch down is to be in accordance with the T568B color code. Reassignment ofpairs is forbidden.

    The screened connectors from modular patch panel shall provide terminationfacilities for the drain wire of each category 6A F/UTP cable.

    All conductors from the 4 pair cable are to be terminated on the respectivecontacts. To avoid installation errors, IDC blocks must be identified by the samestandard color coding as the wires.

    Each patch panel shall provide a means to locate and clamp the incoming cableswithout causing damage to the cables or affecting the performance of link. The

    ITCC in RiyadhResidential ComplexJ10-13300

    16715-8Voice & Data Communication

    Cabling

  • 7/27/2019 16715-Voice & Data Cabling

    9/16

    installer must avoid any risk of cable pinching or compression during theinstallation of cable. Therefore use of Velcro cables is preferred,

    In the rack, the Patch Panels shall be separated by metallic patch-guides thathave a closed front to protect the patch cords. The height of these guides will be1U or 2U depending on the layout of the rack.

    The metal frame of patch panel must not be earthed to the cabinet with aseparate earth strap if the patch panels automatically make contact with themetal frame of the cabinets. If the cabinet is not designed to provide the panelswith automatic earth, then the patch panels must be connected with separateearth strap to the earth key.

    D. Patch Cords: To achieve a Class E 10 G Channel performance all Patch Cordswill be Category 6A rated. All patch cord cable will be made from PVC or LowSmoke Zero Halogen (LSZH) material (when used in plenum areas).

    1. Data Patch Cords: The standard color offered shall be orange for LSZHjacket and grey for PVC jacket. The Category 6A cords must be fitted withCategory 6A RJ45 plugs, booted at each connector. The characteristicimpedance of the pairs must be identical to that of the horizontal cables.The Patch Cords shall have a guaranteed performance level of greaterthan 750 insertions without degradation to the performance level of thesolution.

    The cable used for the Patch Cords shall be Category 6A PVC or LSZHpatch cable. The cable shall be a 4 twisted pair cable with strandedconductors. Trace ability numbers should accompany the cables suppliedfrom the manufacturers packaging to assist in quality validation of the

    installed cable. All pairs must have an impedance of 100 Ohms.

    E. Class E link or channel: Manufacturer should demonstrate guaranteed minimumworst-case performance to compliant with class E channel performance accordingto the ISO/IEC 11801: 2002 standard. Components used must be compliant withthe category 6A standard mentioned above and the manufacturer should be able todemonstrate independent Delta verification. The performance of both thecomponents and the link and channel should show stable performance up to 500MHz in order to allow for possible future applications requiring crosstalk cancellationup to 500 MHz.

    The system supplier must be able to demonstrate in house design and

    manufacturing expertise for all components used (e.g. cables, outlets, panels andcords) in order to ensure compatibility of system elements

    2.4 BACKBONE CABLING:

    A. Data Backbone: This backbone will link the Switches located in the FloorDistributors (FD) to the Data network server through the Building Distributor (BD).

    1 Optical Fiber Cable: The cable shall be suitable for connector manufacturer

    termination processes (LC, SC or ST connectors). Fiber splicing methodshould be used for termination of Fiber Cables using fiber pigtails

    ITCC in RiyadhResidential ComplexJ10-13300

    16715-9Voice & Data Communication

    Cabling

  • 7/27/2019 16715-Voice & Data Cabling

    10/16

    manufactured by the same vendor.Construction: Tight buffered with water blocking Aramid/Glass yarnreinforcements or tape and shall be suitable for indoor or outdoor usemaking it ideal for short campus links without the use of transition joints.The cable strength member shall be glass yarn laid longitudinally betweenthe fibers and the inside wall of the outer jacket. The cable shall bedielectric construction, i.e. with no metallic content. The cable shall be a dryconstruction i.e. with no gel content. The jacket material shall be waterproofLSZH with a minimum fire performance of IEC 332 part 3C.

    2 Multimode Fiber Optic Cable: The Cabling system must be designed andinstalled according to ISO 11801 OM2 & OM3 compliant and should alsomeet EN50173 2nd editions and TIA/EIA 568B3. The Cable shall have 6 or12 or 24 cores, 50/125 m universal distribution cable with improvedperformance.

    Gigabit Ethernet should be supported up to a minimum distance of 550 m.If required, extended distance option with laser optimization should beavailable to increase this distance up to 800 m in case of 850 nm fiber and2,000 m in case of 1300 nm.

    In case 10G Ethernet application has to be used, the fiber shall be OM3compliant and should support transmission of 10G signal up to a distanceof 300 m for 850 nm fiber and 550 m for 1300 nm fiber.

    3 Single Mode Fiber Optic Cable: The Cabling system must be designed andinstalled according to ISO 11801 OS1 compliant and should also meetEN50173 2nd editions and TIA/EIA 568B3. The Cable shall have 6 or 12 or24 cores, 9.2/125 m universal distribution cable with improved

    performance.

    Gigabit Ethernet should be supported up to a distance of 10,000 m using1300 nm fiber. In case 10G Ethernet application has to be used, the fibershould support transmission of 10G signal up to a distance of 10,000m for1300nm fiber.

    4 Optical Fiber Patch Panel: Optical fiber Patch Panels shall be mounted in 19"frames of the cabinets. The patch panels shall be equipped with amechanism that ensures the retention and support of incoming cables. AnEarth Key shall be provided within the patch panel to earth any metallic partof the cable. The patch panel shall be designed with a sliding mechanism

    enabling front side installation and maintenance work to be carried outwithout having to remove the entire panel.

    The patch panel shall provide facilities to recess the front connector platedeeper than the front of the 19" rails of the cabinet. This will providesufficient bend radius for the patch cords once connected to the panel. Thisshall also prevent damage to the patch cords when the cabinet doors areclosed.Direct Termination of the connectors on to the fibers as well as splicing ofpigtails shall be possible. The Patch Panel shall provide management for1m of fiber per link after breaking the fibers out from the cable. The Patch

    Panel shall support the connector type specified for this installation. Formultimode fiber links, these can be LC, SC and ST. The panel-mounted

    ITCC in RiyadhResidential ComplexJ10-13300

    16715-10Voice & Data Communication

    Cabling

  • 7/27/2019 16715-Voice & Data Cabling

    11/16

    couplers shall be protected on the front presentation side of the patchPanel for safety purposes.

    5 Optical Fiber Patch Cords: The Fiber adapters will be connected to the active

    equipment by means of duplex patch cords 2LC-2LC, 2 SC-2 SC or 2 ST-2ST as per client site standard.The patch cords consist of 50/125 microns fibers and a LSHF-FR jacket.The SC or ST connectors shall comply with the International standard IEC74-13. The patch cords should be available in lengths of 2 and 5 meters.

    To avoid mix of patch cords built around different types of fiber, cordsproduced with LASER-optimized fiber will be used for both OM1 and OM2optical fiber cables. When using OM3 optical fiber cables, patch cordsproduced with the same OM3 fiber have to be installed.

    6 Fiber cables shall interface and connect to fiber interface unit at both ends aspart of the fiber contractor work.

    2.5 CABINETS:

    A. The metal cabinets shall have a footprint of 800x800 mm. In the frames 19components can be mounted by means of the standard cage nuts. The frontdoor consists of a metal framework with hinges and a central security glass. Theside panels and the panel in the back have to be equipped with a hinge on theleft or the right in order to facilitate the access to the equipment. A 42 HU cabinetis preferred providing enough space for active equipment.

    B. For an orderly cord storage and easy to manage installation, the followingaccessories shall be used:

    Closed 1 or 2 HU patch guides between the patch panels; Lateral cable rings installed at both sides of the frames. The patch rings can

    be removed very easily by rotation and have to be located on the front railsof the 19" frames in the cabinets.

    The cabinets should be supplied with:

    A power bar with 6 * 240VAC electrical sockets and a mains isolator switch

    Up to 4 fans (240VAC) for expelling air, approximately 220W each

    C. Earthing has to be achieved by means of the 19" frame attachments, thusensuring continuity. The cabinet and frame assembly when installed will also

    serve as equi-potential plane so that damaging external EMI currents can bedrained off. To this end, the inter-cabinet connections shall also be made off byextending the earth connection from cabinet to cabinet in a suite of cabinets. Thesuite of cabinets shall be connected to the grounding network of the building.

    D. The Earth key of the cabinet must be connected to the protective earth. Thedimension of the earth conductor is 6mm. If no or only a poor protective earthsystem is present in the building, a separate earthing to the main earth terminalof the building is required. The dimensions of the conductor should then be16mm.

    E. Cabinet Mounted UPS (Uninterruptible Power Supply): To enable Power overEthernet (PoE) a smart UPS shall be supplied and installed as a part of thecabinet. The UPS shall have the following minimum features:

    ITCC in RiyadhResidential ComplexJ10-13300

    16715-11Voice & Data Communication

    Cabling

  • 7/27/2019 16715-Voice & Data Cabling

    12/16

    1. Output

    a. Output Power Capacity: 2250 Watts/3000 VA

    b. Max. Configurable Power: 2250 Watt/3000 VA

    c. Nominal Output Voltage: 230 V or as indicated on powerdrawings

    d. Typical Back Time: At full load 5.7 minutes (2250 Watts)

    2. Communications & Management

    a. Interface Port(s): DB-9 RS-232, SmartSlot

    b. Control Panel: LED status display with load and battery bar-graphsand on line: on battery: replace Battery: and overload indicators

    c. Alarm when on battery: distinctive low battery alarm: configurabledelays

    3. Rack height for UPS shall be 5U or as per manufacturer standards

    4. Operating environment shall be 0 - 400C

    5. The system shall conform to EN 50091-1 and EN 50091-2

    6. Output Voltage Notes: configurable to 230 nominal output voltage or asrequired on power drawings

    7. Output voltage distortion: Less than 5% at full load

    8. Output frequency: 57 63 Hz for 60 Hz nominal

    9. Waveform type: Sine wave

    10. Output connection:

    a. (8) IEC 320 C 13

    b. (1) IEC 320 C 19

    c. (3) IEC Jumpers

    11. Input

    a. Nominal Input: Voltage: 230 V or as indicated on power drawings

    b. Input frequency: 60 Hz 3 (auto sensing)

    c. Input connections: IEC 320 C20 or as required on site

    d. Input voltage range for main operation 174 286 V or as requiredon site

    e. Input voltage adjustable range for main operation: 168 302 V or

    ITCC in RiyadhResidential ComplexJ10-13300

    16715-12Voice & Data Communication

    Cabling

  • 7/27/2019 16715-Voice & Data Cabling

    13/16

    as required on site

    12. Batteries:

    a. Type: Maintenance-free sealed Lead-Acid battery with suspendedelectrolyte leak proof

    b. Typical recharge time: 3 hour(s)

    c. Typical recharge time at half load: 19.2 minutes (1125 Watts)

    PART 3 - EXECUTION

    3.1 INSTALLATION:

    A. The entire system shall be installed by specialist subcontractor approved by theEngineer.

    B. Installation shall be in accordance with the approved drawings and manufacturer'swritten instructions.

    C. System components and appurtenances shall be installed in accordance withISO/IEC 11801, manufacturer's written instructions and as shown. Necessaryinterconnections, services, and adjustments required for a complete andoperable signal distribution system shall be provided. Components shall belabeled in accordance with EIA/TIA 606. Penetrations in fire-rated constructionshall be firestopped. Conduits, outlets and raceways shall be installed inaccordance with Section 16050 - BASIC ELECTRICAL MATERIALS ANDMETHODS. Wiring shall be installed in accordance with ISO/IEC 11801, EIA/TIA568A and EIA/TIA 568B. Cables shall not be installed in the same cable tray,utility pole compartment, or floor trench compartment with ac power cables.

    D. Horizontal Distribution Cable: The rated cable pulling tension shall not be exceeded.Cable shall not be stressed such that twisting, stretching or kinking occurs. Cableshall not be spliced. Cable shall not be run through structural members or incontact with pipes, ducts, or other potentially damaging items. Placement ofcable parallel to power conductors shall be avoided, if possible; a minimumseparation of 300 mm shall be maintained when such placement cannot beavoided. Cables shall be terminated; no cable shall contain unterminatedelements. Minimum bending radius shall not be exceeded during installation or

    once installed. Cable ties shall not be excessively tightened such that thetransmission characteristics of the cable are altered.

    E. Riser and Backbone Cable: Vertical cable support intervals shall be permanufacturers recommendations. Cable bend radius shall not be less than tentimes the outside diameter of the cable during installation and once installed.Maximum tensile strength rating of the cable shall not be exceeded. Cable shallnot be spliced.

    F. Data Outlets: As a minimum each jack shall be labeled as to its function and aunique number to identify cable link. Minimum of 6 inches of slack cable looselycoiled into the data outlet boxes. Minimum manufacturers bend radius for each

    type of cable shall not be exceeded.

    ITCC in RiyadhResidential ComplexJ10-13300

    16715-13Voice & Data Communication

    Cabling

  • 7/27/2019 16715-Voice & Data Cabling

    14/16

    G. Unshielded Twisted Pair Patch Panels: Patch panels shall be mounted inequipment racks with sufficient modular jacks to accommodate the installed cableplant plus 10 percent spares. Cable guides shall be provided above, below andbetween each panel.

    H. Fiber Optic Patch Panels: Patch Panels shall be mounted in equipment racks withsufficient ports to accommodate the installed cable plant plus 10 percent spares.A slack loop of fiber shall be provided within each panel. Loop shall be 900 mmin length. The outer jacket of each cable entering a patch panel shall be securedto the panel to prevent movement of the fibers within the panel, using clamps orbrackets specifically manufactured for that purpose.

    I. For excavation and backfilling refer to Section 02200 - EARTHWORK.

    3.2 ELECTRICAL SAFETY:

    A. Separation of telecommunication circuits from the building electrical system andelectrical equipment shall conform to the latest publications of Articles 800-3 (a) and820-13 of National Electric Code (NEC).

    B. An earth or ground shall be provided and extended to the termination box andconnected to each station protector. The earth or ground shall be installed andbonded in accordance with Article 250, 800 and 820 of National Electric Code(NEC).

    3.3 TESTING:

    A. General: After installation of entire system and prior to acceptance of work,manufacturer's standard tests shall be conducted in the presence of the Engineer to

    show proper operation of each equipment and the system entirely. Themanufacturer of the cabling system shall provide copper (Data) and optical fibertesting procedures that clearly describes the tools and settings to be used toensure correct measurements of the system. The result of testing shall meet orexceed the requirements of ISO/IEC 11801, latest edition and ISO/IEC TR 24750.

    B. Testing of Class E: 100 % of the installed horizontal links shall be tested. Thetesting procedure has to comply with the standard ISO/IEC 11801: 2002for ClassE, according to the procedure for Channel or Permanent Link. Themeasurements shall be done using Level III testing equipment. Channel testingshall be preferred. Channels shall be tested to support 10 G 500 MHz

    The testers have to be calibrated according to the recommendations made by thesupplier of the testing equipment. The following parameters have to be testedPair continuity (wiremap)

    Pair length

    DC Loop resistance per pair

    Insertion loss (Attenuation) per pair

    NEXT and Powersum NEXT for every pair combination

    FEXT and Powersum FEXT for every pair combination

    The ACR (ratio NEXT/ insertion loss) for every pair combination Return Loss (impedance match, retransmitted signal)

    ITCC in RiyadhResidential ComplexJ10-13300

    16715-14Voice & Data Communication

    Cabling

  • 7/27/2019 16715-Voice & Data Cabling

    15/16

    The complete test results of all the installed links or channels shall be collected ina certification file. It is preferred to have the test result in electronic format tofacilitate the certification procedure. Apart from all the test results mentionedabove, a few more documents shall be added to the file: a list of material usedfor the project, a design of the network, a Cable schedule per distributor andfinally all the necessary co-ordinates of the persons responsible of the project.

    C. Vertical Fiber Testing: The procedure shall comply with the ISO/IEC 14763-3standard. The ISO/IEC 14763 standard specifies the implementation andoperation of customer premises cabling. The part 3 of this ISO document (14763-3) details test procedures for optical fiber cabling designed in accordance withISO/IEC 11801:2002 and installed according to the recommendations of ISO/IEC14763-2 (Planning and installation of customer premises cabling).

    For Multimode fibers, the test procedure is based on the use of the one-jumpermethod specified by Method 2 of IEC 61280-4-1. This procedure is used fortesting links for which the connector loss is a significant portion of the total linkattenuation. This is the case for LAN premises links.For Singlemode fibers, the test procedure to be applied is the same and is basedon the use of the one-jumper method specified by Method 1a of IEC 61280-4-2.

    Fiber-optic Tests applied to links and exclude equipment and work area cord.OF Attenuation testing is used to verify the initial performance of the installedlink.All 100 % of the installed OF links have to be tested and must pass theacceptance criteria.

    The attenuation of the link is measured using the insertion loss method. This

    method uses an optical source and an optical power meter to compare thedifference between two optical power levels.

    When testing multimode optical fiber links with a Light Source and a PowerMeter, this measurement kit has to be capable of operating at

    850nm and 1300nm for multimode fibers (OM1, OM2 & OM3)

    1310nm and 1550nm for singlemode fibers (OS1)

    The test scenario with a Light Source and a Power Meter shall be one of the

    following for each link:

    Single direction @ 850nm and @ 1300nm for multimode fibers

    Single direction @ 1310nm and @ 1550nm for singlemode fibers

    The use of certification tool is recommended. Those tools are capable ofproducing a report logging the time of the test the link identification under test,the link length, the attenuation at the window tested and the acceptable linkattenuation. The report shall also identify in which direction the testing wasimplemented.

    When testing with basic optical source and power meter, the operator will fill up areport logging:

    ITCC in RiyadhResidential ComplexJ10-13300

    16715-15Voice & Data Communication

    Cabling

  • 7/27/2019 16715-Voice & Data Cabling

    16/16

    The time of the test,

    The link identification under test,

    The link length and attenuation at the window tested.

    The report shall also identify in which direction the testing was implemented.

    Acceptable link attenuation (To be calculated)

    The measured attenuation of the links shall have a lower value than theacceptable link attenuation calculated.

    END OF SECTION

    ITCC in RiyadhResidential ComplexJ10-13300

    16715-16Voice & Data Communication

    Cabling