  • DEPARTMENT OF ELECTRICAL ENGINEERING VIIIth SEM B.E.

    G.H.RAISONI COLLEGE OF ENGINEERING, NAGPUR 1

    G. H. RAISONI COLLEGE OF ENGINEERING DEPARTMENT OF ELECTRICAL ENGG.

    VIII SEMESTER B.E. SWITCHGEAR AND PROTECTION LAB

    INDEX

    Sr. No.

    Name of Experiment Page No.

    1 TO STUDY THE OPERATION OF DEFINITE TIME OVERCURRENT RELAY.

    2

    2 TO PLOT THE CHARACTERISTICS OF SINGLE POLE OVER CURRENT OR EARTH FAULT USING STATIC I.D.M.T. RELAYS

    5

    3 TO STUDY THE OPERATION OF STATIC OVER VOLTAGE RELAY

    8

    4 TO PLOT THE CHRACTERISTICS OF ELECTROMAGNETIC IDMT RELAY (MODEL NO.ICM-21NP)

    10

    5 TO STUDY THE OPERATION OF STATIC DEFINITE TIME REVERSE POWER RELAY (MODEL APDR-21)

    13

    6 A) TO STUDY THE MAGNETISATION CHARACTERISTICS OF C.T. B) TO STUDY THE PROBLEM ASSOCIATED WITH C.T. MAGNETISATION.

    16

    7 TO PLOT THE CHARACTERISTICS OF FUSE WIRE 18 8

    TO STUDY DIRECTIONAL OVER CURRENT RELAY ( ACDR 11 HPD)

    20

    9 TO STUDY AND PLOT THE CHARACTERISTICS OF IMPEDANCE RELAY ( ABB-RAKZB

    23

    10 TO STUDY TRANSFORMER DIFFERENTIAL PROTECTION 26 11 TO STUDY UNRESTRICTED EARTH FAULT RELAYS. 28

  • DEPARTMENT OF ELECTRICAL ENGINEERING VIIIth SEM B.E.

    G.H.RAISONI COLLEGE OF ENGINEERING, NAGPUR 2

    EXPERIMENT NO.1

    AIM: - TO STUDY THE OPERATION OF DEFINITE TIME OVERCURRENT RELAY.

    APPARATUS: -

    1) Timer 2) Static definite O/C relay (Model ACTU 32 P) 3) Auxiliary D.C. supply = 110V 4) 1 phase variac =230V, 4A 5) Ammeter AC (0-5A) and (0-1/2 A) 6) Rheostat (100 ohm, 5Amp) 7) Experiment Kit 8) Connecting wires

    CIRCUIT DIAGRANM:

    A

    (0-5A)

    1PH230V50 HZ

    SUPPLY

    ON

    OFF

    46

    35

    110VDC+ -

    1211

    36 OHM, 8.5A

    230V1-PH

    SUPPLY

    STARTSTOPTIMER

    THEORY:

    1. Principle and operation of static definite time over current relay, time current charact. equation.

    2. Block diagram of static over current relay.

  • DEPARTMENT OF ELECTRICAL ENGINEERING VIIIth SEM B.E.

    G.H.RAISONI COLLEGE OF ENGINEERING, NAGPUR 3

    PROCEDURE: -

    1) Connect the ckt as shown in fig procedure is done & time is noted. 2) Set current and time setting of relays as per requirement 3) Connect Auxiliary D.C. Supply (110) to pin 11 & 12 of relay and pin no.

    3&4 to the time interval meter. 4) Switch on the D.C. supply & make sure that relay is on Glowing of LED

    on the front panel of the relay. 5) Switch on power supply from dimmer as well as to time interval meter. 6) Adjust the current setting of the relay. 7) Adjust the time setting of relay. 8) Now by making DPDT switch on, increase the value of current by

    dimmer stat up to the point at which the relay trip. Trip can be observed by glowing of trip LED on front panel of relay.

    9) Switch is made off and relay is reset. 10) Now Switch is made on & time interval meter reading is noted. 11) For the same current setting , time setting is changed & same procedure

    is repeated until all the time setting are covered. 12) Again current setting is changed & same PROCEDURE IS REPEATED.

    OBSERVATION TABLE: -

    Sr. No.

    Relay set time in sec

    Set phase trip =100% Ammeter reading

    Timer time

    Set phase tri[p =180 % Ammeter reading

    Timer time

    1. 2. 3. 4.

    CHARACTERISTICS TABLE: -

    Current setting = , Pick up current =

    Sr. No. Fault current (A) PSM Timer time, for TMS =

    Timer time, for TMS =

    Timer time, for TMS =

    1

  • DEPARTMENT OF ELECTRICAL ENGINEERING VIIIth SEM B.E.

    G.H.RAISONI COLLEGE OF ENGINEERING, NAGPUR 4

    2 .

    .

    .

    10 RESULT & CONCLUSION: -

    The operation of definite time O/C relay is studied in this experiment. The reading is obtained for various time settings as well as current setting. It was found that for various time delay observed for peak up values of current is same.

    Viva Question 1 Application of DTOC relay. 2 Draw back of DTOC relay 3 Importance of DC supply 4 Detail of other O/C relays 5 Use of timer

  • DEPARTMENT OF ELECTRICAL ENGINEERING VIIIth SEM B.E.

    G.H.RAISONI COLLEGE OF ENGINEERING, NAGPUR 5

    EXPERIMENT NO.2

    AIM: - TO PLOT THE CHARACTERISTICS OF SINGLE POLE OVER CURRENT OR EARTH FAULT USING STATIC I.D.M.T. RELAYS

    APPARATUS: -

    1) Timer 2) IDMT relay (Model APR-11 P) 3) Auxiliary D.C. supplies = 110V 4) 1 phase Dimmer stat = 230V, 10A 6) Ammeter AC (0-15A) 7) Rheostat (38 ohm, 8.5 Amp) 8) Experiment Kit 9) Connecting wires

    CIRCUIT DIAGRAM

    A

    (0-15A)

    1PH230V50 HZ

    SUPPLY

    ON

    OFF

    46

    35

    110VDC+ -

    1211

    36 OHM, 8.5A

    230V1-PH

    SUPPLY

    STARTTIMERSTOP

    THEORY: -

    1. Define PSM, TSM. 2. Equation of time current characteristics. 3. Principle & Operation of static IDMT Relay with block diagram

  • DEPARTMENT OF ELECTRICAL ENGINEERING VIIIth SEM B.E.

    G.H.RAISONI COLLEGE OF ENGINEERING, NAGPUR 6

    PROCEDURE: -

    1) Make the connection as shown in fig. 2) Set current and time setting of relays as per requirement 3) Set phase trip to 50% and set phase time at X1 with phase TMS

    at maximum position. 4) Switch on variac and check power ON indication provided on

    relay front panel. 5) Very dimmer state with fault current of 1A,relayb will trip after

    certain time delay. 6) Switch OFF dimmer state without disrobing its position and

    change the position of DPT switch. Also reset time. 7) Switch ON dimmer state change the position of switch and

    measure the relay time from timer. 8) Reap eat same procedure for varying a different fault current. 9) Repeat this procedure consider different set phase time (TMS)

    OPERATION: -

    With supply on load are continuously monitored Electronic comparator checks this value with set value (N) of phase & earth fault trip, which can be adjusted on front plate. Pick up response is (1.1 N) IDMT timing is applicable to over current above 2N as per chosen curve. Time setting multiplier for actual tripping time delay. TMS is adjusted by 11-position switch & with variable preset pot. These pots adjusted time for intermediate values indicated on TMS switch. Tripping cause is indicated by LED lamp (OC/EF). When over current trips the circuit relay NO contact changes to NC when relay trips indicating LED to NC when relay trip indicating LED to NC when relay trips indicating LED to NC when relay trip indicating LED flag will remain ON till manually reset.

    OBSERVATION

    1 CHARACTERISTICS TABLE: - current setting =, Phase TMS

    Sr. No.

    Fault current (A)

    PSM Timer time for TSM =

    Timer time for TSM=

    Timer time for TSM=

    1 2 .

    .

    10

  • DEPARTMENT OF ELECTRICAL ENGINEERING VIIIth SEM B.E.

    G.H.RAISONI COLLEGE OF ENGINEERING, NAGPUR 7

    RESULT:

    For lower values of current the time current characteristics are inverse and for higher value of current, time observed is constant.

    Viva Question 1 Application of IDMT relay. 2 Draw back of IDMT relay 3 Importance of DC supply 4 Detail of other Inverse type of relays 5 Importance of static relays 6 Why IDMT relay suitable for protection of long length of LV/MV TL.

  • DEPARTMENT OF ELECTRICAL ENGINEERING VIIIth SEM B.E.

    G.H.RAISONI COLLEGE OF ENGINEERING, NAGPUR 8

    EXPERIMENT NO.3

    AIM: - TO STUDY THE OPERATION OF STATIC OVER VOLTAGE RELAY APPARATUS: -

    1) Static over voltage relay (Model No.: -ASOV) 2) Auxiliary D.C. supplies 110V 3) Time interval meter 4) Single pole variac 230V, 4A 5) Voltmeter (0-300V) AC 6) Rheostat (400 ohm, 1.7 Amp) 7) Connecting wires 8) Experiment Kit

    CIRCUIT DIAGRAM:-

    v

    OFF

    ON

    STARTSTOP

    TIMER

    110VDC11

    +

    12-

    (0-300V)9

    10

    3

    4

    1-PH230V,50HZ,

    SUPPLY

    300 OHM,1.7A

    STATIC OVER VOLTAGE RELAY

    THEORY: -

    1. Principle and operation of static over voltage relay. 2. Application of static over voltage relay.

    PROCEDURE:-

  • DEPARTMENT OF ELECTRICAL ENGINEERING VIIIth SEM B.E.

    G.H.RAISONI COLLEGE OF ENGINEERING, NAGPUR 9

    1) Connect the ckt as shown in fig procedure is done & time is noted.

    2) Set current and time setting of relays as per requirement 3) Connect Auxiliary D.C. Supply (110) to pin 11 & 12 of relay and

    pin no. 3&4 to the time interval meter. 4) Switch on the D.C. supply & make sure that relay is on Glowing

    of LED on the front panel of the relay. 5) Switch on power supply from dimmer as well as to time interval

    meter. 6) Adjust the voltage setting of the relay. 7) Adjust the time setting of relay. 8) Now by making DPDT switch on, increase the value of voltage

    by dimmer stat up to the point at which the relay trip. Trip can be observed by glowing of trip LED on front panel of relay.

    9) Switch is made off and relay is reset. 10) Now Switch is made on & time interval meter reading is noted. 11) For the same voltage setting , time setting is changed & same

    procedure is repeated until all the time setting are covered. 12) Again voltage setting is changed & same PROCEDURE IS

    REPEATED.

    OBSERVATION TABLE: -

    Sr. No.

    Time Knob Position in seconds.

    Set Voltage 105%=

    Timer time

    Set Voltage 130%=

    Timer time

    Set Voltage 155%=

    Timer time

    1 2 .

    .

    10

    RESULT: The static over-voltage relay is studied.

    Viva Question 1 Application of over and under voltage relay. 2 Draw back of electromagnetic as compare to static relays relay 3 Importance of DC supply 4 Range of under voltage relay

  • DEPARTMENT OF ELECTRICAL ENGINEERING VIIIth SEM B.E.

    G.H.RAISONI COLLEGE OF ENGINEERING, NAGPUR 10

    EXPERIMENT NO.4

    AIM: - TO PLOT THE CHRACTERISTICS OF ELECTROMAGNETIC IDMT RELAY (MODEL NO.ICM-21NP)

    APPARATUS: -

    1) Timer 2) IDMT relay (MODEL NO.ICM-21NP)) 3) Auxiliary D.C. supplies = 110V 4) 1 phase Dimmer stat = 230V, 10A 5) Ammeter AC (0-15A) 6) Rheostat (38 ohm, 8.5 Amp) 7) Experiment Kit 8) Connecting wires

    CIRCUIT DIAGRAM :

    A

    (38 ohm,8.5A)

    OFF

    ON

    110VDC

    230V1-PH50HZ

    SUPPLY

    (0-10A)230V50HZ,1-PH

    SUPPLY

    1

    2

    5

    6

    +3 - 4

    STOP

    STARTTI

    MER

  • DEPARTMENT OF ELECTRICAL ENGINEERING VIIIth SEM B.E.

    G.H.RAISONI COLLEGE OF ENGINEERING, NAGPUR 11

    THEORY: -

    1) Construction and operation of Induction disc/ watt-metric type electromagnetic Relays.

    2) Time current characteristics equation 3) Derivation of torque produced.

    PROCEDURE: -

    1) Make the connection as shown in the circuit diagram. 2) Select current setting (set phase trip) less than 100%, keeping

    phase TMS at maximum position. 3) Select any time setting. 4) Switch on variac and check power ON indication provided on

    relay front panel. 5) Vary dimmer stat and observe current value till Pick-Up will

    show Red indication when current value exceeds set phase trip position.

    6) Switch OFF dimmer stat without disturbing its position with the help of DPT switch. Also reset time.

    7) Measure the relay time from timer by switching on DPT switch. 8) Now increase the fault current and note down timer time after

    switching OFF and DPT switch every time with same time setting.

    9) Repeat same procedure for different time setting keeping current setting same.

    OBSERVATION TABLE OR CHARACTERISTICS TABLE: -

    Sr. No.

    Fault current (A) PSM Timer time For TSM =

    Timer time For TSM=

    Timer time For TSM=

    1 2 .

    .

    .

    10

    RESULT:

  • DEPARTMENT OF ELECTRICAL ENGINEERING VIIIth SEM B.E.

    G.H.RAISONI COLLEGE OF ENGINEERING, NAGPUR 12

    For lower values of current the time current characteristics are inverse and for higher value for current observed times are constant.

    Viva Question 1 Pickup, PSM and TSM 2 Draw back of IDMT relay 3 Derivation of Torque equation in detail 4 Detail of other Inverse type of relays

    5 Why IDMT relay suitable for protection of long length of LV/MV TL. 6 Reset time and trip time

    7 Why characteristics is plotted between PSM and operating time?

  • DEPARTMENT OF ELECTRICAL ENGINEERING VIIIth SEM B.E.

    G.H.RAISONI COLLEGE OF ENGINEERING, NAGPUR 13

    EXPERIMENT NO.5

    AIM: - TO STUDY THE OPERATION OF STATIC DEFINITE TIME REVERSE POWER RELAY (MODEL APDR-21)

    APPARATUS: -

    1) Timer 2) Static definite time reverse power relay (Model APDR 21) 3) Auxiliary D.C. supply = 110V 4) 3 phase variac =440V, 50 Hz, 8A 5) 1 phase variac =230V, 4A 6) Ammeter AC (0-1A) AC 7) Rheostat (300 ohm, 1.7Amp) 8) Phase shifting transformer 9) Voltmeter (0-300V) AC 10) Experiment Kit 11) Connecting wires

    CIRCUIT DIAGRAM :

    A

    V

    PHASE

    SHIFTING

    TRANFORMER

    R R

    Y

    B

    N N

    (0-300V)

    1 PHVARIAC270V,

    4A

    RELAY

    CT7 8

    11 3

    12 4

    PT

    START

    STOP

    1 PH230V,

    50HZ, ACSUPPLY

    R

    Y

    B

    N

    3 PH440VAC

    SUPPLY

    (0-2A)

    TIMER

  • DEPARTMENT OF ELECTRICAL ENGINEERING VIIIth SEM B.E.

    G.H.RAISONI COLLEGE OF ENGINEERING, NAGPUR 14

    THEORY:

    1. Describe the operating principle, constructional feature and area of application of reverse power relay.

    2. Draw simplified block diagram of static reverse power O/C relay.

    OPERATION: -

    Solid static state voltage and current sensing circuits measure the instantaneous voltage and current value in scales down format .The algorithmic circuit does the multiplication of the derived data. The output of this circuit remains positive as the moment when power reversal occurs, output of the circuits changes again. It is noted as pick up point and thus indicated by pick up LED. This also triggers the internal timer cit. This timer is adjustable by 11 positive switches. It has very high repeat accuracy. (Better than class 17) After the end of set timing and if power conduction are still reverse.

    PROCEDURE: -

    1) Make the connection as shown in fig. 2) Set current and time setting of relays as per requirement 3) Switch on supply to 3phase dimmerstate and also D.C. supply to

    relay. 4) By vaaarying 3 phase dimmerstate adjust the value of current . 5) Now keeping current at this val;ue constant change the angle of

    phase shifting tranfofmer gradually. 6) Observe the tripping zone of reverse power relay. 7) The relay will trip at certain angle of phase shifting transformer note

    down the angle and reset the relay. 8) Again increase the angle and observe tripping of relay. 9) Plot the tripping region of reverse power relay on the graph paper.

    OBSERVATION TABLE: -

    Sr. No. Phase angle Trip response 1 0 2 30 3 60 - -

    - -

    - -

    - Till 360

  • DEPARTMENT OF ELECTRICAL ENGINEERING VIIIth SEM B.E.

    G.H.RAISONI COLLEGE OF ENGINEERING, NAGPUR 15

    Sr.No. Time setting in sec Trip time in sec 1 0 2 1 3 - 4 - Till 10

    RESULT: The operation of definite time reverse power relay is studied and triggering zone is plotted in the graph paper.

    Viva Question 1 Application of Reverse power relay 2 Types of relays used and its setting for protection of ring main feeders 3 Comparison of other directional relays and reverse power relays

  • DEPARTMENT OF ELECTRICAL ENGINEERING VIIIth SEM B.E.

    G.H.RAISONI COLLEGE OF ENGINEERING, NAGPUR 16

    EXPERIMENT NO: - 06

    A) TO STUDY THE MAGNETISATION CHARACTERISTICS OF C.T.

    B) TO STUDY THE PROBLEM ASSOCIATED WITH C.T. MAGNETISATION.

    APPARATUS:- 1) Current transformer ( CT ) 5/1 Amp 2) Ammeter :- ( 0-10 A) 3) Multimeter 4) Rheostat ( 38 ohm , 1.7 amp ) 5) 1 phase Dimmerstate.

    THEORY:- Plot the excitation curve and explain

    (i) From origin to ankle point (ii) From ankle pt. to knee (iii) Knee region (iv) Saturation region

    CIRCUIT DIAGRAM :

    A

    (O-1A)

    V

    1:5 A CURRENT

    TRANSFORMER

    (0-75V)OR

    MULTIMETER

    230V50HZ,1PH,

    SUPPLY

    300ohm,1.7A

    O.C.

    PROCEDURE:-

    (1) Make connections as shown (2) Current is increased by 1 phase shown (3) A certain value of current , measure voltage from

    multimeter

  • DEPARTMENT OF ELECTRICAL ENGINEERING VIIIth SEM B.E.

    G.H.RAISONI COLLEGE OF ENGINEERING, NAGPUR 17

    (4) Again increase the value of current and note down voltage. (5) Similar procedure is done and current is increased till the

    saturation of C.T. (6) Draw graph of current Vs voltage.

    CONCLUSION :- Magnetization curve of C.T. is studied. Ankle point, knee point and saturation is observed.

    Viva Question 1 Difference between protective CTs and measuring CTS 2 Why CT get saturate in differential protective scheme during external fault 3 Use of CTs in protection of any equipment 4 No. of CTs require for protection of transformer and generator and their

    connection.

  • DEPARTMENT OF ELECTRICAL ENGINEERING VIIIth SEM B.E.

    G.H.RAISONI COLLEGE OF ENGINEERING, NAGPUR 18

    EXPERIMENT NO :- 07

    AIM :- To plot the characteristics of Fuse wire

    APPARATUS- 1) Fuse wire 2) Ammeter AC (0-10 A) 3) Stop watch 4) 1 ph Dimmerstat 230V, 10 A 5) Loading Rheostat 6) Rheostat (38 Ohm, 8.5 A) 7) Experimental Kit 8) Connecting Wires

    CIRCUIT DIAGRAM:-

    LOAD

    FUSE

    DIMMERSTATE1PH

    230V,8A

    1PH230V50HZ,

    SUPPLY

    A(0-15A) 38 ohm,8.5A

    THEORY: - 1) Detail theory and operation of fuses 2) Characteristics of Fuse 3) Types of Fuses

    PROCEDURE: - 1) Make the connections as shown in Fig.

  • DEPARTMENT OF ELECTRICAL ENGINEERING VIIIth SEM B.E.

    G.H.RAISONI COLLEGE OF ENGINEERING, NAGPUR 19

    2) Switch on the supply and keep the full load in the on position. Adjust the current to certain value with the help of dimmerstat

    3) Stop watch is stopped when the fuse element is blown which is indicated by decreasing of current in ammeter to zero. Note down the time of stop watch.

    4) Again after changing the fuse element increase the current to certain value and repeat above procedure .

    OBSERVATION:

    Sr.No Current ( Amp) Time (Sec) 1 .

    .

    5

    RESULT AND CONCLUSION :-

    The characteristics of fuse wire is studied in this experiment and is found to be inverse type ,and is plotted on graph paper .

    Viva Question 1 Application of fuse wire 2 comparisons of fuse and circuit breaker 3 Types of fuses and their application 4 types of fuse require for protection of transformer, generator and induction motor

  • DEPARTMENT OF ELECTRICAL ENGINEERING VIIIth SEM B.E.

    G.H.RAISONI COLLEGE OF ENGINEERING, NAGPUR 20

    EXPERIEMNT NO:- 08

    AIM :- TO STUDY DIRECTIONAL OVER CURRENT RELAY ( ACDR 11 HPD)

    APPARATUS :- 1) ASHIDA make single pole directional O/C relay ACDR 11 HPD 2) Phase shifting transformer 3) Dimmerstat ( 3 phase , 440 volt, 50 Hz ) 4) Ammeter (0-1 Amp) 5) Rheostate ( 300 ohm , 1.7 Amp) 6) Dimmerstat ( 1 phase , 230 volt, 4 Amp) 7) DC Power Supply ( 110 Volt )

    CIRCUIT DIAGRAM:

    A

    (0-2A)

    3-PHSHIFTINGTRANSFO

    RMER

    R R

    Y

    B

    N N3 4

    12 8

    7

    1615

    110VDC+ -

    TO TRIPCIRCUIT

    B

    Y

    R

    3-PH440V50 HZ

    ACSUPPLY

    PTCT

    TIMER

    1000ohm,1.2A

    11

  • DEPARTMENT OF ELECTRICAL ENGINEERING VIIIth SEM B.E.

    G.H.RAISONI COLLEGE OF ENGINEERING, NAGPUR 21

    THEORY : - 1. Directional O/C relay 2. Directional relay connection

    OPERATION-

    Load current is continuously monitored and compared to set value and polarized with voltage for direction sensing. As soon as the current exceeds the set value and it is operating direction then N value (Time set value) is calculated and then the delay time count is started , two types of curves 10 times ( N=10 ) current 3.0 sec . Delay and 1.3 sec delay can be provided. At the end of the time count if the current still exceeds the set value TRIP is exceeded. All the monitored current value is available at the front D is skeets for external recording . If the direction is reverse then the TRIP execution is (represented) restrained high fault setting is also provided (2N. 20 N) IF the current value exceeds the HF set value instant trip (i.e. 100 msec.) is executed, by passing the directional restraint.

    PROCEDURE:-

    1) Make the connections as shown in the fig. 2) Apply the voltage across the P.T of relay 3) The pick up current through the relay coil. 4) Set current and time setting of relays as per requirement 5) Switch on the supply. 6) Find out the operating region and non-operating region of

    relay by changing angle using the phase shifting transformer. 7) Adjust the current to such a value, which is more than plug

    setting. 8) Change the shifter angle such that relay operates in that

    region.

    OBSERRVATION TABLE :

    Sr. No.

    Phase angle MTS = MAX torque setting

    45 degree 60 Degree 9th Line 1 0

    2 30

    3 60

    4 90

    5 120

    6 150

    7 180

    8 -150 degree till

    9 0 degree

  • DEPARTMENT OF ELECTRICAL ENGINEERING VIIIth SEM B.E.

    G.H.RAISONI COLLEGE OF ENGINEERING, NAGPUR 22

    RESULT:- The static directional relay is studied and graph for different maximum torque setting is drawn.

    Viva Question 1 Application of Directional over current relay 2 Derivation of max. torque angle in directional O/C relay 3 Protection of ring main feeders 4 300, 600and 900 connection in directional relays

  • DEPARTMENT OF ELECTRICAL ENGINEERING VIIIth SEM B.E.

    G.H.RAISONI COLLEGE OF ENGINEERING, NAGPUR 23

    EXPERIMENT NO : 09

    AIM :- TO STUDY AND PLOT THE CHARACTERISTICS OF IMPEDANCE RELAY ( ABB-RAKZB)

    APPARATUS :-

    1) 3 Phase AC Autotransformer 2) Voltmeter (0-150 V) 3) Ammeter(0- 2 Amp) 4) Rheostat ( 300 ohm , 1.7 Amp) 5) 3 Phase Impedance Relay 6) Phase shifting Transformer 7) 1 Phase Variac / DIMMERSTAT 8) Auxiliary DC Supply

    CIRCUIT DIAGRAM :

    3PHDIMMERSTAT

    IMPEDANCERELAYV (0-75V)

    Ru

    Su

    Tu

    O/P

    +1

    -

    18

    A

    (0-2A)

    R

    N

    O/P

    PHASESHIFTING

    TRANSFORMER

    R

    Y

    B

    3 PH440V

    50 HZ,AC

    SUPPLY

    3 PH440V

    50 HZ,AC

    SUPPLY

    S1 S1

    1000 ohm,1.7A

    N

  • DEPARTMENT OF ELECTRICAL ENGINEERING VIIIth SEM B.E.

    G.H.RAISONI COLLEGE OF ENGINEERING, NAGPUR 24

    THEORY : 1) Explain Unit and non unit protection with examples 2) Explain characteristics of different distances relay on R-X diagram 3) Explain static impedance relay with amplitude and phase comparator. 4) Advantages of static relay over electromechanical relay.

    PROCEDURE :

    1) Make the connections as shown in the circuit diagram. 2) Keep the rheostat in the middle position. 3) Switch on the supply to the phase shifter and also the DC supply. 4) Now reduce the voltage of the autotransformer, note the voltages at

    which the relay operates. 5) Change the position of phase shifter & repeat the steps 4,5,6. 6) After taking no of readings change the value of current and repeat

    the above steps. 7) Note down the pickup impedance value of the relay. 8) Plot the operating and non-operating region of relay on R-X plane.

    NOTE :- The output voltage of phase shifter is set at 110V and the voltage output from the auto transformer is also 100 V maximum permissible value .

    OBSERVATION TABLE:

    For A=20, B=6, Ia= 01 Amp

    Sr No. Phase Angle( ) Voltage ( V) 1) 0 degree 2) 30 degree 3) 60 degree 4) 90 degree 5) 120 degree 6) 150 degree 7) : 8) : 9) 360 degree 10) 0 degree

  • DEPARTMENT OF ELECTRICAL ENGINEERING VIIIth SEM B.E.

    G.H.RAISONI COLLEGE OF ENGINEERING, NAGPUR 25

    Same table for A =40, B= 8, Ia =0.5 Amp

    Sr. / No.

    I (Amp) Voltage (V) volts

    1 0.1 2 0.2 3 0.3 4 0.4 5 0.5 6 0.6 7 0.7 8 0.8 9 0.9

    10 1.0

    RESULT :- The relay operates for any value of the radius less than the radius of the circle, hence the operating region of the relay inside the circle.

    Viva Questions:

    1 Torque equation of Reactance and mho relay with their characteristics. 2 Effect of arc resistance in distance relay 3 Selection of distance relay. 4 Effect of power swing in distance relay

  • DEPARTMENT OF ELECTRICAL ENGINEERING VIIIth SEM B.E.

    G.H.RAISONI COLLEGE OF ENGINEERING, NAGPUR 26

    EXPERIMENT NO : 10

    AIM :- TO STUDY TRANSFORMER DIFFERENTIAL PROTECTION

    APPARATUS :-

    1) Static Differential Relay (Model No. ACDF 31 HA) 2) 1 Ph Dimmerstat 230V, 10 A 3) 2 CT (10/ 5A and 20/5A) 4) Ammeter AC (0- 15 A) 3 No. 5) Ammeter AC (0- 5 A) 2 No. 6) Rheostat (38 ohm, 8.5 A) 7) Loading Rheostat 8) Multimeter 9) 1 ph Transformer 230/115 V, 50 Hz, 1 KVA 10) Connecting wires

    CIRCUIT DIAGRAM :

    A A

    AA

    A

    LOAD

    110V DC

    7

    27

    8

    28

    1PH230

    50 HZA.C.

    SUPPLY

    (0-15A)

    (0-15A)

    (0-5A)

    (0-20A)

    (0-5A)

    M LL

    M

    38ohm, 8.5A

    - 16+15

    THEORY: -

    1. Differential protection theory

  • DEPARTMENT OF ELECTRICAL ENGINEERING VIIIth SEM B.E.

    G.H.RAISONI COLLEGE OF ENGINEERING, NAGPUR 27

    2. 1ph and 3 ph Transformer differential protection scheme 3. Difference between Transformer and generator Differential

    protection.

    PROCEDURE: -

    1) Make circuit connection as shown in ckt. Diagram. 2) Open the parallel path of secondary transformer containg rheostat with

    ammeter. Transformer is connected now at full load condition. 3) With the help of dimmerstat, give some supply voltage to primary side

    of transformer and observe its current. Make sure secondary current is varying in proportion to turn ratio. And current through secondary side of two CTs are zero.

    4) Now connect the parallel path of secondary transformer by touching wire to the secondary terminal of transformer and observe the current through secondary side of two CTs. There is a difference of two CTs currents and at this condition differential relay will trip.

    5) Note down values of these currents through secondary side of two CTs 6) Plot the characteristics between summation and difference of these two

    currents. OBSERVATION

    Sr. No.

    Secondary current of CT= i1(A)

    Secondary current of CT= i2(A)

    Restraining Torque= (i1(A) + i2(A))/2

    Operating Torque= i1(A) - i2(A)

    1

    2

    .

    5

    RESULT- Transformer differential relay is studied. The characteristics between restraining and operating torque are straight line. Viva question:

    1 Why ratio of two Cts is different? 2 Circuit connection of 3 phase Y transformer 3 Explain biased differential relay 4 Types of fault occur in transformer 5 No. of CTs require and their connection for protection of 3 phase

    transformer

  • DEPARTMENT OF ELECTRICAL ENGINEERING VIIIth SEM B.E.

    G.H.RAISONI COLLEGE OF ENGINEERING, NAGPUR 28

    EXPERIMENT NO : 11

    AIM- To study unrestricted earth fault relays.

    APPARATUS- 1) Static IDMT earth fault relays ( Model No. APR 41 ) 2) Rheostat ( 100 ohm, 5 A).3 Nos. 3) Ammeter AC ( 0- 5A).3 Nos. 4) Ammeter AC ( 0- 1A) 5) Experimental kit 6) Aux. DC supply- 110 V DC 7) Timer 8) 3 ph Dimmerstat 9) Connecting wires

    CIRCUIT DIAGRAM

    +-

    110V DC

    TIMER

    ON OFF

    3PH

    DIMMERSTAT

    A

    A

    AR

    Y

    B

    3 - PHAC

    SUPPLY440V,50 HZ

    (0-5A)

    (0-5A)

    (0-5A)

    N

    I/P O/P

    100ohm,5A

    100ohm,5A100ohm,5A

    3

    4

    11 12

    STARTSTOP

    1 phsupply

  • DEPARTMENT OF ELECTRICAL ENGINEERING VIIIth SEM B.E.

    G.H.RAISONI COLLEGE OF ENGINEERING, NAGPUR 29

    THEORY- 1) Unrestricted and restricted earth fault relays with ckt connection 2) Their application.

    PROCEDURE- 1) Connect the circuit as shown in figure. 2) Set current and time setting of relays as per requirement 2) Give 3 ph. Supply to stat connected rheostat (load) 3) balance the load by making all three phase currents equal in magnitude. 4) Create a fault by short circuiting some of the winding of a single phase load. 5) Note down fault current and take corresponding time for tripping relay by resetting relay and timer by switching off without disturbing dimmerstat position. 6) Repeat same procedure with different fault current and plot characteristics between PSM and operating time

    OBSERVATION TABLE: Relay current Setting - TMS -

    Sr. No. Fault Current (A) Timer time( Sec)

    RESULT: The unrestricted earth fault relay is studied

    Viva question:

    1 Application of earth fault relay. 2 Importance of high impedance connected between neutral to ground 3 Difference between setting of earth fault and phase fault relays

  • DEPARTMENT OF ELECTRICAL ENGINEERING VIIIth SEM B.E.

    G.H.RAISONI COLLEGE OF ENGINEERING, NAGPUR 30