MINISTRY OF HOUSING Western Sector Projects Sitework & Infrastructure OMRANIA and ASSOCIATES Project Specification VOICE AND DATA CABLING SYSTEM SECTION 27 15 00.13 - 1 SECTION 27 15 00.13 VOICE AND DATA CABLING SYSTEM PART 1: GENERAL 1.01 SECTION INCLUDES A Voice and Data Cabling Systems supporting the following network topologies: 1. Analog voice circuits. 2. AppleTalk. 3. Ethernet 10BaseT. 4. IBM Token Ring 4 Mbps and 16 Mbps and future TP-PMD. 5. ATM-155 Mbps and 100BaseT. 6. Voice and data grade unshielded twisted pair (UTP) cable. B Electrical and mechanical components and systems for Voice and Data Cabling Systems, including rough-in, pathways, conduits, boxes and backboards. 1.02 RELATED SECTIONS A Section 27 31 13 Telephone System Equipment. B Section 27 21 00.13 Computer Networking L.A.N. Equipment. C Section 26 08 00 Testing and Commissioning of Electrical Systems 1.03 REFERENCES A NEC National Electric Code. B NFPA National Fire Protection Association. C TIA/ EIA568 B Telecommunication Industry Associations/Electronic Industries Associations - Commercial Building Telecommunications Standard. D TIA/EIA606 Administration Standard for the Telecommunications Infrastructure of Commercial buildings. E TIA/EIA 607 Commercial Building Grounding and bonding Requirements for Telecommunications. F UL Underwriters Laboratories. G. Local Codes as applicable. 1.04 SUBMITTALS A Comply with Section 01 33 00.

Upload: masoodae

Post on 20-Sep-2015

225 views

Category:

Documents


0 download

TRANSCRIPT

  • MINISTRY OF HOUSING

    Western Sector Projects

    Sitework & Infrastructure

    OMRANIA and ASSOCIATES Project Specification

    VOICE AND DATA CABLING SYSTEM SECTION 27 15 00.13 - 1

    SECTION 27 15 00.13

    VOICE AND DATA CABLING SYSTEM

    PART 1: GENERAL

    1.01 SECTION INCLUDES

    A Voice and Data Cabling Systems supporting the following network topologies:

    1. Analog voice circuits.

    2. AppleTalk.

    3. Ethernet 10BaseT.

    4. IBM Token Ring 4 Mbps and 16 Mbps and future TP-PMD.

    5. ATM-155 Mbps and 100BaseT.

    6. Voice and data grade unshielded twisted pair (UTP) cable.

    B Electrical and mechanical components and systems for Voice and Data Cabling Systems, including rough-in, pathways, conduits, boxes and backboards.

    1.02 RELATED SECTIONS

    A Section 27 31 13 Telephone System Equipment.

    B Section 27 21 00.13 Computer Networking L.A.N. Equipment.

    C Section 26 08 00 Testing and Commissioning of Electrical Systems

    1.03 REFERENCES

    A NEC National Electric Code.

    B NFPA National Fire Protection Association.

    C TIA/ EIA568 B Telecommunication Industry Associations/Electronic Industries Associations - Commercial Building Telecommunications Standard.

    D TIA/EIA606 Administration Standard for the Telecommunications Infrastructure of Commercial buildings.

    E TIA/EIA 607 Commercial Building Grounding and bonding Requirements for Telecommunications.

    F UL Underwriters Laboratories.

    G. Local Codes as applicable.

    1.04 SUBMITTALS

    A Comply with Section 01 33 00.

  • MINISTRY OF HOUSING

    Western Sector Projects

    Sitework & Infrastructure

    OMRANIA and ASSOCIATES Project Specification

    VOICE AND DATA CABLING SYSTEM SECTION 27 15 00.13 - 2

    B Submit 6 complete sets of shop drawings for the proposed system. The submittal shall be neatly bound in a three ring or comb type binder, with protective covers. The cover shall

    identify the project, system, date and vendor name. The submittal shall include, but not be

    limited to the following items:

    1. Title sheet showing the Contractor's name, address, phone number and date submitted. Clear area shall be provided on the title sheet for shop drawing review stamps.

    2. Material list showing quantity, manufacturer and description of each item being furnished.

    3. Engineered riser diagrams showing all distribution equipment, connections and calculated tap values and signal strength levels at each device and outlet.

    4. Product data sheets with complete technical data for each item being furnished.

    C Submit details of training program for installation personnel in installation of extended performance data cabling.

    1.05 QUALITY ASSURANCE

    A Installer: Firms regularly engaged and qualified with a minimum of 5 years experience in the installation and service of voice/data cabling communications systems and registered with

    the equipment manufacturer(s) as franchised reseller of registered systems and to serve as the

    installing contractor and ongoing registered service provider. Written certification by the

    warranting manufacturer(s) shall be provided with shop drawings.

    B Provide 3 references of projects of comparable size and scope that have been completed within the last 2 years. References shall include project name, address, date of substantial

    completion, and name and telephone number of manager of the system.

    C Installation shall be by installers trained in the installation of voice and extended performance data grade cable and equipment. Installing contractor shall provide certificates

    of training for Voice and Data cabling as EIA/TIA-568-A for supervisors of installation

    personnel. Certificates shall be acceptable from a manufacturer of the equipment listed or an

    independent training company.

    D All installing personnel shall be trained in the proper installation of extended performance data cable prior to installation by outside training course or in-house training program.

    E Contractors not meeting the above minimum qualifications shall not be approved for this project.

    1.06 SYSTEM DESCRIPTION

    A Voice and Data Cabling System shall include:

    1. Horizontal cable system consisting of:

    a. Data transmission cable system including data grade cable and outlet and termination hardware.

    b. Voice transmission cable system including data grade cable and outlet and termination hardware.

  • MINISTRY OF HOUSING

    Western Sector Projects

    Sitework & Infrastructure

    OMRANIA and ASSOCIATES Project Specification

    VOICE AND DATA CABLING SYSTEM SECTION 27 15 00.13 - 3

    B Communications outlets and connecting hardware:

    Outlets shall comprise:

    a. Data grade connecting devices shall be 8-pin modular jacks (Category 6).

    b. Voice grade connecting devices shall include 8-pin modular jacks (Category 6).

    c. Outlet plates for modular furniture shall be compatible with furniture system.

    C Labeling of communications outlets and connecting hardware.

    1. Identify each outlet with the following label format. Labeling shall be by a permanent labeling method. The room number identification shall be the final room number

    provided by the Owner.

    2. Closet number, followed by a dash and room number, followed by a dash and number of outlet in room (if multiple outlets are in the room):

    a. Closet end:

    i. Sample A-205-V 2: closet A - location 205 - Voice cable No. 2.

    ii. Sample C-205-D 4: closet C - location 205 - Data cable No. 4.

    b. Outlet end: Sample B-205: closet B - location 205.Identify individual jacks on each plate with outlet type and number, if multiple outlets occur in the room, label

    adjacent to each outlet with a "D" for each data outlet, "V" for each voice outlet and

    "TV" for each RF television outlet (multiple TV outlets need not be identified);

    "D2", "D3", "V2", etc. if multiple drops.

    3. Color code for communications outlets shall be as follows:

    a. Data jacks for Instruction, black jack inserts.

    b. Data jacks for Administration, black jack inserts.

    c. Voice jacks, yellow jack inserts.

    d. Data jacks for Computer Labs, black jack inserts.

    4. The outlet plate labeling shall be engraved text 5 mm high, onto the cover plates and black filled. No other labeling method shall be accepted for the device outlet plates.

    D Terminal blocks in the head end room and communications closets, for voice and data cabling shall be color coded by type of cable as follows:

    1. Demarcation point (MPOP) ORANGE

    2. Network connections GREEN

    3. Common equipment (PBX, Host, LANs, Muxes) PURPLE

    4. Backbone WHITE

  • MINISTRY OF HOUSING

    Western Sector Projects

    Sitework & Infrastructure

    OMRANIA and ASSOCIATES Project Specification

    VOICE AND DATA CABLING SYSTEM SECTION 27 15 00.13 - 4

    5. Station BLUE

    6. Inter-building backbone BROWN

    7. Miscellaneous (Fire alarm, Security, Intercom) YELLOW

    E Provide fire stopping at all penetrations through fire rated walls and ceiling/floor systems designated for technology use. Fire stopping method shall meet or exceed the minimum

    rating of the wall, ceiling or floor penetrated.

    F Coordinate the installation of the technology outlets in the modular furniture with the supplier of the furniture. All wiring shall be installed in the modular furniture raceway.

    Provide all cover plates for the technology outlets. If cable is exposed from wall outlet to

    furniture base, provide a flexible protective cover of round plastic sheathing.

    1.07 WARRANTY

    A Comply with Section 01 78 36.

    B Warranty shall be for a minimum period of 20 years from the Substantial Completion date of the structured cabling system (voice/data), based on the written acceptance of the Owner for

    compliance with the Specification.

    PART 2: PRODUCT

    A One manufacturer's brand shall be used for each component throughout the building.

    B One manufacturer's product line shall be used for all termination equipment at both the outlet end and at the administration end of all cabling.

    2.01 VOICE AND DATA CABLE

    Voice and Data Cable shall be 4 pair cable Category 6A F1/UTP to meet the quality and

    performance criteria necessary to ensure correct operation of the installation for frequencies

    up to 500 MHz and to ensure the compliance with the warranty.

    The installation design and routing of all cables shall take account of the manufacturer limits for the continued performance of the cables and the compliance with the warranty. The cable shall be a 4 twisted pair cable with AWG 23 plain copper conductors and shall have an external sheathing in a material that does not give off toxic fumes (Zero Halogen) in case of fire and offer flame propagation retardant properties. The cable shall be compliant to the IEC 60332-1 standard. Traceability numbers should accompany the cable supplied from the manufacturers packaging to assist in quality validation of the installed cable. In order to provide alien cross-talk (AXT) immunity for 10 GBASE-T Ethernet transmission, the use of screened cable is mandatory.

    Independent certification shall be provided by the manufacturer to show compliance to

    ISO/IEC 11801:2011 or EN 50173:20112 Channel headroom requirements for both Alien

    NEXT (A-NEXT) and Alien FEXT (A-FEXT) parameters.

  • MINISTRY OF HOUSING

    Western Sector Projects

    Sitework & Infrastructure

    OMRANIA and ASSOCIATES Project Specification

    VOICE AND DATA CABLING SYSTEM SECTION 27 15 00.13 - 5

    In the construction of the cable NEXT performance shall be maintained using a C (Central dielectric Cross-talk Cancellation) member set between the 4 pairs. All pairs must have a fitted impedance of 100 Ohms, with a tolerance of +/- 5 Ohms.

    Conductor pairs shall be identified by insulation utilising standardised colour code (Blue/White,

    Orange/White, Green/White, Brown/White). The cable shall contain 1 foil screen. The foil shall have the metallic side facing outwards, allowing the cable to be automatically grounded during the termination process without having to fold back the foil. This will provide instant 360 grounding contact to ensure immunity from Alien Crosstalk and other external interference. A tinned copper drain wire, shall be provided between the aluminium screen and the external sheathing. The Cat.6A cable shall comply to the following electrical performances. Max. And Min. Values shall be warranted by the manufacturer.

    Max Typ Min. Typ. Min. Typ. Min. Typ. Min. Typ. Min. Typ. Min. Typ. Min. Typ.

    1 2.1 2.1 74.3 79.3 72.3 77.3 67.8 92.8 64.8 >60 67.0 90.0 67.0 87.9 20.0 26.0

    4 3.8 3.8 65.3 70.3 63.3 68.3 55.8 80.8 52.8 57.2 67.0 90.0 66.2 75.9 23.0 29.0

    10 5.9 5.9 59.3 64.3 57.3 62.3 47.8 72.8 44.8 49.3 67.0 87.0 58.2 67.9 25.0 31.0

    16 7.5 7.5 56.2 61.2 54.2 59.2 43.7 68.7 40.7 45.2 67.0 85.0 54.1 63.8 25.0 31.0

    20 8.4 8.4 54.8 59.8 52.8 57.8 41.8 66.8 38.8 43.2 67.0 84.0 52.2 61.9 25.0 31.0

    31.25 10.5 10.5 51.9 56.9 49.9 54.9 37.9 62.9 34.9 39.4 67.0 82.1 48.3 58.0 23.6 29.6

    62.5 15.0 15.0 47.4 52.4 45.4 50.4 31.9 56.9 28.9 33.3 65.6 79.0 42.3 52.0 21.5 27.5

    100 19.1 19.1 44.3 49.3 42.3 47.3 27.8 52.8 24.8 29.3 62.5 77.0 38.2 47.9 20.1 26.1

    155 24.1 24.1 41.4 46.4 39.4 44.4 24.0 49.0 21.0 25.5 59.6 74.1 34.4 44.1 18.8 24.8

    200 27.6 27.6 39.8 44.8 37.8 42.8 21.8 46.8 18.8 23.2 58.0 72.5 32.2 41.9 18.0 24.0

    250 31.1 31.1 38.3 43.3 36.3 41.3 19.8 44.8 16.8 21.3 56.5 71.0 30.2 39.9 17.3 23.3

    300 34.3 34.3 37.1 42.1 35.1 40.1 18.3 43.3 15.3 19.7 55.3 69.8 28.7 38.4 16.8 22.8

    500 45.3 45.3 33.8 38.8 31.8 36.8 13.8 38.8 10.8 15.3 52.0 66.5 24.2 33.9 15.2 21.2

    PS AACR-F (dB) RL (dB)

    Electrical Performance Cat.6A F1/UTP cable

    Frequency

    MHz

    Attn NEXT (dB) PSNEXT (dB) ACR-F (dB) PS ACR-F (dB) PS ANEXT (dB)

    Conductor pairs shall be identified by insulation utilising standardised colour code (Blue/White,

    Orange/White, Green/White, Brown/White).

    1. Nominal outside diameter shall not exceed 6 mm.

    2. Cable shall meet NEC, CMR and CMP rated insulation and jacket material as required for specific installation.

    3. Data cable shall have a yellow jacket.

    4. Voice cable shall have a blue jacket

    2.02 TERMINATION EQUIPMENT

    A Voice and Data outlets shall be 8-pin modular outlets rated by manufacturer to meet the following minimum performance criteria:

  • MINISTRY OF HOUSING

    Western Sector Projects

    Sitework & Infrastructure

    OMRANIA and ASSOCIATES Project Specification

    VOICE AND DATA CABLING SYSTEM SECTION 27 15 00.13 - 6

    1. TIA/EIA 568A Category 6. Category 6 classification shall be printed on the cable. Compliance with NEXT figures shall be based on the power sum method of testing by

    the manufacturer.

    2. Labeling on outlets shall identify them as Category 6a and power sum compliant.

    3. Pin configuration shall be T 568 B.

    B Outlet frames shall be plastic frames with positions for 2 and 4 modular jack inserts of the same manufacturer.

    1. Frames shall accept double duplex type cover p

    2. lates.

    3. Frame color shall be gray.

    1. Plate color shall be gray.

    2. Plates shall be labeled with identification as described in clause 1.06 of this Section. The label shall be covered with clear plastic to protect the label.

    C Wall outlets for wall mount telephones: Single gang receptacles with 6 or 8-pin modular jack insert and mounting posts for wall mount telephone. Jack shall have Insulation Displacing

    Connectors (IDC) direct connection. Plate shall be stainless steel.

    2.03 FIRE STOPPING:

    A. Comply with Section 07 84 00.

    PART 3: EXECUTION

    3.01 INSTALLATION

    A All equipment shall be installed in a neat professional manner:

    1. Device plates shall be vertically plumb with edges flush to the wall and covering the outlet box.

    2. Cable terminations shall comply with manufacturers installation instructions and industry guide lines.

    3. Installer shall observe factory installation guidelines for pulling tension, bending radius, kinking, and proximity to lighting and other electrical equipment for all cables.

    B Cables shall be concealed within conduit or raceway below finished ceilings and continuously below exposed structural ceilings.

    C Cables routed above accessible ceilings and in utility areas shall be installed in cable trays and in conduits provided in the building. Where cables leave the cable tray, they shall be

    supported by bar joists or new tie wires in drop ceiling areas. A buffer tie shall be installed

    on tie wires to minimize cutting or kinking of communications cables.

  • MINISTRY OF HOUSING

    Western Sector Projects

    Sitework & Infrastructure

    OMRANIA and ASSOCIATES Project Specification

    VOICE AND DATA CABLING SYSTEM SECTION 27 15 00.13 - 7

    D Cables not installed in cable tray or raceway, shall be supported at intervals of 1524 mm or less along their entire length with cable support hooks.

    E All communications outlet boxes shall be finished with a cover plate, including outlets in modular furniture. Blank plates shall be provided for all boxes that are not to be cabled at

    the time of installation as indicated on the plans.

    F Fire Stopping: Fire stop all wall and floor/ceiling penetrations and pass-through to provide same fire rating as the wall or floor/ceiling.

    3.02 GROUNDING

    A Comply with TIA/EIA 607 and NEC.

    3.03 TESTING

    A Perform the following tests for voice and data station cables:

    1. For 100% of the pairs, perform testing as described in bulletin TSB-67, level I, basic link. Record the results of the test with cable identification and provide as part of the as-

    built drawings and cable management software. Any cable that fails shall be re-

    terminated and retested. If the cable does not retest satisfactorily, the cable shall be

    replaced and retested.

    B Record test data records to the cable management software data base. Data base shall be loaded with structured cabling information for each drop, room closet, general path, cross

    connects completed by contractor for riser cables and fiber and terminal block layouts.

    C Perform loss testing on all fibers of the fiber-optic cables and record results in the data base to be included in the as built documents.

    3.04 TRAINING

    A Provide (EDIT/INPUT FOR EACH PROJECT) hours instruction and training to Owners personnel for the following:

    1. Labeling system and cross reference to documentation.

    2. Interpretation of cable test results.

    E