3"3"---FOOTINGS
2"1
1
2
"
3
4
"WALLS
2"1
1
2
"1
1
2
" ---
---
3"
TABLE 2: CONCRETE PROTECTION
TYPE OF
STRUCTURE
NOT EXPOSED
TO EARTH OR
WEATHER IN
SERVICE
EXPOSED TO EARTH OR
WEATHER IN SERVICE
EARTH
FORMED
#5 OR
SMALLER
#6 OR
LARGER
SLABS
3
4
" 1
1
2
" 2" 3"
CONSTRUCTION SHALL COMPLY WITH, AND DESIGN HAS BEEN PERFORMED IN
ACCORDANCE WITH, THE PROJECT SPECIFICATIONS AND THE NOTES BELOW. IF THERE
ARE ANY PERCEIVED CONFLICTS BETWEEN THE SPECIFICATIONS AND THE NOTES OR THE
DRAWINGS, THE CONTRACTOR SHALL SUBMIT A WRITTEN REQUEST FOR CLARIFICATION TO
THE COTR. SEE THE CONTRACT SPECIFICATIONS FOR QUALITY ASSURANCE
REQUIREMENTS.
A. CODES, STANDARDS, AND REFERENCES
1. BUILDING CODE: INTERNATIONAL BUILDING CODE (IBC)-2012.
2. CONCRETE CODES: SPECIFICATIONS FOR STRUCTURAL CONCRETE ( ACI 301-10)
AND BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE ( ACI 318-11).
REINFORCING DETAILS SHALL CONFORM TO THE ACI DETAILING MANUAL AND CRSI
STANDARDS.
3. STEEL CODES: SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS (ANSI/AISC
360-10). STRUCTURAL WELDING CODE - STEEL (AWS D1.1-2010).
4. MASONRY CODE: BUILDING CODE REQUIREMENTS AND SPECIFICATIONS FOR
MASONRY STRUCTURES ACI 530/530.1-11.
C. FLOOR LIVE LOADS
1. LIGHT STORAGE: 125 PSF.
2. HEAVY STORAGE: 250 PSF.
D. ROOF LIVE LOAD
1. FLAT ROOF: 20 PSF.
F. SNOW LOADS
1. GROUND SNOW LOAD (P
g
): 25 PSF.
2. FLAT ROOF SNOW LOAD (P
f
): 20 PSF.
3. SNOW IMPORTANCE FACTOR (I
S
): 1.0.
4. SNOW EXPOSURE FACTOR (C
e
): 0.9.
5. SNOW LOAD THERMAL FACTOR (C
T
): 1.0.
6. IN ADDITION TO THE UNIFORM ROOF SNOW LOAD STATED ABOVE, DRIFTING SNOW
HAS BEEN EVALUATED. WHERE DRIFTING SNOW GOVERNS OVER THE FLAT ROOF
LIVE LOAD STATED ABOVE, MAXIMUM DRIFT LOAD IS 94 PSF AND TAPERS TO THE
FLAT ROOF SNOW LOAD AT A DISTANCE OF 18'-2".
G. WIND LOADS
1. ULTIMATE DESIGN/BASIC WIND SPEED (3 SECOND GUST) (V
ult
/V
3s
): 115 MPH.
2. NOMINAL DESIGN WIND SPEED (V
asd
): 89 MPH.
3. WIND EXPOSURE CATEGORY: C.
4. WIND INTERNAL PRESSURE COEFFICIENTS (GC
pi
): +/- 0.18.
5. COMPONENTS AND CLADDING WIND PRESSURES ARE 32.5 PSF (PRESSURE) AND
43.5 PSF (SUCTION). NOTE: THESE PRESSURES ARE BASED ON AN EFFECTIVE
WIND AREA OF 10 SQUARE FEET. COMPONENTS AND CLADDING DESIGN
PRESSURES MAY BE REDUCED IN ACCORDANCE WITH THE BUILDING CODE.
J. GEOTECHNICAL CRITERIA
1. THE GEOTECHNICAL CRITERIA LISTED BELOW IS IN ACCORDANCE WITH THE
GEOTECHNICAL REPORT PREPARED BY SCHNABEL ENGINEERING AND DATED MAY
15, 2015.
2. GEOTECHNICAL REPORT RECOMMENDS THE INSTALLATION OF STONE COLUMNS
FOR GROUND IMPROVEMENT TO ACHIEVE THE DESIGN SOIL BEARING PRESSURE.
SEE SPECIFICATION SECTION 31 32 00.
3. DESIGN SOIL BEARING PRESSURE: 3000 PSF.
4. STATIC ACTIVE LATERAL EARTH PRESSURE FOR RETAINING WALLS: 45 PSF/FT.
5. PASSIVE EARTH PRESSURE: 330 PSF/FT.
6. HORIZONTAL SURCHARGE PRESSURE COEFFICIENT: 0.36.
7. FRICTION COEFFICIENT: 0.34.
H. SEISMIC CRITERIA
1. SITE CLASS IS: D.
2. SEISMIC IMPORTANCE FACTOR (I
E
): 1.0.
3. MAPPED SPECTRAL RESPONSE ACCELERATION AT SHORT PERIODS (S
S
): 0.164.
4. MAPPED SPECTRAL RESPONSE ACCELERATION AT 1-SECOND PERIOD (S
1
): 0.055.
5. DESIGN SPECTRAL ACCELERATION PARAMETER AT SHORT PERIODS (S
DS
): 0.175.
6. DESIGN SPECTRAL ACCELERATION PARAMETER AT 1-SECOND PERIOD (S
D1
): 0.088.
7. SEISMIC DESIGN CATEGORY: B.
8. BASIC SEISMIC FORCE RESISTING SYSTEM IS STEEL ORDINARY CONCENTRICALLY
BRACED FRAMES.
9. SYSTEM OVERSTRENGTH FACTOR (Ω
0
): 2.0.
10. DEFLECTION AMPLIFICATION FACTOR (C
d
): 3.25.
11. SEISMIC RESPONSE COEFFICIENT (C
s
): 0.054.
12. RESPONSE MODIFICATION COEFFICIENT (R): 3.25.
13. ANALYSIS PROCEDURE: EQUIVALENT LATERAL FORCE PROCEDURE.
14. DESIGN BASE SHEAR (LOW ROOF): 4.8 KIPS.
15. DESIGN BASE SHEAR (HIGH ROOF): 24.8 KIPS.
B. OCCUPANCY
1. RISK CATEGORY: II.
K. MATERIALS AND PHYSICAL PROPERTIES
1. "(___)" INDICATES ASTM STANDARD FOR WHICH MATERIAL SHALL CONFORM.
2. CONCRETE PROPERTIES SHALL CONFORM TO THE CRITERIA SPECIFIED IN TABLE 1
BELOW.
3. CONCRETE REINFORCEMENT (A615, GRADE 60)................................. Fy=60,000 psi
4. MASONRY.................................................................................................... f'm=1,500 psi
5. CONCRETE BLOCK FOR REINFORCED CONSTRUCTION SHALL BE TWO CELL UNITS
CONFORMING TO (C90, TYPE I), MEDIUM-WEIGHT CONCRETE.
6. MORTAR SHALL BE PORTLAND CEMENT/LIME.
7. MORTAR (C270), TYPE S............................................................................ f'c=1800 psi
8. GROUT (C476)............................................................................................. f'c=5000 psi
9. STRUCTURAL STEEL
a. W-SHAPES (A992)................................................................................. Fy=50,000 psi
b. ANGLES AND PLATES (A36)................................................................ Fy=36,000 psi
10. WELDING ELECTRODES: PER TABLE 3.1 OF AWS D1.1 FOR THE SMAW PROCESS OR
ANY OTHER PREQUALIFIED WELDING PROCEDURES SPECIFICATIONS (WPS).
11. STEEL BOLTS AND THREADED RODS
a. HIGH STRENGTH BOLTS (A325) 0.5"Ø TO 1"Ø (INCL)...................... Fu=120,000 psi
b. THREADED STEEL RODS (A36).................................... Fy=36,000 psi, Fu=58,000 psi
c. ANCHOR RODS (F1554, GRADE 36)............................. Fy=36,000 psi, Fu=58,000 psi
12. ROOF DECK, AND ACCESSORIES (A653)................................................ Fy=33,000 psi
L. FOOTINGS
1. FOOTING ELEVATIONS SHOWN ON THE PLANS ARE AT TOP OF FOOTINGS.
2. LOCATION OF FOOTING STEPS SHOWN ON THE FOUNDATION PLAN ARE
APPROXIMATE AND INTENDED FOR USE BY THE CONTRACTOR IN BIDDING. EXACT
LOCATION SHALL BE DETERMINED IN THE FIELD BY THE GENERAL CONTRACTOR
USING THE SITE PLAN AND THE GEOTECHNICAL REPORT.
3. THE BOTTOM ELEVATION OF NEW FOOTINGS ADJACENT TO EXISTING FOOTINGS
MUST MATCH THE BOTTOM ELEVATION OF THE EXISTING FOOTINGS UNLESS
OTHERWISE DETAILED ON THE DRAWINGS.
4. ELEVATIONS OF THE TOP OF EXISTING FOOTINGS THAT ARE SHOWN ON THE
DRAWINGS ARE BASED UPON EXISTING BUILDING DRAWING 360-S1, DATED
OCTOBER 10, 1984. CONTRACTOR MUST FIELD VERIFY EXISTING CONDITIONS AND
ADJUST THE NEW FOOTING ELEVATIONS AS REQUIRED TO MATCH THE ELEVATION
OF THE EXISTING BOTTOM OF FOOTING.
5. BOTTOMS OF ALL FOOTINGS SHALL EXTEND 1'-0" MINIMUM INTO UNDISTURBED
SOIL AND, WHERE SUBJECT TO FROST ACTION, AT LEAST 2'-6" FEET BELOW
FINISHED GRADE.
6. IF THE DESIGN SOIL BEARING PRESSURE NOTED IN THE STRUCTURAL NOTES
SECTION "GEOTECHNICAL CRITERIA" CANNOT BE ACHIEVED AT THE FOOTING
ELEVATIONS INDICATED ON THE FOUNDATION PLAN, THE COTR SHALL BE NOTIFIED
IN WRITING FOR GUIDANCE.
7. FOOTING SUBGRADE SHALL BE APPROVED BY THE COTR PRIOR TO PLACEMENT OF
THE FOOTINGS.
8. UNLESS NOTED OTHERWISE, WHERE UTILITIES ENTER THE BUILDING 4 FEET OR
LESS BELOW THE BOTTOM OF FOOTING ELEVATION, THE FOOTING SHALL BE
STEPPED DOWN TO ALLOW THE UTILITIES TO PASS THROUGH THE FOUNDATION
WALL AND THE WALL PENETRATION SHALL BE SLEEVED AND PATCHED, SEE DETAIL
3/S501. WHERE UTILITIES ENTER THE BUILDING MORE THAN 4 FEET BELOW THE
BOTTOM OF FOOTING ELEVATION, THE UTILITIES SHALL PASS UNDER THE
FOOTING, PER DETAIL 4/S501. COORDINATE WITH MEP DRAWINGS.
M. BACKFILL PLACEMENT AND COMPACTION
1. BACKFILLING AGAINST WALLS WILL NOT BE PERMITTED UNTIL STRUCTURAL
BRACING ELEMENTS ARE OR FLOOR CONSTRUCTION IS IN PLACE. BRACING
ARRANGEMENTS SHALL BE APPROVED BY THE COTR PRIOR TO BACKFILLING.
2. THE CONTRACTOR SHALL TAKE ALL NECESSARY PRECAUTIONS TO BRACE
FOUNDATION AND BASEMENT WALLS WHEN BACKFILLING AND WHEN THERE IS A
POSSIBILITY OF DAMAGE BY EXCESS WATER. BACKFILLING AGAINST SUCH WALLS
SHALL BE DONE IN A MANNER THAT WILL NOT DAMAGE WALLS. ALL PRECAUTIONS
SHOULD BE TAKEN FOR ADEQUATE DRAINAGE PRIOR TO AND AFTER SUCH
BACKFILLING.
3. ALL FILL MATERIAL SHALL BE PLACED IN MAXIMUM LOOSE LIFTS OF 8" AND SHALL
BE COMPACTED TO DRY DENSITIES OF AT LEAST 95 PERCENT OF THE STANDARD
PROCTOR MAXIMUM DRY DENSITY (ASTM D-698).
N. CAST-IN-PLACE CONCRETE CONSTRUCTION
1. CONCRETE WORK SHALL CONFORM TO ALL REQUIREMENTS OF ACI 318, ACI 301,
AND THE ACI DETAILING MANUAL, EXCEPT AS MODIFIED BY THE CONTRACT
SPECIFICATIONS AND SUPPLEMENTAL REQUIREMENTS BELOW.
2. SEE STRUCTURAL NOTES SECTION "MATERIALS AND PHYSICAL PROPERTIES" FOR
CONCRETE STRENGTHS AND PROPERTIES.
3. PROVIDE VERTICAL CONTROL JOINTS IN REINFORCED CONCRETE WALLS WHERE
INDICATED ON PLAN, BUT AT NOT MORE THAN 25 FEET ON CENTER. STOP ALL
HORIZONTAL BARS IN EXPOSED FACE AT JOINTS (SEE SHEET S505 FOR TYPICAL
DETAIL).
4. PROVIDE CONTINUOUS INTENTIONALLY ROUGHENED JOINT (1/4" MIN AMPLITUDE)
AT INTERFACE WHERE CONCRETE WALLS ARE SUPPORTED ON FOOTINGS AND
WHERE CONCRETE SLABS ARE SUPPORTED ON CONCRETE WALLS.
5. ADD HIGH-RANGE WATER REDUCING ADMIXTURE (SUPER PLASTICIZER) TO
CONCRETE MIX FOR PUMPED CONCRETE AND WHERE REQUIRED FOR
WORKABILITY. LIMIT SLUMP IN CONCRETE TO 8" AFTER ADDITION OF HIGH-RANGE
WATER REDUCER TO CONCRETE VERIFIED TO HAVE A 2"-4" SLUMP.
6. CONCRETE TEST CYLINDERS SHALL BE TAKEN IN ACCORDANCE WITH THE
REQUIREMENTS OF ACI 318, CHAPTER 5 AND THE CONTRACT SPECIFICATIONS.
7. SEE CONTRACT SPECIFICATIONS, SECTION 033000 "CAST-IN-PLACE CONCRETE"
FOR ADMIXTURE REQUIREMENTS. ADMIXTURE DOSAGE, ADDITION TIMES,
COMPATIBILITY WITH OTHER ADMIXTURES, AND COMPATIBILITY WITH OTHER MIX
CONSTITUENTS SHALL BE THE RESPONSIBILITY OF THE MANUFACTURER.
P. CONCRETE REINFORCEMENT
1. SEE STRUCTURAL NOTES SECTION "MATERIALS AND PHYSICAL PROPERTIES" FOR
CONCRETE REINFORCEMENT STRENGTH.
2. DETAILS OF STEEL REINFORCEMENT SHALL CONFORM TO ACI 318 AND CRSI
STANDARDS.
3. FOR ADDITIONAL CONCRETE REINFORCING INFORMATION REGARDING
SLABS-ON-GRADE, REFER TO THE CORRESPONDING STRUCTURAL NOTES SECTION
AND THE DRAWINGS.
4. CONCRETE PROTECTION FOR STEEL REINFORCEMENT OF CAST-IN-PLACE
CONCRETE SHALL BE AS SPECIFIED IN TABLE 2 ON THIS SHEET, UNLESS NOTED
OTHERWISE.
5. UNLESS NOTED OTHERWISE, FOOTING DOWELS FOR CANTILEVERED "RETAINING"
WALLS SHALL PROJECT INTO WALL AS SHOWN ON RETAINING WALL SECTION(S).
6. UNLESS NOTED OTHERWISE, FOOTING DOWELS FOR BUILDING WALLS AND PIERS
SHALL PROJECT ABOVE THE FOOTING AS REQUIRED TO LAP SPLICE WITH THE
VERTICAL WALL/PIER REINFORCEMENT.
7. UNLESS NOTED OTHERWISE, ALL SPLICES FOR REINFORCING SHALL BE CLASS B
LAP SPLICES. WELDED SPLICES SHALL NOT BE USED.
8. WHEN REINFORCING STEEL IS NOTED AS CONTINUOUS IN WALLS, WALL FOOTINGS,
AND SLABS, SPLICE CONTINUOUS REINFORCING STEEL ONLY WHEN UNAVOIDABLE
DUE TO STOCK LENGTHS. STAGGER ALL SPLICES A MINIMUM OF 8'-0". ADJACENT
BAR SPLICES ARE NOT ACCEPTABLE. FOR REINFORCING SPLICES IN SLABS,
LOCATE THE TOP BAR SPLICES WITHIN THE MIDDLE HALF OF THE SPAN AND
LOCATE THE BOTTOM BAR SPLICES AT SUPPORTS , UNLESS NOTED OTHERWISE ON
THE PLANS, DETAILS, OR SCHEDULES.
9. FIBER REINFORCEMENT SHALL BE MONOFILAMENT MICRO-FIBERS. FIBER
REINFORCEMENT SHALL BE USED WHERE INDICATED AND APPLIED IN STRICT
ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATION AS TO FIBER
LENGTH AND QUANTITY. THE FIBER MANUFACTURER OR APPROVED DISTRIBUTOR
SHALL PROVIDE THE SERVICES OF A QUALIFIED REPRESENTATIVE FOR A
PRE-CONSTRUCTION JOB MEETING.
10. UNLESS NOTED OTHERWISE FIBER-REINFORCED CONCRETE SHALL HAVE A
DOSAGE RATE OF 1.5 LB/CY.
Q. SLABS-ON-GRADE
1. UNLESS NOTED OTHERWISE, SLABS-ON-GRADE SHALL BE 6 INCH THICK POURED
CONCRETE AND REINFORCED WITH FIBER REINFORCEMENT AS SPECIFIED IN THE
STRUCTURAL NOTES SECTION "CONCRETE REINFORCEMENT" AND PER 1/S503.
2. UNLESS NOTED OTHERWISE, PROVIDE A VAPOR BARRIER WITH A MINIMUM
THICKNESS OF 10 MILS, AS LOCATED ON THE DETAILS.
3. FILL UNDER SLABS-ON-GRADE SHALL BE MADE WITH MATERIAL APPROVED BY THE
COTR AND SHALL BE COMPACTED IN A MANNER THAT WILL NOT DAMAGE
FOUNDATION WALLS. IT SHALL BE WELL TAMPED IN 8" LAYERS IN ROUGH
THICKNESS, TO 95% MAXIMUM DRY DENSITY PER ASTM D-698 (STANDARD
PROCTOR).
4. PROVIDE A CONTINUOUS MANUFACTURED, SAW CUT, OR TOOLED CRACK
CONTROL JOINT IN THE TOP OF THE SLAB WHERE INDICATED ON PLAN BUT AT
SPACING NOT TO EXCEED 18 FEET. CONTROL JOINTS SHALL BE LOCATED ON
COLUMN CENTERLINES AND LOCATED BETWEEN COLUMN CENTERLINES AS
REQUIRED. LAY OUT CONTROL JOINTS TO FORM AS NEARLY SQUARE PANELS AS
PRACTICAL. IN RECTANGULAR PANELS, THE LONG SIDE SHALL NOT BE LONGER
THAN 1
1
2
TIMES THE DIMENSION OF THE SHORT SIDE.
5. PROVIDE AN ISOLATION JOINT AROUND COLUMNS AS SHOWN ON THE DRAWINGS
AND AT THE PERIMETER OF THE SLAB UNLESS NOTED OTHERWISE
R. MASONRY
1. SEE STRUCTURAL NOTES SECTION "MATERIALS AND PHYSICAL PROPERTIES" FOR
MASONRY BLOCK, GROUT, AND MORTAR PROPERTIES AND STRENGTHS.
2. UNLESS NOTED OTHERWISE, PROVIDE 1 COURSE OF 100% SOLID (NOT FILLED)
BLOCK OR 2 COURSES OF GROUTED BLOCK UNDER ALL CONCRETE SLABS
BEARING ON THE MASONRY WALLS.
3. UNLESS NOTED OTHERWISE, PROVIDE HORIZONTAL JOINT REINFORCING IN
ACCORDANCE WITH THE CONTRACT SPECIFICATIONS AT 16" ON CENTER MAX
VERTICALLY IN ALL MASONRY WALLS.
4. HIGH-LIFT GROUTING SHALL NOT BE PERMITTED.
5. LOCATE CONTROL JOINTS IN MASONRY CONSTRUCTION IN ACCORDANCE WITH
THE ARCHITECTURAL DRAWINGS.
6. SPECIAL INSPECTION AND TESTING ARE REQUIRED FOR THIS PROJECT. SEE
QUALITY ASSURANCE NOTES ON SHEET S003.
7. TESTING AND INSPECTION SHALL BE PERFORMED BY AN INDEPENDENT
INSPECTION AGENCY, HIRED BY THE CONTRACTOR.
8. AT A MINIMUM, FIELD INSPECTION AND TESTING SHALL BE PERFORMED ON ALL
BEARING WALLS . FIELD INSPECTION OF BEARING WALLS SHALL OCCUR AT THE
FOLLOWING INTERVALS: A) CONSTRUCTION START-UP; B) ONE-QUARTER
COMPLETION OF CONSTRUCTION; C) TWO-THIRDS COMPLETION OF
CONSTRUCTION; AND D) 95% COMPLETION OF CONSTRUCTION.
9. AT A MINIMUM, FIELD INSPECTION OF GROUTED MASONRY SHALL INCLUDE, BUT
NOT BE LIMITED TO, REVIEW OF HOLLOW CELLS PRIOR TO GROUTING,
MONITORING OF GROUT PLACEMENT, AND REVIEW PRIOR TO IMPOSING LOADS.
10. TEST MATERIALS AS REQUIRED BY THE PROJECT SPECIFICATIONS IN
ACCORDANCE WITH THE UNIT STRENGTH METHOD FOR DETERMINATION OF
MASONRY COMPRESSIVE STRENGTH PER ACI 530.1, SECTION 1.6. IN ADDITION,
TEST MORTAR AND GROUT FOR COMPLIANCE TO ASTM C270 AND ASTM C476,
RESPECTIVELY, PER THE REQUIREMENTS OF THE PROJECT SPECIFICATIONS.
FIELD INSPECTION AND TESTING SHALL BE PERFORMED BY AN APPROVED
INDEPENDENT INSPECTION AGENCY. INSPECTION AND TEST RESULTS SHALL BE
FURNISHED TO THE COTR FOR REVIEW.
U. STRUCTURAL STEEL
1. SEE STRUCTURAL NOTES SECTION "MATERIALS AND PHYSICAL PROPERTIES" FOR
THE STRENGTHS OF STRUCTURAL STEEL, BOLTS, THREADED RODS, ANCHOR
RODS, AND WELDS.
2. UNLESS NOTED OTHERWISE, FRAMED BEAM CONNECTIONS SHALL BE DESIGNED
BY THE FABRICATOR FOR A VERTICAL REACTION AS LISTED ON THE CONTRACT
DRAWINGS.
3. FOR BEAMS WITH NO REACTIONS LISTED, FRAMED BEAM CONNECTIONS SHALL BE
DESIGNED FOR A VERTICAL REACTION EQUAL TO ONE-HALF THE MAXIMUM TOTAL
UNIFORM LOADS (LRFD) (MINIMUM OF 6 KIPS) PRESENTED IN TABLE 3-6 OF THE
AISC "MANUAL OF STEEL CONSTRUCTION, 14TH EDITION.
4. THE LENGTH OF CONNECTION ANGLE(S) OR PLATE(S) SHALL NOT BE LESS THAN
HALF OF THE "T" DISTANCE OF THE BEAM WEB.
5. UNLESS NOTED OTHERWISE, BEAM CONNECTIONS FOR BEAMS ALONG BRACED
FRAMES SHALL BE DESIGNED BY THE FABRICATOR FOR THE AXIAL LOADS LISTED
ON THE BEAM AXIAL DESIGN LOAD SCHEDULE, 3/S506.
6. UNLESS NOTED OTHERWISE, HIGH STRENGTH BOLTS SHALL BE TIGHTENED TO A
SNUG TIGHT CONDITION AS DEFINED BY THE RCSC "SPECIFICATION FOR
STRUCTURAL JOINTS USING HIGH-STRENGTH BOLTS" (2009 EDITION).
7. WELDS SHALL BE INSTALLED BY WELDERS QUALIFIED IN ACCORDANCE WITH AWS
PROCEDURES FOR WELDER QUALIFICATION.
8. STRUCTURAL STEEL BELOW GRADE SHALL HAVE A MINIMUM OF 3" CONCRETE
COVER OR 4" SOLID MASONRY COVER.
9. UNLESS NOTED OTHERWISE, ALL STRUCTURAL STEEL MEMBERS SHALL BE
PAINTED WITH ONE COAT OF FABRICATORS STANDARD PRIMER PAINT, TWO MILS
DRY FILM THICKNESS.
10. WELDING INSPECTION SHALL BE MADE IN ACCORDANCE WITH THE INSPECTION
CHAPTER OF AWS D1.1 (2010).
11. TESTING AND INSPECTION SHALL BE IN ACCORDANCE WITH THE STRUCTURAL
NOTES FOR QUALITY ASSURANCE AND SPECIAL INSPECTION ON SHEET S003.
V. STEEL JOISTS
1. MATERIAL, FABRICATION, ACCESSORIES, BRIDGING, AND ERECTION SHALL
CONFORM TO THE SJI STANDARD SPECIFICATIONS FOR OPEN WEB STEEL JOISTS,
K-SERIES.
2. STANDARD STEEL JOISTS SHALL BE DESIGNED FOR THE LOADS SHOWN IN THE
STRUCTURAL NOTES SECTIONS "ROOF LIVE LOADS", "ROOF DEAD LOADS", AND
"SNOW LOADS". STEEL JOISTS DESIGNATED ON THE PLANS AS SP# SHALL BE
DESIGNED FOR THE LOADS SHOWN IN THE SPECIAL JOIST LOAD SCHEDULE ON
SHEET S507.
3. ALL STEEL ROOF JOISTS SHALL BE DESIGNED AND BRACED TO RESIST A
SUPERIMPOSED NET UPLIFT PRESSURE OF 35 PSF (LRFD LOAD COMBINATION
0.9D+1.0W PER ASCE 7-10).
4. CONCENTRATED LOADS IN EXCESS OF 50 POUNDS SHALL NOT BE APPLIED
BETWEEN PANELS POINTS, UNLESS AN ADDED WEB MEMBER IS PROVIDED FOR THE
POINT OF APPLICATION OF THE LOAD ON THE CHORD TO THE NEAREST PANEL
JOINT ON THE OPPOSITE CHORDS. SEE DETAILS ON SHEET S507 FOR ADDITIONAL
INFORMATION.
5. BRIDGING SHALL BE WELDED TO BEAMS SPANNING PARALLEL TO STEEL JOISTS.
6. INSPECTION AND TESTING OF STEEL JOIST CONSTRUCTION SHALL BE IN
ACCORDANCE WITH THE STRUCTURAL NOTES FOR QUALITY ASSURANCE AND
SPECIAL INSPECTION ON SHEET S003.
STRUCTURAL NOTES
6%0.663000
f'
c
(MINIMUM
ULTIMATE
COMPRESSIVE
STRENGTH
AT 28 DAYS (PSI)
MAXIMUM
WATER/
CEMENTITIOUS
MATERIALS
RATIO
ENTRAINED
AIR CONTENT
(%)
TABLE 1: CONCRETE PROPERTIES
FOUNDATIONS
STRUCTURE
TYPE
EXT. WALLS, PIERS,
AND ELEV.'D SLABS
3000 0.58 6%
INTERIOR SLABS W/
FOOT OR VEHICLE
TRAFFIC
3500 0.59 UP TO 2%
UNIT
WEIGHT
NW
NOTE: NW DESIGNATES NORMAL WEIGHT CONCRETE.
NW
NW
PIERS
T. ANCHORS
1. PROPOSED ANCHORS SHALL BE SUBMITTED TO THE COTR FOR REVIEW AND
APPROVAL PRIOR TO FIELD OPERATIONS.
2. ALL ANCHORS SHALL BE INSTALLED IN ACCORDANCE WITH THE
RECOMMENDATIONS OF THE MANUFACTURER.
3. ADHESIVE ANCHORS (CONCRETE AND SOLID/GROUTED MASONRY)
a. SHALL BE HILTI HIT-HY 200 ANCHORING SYSTEM OR AN APPROVED EQUIVALENT
WITH ACCOMPANYING ICC EVALUATION REPORT;
b. SHALL USE INJECTABLE ADHESIVE;
c. SHALL USE THREADED RODS MEETING ONE OF THE FOLLOWING STANDARDS:
i. ASTM A 193 B7.
4. MASONRY ADHESIVE ANCHORS (UNREINFORCED, HOLLOW MASONRY)
a. SHALL BE HILTI HIT-HY 70 MANUFACTURED BY HILTI FASTENING SYSTEMS OR AN
APPROVED EQUIVALENT WITH ACCOMPANYING ICC EVALUATION REPORT;
b. SHALL USE INJECTABLE ADHESIVE;
c. RODS SHALL BE MANUFACTURED WITH CHAMFERED ENDS (EACH END) AND
MEET ONE OF THE FOLLOWING STANDARDS:
i. ASTM A3.
5. IF MINIMUM REQUIREMENTS (EMBEDMENT, SPACING, AND EDGE DISTANCE) FOR
ANCHORS CANNOT BE ACHIEVED DUE TO FIELD CONDITIONS, NOTIFY THE COTR
FOR GUIDANCE PRIOR TO DRILLING HOLES FOR ANCHORS.
6. HOLES FOR ANCHORS TO BE INSTALLED IN MASONRY SHALL BE DRILLED WITH A
ROTARY DRILL ONLY, NOT A ROTARY-HAMMER DRILL.
7. A FIELD TECHNICIAN EMPLOYED BY THE ANCHOR MANUFACTURER SHALL BE ON
SITE DURING ALL DRILLING AND INSTALLATION PROCESSES FOR EACH TYPE OF
ANCHOR INSTALLED.
8. CURING TIME FOR ADHESIVE AND EPOXY ADHESIVE ANCHOR SYSTEM SHALL BE A
MINIMUM OF 48 HOURS OR AS RECOMMENDED BY THE ANCHOR MANUFACTURER,
WHICHEVER IS MORE STRINGENT.
E. ROOF DEAD LOAD
1. FLAT ROOF: 21 PSF.
ANGLE SIZE
PRECAST CONCRETE
SIZE & REINFORCING
TABLE 3: LINTELS
TO 3'-0"
OPENING WIDTH
L3
1
2
x3x
5
16
4"x8" PCC W/ #3 T&B
4"x8" PCC W/ #3 T&BL3
1
2
x3
1
2
x
5
16
3'-1" TO 4'-0"
5'-1" TO 6'-0" L5x3
1
2
x
5
16
4"x8" PCC W/ #4 T&B
4"x8" PCC W/ #4 T&BL4x3
1
2
x
5
16
4'-1" TO 5'-0"
S. LINTELS
1. PROVIDE PRECAST OR STEEL LINTELS FOR OPENINGS IN MASONRY PARTITIONS AS
SPECIFIED IN TABLE 3 ON THIS SHEET. PROVIDE (1) LINTEL FOR EACH 4" OF WALL
THICKNESS WITH A MINIMUM BEARING LENGTH OF 6" AT EACH END.
2. STEEL ANGLE LINTELS SHALL BE INSTALLED WITH THE VERTICAL LEGS INSIDE THE
WALL AND THE HORIZONTAL LEGS POINTING TO THE OUTSIDE FACES OF THE
WALLS. VERTICAL LEGS OF STEEL ANGLES MAY NOT BE EXPOSED AT THE FACES
OF THE WALLS.
4'ON
E EI
GHTH
INCH
= O
NE F
OOT
( 1/8"
= 1'
-0" )
08'
16'
04'
8'4'
04'
02'
6"0
02'
6"0
1'6"
6"ON
E QU
ATER
INCH
= O
NE F
OOT
( 1/4"
= 1'
-0" )
THRE
E EI
GHTH
S IN
CH =
ONE
FOO
T ( 3
/8" =
1'-0
" )ON
E HA
LF IN
CH =
ONE
FOO
T ( 1
/2" =
1'-0
" )TH
REE
QUAT
ERS
INCH
= O
NE F
OOT
( 3/4"
= 1'
-0" )
ONE
INCH
= O
NE F
OOT
( 1" =
1'-0
" )ON
E AN
D ON
E HA
LF IN
CHES
= O
NE F
OOT
( 1 1/
2" =
1'-0
" )TH
REE
INCH
ES =
ONE
FOO
T ( 3
" = 1'
-0" )
OKKS Studios, Inc.2 Wisconsin Circle / Suite 820Chevy Chase, MD 20815-7003Tel: (301) 718-0080Fax: (301) 718-9520www.okksstudios.com
Nobis Engineering, Inc.20410 Century Boulevard, Suite 230
Germantown, MD 20874Tel: (301) 528 2010
Woods Peacock Engineering Consultants5250 Cherokee Avenue, Suite 420
Alexandria, VA 22312-2052Tel: (703) 658-4400
Fax: (703) 658-4404
Henry Adams ConsultingEngineers, LLC600 Baltimore Avenue, 4th FloorBaltimore, MD 21204Tel: (410) 296-6500Fax: (410) 296-6501
The Protection Engineering Group2809 Boston Street, Suite 7Baltimore, MD 21224 USA
Tel: (443) 708-4096Fax:
SCHEMATIC DESIGN (30%) SUBMISSION09/11/15DESIGN DEVELOPMENT (60%) SUBMISSION11/23/15CONSTRUCTION DOCUMENTS (90% SUBMISSION)
03/17/16
TMP CAD
PERRY POINT, MD
WAREHOUSE RENOVATION& EXPANSION
03/17/16BID DOCUMENTS SUBMISSION
03/25/15
Professional Certification. I hereby certify that these documentswere prepared or approved by me, and that I am a duly licensedprofessional engineer under the laws of the State of Maryland,License No. 14484, Expiration Date: June 27, 2017.
STRUCTURAL NOTES
S001
![Page 2: 14012 - VAMC BLDG 360 - CENTRAL elorenz - rlscg.comrlscg.com/site/wp-content/uploads/VA245-16-B-0095-010.pdf · 10.welding electrodes: per table 3.1 of aws d1.1 for the smaw process](https://reader034.vdocuments.us/reader034/viewer/2022052608/5add35567f8b9a213e8c8f07/html5/thumbnails/2.jpg)
W. STEEL ROOF DECK
1. STEEL ROOF DECK SHALL BE MANUFACTURED IN ACCORDANCE WITH THE
RECOMMENDATIONS OF THE STEEL DECK INSTITUTE AND INSTALLED IN
ACCORDANCE WITH THE RECOMMENDATIONS OF THE MANUFACTURER AND THE
STEEL DECK INSTITUTE.
2. STEEL ROOF DECK SHALL BE THE DEPTH AND THICKNESS SHOWN ON THE
DRAWINGS, WITH NESTABLE SIDE LAP.
3. STEEL ROOF DECK SHALL BE GALVANIZED.
4. SEE SPECIFICATION SECTION 05 31 00 FOR FASTENING REQUIREMENTS OF ROOF
DECK.
X. ROOF OPENINGS
1. SEE ARCHITECTURAL AND MEP DRAWINGS FOR THE EXACT SIZE AND LOCATION OF
ROOF OPENINGS. IF OPENING DIMENSIONS SHOWN ON THE ARCHITECTURAL AND
MEP DRAWINGS CONFLICT WITH STRUCTURAL MEMBERS, THE COTR SHALL BE
NOTIFIED, IN WRITING, PRIOR TO PROCEEDING WITH FABRICATION AND
CONSTRUCTION OF THE OPENING.
2. ROOF DECK SHALL BE SUPPORTED AROUND OPENINGS BY STRUCTURAL STEEL
FRAMING PER "TYPICAL METAL ROOF DECK FRAMING AT OPENING" DETAIL ON
SHEET S507.
Y. GENERAL CONTRACTOR
1. STRUCTURAL DRAWINGS SHALL BE USED ONLY IN CONJUNCTION WITH THE
ARCHITECTURAL, CIVIL, AND MEP DRAWINGS, WHICH SHALL BE PROVIDED TO ALL
SUBCONTRACTORS RESPONSIBLE FOR STRUCTURAL CONSTRUCTION.
2. SHOP DRAWINGS FOR ALL STRUCTURAL ITEMS ARE PART OF THE STRUCTURAL
DESIGN AND SHALL BE SUBMITTED TO THE COTR FOR REVIEW AND APPROVAL
PRIOR TO FABRICATION AND CONSTRUCTION.
3. ALL STRUCTURAL ELEMENTS SHALL BE TEMPORARILY SHORED AND BRACED AS
REQUIRED TO RESIST THE LOADS TO WHICH THEY MAY BE SUBJECT DURING
CONSTRUCTION.
4. ALL TEMPORARY SHORING AND BRACING SHALL BE DESIGNED BY A REGISTERED
PROFESSIONAL ENGINEER RETAINED BY THE CONTRACTOR AND SHALL REMAIN
IN-PLACE UNTIL THE STRUCTURE IS CAPABLE OF SUPPORTING THE LOADS TO
WHICH IT MAY BE SUBJECT. DETERMINATION OF WHEN TEMPORARY SHORING AND
BRACING CAN BE REMOVED IS THE RESPONSIBILITY OF THE SHORING ENGINEER.
5. THE DESIGN OF ALL TEMPORARY SHORING AND BRACING WILL BE THE
RESPONSIBILITY OF THE CONTRACTOR. SIGNED AND SEALED SHOP DRAWINGS
FOR TEMPORARY SHORING AND BRACING SHALL BE SUBMITTED PRIOR TO
CONSTRUCTION.
6. IMPOSED CONSTRUCTION LOADS INCLUDING CRANE LOADS, IN EXCESS OF THE
STATED DESIGN LOADS MUST BE APPROVED BY THE COTR PRIOR TO THE
IMPOSITION OF SUCH LOADS.
7. THE DESIGN AND CONSTRUCTION OF SHORING REQUIRED TO MAINTAIN THE
STABILITY OF EXCAVATIONS SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR.
ALL EXCAVATIONS SHALL COMPLY WITH OSHA REGULATIONS.
8. PROVIDE CONTINUOUS DRAINAGE SYSTEM BEHIND WALLS BELOW GRADE IN
ACCORDANCE WITH THE DETAILS ON SHEET S501.
Z. EXISTING STRUCTURE
1. INFORMATION SHOWN ON THE STRUCTURAL DRAWINGS REGARDING THE EXISTING
STRUCTURE IS BASED ON THE EXISTING DRAWINGS DATED OCTOBER 10, 1984.
WOODS PEACOCK ASSUMES NO RESPONSIBILITY FOR THEIR ACCURACY.
2. DIMENSIONS OF EXISTING CONSTRUCTION SHOWN ON THE STRUCTURAL
DRAWINGS ARE APPROXIMATE AND SHALL BE FIELD VERIFIED BY THE
CONTRACTOR PRIOR TO BEGINNING CONSTRUCTION.
3. IF DEVIATIONS ARE FOUND BETWEEN THE EXISTING INFORMATION SHOWN ON THE
STRUCTURAL DRAWINGS AND ACTUAL CONDITIONS WHICH WILL NOT PERMIT NEW
STRUCTURAL WORK TO BE PERFORMED AS SPECIFIED, THE COTR SHALL BE
NOTIFIED IN WRITING FOR GUIDANCE PRIOR TO THE START OF THE WORK IN
QUESTION.
4. CONTRACTOR SHALL SUBMIT METHODS AND SEQUENCING FOR THE REMOVAL OF
THE EXISTING STRUCTURE, AS WELL AS TYPES OF TOOLS AND EQUIPMENT TO BE
USED, TO THE COTR FOR REVIEW AND APPROVAL PRIOR TO COMMENCING ANY
DEMOLITION OR ALTERATIONS. EXTREME CARE SHALL BE TAKEN TO PROTECT
THE INTEGRITY OF ADJACENT EXISTING STRUCTURE AT ALL TIMES. THE
CONTRACTOR SHALL BEAR THE COST OF REPAIRS OR REPLACEMENT FOR
DAMAGE TO ANY PART OF EXISTING STRUCTURES OR ADJOINING PROPERTY.
5. WHERE UNDERPINNING AND/OR SHORING IS REQUIRED AT ADJACENT EXISTING
STRUCTURES, THE METHOD AND SEQUENCE SHALL BE SUBMITTED TO THE COTR
FOR APPROVAL PRIOR TO STARTING FIELD OPERATIONS.
6. WHERE ARCHITECTURAL DRAWINGS INDICATE NEW OPENINGS IN EXISTING
MASONRY PARTITIONS, PROVIDE LINTELS AS INDICATED IN THE STRUCTURAL
NOTES SECTION "LINTELS".
LIST OF ABBREVIATIONS
& AND
@ AT
℄ CENTERLINE
Ø DIAMETER
(E), EXIST EXISTING
(H) HIGH
(L) LOW
#, NO. NUMBER
% PERCENT
ABV ABOVE
ACI AMERICAN CONCRETE
INSTITUTE
ADDL ADDITIONAL
AHU AIR HANDLING UNIT
AISC AMERICAN INSTITUTE OF
STEEL CONSTRUCTION
AISI AMERICAN IRON AND STEEL
INSTITUTE
ANSI AMERICAN NATIONAL
STANDARDS INSTITUTE
APPROX APPROXIMATE
ARCH ARCHITECTURAL
ASCE AMERICAN SOCIETY OF CIVIL
ENGINEERS
ASTM AMERICAN SOCIETY FOR
TESTING AND MATERIALS
AWS AMERICAN WELDING SOCIETY
BLDG BUILDING
B.O. BOTTOM OF
BRG BEARING
C.J. CONTROL JOINT
CLR CLEAR
CMU CONCRETE MASONRY UNIT
COL COLUMN
CONC CONCRETE
CONT CONTINUOUS
COORD COORDINATE
CRSI CONCRETE REINFORCING
STEEL INSTITUTE
DEMO DEMOLISH, DEMOLITION
DIA DIAMETER
DIV DIVISION
DL DEAD LOAD
DWG(S) DRAWING(S)
E.J. EXPANSION JOINT
E.F. EACH FACE
EL, ELEV ELEVATION
ELEV'D ELEVATED
EMBED EMBEDMENT
EQ EQUAL
EQUIP EQUIPMENT
EQUIV EQUIVALENT
E.W. EACH WAY
FDN FOUNDATION
F.S. FOOTING STEP
FT FOOT OR FEET
FTG FOOTING
HORIZ HORIZONTAL
IBC INTERNATIONAL BUILDING
CODE
ICC INTERNATIONAL CODE
COUNCIL
I.D. INSIDE DIAMETER
IN INCH
ISO INTERNATIONAL
STANDARDIZATION
ORGANIZATION
JST JOIST
K KIP(S)
KSF KIPS PER SQUARE FOOT
KSI KIPS PER SQUARE INCH
LB, # POUNDS
LL LIVE LOAD
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LRFD LOAD AND RESISTANCE
FACTOR DESIGN
MAS MASONRY
MAX MAXIMUM
MEP MECHANICAL, ELECTRICAL &
PLUMBING
MTL METAL
MFR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
MPH MILES PER HOUR
NTS NOT TO SCALE
O.C. ON CENTER
O.D. OUTSIDE DIAMETER
OPP OPPOSITE
PL PLATE
PLF POUNDS PER LINEAR FOOT
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
RCSC RESEARCH COUNCIL ON
STRUCTURAL CONNECTIONS
REINF REINFORCING,
REINFORCEMENT
REQD REQUIRED
SIM SIMILAR
SJI STEEL JOIST INSTITUTE
(SL) SLOPED
SOG SLAB ON GRADE
SPA SPACES (SPACING)
SPECS SPECIFICATIONS
STD STANDARD
T&B TOP AND BOTTOM
TEMP TEMPORARY
THRU THROUGH
T.O. TOP OF
T&S TEMPERATURE AND
SHRINKAGE
TYP TYPICAL
U.N.O. UNLESS NOTED OTHERWISE
VERT VERTICAL
WL WIND LOAD
W.P. WORKING POINT
W/ WITH
W/O WITHOUT
4'ON
E EI
GHTH
INCH
= O
NE F
OOT
( 1/8"
= 1'
-0" )
08'
16'
04'
8'4'
04'
02'
6"0
02'
6"0
1'6"
6"ON
E QU
ATER
INCH
= O
NE F
OOT
( 1/4"
= 1'
-0" )
THRE
E EI
GHTH
S IN
CH =
ONE
FOO
T ( 3
/8" =
1'-0
" )ON
E HA
LF IN
CH =
ONE
FOO
T ( 1
/2" =
1'-0
" )TH
REE
QUAT
ERS
INCH
= O
NE F
OOT
( 3/4"
= 1'
-0" )
ONE
INCH
= O
NE F
OOT
( 1" =
1'-0
" )ON
E AN
D ON
E HA
LF IN
CHES
= O
NE F
OOT
( 1 1/
2" =
1'-0
" )TH
REE
INCH
ES =
ONE
FOO
T ( 3
" = 1'
-0" )
OKKS Studios, Inc.2 Wisconsin Circle / Suite 820Chevy Chase, MD 20815-7003Tel: (301) 718-0080Fax: (301) 718-9520www.okksstudios.com
Nobis Engineering, Inc.20410 Century Boulevard, Suite 230
Germantown, MD 20874Tel: (301) 528 2010
Woods Peacock Engineering Consultants5250 Cherokee Avenue, Suite 420
Alexandria, VA 22312-2052Tel: (703) 658-4400
Fax: (703) 658-4404
Henry Adams ConsultingEngineers, LLC600 Baltimore Avenue, 4th FloorBaltimore, MD 21204Tel: (410) 296-6500Fax: (410) 296-6501
The Protection Engineering Group2809 Boston Street, Suite 7Baltimore, MD 21224 USA
Tel: (443) 708-4096Fax:
SCHEMATIC DESIGN (30%) SUBMISSION09/11/15DESIGN DEVELOPMENT (60%) SUBMISSION11/23/15CONSTRUCTION DOCUMENTS (90% SUBMISSION)
03/17/16
TMP CAD
PERRY POINT, MD
WAREHOUSE RENOVATION& EXPANSION
03/17/16BID DOCUMENTS SUBMISSION
03/25/15
Professional Certification. I hereby certify that these documentswere prepared or approved by me, and that I am a duly licensedprofessional engineer under the laws of the State of Maryland,License No. 14484, Expiration Date: June 27, 2017.
STRUCTURAL NOTES
S002
![Page 3: 14012 - VAMC BLDG 360 - CENTRAL elorenz - rlscg.comrlscg.com/site/wp-content/uploads/VA245-16-B-0095-010.pdf · 10.welding electrodes: per table 3.1 of aws d1.1 for the smaw process](https://reader034.vdocuments.us/reader034/viewer/2022052608/5add35567f8b9a213e8c8f07/html5/thumbnails/3.jpg)
A. SPECIAL INSPECTIONS GENERAL
THE CONTRACTOR SHALL RETAIN THIRD-PARTY QUALITY ASSURANCE AGENCIES TO CONDUCT THE
SPECIAL INSPECTIONS REQUIRED BY THE IBC 2012. THE QUALIFIED SPECIAL INSPECTOR SHALL IMPLEMENT
THE SPECIAL INSPECTIONS PROGRAM AND TO PERFORM INSPECTIONS DURING CONSTRUCTION ON THE
TYPES OF WORK LISTED UNDER SECTION 1704 OF IBC 2012. FOR REFERENCE, A SUMMARY OF SPECIAL
INSPECTIONS HAS BEEN PROVIDE BELOW. THESE INSPECTIONS ARE IN ADDITION TO THE INSPECTIONS
IDENTIFIED IN SECTION 110 OF IBC 2012. THE INSPECTING AGENCY SHALL PROVIDE REPORTS OF THE
SPECIAL INSPECTIONS DIRECTLY TO THE COTR.
REFERENCE THE SPECIFICATIONS FOR ADDITIONAL SPECIAL INSPECTION REQUIREMENTS FOR THE
PROJECT. THE SPECIAL INSPECTION REQUIREMENTS SHALL BE STATED IN THE STATEMENT OF SPECIAL
INSPECTIONS, SCHEDULE OF INSPECTION AND TESTING AGENCIES, QUALITY ASSURANCE PLANS, AND
QUALIFICATIONS OF INSPECTORS AND TESTING AGENCIES, AND THE SCHEDULE OF SPECIAL INSPECTIONS
LISTED BELOW. IF THERE ARE ANY PERCEIVED CONFLICTS BETWEEN THE SPECIFICATIONS AND THE
NOTES OR THE DRAWINGS, THE CONTRACTOR SHALL SUBMIT A WRITTEN REQUEST FOR CLARIFICATION TO
THE COTR.
B. QUALIFICATIONS OF SPECIAL INSPECTORS
THE MINIMUM QUALIFICATIONS OF PERSONNEL PERFORMING SPECIAL INSPECTIONS ARE STATED IN THE
STATEMENT OF SPECIAL INSPECTIONS INCLUDED IN THE SPECIFICATIONS FOR THE PROJECT. THE
SPECIAL INSPECTOR SHALL BE A QUALIFIED PERSON WHO SHALL DEMONSTRATE COMPETENCE, TO THE
SATISFACTION OF THE COTR, FOR THE INSPECTION OF THE PARTICULAR TYPE OF CONSTRUCTION OR
OPERATION REQUIRING SPECIAL INSPECTION. THE REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE
CHARGE AND ENGINEERS OF RECORD INVOLVED IN THE DESIGN OF THE PROJECT ARE PERMITTED TO ACT
AS THE APPROVED AGENCY AND THEIR PERSONNEL ARE PERMITTED TO ACT AS THE SPECIAL INSPECTOR
FOR THE WORK DESIGNATED TO THEM, PROVIDED THOSE PERSONNEL MEET THE QUALIFICATION
REQUIREMENTS STATED ABOVE TO THE SATISFACTION OF THE COTR. THE SPECIAL INSPECTOR SHALL
PROVIDE WRITTEN DOCUMENTATION TO THE COTR DEMONSTRATING HIS OR HER COMPETENCE AND
RELEVANT EXPERIENCE OR TRAINING. EXPERIENCE OR TRAINING SHALL BE CONSIDERED RELEVANT
WHEN THE DOCUMENTED EXPERIENCE OR TRAINING IS RELATED IN COMPLEXITY TO THE SAME TYPE OF
SPECIAL INSPECTION ACTIVITIES FOR PROJECTS OF SIMILAR COMPLEXITY AND MATERIAL QUALITIES.
THESE QUALIFICATIONS ARE IN ADDITION TO QUALIFICATIONS SPECIFIED IN OTHER SECTIONS OF THE IBC
2012 AND THE SPECIFICATIONS.
C. REPORT REQUIREMENTS
SPECIAL INSPECTORS SHALL KEEP RECORDS OF INSPECTIONS. THE SPECIAL INSPECTOR SHALL FURNISH
INSPECTION REPORTS TO THE COTR, AND TO THE REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE
CHARGE. REPORTS SHALL INDICATE THAT WORK INSPECTED WAS OR WAS NOT COMPLETED IN
CONFORMANCE TO APPROVED CONSTRUCTION DOCUMENTS. DISCREPANCIES SHALL BE BROUGHT TO
THE IMMEDIATE ATTENTION OF THE CONTRACTOR FOR CORRECTION. IF THEY ARE NOT CORRECTED, THE
DISCREPANCIES SHALL BE BROUGHT TO THE ATTENTION OF THE COTR AND TO THE REGISTERED DESIGN
PROFESSIONAL IN RESPONSIBLE CHARGE PRIOR TO THE COMPLETION OF THAT PHASE OF THE WORK. A
FINAL REPORT DOCUMENTING REQUIRED SPECIAL INSPECTIONS AND CORRECTION OF ANY
DISCREPANCIES NOTED IN THE INSPECTIONS SHALL BE SUBMITTED AT A POINT IN TIME AGREED UPON AT
THE PRECONSTRUCTION MEETING.
THE FOLLOWING SAMPLE FORMS ARE AVAILABLE UPON REQUEST:
1. STATEMENT OF SPECIAL INSPECTIONS.
2. FINAL REPORT OF SPECIAL INSPECTIONS.
3. CONTRACTOR'S STATEMENT OF RESPONSIBILITY.
4. FABRICATOR'S CERTIFICATE OF COMPLIANCE.
THE FORMS LISTED ABOVE SHALL BE FURNISHED BY THE COTR.
F. MINIMUM INSPECTION REQUIREMENTS:
THE REQUIREMENTS IN THE FOLLOWING TABLES, FOR EACH TRADE, REPRESENT THE MINIMUM SPECIAL
INSPECTION REQUIREMENTS DICTATED BY THE CODE FOR THIS PROJECT. ADDITIONAL INSPECTIONS FOR
SPECIAL CASES MAY BE REQUIRED, AT THE DISCRETION OF THE COTR, AS STATED IN SECTION 1705.1.1 OF
IBC 2012 AND AS FOLLOWS:
1. CONSTRUCTION MATERIALS AND SYSTEMS THAT ARE ALTERNATIVES TO MATERIALS AND
SYSTEMS PRESCRIBED BY THE IBC 2012.
2. UNUSUAL DESIGN APPLICATIONS OF MATERIALS DESCRIBED IN THE IBC 2012.
3. MATERIALS AND SYSTEMS REQUIRED TO BE INSTALLED IN ACCORDANCE WITH ADDITIONAL
MANUFACTURER'S INSTRUCTIONS THAT PRESCRIBE REQUIREMENTS NOT CONTAINED IN THE IBC
2012 OR IN STANDARDS REFERENCED BY THE IBC 2012.
THE MINIMUM SPECIAL INSPECTION REQUIREMENTS IN THE FOLLOWING TABLES ARE PART OF THE
CONTRACT DOCUMENTS FOR THIS PROJECT. THE INSPECTIONS STATED BELOW MUST BE PERFORMED
FOR THE WORK SHOWN ON THESE DRAWINGS AND CANNOT BE WAIVED. INSPECTIONS SHALL FULFILL THE
REQUIREMENTS OF BOTH THE CONTRACT DOCUMENTS AND THE SPECIAL INSPECTIONS PROGRAM.
CONTINUOUS SPECIAL INSPECTION IS THE FULL-TIME OBSERVATION OF THE WORK, REQUIRING SPECIAL
INSPECTION, BY AN APPROVED SPECIAL INSPECTOR WHO IS PRESENT IN THE WORK AREA WHENEVER
WORK IS BEING PERFORMED.
PERIODIC SPECIAL INSPECTION IS THE PART-TIME OR INTERMITTENT OBSERVATION OF THE WORK,
REQUIRING SPECIAL INSPECTION, BY AN APPROVED SPECIAL INSPECTOR WHO IS PRESENT IN THE WORK
AREA WHILE WORK IS BEING PERFORMED. THE PART-TIME OR INTERMITTENT OBSERVATION PERIODS
SHALL BE AT THE COMMENCEMENT AND COMPLETION OF THE WORK, AT TIMES OF SIGNIFICANT WORK,
SHALL OCCUR OVER THE COMPLETE WORK PERIOD, AND TOTAL AT LEAST 25 PERCENT OF THE TOTAL
WORK TIME.
L. SUMMARY OF SPECIAL INSPECTIONS
1. TABLES SHOWN ON SHEETS S003 THROUGH S005 ARE TAKEN DIRECTLY FROM THE IBC 2012 OR OTHER
REFERENCE STANDARDS AS REFERENCE BY THE IBC 2012. VERIFICATION AND INSPECTION ITEMS NOT
REQUIRED ARE LISTED AS NOT APPLICABLE. ADDITIONAL INSPECTION REQUIREMENTS ARE LISTED IN
TABLES LABELED SUPPLEMENTAL INSPECTION REQUIREMENTS.
2. REQUIRED VERIFICATION AND INSPECTION OF CONCRETE CONSTRUCTION, SEE TABLE 1705.3 ON
SHEET S004 OR IN THE IBC 2012.
3. REQUIRED VERIFICATION AND INSPECTION OF STEEL CONSTRUCTION SHALL BE IN ACCORDANCE WITH
THE QUALITY ASSURANCE INSPECTION REQUIREMENTS OF ANSI/AISC 360-10.
A. ANSI/AISC 360-10 "SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS": SEE CHAPTER N. QUALITY
CONTROL AND QUALITY ASSURANCE FOR MINIMUM REQUIREMENTS FOR QUALITY CONTROL,
QUALITY ASSURANCE AND NONDESTRUCTIVE TESTING FOR STRUCTURAL STEEL SYSTEMS AND
STEEL ELEMENTS OF COMPOSITE MEMBERS FOR BUILDINGS AND OTHER STRUCTURES.
B. AISC 303-10 "CODE OF STANDARD PRACTICE FOR STEEL BUILDINGS AND BRIDGES": SEE SECTION
8. QUALITY CONTROL FOR ADDITIONAL QUALITY CONTROL REQUIREMENTS.
4. FOR MINIMUM REQUIRED INSPECTION OF STRUCTURAL STEEL BUILDINGS, SEE TABLES N5.4-1, N5.4-2,
N5.4-3, N5.6-1, N5.6-2, AND N5.6-3 ON SHEET S003 OR IN THE ANSI/AISC 360-10.
A. INSPECTION TASKS ARE AS FOLLOWS FOR TABLES N5.4-1, N5.4-2 AND N5.4-3:
O - OBSERVE THESE ITEMS ON A RANDOM BASIS. OPERATIONS NEED NOT BE DELAYED PENDING
THESE INSPECTIONS.
P - PERFORM THESE TASKS FOR EACH WELDED JOINT OR MEMBER.
B. INSPECTION TASKS ARE AS FOLLOWS FOR TABLES N5.6-1, N5.6-2 AND N5.6-3:
O - OBSERVE THESE ITEMS ON A RANDOM BASIS. OPERATIONS NEED NOT BE DELAYED PENDING
THESE INSPECTIONS.
P - PERFORM THESE TASKS FOR EACH BOLTED CONNECTION.
5. REQUIRED VERIFICATION AND INSPECTION OF STEEL CONSTRUCTION OTHER THAN STRUCTURAL
STEEL SHALL BE IN ACCORDANCE WITH THE TABEL 1705.2.2 ON SHEET S004 ON IN THE IBC 2012.
6. REQUIRED VERIFICATION AND INSPECTION OF MASONRY CONSTRUCTION SHALL BE IN ACCORDANCE
WITH THE TMS 402/ACI530/ASCE 5 AND TMS 602/ACI 530.1/ASCE 6 QUALITY ASSURANCE PROGRAM
REQUIREMENTS.
7. FOR MINIMUM REQUIRED QUALITY ASSURANCE PROGRAM FOR MASONRY CONSTRUCTION, SEE TABLE
1.19.2 - LEVEL B QUALITY ASSURANCE ON SHEET S005 OR IN THE TMS 402/ACI 530/ASCE 5.
8. REQUIRED VERIFICATION AND INSPECTION OF SOILS, SEE TABLE 1705.6 ON SHEET S005 OR IN THE IBC
2012.
I. STATEMENT OF SPECIAL INSPECTIONS: SEISMIC RESISTANCE
1. SEISMIC DESIGN CATEGORY: B.
2. DESCRIPTION OF THE DESIGNATED SEISMIC SYSTEMS AND SEISMIC FORCE-RESISTING SYSTEMS THAT
ARE SUBJECT TO SPECIAL INSPECTIONS PER SECTION 1705.11 OR 1705.12 OF IBC 2012:
a. SEISMIC-FORCE-RESISTING SYSTEM PER ASCE 7-10, TABLE 12.2-1: STEEL ORDINARY
CONCENTRICALLY BRACED FRAMES.
G. STATEMENT OF SPECIAL INSPECTIONS: WIND RESISTANCE
1. BASIC WIND SPEED (3 SECOND GUST): 115 MPH.
2. WIND EXPOSURE CATEGORY: C.
3. DESCRIPTION OF MAIN WINDFORCE-RESISTING SYSTEMS AND WIND-RESISTING COMPONENTS
SUBJECT TO SPECIAL INSPECTION PER SECTION 1705.10 OF IBC 2012:
a. MAIN WIND-FORCE-RESISTING SYSTEM: STEEL ORDINARY CONCENTRICALLY BRACED FRAMES.
D. STATEMENT OF CONTRACTOR RESPONSIBILITY
EACH CONTRACTOR RESPONSIBLE FOR THE CONSTRUCTION OF A MAIN WIND- OR
SEISMIC-FORCE-RESISTING SYSTEM, DESIGNATED SEISMIC SYSTEM OR A WIND- OR SEISMIC-RESISTING
COMPONENT LISTED IN THE STATEMENT OF SPECIAL INSPECTIONS SHALL SUBMIT A WRITTEN STATEMENT
OF RESPONSIBILITY TO THE COTR AND THE OWNER PRIOR TO THE COMMENCEMENT OF WORK ON THE
SYSTEM OR COMPONENT. THE CONTRACTOR'S STATEMENT OF RESPONSIBILITY SHALL CONTAIN
ACKNOWLEDGMENT OF AWARENESS OF THE SPECIAL REQUIREMENTS CONTAINED IN THE STATEMENT OF
SPECIAL INSPECTION.
J. SPECIAL INSPECTIONS FOR SEISMIC RESISTANCE
1. IBC 2012, SECTION 1705.11.1 STRUCTURAL STEEL: SPECIAL INSPECTION FOR STRUCTURAL STEEL
SHALL BE IN ACCORDANCE WITH THE QUALITY ASSURANCE PLAN REQUIREMENTS OF AISC 341.
K. TESTING AND QUALIFICATION FOR SEISMIC RESISTANCE
1. IBC 2012, SECTION 1705.12.2 STRUCTURAL STEEL: TESTING FOR STRUCTURAL STEEL SHALL BE IN
ACCORDANCE WITH THE QUALITY ASSURANCE PLAN REQUIREMENTS OF AISC 341.
2. IBC 2012, SECTION 1705.12.3 SEISMIC CERTIFICATION OF NONSTRUCTURAL COMPONENTS: THE
REGISTERED DESIGN PROFESSIONAL SHALL SPECIFY ON THE CONSTRUCTION DOCUMENTS THE
REQUIREMENTS FOR CERTIFICATION BY ANALYSIS, TESTING OR EXPERIENCE DATA FOR
NONSTRUCTURAL COMPONENTS AND DESIGNATED SEISMIC SYSTEMS IN ACCORDANCE WITH SECTION
13.2 OF ASCE 7, WHERE SUCH CERTIFICATION IS REQUIRED BY SECTION 1705.12.
H. SPECIAL INSPECTIONS FOR WIND REQUIREMENTS
1. IBC 2012, SECTION 1705.10.3 WIND-RESISTING COMPONENTS: PERIODIC SPECIAL INSPECTION IS
REQUIRED FOR THE FOLLOWING SYSTEMS AND COMPONENTS:
a. ROOF CLADDING.
b. WALL CLADDING.
E. FABRICATOR APPROVAL
WHERE FABRICATION OF STRUCTURAL LOAD-BEARING MEMBERS AND ASSEMBLIES IS BEING PERFORMED
ON THE PREMISES OF A FABRICATOR'S SHOP, THE SPECIAL INSPECTOR SHALL VERIFY THAT THE
FABRICATOR MAINTAINS DETAILED FABRICATION AND QUALITY CONTROL PROCEDURES THAT PROVIDE A
BASIS FOR INSPECTION CONTROL OF THE WORKMANSHIP AND THE FABRICATOR'S ABILITY TO CONFORM
TO APPROVED CONSTRUCTION DOCUMENTS AND REFERENCED STANDARDS. THE SPECIAL INSPECTOR
SHALL REVIEW THE PROCEDURES FOR COMPLETENESS AND ADEQUACY RELATIVE TO THE CODE
REQUIREMENTS FOR THE FABRICATOR'S SCOPE OF WORK.
SPECIAL INSPECTIONS REQUIRED BY SECTION 1704 OF IBC 2012 ARE NOT REQUIRED WHERE THE WORK IS
DONE ON THE PREMISES OF A FABRICATOR REGISTERED AND APPROVED TO PERFORM SUCH WORK
WITHOUT SPECIAL INSPECTION. APPROVAL SHALL BE BASED UPON REVIEW OF THE FABRICATOR'S
WRITTEN PROCEDURAL AND QUALITY CONTROL MANUALS AND PERIODIC AUDITING OF FABRICATION
PRACTICES BY AN APPROVED SPECIAL INSPECTION AGENCY. AT COMPLETION OF FABRICATION, THE
APPROVED FABRICATOR SHALL SUBMIT A CERTIFICATE OF COMPLIANCE TO THE COTR STATING THAT THE
WORK WAS PERFORMED IN ACCORDANCE WITH THE APPROVED CONSTRUCTION DOCUMENTS.
TABLE N5.4-1
INSPECTION TASKS PRIOR TO WELDING
INSPECTION TASKS PRIOR TO WELDING
QUALITY
CONTROL
(QC)
QUALITY
ASSURANCE
(QA)
NOT
APPLICABLE
WELDING PROCEDURE SPECIFICATION (WPSs)
AVAILABLE
P P ---
MANUFACTURER CERTIFICATIONS FOR WELDING
CONSUMABLES AVAILABLE
P P ---
MATERIAL IDENTIFICATION (TYPE/GRADE)
O O ---
WELDER IDENTIFICATION SYSTEM
1
O O ---
FIT-UP OF GROOVE WELDS (INCLUDING JOINT
GEOMETRY)
- JOINT PREPARATION
- DIMENSIONS (ALIGNMENT, ROOT OPENING,
ROOT FACE, BEVEL
- CLEANLINESS (CONDITION OF STEEL SURFACE)
- TACKING (TACK WELD QUALITY AND LOCATION)
- BACKING TYPE AND FIT (IF APPLICABLE)
--- --- N/A
CONFIGURATION AND FINISH OF ACCESS HOLES --- --- N/A
FIT-UP OF FILLET WELDS
- DIMENSIONS (ALIGNMENT, GAPS AT ROOT)
- CLEANLINESS (CONDITION OF STEEL
SURFACES)
- TACKING (TACK WELD QUALITY AND LOCATION)
O O ---
CHECK WELDING EQUIPMENT O --- ---
1
THE FABRICATOR OR ERECTOR, AS APPLICABLE, SHALL MAINTAIN A SYSTEM BY WHICH A WELDER
WHO HAS WELDED A JOINT OR MEMBER CAN BE IDENTIFIED. STAMPS, IF USED, SHALL BE THE
LOW-STRESS TYPE.
TABLE N5.4-2
INSPECTION TASKS DURING WELDING
INSPECTION TASKS DURING WELDING
QUALITY
CONTROL
(QC)
QUALITY
ASSURANCE
(QA)
NOT
APPLICABLE
USE OF QUALIFIED WELDERS O O ---
CONTROL AND HANDLING OF WELDING
CONSUMABLES
- PACKAGING
- EXPOSURE CONTROL
O O ---
NO WELDING OVER CRACKED TACK WELDS O O ---
ENVIRONMENTAL CONDITIONS
- WIND SPEED WITHIN LIMITS
- PRECIPITATION AND TEMPERATURE
O O ---
WPS FOLLOWED
- SETTINGS ON WELDING EQUIPMENT
- TRAVEL SPEED
- SELECTED WELDING MATERIALS
- SHIELDING GAS TYPE/FLOW RATE
- PREHEAT APPLIED
- INTERPASS TEMPERATURE MAINTAINED
(MIN/MAX)
- PROPER POSITION (F, V, H, OH)
O O ---
WELDING TECHNIQUES
- INTERPASS AND FINAL CLEANING
- EACH PASS WITHIN PROFILE LIMITATIONS
- EACH PASS MEETS QUALITY REQUIREMENTS
O O ---
TABLE N5.4-3
INSPECTION TASKS AFTER WELDING
INSPECTION TASKS AFTER WELDING
QUALITY
CONTROL
(QC)
QUALITY
ASSURANCE
(QA)
NOT
APPLICABLE
WELDS CLEANED O O ---
SIZE, LENGTH AND LOCATION OF WELDSP P ---
WELDS MEET VISUAL ACCEPTANCE CRITERIA
- CRACK PROHIBITION
- WELD/BASE-METAL FUSION
- CRATER CROSS SECTION
- WELD PROFILES
- WELD SIZE
- UNDERCUT
- POROSITY
P P ---
ARC STRIKES P P ---
k-AREA
1
P P ---
BACKING REMOVED AND WELD TABS REMOVED
(IF REQUIRED)
--- --- N/A
REPAIR ACTIVITIES P P ---
DOCUMENT ACCEPTANCE OR REJECTION OF
WELDED JOINT OR MEMBER
P P ---
1
WHEN WELDING OF DOUBLER PLATES, CONTINUITY PLATES OR STIFFENERS HAS BEEN
PERFORMED IN THE k-AREA, VISUALLY INSPECT THE WEB k-AREA FOR CRACKS WITHIN 3 IN (75 mm)
OF THE WELD.
TABLE N5.6-1
INSPECTION TASKS PRIOR TO BOLTING
INSPECTION TASKS PRIOR TO BOLTING
QUALITY
CONTROL
(QC)
QUALITY
ASSURANCE
(QA)
NOT
APPLICABLE
MANUFACTURER'S CERTIFICATIONS AVAILABLE
FOR FASTENER MATERIAL
O P ---
FASTENERS MARKED IN ACCORDANCE WITH
ASTM REQUIREMENTS
O O ---
PROPER FASTENERS SELECTED FOR THE JOINT
DETAIL (GRADE, TYPE, BOLT LENGTH IF
THREADS ARE TO BE EXCLUDED FROM SHEAR
PLANE)
O O ---
PROPER BOLTING PROCEDURE SELECTED FOR
JOINT DETAIL
O O ---
CONNECTING ELEMENTS, INCLUDING THE
APPROPRIATE FAYING SURFACE CONDITION
AND HOLE PREPARATION, IF SPECIFIED, MEET
APPLICABLE REQUIREMENTS
O O ---
PRE-INSTALLATION VERIFICATION TESTING BY
INSTALLATION PERSONNEL OBSERVED AND
DOCUMENTED FOR FASTENER ASSEMBLIES AND
METHODS USED
P O ---
PROPER STORAGE PROVIDED FOR BOLTS, NUTS,
WASHERS AND OTHER FASTENER
COMPONENETS
O O ---
TABLE N5.6-2
INSPECTION TASKS DURING BOLTING
INSPECTION TASKS DURING BOLTING
QUALITY
CONTROL
(QC)
QUALITY
ASSURANCE
(QA)
NOT
APPLICABLE
FASTENER ASSEMBLIES, OF SUITABLE
CONDITION, PLACED IN ALL HOLES AND
WASHERS (IF REQUIRED) ARE POSITIONED AS
REQUIRED
O O ---
JOINT BROUGHT TO THE SNUG-TIGHT
CONDITION PRIOR TO THE PRETENSIONING
OPERATION
O O ---
FASTENER COMPONENT NOT TURNED BY THE
WRENCH PREVENTED FROM ROTATING
O O ---
FASTENERS ARE PRETENSIONED IN
ACCORDANCE WITH THE RCSC SPECIFICATION,
PROGRESSING SYSTEMATICALLY FROM THE
MOST RIGID POINT TOWARD THE FREE EDGES
--- --- N/A
TABLE N5.6-3
INSPECTION TASKS AFTER BOLTING
INSPECTION TASKS AFTER BOLTING
QUALITY
CONTROL
(QC)
QUALITY
ASSURANCE
(QA)
NOT
APPLICABLE
DOCUMENT ACCEPTANCE OR REJECTION OF
BOLTED CONNECTIONS
P P ---
STRUCTURAL NOTES FOR QUALITY
ASSURANCE PLAN AND SPECIAL INSPECTION
4'ON
E EI
GHTH
INCH
= O
NE F
OOT
( 1/8"
= 1'
-0" )
08'
16'
04'
8'4'
04'
02'
6"0
02'
6"0
1'6"
6"ON
E QU
ATER
INCH
= O
NE F
OOT
( 1/4"
= 1'
-0" )
THRE
E EI
GHTH
S IN
CH =
ONE
FOO
T ( 3
/8" =
1'-0
" )ON
E HA
LF IN
CH =
ONE
FOO
T ( 1
/2" =
1'-0
" )TH
REE
QUAT
ERS
INCH
= O
NE F
OOT
( 3/4"
= 1'
-0" )
ONE
INCH
= O
NE F
OOT
( 1" =
1'-0
" )ON
E AN
D ON
E HA
LF IN
CHES
= O
NE F
OOT
( 1 1/
2" =
1'-0
" )TH
REE
INCH
ES =
ONE
FOO
T ( 3
" = 1'
-0" )
OKKS Studios, Inc.2 Wisconsin Circle / Suite 820Chevy Chase, MD 20815-7003Tel: (301) 718-0080Fax: (301) 718-9520www.okksstudios.com
Nobis Engineering, Inc.20410 Century Boulevard, Suite 230
Germantown, MD 20874Tel: (301) 528 2010
Woods Peacock Engineering Consultants5250 Cherokee Avenue, Suite 420
Alexandria, VA 22312-2052Tel: (703) 658-4400
Fax: (703) 658-4404
Henry Adams ConsultingEngineers, LLC600 Baltimore Avenue, 4th FloorBaltimore, MD 21204Tel: (410) 296-6500Fax: (410) 296-6501
The Protection Engineering Group2809 Boston Street, Suite 7Baltimore, MD 21224 USA
Tel: (443) 708-4096Fax:
SCHEMATIC DESIGN (30%) SUBMISSION09/11/15DESIGN DEVELOPMENT (60%) SUBMISSION11/23/15CONSTRUCTION DOCUMENTS (90% SUBMISSION)
03/17/16
TMP CAD
PERRY POINT, MD
WAREHOUSE RENOVATION& EXPANSION
03/17/16BID DOCUMENTS SUBMISSION
03/25/15
Professional Certification. I hereby certify that these documentswere prepared or approved by me, and that I am a duly licensedprofessional engineer under the laws of the State of Maryland,License No. 14484, Expiration Date: June 27, 2017.
SPECIAL INSPECTION NOTES
S003
![Page 4: 14012 - VAMC BLDG 360 - CENTRAL elorenz - rlscg.comrlscg.com/site/wp-content/uploads/VA245-16-B-0095-010.pdf · 10.welding electrodes: per table 3.1 of aws d1.1 for the smaw process](https://reader034.vdocuments.us/reader034/viewer/2022052608/5add35567f8b9a213e8c8f07/html5/thumbnails/4.jpg)
IBC 2012 - TABLE 1705.3
REQUIRED VERIFICATION AND INSPECTION OF CONCRETE CONSTRUCTION
VERIFICATION AND INSPECTION CONTINUOUS PERIODIC
NOT
APPLICABLE
REFERENCED
STANDARD
a
IBC
REFERENCE
1. INSPECTION OF REINFORCING
STEEL, INCLUDING PRESTRESSING
TENDONS, AND PLACEMENT.
--- X ---ACI 318: 3.5, 7.1-7.7
1910.4
2. INSPECTION OF REINFORCING
STEEL WELDING IN ACCORDANCE
WITH TABLE 1705.2.2 (IBC 2012), ITEM
2b.
--- --- X
AWS D1.4
ACI 318: 3.5.2
---
3. INSPECTION OF ANCHORS CAST IN
CONCRETE WHERE ALLOWABLE
LOADS HAVE BEEN INCREASED OR
WHERE STRENGTH DESIGN IS USED.
--- X ---ACI 318: 8.1.3, 21.2.8 1908.5, 1909.1
4. INSPECTION OF ANCHORS
POST-INSTALLED IN HARDENED
CONCRETE MEMBERS
b
.
--- --- X
ACI 318: 3.8.6, 8.1.3,
21.2.8
1909.1
5. VERIFYING USE OF REQUIRED MIX
DESIGN.
--- X ---
ACI 318: CHAPTER 4,
5.2-5.4
1904.2, 1910.2,
1910.3
6. AT THE TIME FRESH CONCRETE IS
SAMPLED TO FABRICATE SPECIMENS
FOR STRENGTH TESTS, PERFORM
SLUMP AND AIR CONTENT TESTS,
AND DETERMINE THE TEMPERATURE
OF THE CONCRETE.
X --- ---
ASTM C 172
ASTM C 31
ACI 318: 5.6, 5.8
1910.10
7. INSPECTION OF CONCRETE AND
SHOTCRETE PLACEMENT FOR
PROPER APPLICATION TECHNIQUES.
X --- ---ACI 318: 5.9, 5.10
1910.6, 1910.7,
1910.8
8. INSPECTION FOR MAINTENANCE
OF SPECIFIED CURING
TEMPERATURE AND TECHNIQUES.
--- X --- ACI 318: 5.11-5.13 1910.9
9. INSPECTION OF PRESTRESSED CONCRETE:
a. APPLICATION OF
PRESTRESSING FORCES.
--- --- X ACI 318: 18.20 ---
b. GROUTING OF BONDED
PRESTRESSING TENDONS IN
THE
SEISMIC-FORCE-RESISTING
SYSTEM.
--- --- X ACI 318: 18.18.4 ---
10. ERECTION OF PRECAST
CONCRETE MEMBERS.
--- --- X
ACI 318: CHAPTER
16
---
11. VERIFICATION OF IN-SITU
CONCRETE STRENGTH, PRIOR TO
STRESSING OF TENDONS IN
POSTTENSIONED CONCRETE AND
PRIOR TO REMOVAL OF SHORES AND
FORMS FROM BEAMS AND
STRUCTURAL SLABS.
--- --- X ACI 318: 6.2 ---
12. INSPECT FORMWORK FOR
SHAPE, LOCATION AND DIMENSIONS
OF THE CONCRETE MEMBER BEING
FORMED.
--- X --- ACI 318: 6.1.1 ---
a
WHERE APPLICABLE, SEE ALSO SECTION 1705.11 (IBC 2012), SPECIAL INSPECTIONS FOR SEISMIC RESISTANCE.
b
SPECIFIC REQUIREMENTS FOR SPECIAL INSPECTION SHALL BE INCLUDED IN THE RESEARCH REPORT FOR THE ANCHOR ISSUED
BY AN APPROVED SOURCE IN ACCORDANCE WITH ACI 355.2 OR OTHER QUALIFICATION PROCEDURES. WHERE SPECIFIC
REQUIREMENTS ARE NOT PROVIDED, SPECIAL INSPECTION REQUIREMENTS SHALL BE SPECIFIED BY THE REGISTERED DESIGN
PROFESSIONAL AND SHALL BE APPROVED BY THE BUILDING OFFICIAL PRIOR TO COMMENCEMENT OF THE WORK.
SUPPLEMENTAL INSPECTION REQUIRED
OF CONCRETE CONSTRUCTION
VERIFICATION AND INSPECTION CONTINUOUS PERIODIC
NOT
APPLICABLE
S1. MIX DESIGN
a. REVIEW CONCRETE BATCH TICKETS AND
VERIFY COMPLIANCE WITH APPROVED MIX
DESIGN. VERIFY THAT WATER ADDED AT THE
SITE DOES NOT EXCEED THAT ALLOWED BY THE
MIX DESIGN.
--- X ---
S2. REINFORCEMENT INSTALLATION
a. INSPECT SIZE, SPACING, COVER,
POSITIONING AND GRADE OF REINFORCING
STEEL. VERIFY THAT REINFORCING BARS ARE
FREE OF FORM OIL OR OTHER DELETERIOUS
MATERIALS. INSPECT BAR LAPS AND
MECHANICAL SPLICES. VERIFY THAT BARS ARE
ADEQUATELY TIED AND SUPPORTED ON CHAIRS
OR BOLSTERS.
--- X ---
S3. POST-TENSIONING OPERATIONS
a. INSPECT PLACEMENT, STRESSING, GROUTING
AND PROTECTION OF POST-TENSIONING
TENDONS. VERIFY THAT TENDONS ARE
CORRECTLY POSITIONED, SUPPORTED, TIED
AND WRAPPED. RECORD TENDON
ELONGATIONS.
--- --- X
S4. WELDING OF REINFORCING
a. VISUALLY INSPECT ALL REINFORCING STEEL
WELDS. INSPECT PREHEATING OF STEEL WHEN
REQUIRED.
--- --- X
S5. CONCRETE PLACEMENT
a. VERIFY THAT CONCRETE CONVEYANCE AND
DEPOSITING AVOIDS SEGREGATION OR
CONTAMINATION. VERIFY THAT CONCRETE IS
PROPERLY CONSOLIDATED.
--- X ---
S6. SAMPLING AND TESTING OF CONCRETE
a. TEST CONCRETE COMPRESSIVE STRENGTH
(ASTM C31 & C39), SLUMP (ASTM C143),
AIR-CONTENT (ASTM C231 OR C173) AND
TEMPERATURE (ASTM C1064)
--- X ---
IBC 2012 - TABLE 1705.2.2
REQUIRED VERIFICATION AND INSPECTION OF STEEL CONSTRUCTION
OTHER THAN STRUCTURAL STEEL
VERIFICATION AND INSPECTION CONTINUOUS PERIODIC
NOT
APPLICABLE
REFERENCED
STANDARD
a
1. MATERIAL VERIFICATION OF COLD-FORMED STEEL DECK:
a. IDENTIFICATION MARKINGS
TO CONFORM TO ASTM
STANDARDS SPECIFIED IN THE
APPROVED CONSTRUCTION
DOCUMENTS.
--- X ---
APPLICABLE ASTM
MATERIAL
STANDARDS
b. MANUFACTURER'S
CERTIFIED TEST REPORTS.
--- X --- ---
2. INSPECTION OF WELDING:
a. COLD-FORMED STEEL DECK:
1) FLOOR AND ROOF
DECK WELDS.
--- X --- AWS D1.3
b. REINFORCING STEEL:
1) VERIFICATION OF
WELDABILITY OF
REINFORCING STEEL
OTHER THAN ASTM A 706.
--- --- X
AWS D1.4
ACI 318: SECTION
3.5.2
2) REINFORCING STEEL
RESISTING FLEXURAL
AND AXIAL FORCES IN
INTERMEDIATE AND
SPECIAL MOMENT
FRAMES, AND BOUNDARY
ELEMENTS OF SPECIAL
STRUCTURAL WALLS OF
CONCRETE AND SHEAR
REINFORCEMENT.
--- --- X
3) SHEAR
REINFORCEMENT.
X --- ---
4) OTHER REINFORCING
STEEL.
--- X ---
3. INSPECTION OF STEEL FRAME JOINT DETAILS FOR COMPLIANCE:
a. DETAILS SUCH AS BRACING
AND STIFFENING.
--- X ---
---
b. MEMBER LOCATIONS. --- X ---
c. APPLICATION OF JOINT
DETAILS AT EACH
CONNECTION.
--- X ---
a
WHERE APPLICABLE, SEE ALSO SECTION 1705.11, SPECIAL INSPECTIONS FOR SEISMIC RESISTANCE.
SUPPLEMENTAL INSPECTION REQUIRED
OF STEEL CONSTRUCTION
VERIFICATION AND INSPECTION CONTINUOUS PERIODIC
NOT
APPLICABLE
S1. FABRICATOR CERTIFICATION / QUALITY CONTROL PROCEDURES
a. REVIEW SHOP FABRICATION AND QUALITY
CONTROL PROCEDURES.
--- X ---
S2. WELDING
a. VISUALLY INSPECT ALL WELDS. --- X ---
b. INSPECT PRE-HEAT, POST-HEAT AND
SURFACE PREPARATION BETWEEN PASSES.
--- X ---
c. VERIFY SIZE AND LENGTH OF FILLET WELDS. --- X ---
d. ULTRASONIC TESTING OF ALL
FULL-PENETRATION WELDS.
--- --- X
S3. SHEAR CONNECTORS
a. INSPECT SIZE, NUMBER, POSITIONING AND
WELDING OF SHEAR CONNECTORS. INSPECT
STUDS FOR FULL 360 DEGREE FLASH. RING
TEST ALL SHEAR CONNECTORS WITH A 3 LB
HAMMER. BEND TEST ALL QUESTIONABLE
STUDS TO 15 DEGREES.
--- --- X
S4. STRUCTURAL DETAILS
a. INSPECT STEEL FRAME FOR COMPLIANCE
WITH STRUCTURAL DRAWINGS, INCLUDING
BRACING, MEMBER CONFIGURATION AND
CONNECTION DETAILS.
--- X ---
4'ON
E EI
GHTH
INCH
= O
NE F
OOT
( 1/8"
= 1'
-0" )
08'
16'
04'
8'4'
04'
02'
6"0
02'
6"0
1'6"
6"ON
E QU
ATER
INCH
= O
NE F
OOT
( 1/4"
= 1'
-0" )
THRE
E EI
GHTH
S IN
CH =
ONE
FOO
T ( 3
/8" =
1'-0
" )ON
E HA
LF IN
CH =
ONE
FOO
T ( 1
/2" =
1'-0
" )TH
REE
QUAT
ERS
INCH
= O
NE F
OOT
( 3/4"
= 1'
-0" )
ONE
INCH
= O
NE F
OOT
( 1" =
1'-0
" )ON
E AN
D ON
E HA
LF IN
CHES
= O
NE F
OOT
( 1 1/
2" =
1'-0
" )TH
REE
INCH
ES =
ONE
FOO
T ( 3
" = 1'
-0" )
OKKS Studios, Inc.2 Wisconsin Circle / Suite 820Chevy Chase, MD 20815-7003Tel: (301) 718-0080Fax: (301) 718-9520www.okksstudios.com
Nobis Engineering, Inc.20410 Century Boulevard, Suite 230
Germantown, MD 20874Tel: (301) 528 2010
Woods Peacock Engineering Consultants5250 Cherokee Avenue, Suite 420
Alexandria, VA 22312-2052Tel: (703) 658-4400
Fax: (703) 658-4404
Henry Adams ConsultingEngineers, LLC600 Baltimore Avenue, 4th FloorBaltimore, MD 21204Tel: (410) 296-6500Fax: (410) 296-6501
The Protection Engineering Group2809 Boston Street, Suite 7Baltimore, MD 21224 USA
Tel: (443) 708-4096Fax:
SCHEMATIC DESIGN (30%) SUBMISSION09/11/15DESIGN DEVELOPMENT (60%) SUBMISSION11/23/15CONSTRUCTION DOCUMENTS (90% SUBMISSION)
03/17/16
TMP CAD
PERRY POINT, MD
WAREHOUSE RENOVATION& EXPANSION
03/17/16BID DOCUMENTS SUBMISSION
03/25/15
Professional Certification. I hereby certify that these documentswere prepared or approved by me, and that I am a duly licensedprofessional engineer under the laws of the State of Maryland,License No. 14484, Expiration Date: June 27, 2017.
SPECIAL INSPECTION NOTES
S004
![Page 5: 14012 - VAMC BLDG 360 - CENTRAL elorenz - rlscg.comrlscg.com/site/wp-content/uploads/VA245-16-B-0095-010.pdf · 10.welding electrodes: per table 3.1 of aws d1.1 for the smaw process](https://reader034.vdocuments.us/reader034/viewer/2022052608/5add35567f8b9a213e8c8f07/html5/thumbnails/5.jpg)
IBC 2012 - TABLE 1705.6
REQUIRED VERIFICATION AND INSPECTION OF SOILS
VERIFICATION AND INSPECTION
CONTINUOUS
DURING TASK
LISTED
PERIODICALLY
DURING TASK
LISTED
NOT
APPLICABLE
1. VERIFY MATERIALS BELOW SHALLOW
FOUNDATIONS ARE ADEQUATE TO ACHIEVE THE
DESIGN BEARING CAPACITY.
--- X ---
2. VERIFY EXCAVATIONS ARE EXTENDED TO PROPER
DEPTH AND HAVE REACHED PROPER MATERIAL.
--- X ---
3. PERFORM CLASSIFICATION AND TESTING OF
COMPACTED FILL MATERIALS.
--- X ---
4. VERIFY USE OF PROPER MATERIALS, DENSITIES
AND LIFT THICKNESSES DURING PLACEMENT AND
COMPACTION OF COMPACTED FILL.
X --- ---
5. PRIOR TO PLACEMENT OF COMPACTED FILL,
OBSERVE SUBGRADE AND VERIFY THAT SITE HAS
BEEN PREPARED PROPERLY.
--- X ---
SUPPLEMENTAL INSPECTION REQUIRED
OF SOILS AND FOUNDATIONS
VERIFICATION AND INSPECTION
CONTINUOUS
DURING TASK
LISTED
PERIODICALLY
DURING TASK
LISTED
NOT
APPLICABLE
S1. SHALLOW FOUNDATIONS
a. INSPECT REMOVAL OF UNSUITABLE MATERIAL
AND PREPARATION OF SUBGRAGE PRIOR TO
PLACEMENT OF CONTROLLED FILL.
--- X ---
S2. CONTROLLED STRUCTURAL FILL
a. PERFORM SIEVE TESTS (ASTM D422 & D1140)
AND MODIFIED PROCTOR TESTS (ASTM D1557)
OF EACH SOURCE OF FILL MATERIAL.
--- X ---
b. TEST DENSITY OF EACH LIFT OF FILL BY
NUCLEAR METHODS (ASTM D2922).
--- X ---
c. VERIFY EXTENT AND SLOPE OF FILL
PLACEMENT.
--- X ---
TABLE 1.19.2
LEVEL B QUALITY ASSURANCE
MINIMUM TESTS
VERIFICATION OF SLUMP FLOW AND VISUAL STABILITY INDEX (VSI) AS DELIVERED TO THE PROJECT SITE IN
ACCORDANCE WITH SPECIFICATION ARTICLE 1.5.B.1.b.3 FOR SELF-CONSOLIDATING GROUT
VERIFICATION OF f'm AND f'AAC IN ACCORDANCE WITH SPECIFICATION ARTICLE 1.4 B PRIOR TO CONSTRUCTION,
EXCEPT WHERE SPECIFICALLY EXEMPTED BY THIS CODE
MINIMUM INSPECTION
INSPECTION TASK
FREQUENCY
(a)
REFERENCE FOR CRITERIA
CONTINUOUS PERIODIC
NOT
APPLICABLE
TMS 402/ACI
530/ASCE 5
TMS 602/ACI
530.1/ASCE 6
1. VERIFY COMPLIANCE WITH THE
APPROVED SUBMITTALS
--- X --- --- ART. 1.5
2. AS MASONRY CONSTRUCTION BEGINS, VERIFY THAT THE FOLLOWING ARE IN COMPLIANCE:
a. PROPORTIONS OF
SITE-PREPARED MORTAR.
--- X --- ---
ART. 2.1,
2.6 A
b. CONSTRUCTION OF
MORTAR JOINTS.
--- X --- --- ART. 3.3 B
c. GRADE AND SIZE OF
PRESTRESSING TENDONS
AND ANCHORAGES
--- --- X ---
ART. 2.4 B,
2.4 H
d. LOCATION OF
REINFORCEMENT,
CONNECTORS, AND
PRESTRESSING TENDONS
AND ANCHORAGES.
--- --- X ---
ART. 3.4,
3.6A
e. PRESTRESSING
TECHNIQUE.
--- --- X --- ART. 3.6 B
f. PROPERTIES OF THIN-BED
MORTAR FOR AAC MASONRY
--- --- X --- ART. 2.1 C
3. PRIOR TO GROUTING, THE FOLLOWING SHALL BE VERIFIED TO ENSURE COMPLIANCE:
a. GROUT SPACE --- X --- ---
ART. 3.2 D,
3.2 F
b. GRADE, TYPE, AND SIZE
OF REINFORCEMENT AND
ANCHOR BOLTS, AND
PRESTRESSING TENDONS
AND ANCHORAGES
--- X --- SEC. 1.16ART. 2.4, 3.4
c. PLACEMENT OF
REINFORCEMENT AND
CONNECTORS, AND
PRESTRESSING TENDONS
AND ANCHORAGES
--- X --- SEC. 1.16
ART. 3.2 E,
3.4, 3.6 A
d. PROPORTIONS OF
SITE-PREPARED GROUT AND
PRESTRESSING GROUT FOR
BONDED TENDONS
--- X --- ---
ART. 2.6 B,
2.4 G.1.b
e. CONSTRUCTION OF
MORTAR JOINTS
--- X --- --- ART. 3.3 B
SUPPLEMENTAL INSPECTION REQUIRED
OF MASONRY CONSTRUCTION
VERIFICATION AND INSPECTION CONTINUOUS PERIODIC
NOT
APPLICABLE
S1. EVALUATION OF MASONRY STRENGTH
a. TEST COMPRESSIVE STRENGTH OF MORTAR
AND GROUT CUBE SAMPLES (ASTM C780).
--- X ---
b. TEST COMPRESSIVE STRENGTH OF MASONRY
PRISMS (ASTM C1314).
--- X ---
TABLE 1.19.2
LEVEL B QUALITY ASSURANCE (CONTINUED)
4. VERIFY DURING CONSTRUCTION:
a. SIZE AND LOCATION OF
STRUCTURAL ELEMENTS
--- X --- --- ART. 3.3 F
b. TYPE, SIZE AND
LOCATION OF ANCHORS,
INCLUDING OTHER DETAILS
OF ANCHORAGE OF
MASONRY TO STRUCTURAL
MEMBERS, FRAMES OR
OTHER CONSTRUCTION
--- X ---
SEC. 1.16.4.3,
1.17.1
---
c. WELDING OF
REINFORCEMENT
--- --- X
SEC.
2.1.7.7.2,
3.3.3.4 (c),
8.3.3.4 (b)
---
d. PREPARATION,
CONSTRUCTION AND
PROTECTION OF MASONRY
DURING COLD WEATHER
(TEMPERATURE BELOW 40°F
(4.4°C)) OR HOT WEATHER
(TEMPERATURE ABOVE 90°F
(32.2°C))
--- X --- ---
ART. 1.8 C,
1.8 D
e. APPLICATION OF
MEASUREMENT OF
PRESTRESSING FORCE
--- --- X --- ART. 3.6 B
f. PLACEMENT OF GROUT
AND PRESTRESSING GROUT
FOR BONDED TENDONS IS IN
COMPLIANCE
X --- --- ---
ART. 3.5,
3.6 C
g. PLACEMENT OF AAC
MASONRY UNITS AND
CONSTRUCTION OF
THIN-BED MORTAR JOINTS
--- --- X --- ART. 3.3 B.8
5. OBSERVE PREPARATION OF
GROUT SPECIMENS, MORTAR
SPECIMENS, AND/OR PRISMS
--- X --- ---
ART.
1.4 B.2.a.3,
1.4 B.2.b.3,
1.4 B.2.c.3,
1.4 B.3,
1.4 B.4
(a) FREQUENCY REFERS TO THE FREQUENCY OF INSPECTION, WHICH MAY BE CONTINUOUS DURING THE TASK
LISTED OR PERIODICALLY DURING THE LISTED TASK, AS DEFINED IN THE TABLE.
(b) REQUIRED FOR THE FIRST 5000 SQUARE FEET (465 SQUARE METERS) OF AAC MASONRY.
(c) REQUIRE AFTER THE FIRST 5000 SQUARE FEET (465 SQUARE METERS) OF AAC MASONRY.
4'ON
E EI
GHTH
INCH
= O
NE F
OOT
( 1/8"
= 1'
-0" )
08'
16'
04'
8'4'
04'
02'
6"0
02'
6"0
1'6"
6"ON
E QU
ATER
INCH
= O
NE F
OOT
( 1/4"
= 1'
-0" )
THRE
E EI
GHTH
S IN
CH =
ONE
FOO
T ( 3
/8" =
1'-0
" )ON
E HA
LF IN
CH =
ONE
FOO
T ( 1
/2" =
1'-0
" )TH
REE
QUAT
ERS
INCH
= O
NE F
OOT
( 3/4"
= 1'
-0" )
ONE
INCH
= O
NE F
OOT
( 1" =
1'-0
" )ON
E AN
D ON
E HA
LF IN
CHES
= O
NE F
OOT
( 1 1/
2" =
1'-0
" )TH
REE
INCH
ES =
ONE
FOO
T ( 3
" = 1'
-0" )
OKKS Studios, Inc.2 Wisconsin Circle / Suite 820Chevy Chase, MD 20815-7003Tel: (301) 718-0080Fax: (301) 718-9520www.okksstudios.com
Nobis Engineering, Inc.20410 Century Boulevard, Suite 230
Germantown, MD 20874Tel: (301) 528 2010
Woods Peacock Engineering Consultants5250 Cherokee Avenue, Suite 420
Alexandria, VA 22312-2052Tel: (703) 658-4400
Fax: (703) 658-4404
Henry Adams ConsultingEngineers, LLC600 Baltimore Avenue, 4th FloorBaltimore, MD 21204Tel: (410) 296-6500Fax: (410) 296-6501
The Protection Engineering Group2809 Boston Street, Suite 7Baltimore, MD 21224 USA
Tel: (443) 708-4096Fax:
SCHEMATIC DESIGN (30%) SUBMISSION09/11/15DESIGN DEVELOPMENT (60%) SUBMISSION11/23/15CONSTRUCTION DOCUMENTS (90% SUBMISSION)
03/17/16
TMP CAD
PERRY POINT, MD
WAREHOUSE RENOVATION& EXPANSION
03/17/16BID DOCUMENTS SUBMISSION
03/25/15
Professional Certification. I hereby certify that these documentswere prepared or approved by me, and that I am a duly licensedprofessional engineer under the laws of the State of Maryland,License No. 14484, Expiration Date: June 27, 2017.
SPECIAL INSPECTION NOTES
S005
![Page 6: 14012 - VAMC BLDG 360 - CENTRAL elorenz - rlscg.comrlscg.com/site/wp-content/uploads/VA245-16-B-0095-010.pdf · 10.welding electrodes: per table 3.1 of aws d1.1 for the smaw process](https://reader034.vdocuments.us/reader034/viewer/2022052608/5add35567f8b9a213e8c8f07/html5/thumbnails/6.jpg)
27'-4"
28'-0"
28'-0"
27'-4"
2'-0"
23'-10"±
21'-0"±
21'-0"±
21'-0"±
21'-0"±
21'-0"±
21'-0"±
20'-6"± 20'-6"± 30'-0"± 30'-0"± 32'-0"± 32'-0"± 24'-0"± 33'-0"± 21'-0"±
21'-0"±
31'-10"±
28'-8"±
28'-8"±
26'-8"±
13'-0"±
21'-0"±
9'-6"±
26'-10"
26'-6"
21'-0"21'-0"21'-0"21'-0"21'-0"21'-0"21'-0" 24'-0"± 27'-3"
2'-0" 5'-0"
1
S101 S121
1
S101 S111
4'ON
E EI
GHTH
INCH
= O
NE F
OOT
( 1/8"
= 1'
-0" )
08'
16'
04'
8'4'
04'
02'
6"0
02'
6"0
1'6"
6"ON
E QU
ATER
INCH
= O
NE F
OOT
( 1/4"
= 1'
-0" )
THRE
E EI
GHTH
S IN
CH =
ONE
FOO
T ( 3
/8" =
1'-0
" )ON
E HA
LF IN
CH =
ONE
FOO
T ( 1
/2" =
1'-0
" )TH
REE
QUAT
ERS
INCH
= O
NE F
OOT
( 3/4"
= 1'
-0" )
ONE
INCH
= O
NE F
OOT
( 1" =
1'-0
" )ON
E AN
D ON
E HA
LF IN
CHES
= O
NE F
OOT
( 1 1/
2" =
1'-0
" )TH
REE
INCH
ES =
ONE
FOO
T ( 3
" = 1'
-0" )
OKKS Studios, Inc.2 Wisconsin Circle / Suite 820Chevy Chase, MD 20815-7003Tel: (301) 718-0080Fax: (301) 718-9520www.okksstudios.com
Nobis Engineering, Inc.20410 Century Boulevard, Suite 230
Germantown, MD 20874Tel: (301) 528 2010
Woods Peacock Engineering Consultants5250 Cherokee Avenue, Suite 420
Alexandria, VA 22312-2052Tel: (703) 658-4400
Fax: (703) 658-4404
Henry Adams ConsultingEngineers, LLC600 Baltimore Avenue, 4th FloorBaltimore, MD 21204Tel: (410) 296-6500Fax: (410) 296-6501
The Protection Engineering Group2809 Boston Street, Suite 7Baltimore, MD 21224 USA
Tel: (443) 708-4096Fax:
SCHEMATIC DESIGN (30%) SUBMISSION09/11/15DESIGN DEVELOPMENT (60%) SUBMISSION11/23/15CONSTRUCTION DOCUMENTS (90% SUBMISSION)
03/17/16
TMP CAD
PERRY POINT, MD
WAREHOUSE RENOVATION& EXPANSION
03/17/16BID DOCUMENTS SUBMISSION
03/25/15
Professional Certification. I hereby certify that these documentswere prepared or approved by me, and that I am a duly licensedprofessional engineer under the laws of the State of Maryland,License No. 14484, Expiration Date: June 27, 2017.
1
S101 S101
FOUNDATION/SLAB PLAN
1/16" = 1'-0"
FOUNDATION/SLAB PLAN
S101
GRAPHIC SCALE
0 8' 16' 32'
1/16" = 1'-0"
CAUTION: IF THIS DRAWING
IS A REDUCTION, GRAPHIC
SCALES MUST BE USED.
![Page 7: 14012 - VAMC BLDG 360 - CENTRAL elorenz - rlscg.comrlscg.com/site/wp-content/uploads/VA245-16-B-0095-010.pdf · 10.welding electrodes: per table 3.1 of aws d1.1 for the smaw process](https://reader034.vdocuments.us/reader034/viewer/2022052608/5add35567f8b9a213e8c8f07/html5/thumbnails/7.jpg)
27'-4"
28'-0"
28'-0"
27'-4"
2'-0"
23'-10"±
21'-0"±
21'-0"±
21'-0"±
21'-0"±
21'-0"±
21'-0"±
20'-6"± 20'-6"± 30'-0"± 30'-0"± 32'-0"± 32'-0"± 24'-0"± 33'-0"± 21'-0"±
21'-0"±
31'-10"±
28'-8"±
28'-8"±
26'-8"±
13'-0"±
21'-0"±
9'-6"±
26'-10"
26'-6"
21'-0"21'-0"21'-0"21'-0"21'-0"21'-0"21'-0" 24'-0"± 27'-3"
2'-0" 5'-0"
1
S102 S112
1
S102 S122
4'ON
E EI
GHTH
INCH
= O
NE F
OOT
( 1/8"
= 1'
-0" )
08'
16'
04'
8'4'
04'
02'
6"0
02'
6"0
1'6"
6"ON
E QU
ATER
INCH
= O
NE F
OOT
( 1/4"
= 1'
-0" )
THRE
E EI
GHTH
S IN
CH =
ONE
FOO
T ( 3
/8" =
1'-0
" )ON
E HA
LF IN
CH =
ONE
FOO
T ( 1
/2" =
1'-0
" )TH
REE
QUAT
ERS
INCH
= O
NE F
OOT
( 3/4"
= 1'
-0" )
ONE
INCH
= O
NE F
OOT
( 1" =
1'-0
" )ON
E AN
D ON
E HA
LF IN
CHES
= O
NE F
OOT
( 1 1/
2" =
1'-0
" )TH
REE
INCH
ES =
ONE
FOO
T ( 3
" = 1'
-0" )
OKKS Studios, Inc.2 Wisconsin Circle / Suite 820Chevy Chase, MD 20815-7003Tel: (301) 718-0080Fax: (301) 718-9520www.okksstudios.com
Nobis Engineering, Inc.20410 Century Boulevard, Suite 230
Germantown, MD 20874Tel: (301) 528 2010
Woods Peacock Engineering Consultants5250 Cherokee Avenue, Suite 420
Alexandria, VA 22312-2052Tel: (703) 658-4400
Fax: (703) 658-4404
Henry Adams ConsultingEngineers, LLC600 Baltimore Avenue, 4th FloorBaltimore, MD 21204Tel: (410) 296-6500Fax: (410) 296-6501
The Protection Engineering Group2809 Boston Street, Suite 7Baltimore, MD 21224 USA
Tel: (443) 708-4096Fax:
SCHEMATIC DESIGN (30%) SUBMISSION09/11/15DESIGN DEVELOPMENT (60%) SUBMISSION11/23/15CONSTRUCTION DOCUMENTS (90% SUBMISSION)
03/17/16
TMP CAD
PERRY POINT, MD
WAREHOUSE RENOVATION& EXPANSION
03/17/16BID DOCUMENTS SUBMISSION
03/25/15
Professional Certification. I hereby certify that these documentswere prepared or approved by me, and that I am a duly licensedprofessional engineer under the laws of the State of Maryland,License No. 14484, Expiration Date: June 27, 2017.
1
S102 S102
LOW ROOF FRAMING PLAN
1/16" = 1'-0"
LOW ROOF FRAMING PLAN
S102
GRAPHIC SCALE
0 8' 16' 32'
1/16" = 1'-0"
CAUTION: IF THIS DRAWING
IS A REDUCTION, GRAPHIC
SCALES MUST BE USED.
![Page 8: 14012 - VAMC BLDG 360 - CENTRAL elorenz - rlscg.comrlscg.com/site/wp-content/uploads/VA245-16-B-0095-010.pdf · 10.welding electrodes: per table 3.1 of aws d1.1 for the smaw process](https://reader034.vdocuments.us/reader034/viewer/2022052608/5add35567f8b9a213e8c8f07/html5/thumbnails/8.jpg)
27'-4"
28'-0"
28'-0"
27'-4"
2'-0"
23'-10"±
21'-0"±
21'-0"±
21'-0"±
21'-0"±
21'-0"±
21'-0"±
20'-6"± 20'-6"± 30'-0"± 30'-0"± 32'-0"± 32'-0"± 24'-0"± 33'-0"± 21'-0"±
21'-0"±
31'-10"±
28'-8"±
28'-8"±
26'-8"±
13'-0"±
21'-0"±
9'-6"±
26'-10"
26'-6"
21'-0"21'-0"21'-0"21'-0"21'-0"21'-0"21'-0" 24'-0"± 27'-3"
2'-0" 5'-0"
1
S103 S123
1
S103 S113
4'ON
E EI
GHTH
INCH
= O
NE F
OOT
( 1/8"
= 1'
-0" )
08'
16'
04'
8'4'
04'
02'
6"0
02'
6"0
1'6"
6"ON
E QU
ATER
INCH
= O
NE F
OOT
( 1/4"
= 1'
-0" )
THRE
E EI
GHTH
S IN
CH =
ONE
FOO
T ( 3
/8" =
1'-0
" )ON
E HA
LF IN
CH =
ONE
FOO
T ( 1
/2" =
1'-0
" )TH
REE
QUAT
ERS
INCH
= O
NE F
OOT
( 3/4"
= 1'
-0" )
ONE
INCH
= O
NE F
OOT
( 1" =
1'-0
" )ON
E AN
D ON
E HA
LF IN
CHES
= O
NE F
OOT
( 1 1/
2" =
1'-0
" )TH
REE
INCH
ES =
ONE
FOO
T ( 3
" = 1'
-0" )
OKKS Studios, Inc.2 Wisconsin Circle / Suite 820Chevy Chase, MD 20815-7003Tel: (301) 718-0080Fax: (301) 718-9520www.okksstudios.com
Nobis Engineering, Inc.20410 Century Boulevard, Suite 230
Germantown, MD 20874Tel: (301) 528 2010
Woods Peacock Engineering Consultants5250 Cherokee Avenue, Suite 420
Alexandria, VA 22312-2052Tel: (703) 658-4400
Fax: (703) 658-4404
Henry Adams ConsultingEngineers, LLC600 Baltimore Avenue, 4th FloorBaltimore, MD 21204Tel: (410) 296-6500Fax: (410) 296-6501
The Protection Engineering Group2809 Boston Street, Suite 7Baltimore, MD 21224 USA
Tel: (443) 708-4096Fax:
SCHEMATIC DESIGN (30%) SUBMISSION09/11/15DESIGN DEVELOPMENT (60%) SUBMISSION11/23/15CONSTRUCTION DOCUMENTS (90% SUBMISSION)
03/17/16
TMP CAD
PERRY POINT, MD
WAREHOUSE RENOVATION& EXPANSION
03/17/16BID DOCUMENTS SUBMISSION
03/25/15
Professional Certification. I hereby certify that these documentswere prepared or approved by me, and that I am a duly licensedprofessional engineer under the laws of the State of Maryland,License No. 14484, Expiration Date: June 27, 2017.
1
S103 S103
HIGH ROOF FRAMING PLAN
1/16" = 1'-0"
HIGH ROOF FRAMING PLAN
S103
GRAPHIC SCALE
0 8' 16' 32'
1/16" = 1'-0"
CAUTION: IF THIS DRAWING
IS A REDUCTION, GRAPHIC
SCALES MUST BE USED.
![Page 9: 14012 - VAMC BLDG 360 - CENTRAL elorenz - rlscg.comrlscg.com/site/wp-content/uploads/VA245-16-B-0095-010.pdf · 10.welding electrodes: per table 3.1 of aws d1.1 for the smaw process](https://reader034.vdocuments.us/reader034/viewer/2022052608/5add35567f8b9a213e8c8f07/html5/thumbnails/9.jpg)
32'-0"±32'-0"±
32'-0"±
32'-0"±
32'-0"±
32'-0"±
32'-0"±
32'-0"±
32'-0"±
32'-0"±
32'-0"± 32'-0"±
32'-0"±
32'-0"±
32'-0"±
32'-0"±
32'-0"±
32'-0"±
32'-0"± 32'-0"±
33'-0"±
33'-0"±
33'-0"±33'-0"±
33'-0"± 33'-0"±
33'-0"±33'-0"±
33'-0"±33'-0"±
33'-0"±
33'-0"± 33'-0"± 33'-0"±
33'-0"±
33'-0"±
33'-0"±
33'-0"±
33'-0"±
33'-0"±
33'-0"±
33'-0"±
33'-0"±
33'-0"±
33'-0"±
33'-0"±
33'-0"±
33'-0"±
33'-0"±
31'-0"±
31'-0"±31'-0"±
34'-0"±34'-0"±
34'-0"±
31'-0"±
31'-0"±
30'-0"±
28'-6"±
32'-0"±
27'-6"±
33'-0"±32'-0"±
31'-0"±
32'-0"±
33'-0"±
29'-6"±
31'-0"±
29'-6"±
30'-0"±
27'-6"±
29'-6"±
31'-6"±
33'-0"±
30'-6"±
28'-6"±28'-6"±
27'-6"±
31'-0"±
30'-0"±
30'-0"±31'-0"±
32'-0"±
33'-0"±
31'-0"±
31'-0"±
33'-0"±
34'-0"±
32'-0"±
34'-0"±
32'-0"±
33-0"±
2'-0"
23'-10"±
21'-0"±
21'-0"±
21'-0"±
21'-0"±
21'-0"±
21'-0"±
20'-6"± 20'-6"± 30'-0"± 30'-0"± 32'-0"± 32'-0"± 24'-0"± 33'-0"± 21'-0"±
21'-0"±
31'-10"±
28'-8"±
28'-8"±
26'-8"±
13'-0"±
T.O. SOG
ELEV = 33'-6"±
(E) TRENCH DRAIN
INFILL, TYP OF 2
(E) 6" CONCRETE
PAD
(E) MASONRY
PARTITION WALL,
TYP
T.O. (E) SOG
ELEV = 33'-6"±
1
S111 S401
CMU INFILL, NOTE 3
CMU INFILL, NOTE 3
CMU INFILL,
NOTE 3
CMU INFILL,
NOTE 3
2'-6"
NO
TE
4
5'-0 1/2"
NO
TE
4
5'-0 1/2"
NOTE 4
10'-0"
NOTE 4
CMU INFILL,
NOTE 3
W8x10 LINTEL
ABOVE DOOR
4
S111 S504
METAL STAIR AND LANDING,
PER SPEC SECTION 05 51 00,
NOTE 5
6'-8" 6'-8"
4'-4"
6
S111 S504
6
S111 S504
33'-0"±
6'-8"±
19'-4"±
7
S111 S504
8
S111 S504
(E) CONC CURB AND
SLAB DEMO AND INFILL
4"±
1'-6"±1'-6"±
87'-8"±
4'ON
E EI
GHTH
INCH
= O
NE F
OOT
( 1/8"
= 1'
-0" )
08'
16'
04'
8'4'
04'
02'
6"0
02'
6"0
1'6"
6"ON
E QU
ATER
INCH
= O
NE F
OOT
( 1/4"
= 1'
-0" )
THRE
E EI
GHTH
S IN
CH =
ONE
FOO
T ( 3
/8" =
1'-0
" )ON
E HA
LF IN
CH =
ONE
FOO
T ( 1
/2" =
1'-0
" )TH
REE
QUAT
ERS
INCH
= O
NE F
OOT
( 3/4"
= 1'
-0" )
ONE
INCH
= O
NE F
OOT
( 1" =
1'-0
" )ON
E AN
D ON
E HA
LF IN
CHES
= O
NE F
OOT
( 1 1/
2" =
1'-0
" )TH
REE
INCH
ES =
ONE
FOO
T ( 3
" = 1'
-0" )
OKKS Studios, Inc.2 Wisconsin Circle / Suite 820Chevy Chase, MD 20815-7003Tel: (301) 718-0080Fax: (301) 718-9520www.okksstudios.com
Nobis Engineering, Inc.20410 Century Boulevard, Suite 230
Germantown, MD 20874Tel: (301) 528 2010
Woods Peacock Engineering Consultants5250 Cherokee Avenue, Suite 420
Alexandria, VA 22312-2052Tel: (703) 658-4400
Fax: (703) 658-4404
Henry Adams ConsultingEngineers, LLC600 Baltimore Avenue, 4th FloorBaltimore, MD 21204Tel: (410) 296-6500Fax: (410) 296-6501
The Protection Engineering Group2809 Boston Street, Suite 7Baltimore, MD 21224 USA
Tel: (443) 708-4096Fax:
SCHEMATIC DESIGN (30%) SUBMISSION09/11/15DESIGN DEVELOPMENT (60%) SUBMISSION11/23/15CONSTRUCTION DOCUMENTS (90% SUBMISSION)
03/17/16
TMP CAD
PERRY POINT, MD
WAREHOUSE RENOVATION& EXPANSION
03/17/16BID DOCUMENTS SUBMISSION
03/25/15
Professional Certification. I hereby certify that these documentswere prepared or approved by me, and that I am a duly licensedprofessional engineer under the laws of the State of Maryland,License No. 14484, Expiration Date: June 27, 2017.
1
S101 S111
PARTIAL PLAN - EXISTING BUILDING FOUNDATION/SLAB
1/8" = 1'-0"
NOTES:
1. XX'-XX"± DENOTES EXISTING TOP OF FOOTING ELEVATION.
2. EXISTING TOP OF SLAB-ON-GRADE ELEVATION = 37'-6"±, UNLESS NOTED OTHERWISE.
3. SEE TYPICAL MASONRY WALL BOND ANGLE SECTION, 3/S504, FOR CMU INFILL CONNECTION TO EXISTING MASONRY WALL.
4. COORDINATE RECESSED FLOOR SCALE SIZE AND LOCATION WITH ARCHITECTURAL DRAWINGS.
5. SEE ARCHITECTURAL DRAWINGS FOR SIZES AND QUANTITY OF STAIR TREADS AND RISERS.
PARTIAL PLAN - EXISTING BUILDINGFOUNDATION/SLAB
S111
GRAPHIC SCALE
1/8" = 1'-0"
0 4' 8' 16'
CAUTION: IF THIS DRAWING
IS A REDUCTION, GRAPHIC
SCALES MUST BE USED.
![Page 10: 14012 - VAMC BLDG 360 - CENTRAL elorenz - rlscg.comrlscg.com/site/wp-content/uploads/VA245-16-B-0095-010.pdf · 10.welding electrodes: per table 3.1 of aws d1.1 for the smaw process](https://reader034.vdocuments.us/reader034/viewer/2022052608/5add35567f8b9a213e8c8f07/html5/thumbnails/10.jpg)
2'-0"
23'-10"±
21'-0"±
21'-0"±
21'-0"±
21'-0"±
21'-0"±
21'-0"±
20'-6"± 20'-6"± 30'-0"± 30'-0"± 32'-0"± 32'-0"± 24'-0"± 33'-0"± 21'-0"±
21'-0"±
31'-10"±
28'-8"±
28'-8"±
26'-8"±
13'-0"±
(E
) W
12x19
(E
) W
12x19
(E
) W
12x19
(E
) W
18x35
(E) W16x26 (26)
(E) W16x26 (26)
(E
) W
16x26 (14)
(E
) W
16x26 (14)
(E
) W
16x26 (14)
(E) W16x26 (26)
(E) W21x68 (48)
(E
) W
16x26 (14)
(E) W21x44 (38) (E) W27x84 (48)
(E
) W
16x26
(E) W14x22
(E) W14x22
(E) W12x14
(E) W12x14
(E) W12x14
(E) W12x14
(E) W12x14
(E) W12x14
(E) W12x14
(E) W12x14
(E) W12x14
(E) W21x83 (48)(E) W21x50 (38)(E) W21x44 (32)(E) W21x44 (30)(E) W18x40 (30)
(E) W21x62 (30)
(E) W12x14(E) W12x14
(E) W21x68 (48)(E) W21x44 (38)
(E) W21x44(E) W21x50(E) W18x40(E) W18x40(E) W14x22(E) W14x22
(E) W12x14(E) W12x14
(E) W12x14(E) W12x14
(E) W12x14(E) W12x14
(E) W12x14(E) W12x14
(E) W12x14(E) W12x14
(E) W12x14(E) W12x14
(E) W12x14(E) W12x14
(E) W12x14(E) W12x14
(E) W12x14(E) W12x14
(E) W12x14(E) W12x14
(E) W12x14(E) W12x14
(E) W12x14(E) W12x14
(E) W12x14(E) W12x14
(E) W12x14(E) W12x14
(E) W12x14(E) W12x14
(E) W12x14(E) W12x14
(E) W12x14(E) W12x14
(E) W12x14(E) W12x14
(E) W12x14(E) W12x14
(E) W12x14(E) W12x14
(E) W12x14(E) W12x14
(E) W12x14(E) W12x14
(E) W18x35 (40)
(E) W18x35 (40)
(E) W18x35 (40)
(E) W18x35 (40)
(E) W18x35 (40)
(E) W18x35 (40)
(E) W18x35 (40)
(E) W18x35 (40)
(E) W18x35 (40)
(E) W18x35 (40)
(E) W18x35 (40)
(E) W18x35 (40)
(E) W18x35 (40)
(E) W18x35 (40)
(E) W16x26 (26)
(E) W21x68 (40)
(E) W21x68 (40)
(E) W16x26 (26)
(E
) W
14x22
(E
) W
14x22
(E
) W
14x22
(E
) W
14x22
(E
) W
14x22
(E
) W
14x22
(E
) W
16x26
(E
) W
16x26
(E
) W
16x26
(E
) W
16x26
(E
) W
16x26
(E
) W
16x26
(E
) W
14x22
(E
) W
21x57 (32)
(E
) W
21x57 (32)
(E
) W
21x57 (32)
(E
) W
21x57 (32)
(E
) W
24x62 (32)
(E
) W
18x50 (36)
(E
) W
24x62
(E
) W
24x62
(E
) W
24x62
(E
) W
24x62
(E
) W
24x62
(E
) W
24x62
(E
) W
14x22 (22)
(E
) W
14x22 (22)
(E
) W
14x22 (22)
(E
) W
14x22 (22)
(E
) W
14x30 (22)
(E
) W
14x30 (22)
(E
) W
14x30 (22)
(E
) W
14x30 (22)
(E
) W
14x30 (22)
(E
) W
14x30 (22)
(E
) W
14x22
(E
) W
21x44
(E
) W
21x44 (32)
(E
) W
12x14
(E
) W
12x14
(E
) W
12x14
(E
) W
12x14
(E
) W
12x14
(E
) W
12x14
(E
) W
12x14
(E
) W
12x14
(E
) W
12x14
(E
) W
12x14
(E
) W
12x14
(E
) W
12x14
(E
) W
12x14
(E
) W
12x14
(E
) W
12x14
(E
) W
12x14
(E
) W
12x14
(E
) W
12x14
(E
) W
12x14
(E
) W
12x14
(E
) W
12x14
EDGE OF (E) ROOF
DECK, TYP
T.O. STEEL BEAM ELEV = 51'-0"
T.O
. S
TE
EL B
EA
M E
LE
V =
50'-6 3/4"
T.O. STEEL BEAM ELEV = 50'-6 3/4"
T.O
. S
TE
EL B
EA
M E
LE
V =
48'-0 3/4"
(E) KNEE BRACE, TYP
4'ON
E EI
GHTH
INCH
= O
NE F
OOT
( 1/8"
= 1'
-0" )
08'
16'
04'
8'4'
04'
02'
6"0
02'
6"0
1'6"
6"ON
E QU
ATER
INCH
= O
NE F
OOT
( 1/4"
= 1'
-0" )
THRE
E EI
GHTH
S IN
CH =
ONE
FOO
T ( 3
/8" =
1'-0
" )ON
E HA
LF IN
CH =
ONE
FOO
T ( 1
/2" =
1'-0
" )TH
REE
QUAT
ERS
INCH
= O
NE F
OOT
( 3/4"
= 1'
-0" )
ONE
INCH
= O
NE F
OOT
( 1" =
1'-0
" )ON
E AN
D ON
E HA
LF IN
CHES
= O
NE F
OOT
( 1 1/
2" =
1'-0
" )TH
REE
INCH
ES =
ONE
FOO
T ( 3
" = 1'
-0" )
OKKS Studios, Inc.2 Wisconsin Circle / Suite 820Chevy Chase, MD 20815-7003Tel: (301) 718-0080Fax: (301) 718-9520www.okksstudios.com
Nobis Engineering, Inc.20410 Century Boulevard, Suite 230
Germantown, MD 20874Tel: (301) 528 2010
Woods Peacock Engineering Consultants5250 Cherokee Avenue, Suite 420
Alexandria, VA 22312-2052Tel: (703) 658-4400
Fax: (703) 658-4404
Henry Adams ConsultingEngineers, LLC600 Baltimore Avenue, 4th FloorBaltimore, MD 21204Tel: (410) 296-6500Fax: (410) 296-6501
The Protection Engineering Group2809 Boston Street, Suite 7Baltimore, MD 21224 USA
Tel: (443) 708-4096Fax:
SCHEMATIC DESIGN (30%) SUBMISSION09/11/15DESIGN DEVELOPMENT (60%) SUBMISSION11/23/15CONSTRUCTION DOCUMENTS (90% SUBMISSION)
03/17/16
TMP CAD
PERRY POINT, MD
WAREHOUSE RENOVATION& EXPANSION
03/17/16BID DOCUMENTS SUBMISSION
03/25/15
Professional Certification. I hereby certify that these documentswere prepared or approved by me, and that I am a duly licensedprofessional engineer under the laws of the State of Maryland,License No. 14484, Expiration Date: June 27, 2017.
1
S102 S112
PARTIAL PLAN - EXISTING BUILDING LOW ROOF FRAMING
1/8" = 1'-0"
NOTES:
1. EXISTING TOP OF STEEL BEAM ELEVATION = 50'-10"±, UNLESS NOTED OTHERWISE.
PARTIAL PLAN - EXISTING BUILDINGLOW ROOF FRAMING
S112
GRAPHIC SCALE
1/8" = 1'-0"
0 4' 8' 16'
CAUTION: IF THIS DRAWING
IS A REDUCTION, GRAPHIC
SCALES MUST BE USED.
![Page 11: 14012 - VAMC BLDG 360 - CENTRAL elorenz - rlscg.comrlscg.com/site/wp-content/uploads/VA245-16-B-0095-010.pdf · 10.welding electrodes: per table 3.1 of aws d1.1 for the smaw process](https://reader034.vdocuments.us/reader034/viewer/2022052608/5add35567f8b9a213e8c8f07/html5/thumbnails/11.jpg)
2'-0"
23'-10"±
21'-0"±
21'-0"±
21'-0"±
21'-0"±
21'-0"±
21'-0"±
20'-6"± 20'-6"± 30'-0"± 30'-0"± 32'-0"± 32'-0"± 24'-0"± 33'-0"± 21'-0"±
21'-0"±
31'-10"±
28'-8"±
28'-8"±
26'-8"±
13'-0"±
(E) W14x30
(E
) W
16x31
(E
) W
16x31
(E
) W
16x31
(E
) W
18x35
(E
) W
18x35
(E
) W
18x35
(E) W14x30 (E) W14x30 (E) W14x30
(E) W14x30 (E) W16x36
(E
) W
16x31
(E
) W
24x57
(E
) W
21x50
(E
) W
21x50
(E
) W
21x44
(E
) W
16x26
(E
) W
16x26
(E
) W
24x55
(E
) W
24x62
(E
) W
24x62
(E
) W
24x68
(E
) W
18x40
(E
) W
16x26
(E
) W
24x55
(E
) W
24x62
(E
) W
24x62
(E
) W
24x68
(E
) W
16x31
(E
) W
18x40
(E
) W
18x40
(E
) W
18x40
(E
) W
18x40
(E
) W
18x40
(E
) W
21x50
(E
) W
18x40
(E
) W
21x50
(E
) W
18x40
(E
) W
21x50
(E
) W
30x108
(E
) W
30x108
(E
) W
30x108
(E
) W
30x108
(E) W14x30(E) W14x30(E) W14x30(E) W14x30(E) W14x30(E) W14x30
(E) W16x31
(E) W16x31
(E) W16x31
(E) W16x31
(E) W16x31
(E) W14x22
(E) W14x22
(E) W14x22
(E) W14x22
(E) W14x22
(E) W14x22
(E) W14x22
(E) W14x22
(E) W14x22
(E) W14x22
(E) W14x22
(E) W14x22
(E) W14x22
(E) W14x22
(E) W14x22
(E) W14x22
(E) W14x22
(E) W14x22
(E) W14x22
(E) W14x22
(E) W14x22
(E) W18x35
(E) W18x35
(E) W18x35
(E) W18x35
(E) W18x35
(E) W16x26
(E) W16x26
(E) W16x26
(E) W16x26
(E) W16x26
(E) W16x26
(E) W16x26
(E) W16x26
(E) W16x26
(E) W16x26(E) W16x26(E) W16x26(E) W16x26
(E) W16x26(E) W16x26(E) W16x26
(E) W16x26(E) W16x26(E) W16x26
(E) W16x26
(E) W16x26
(E) W16x26
(E) W16x26(E) W16x26(E) W16x26 (E) W16x26
(E) W16x26(E) W16x26(E) W16x26 (E) W16x26
(E) W16x26(E) W16x26(E) W16x26 (E) W16x26
(E) W16x26(E) W16x26(E) W16x26 (E) W16x26
(E) W16x26(E) W16x26(E) W16x26 (E) W16x26
(E) W16x26(E) W16x26 (E) W16x26
(E) W16x26(E) W16x26 (E) W16x26
(E) W16x26(E) W16x26 (E) W16x26
(E) W16x26(E) W16x26 (E) W16x26
(E) W16x26(E) W16x26 (E) W16x26
(E) W16x26(E) W16x26(E) W16x26 (E) W16x26
(E) W16x26(E) W16x26(E) W16x26 (E) W16x26
(E) W16x26(E) W16x26(E) W16x26 (E) W16x26
(E) W16x26(E) W16x26(E) W16x26 (E) W16x26
(E) W16x26(E) W16x26(E) W16x26 (E) W16x26
(E) W16x31
(E) W16x31
(E) W16x31
(E) W16x31
(E) W16x31
(E) W16x31
(E) W16x31
EDGE OF (E) ROOF
BELOW, TYP
EDGE OF (E) ROOF
DECK, TYP
(E) KNEE BRACE, TYP
4'ON
E EI
GHTH
INCH
= O
NE F
OOT
( 1/8"
= 1'
-0" )
08'
16'
04'
8'4'
04'
02'
6"0
02'
6"0
1'6"
6"ON
E QU
ATER
INCH
= O
NE F
OOT
( 1/4"
= 1'
-0" )
THRE
E EI
GHTH
S IN
CH =
ONE
FOO
T ( 3
/8" =
1'-0
" )ON
E HA
LF IN
CH =
ONE
FOO
T ( 1
/2" =
1'-0
" )TH
REE
QUAT
ERS
INCH
= O
NE F
OOT
( 3/4"
= 1'
-0" )
ONE
INCH
= O
NE F
OOT
( 1" =
1'-0
" )ON
E AN
D ON
E HA
LF IN
CHES
= O
NE F
OOT
( 1 1/
2" =
1'-0
" )TH
REE
INCH
ES =
ONE
FOO
T ( 3
" = 1'
-0" )
OKKS Studios, Inc.2 Wisconsin Circle / Suite 820Chevy Chase, MD 20815-7003Tel: (301) 718-0080Fax: (301) 718-9520www.okksstudios.com
Nobis Engineering, Inc.20410 Century Boulevard, Suite 230
Germantown, MD 20874Tel: (301) 528 2010
Woods Peacock Engineering Consultants5250 Cherokee Avenue, Suite 420
Alexandria, VA 22312-2052Tel: (703) 658-4400
Fax: (703) 658-4404
Henry Adams ConsultingEngineers, LLC600 Baltimore Avenue, 4th FloorBaltimore, MD 21204Tel: (410) 296-6500Fax: (410) 296-6501
The Protection Engineering Group2809 Boston Street, Suite 7Baltimore, MD 21224 USA
Tel: (443) 708-4096Fax:
SCHEMATIC DESIGN (30%) SUBMISSION09/11/15DESIGN DEVELOPMENT (60%) SUBMISSION11/23/15CONSTRUCTION DOCUMENTS (90% SUBMISSION)
03/17/16
TMP CAD
PERRY POINT, MD
WAREHOUSE RENOVATION& EXPANSION
03/17/16BID DOCUMENTS SUBMISSION
03/25/15
Professional Certification. I hereby certify that these documentswere prepared or approved by me, and that I am a duly licensedprofessional engineer under the laws of the State of Maryland,License No. 14484, Expiration Date: June 27, 2017.
1
S103 S113
PARTIAL PLAN - EXISTING BUILDING HIGH ROOF FRAMING
1/8" = 1'-0"
NOTES:
1. EXISTING TOP OF STEEL BEAM ELEVATION = 63'-11"±, UNLESS NOTED OTHERWISE.
PARTIAL PLAN - EXISTING BUILDINGHIGH ROOF FRAMING
S113
GRAPHIC SCALE
1/8" = 1'-0"
0 4' 8' 16'
CAUTION: IF THIS DRAWING
IS A REDUCTION, GRAPHIC
SCALES MUST BE USED.
![Page 12: 14012 - VAMC BLDG 360 - CENTRAL elorenz - rlscg.comrlscg.com/site/wp-content/uploads/VA245-16-B-0095-010.pdf · 10.welding electrodes: per table 3.1 of aws d1.1 for the smaw process](https://reader034.vdocuments.us/reader034/viewer/2022052608/5add35567f8b9a213e8c8f07/html5/thumbnails/12.jpg)
32'-0"±
32'-0"± 32'-0"±
33'-0"±
33'-0"±
33'-0"±
33'-0"±
32'-0"±
33'-0"±
32'-0"
33'-0"
32'-0"
33'-0"
32'-0"
32'-0"
32'-0"
32'-0"
32'-0"
32'-0"±
32'-0" 32'-0" 32'-0" 32'-0" 32'-0" 32'-0" 32'-0"
32'-0"
32'-0"
32'-0"
32'-0"
32'-0"
32'-0"
32'-0"
32'-0"
32'-0"
32'-0"
32'-0"
32'-0"
32'-0"
32'-0"
32'-0"
32'-0"
32'-0"
32'-0"
32'-0"
32'-0"
32'-0"
32'-0"
32'-0"
32'-0"
33'-0"33'-0"33'-0"33'-0"
33'-0"
33'-0"
21'-0"21'-0"21'-0"21'-0"21'-0"21'-0"21'-0"
27'-4"
28'-0"
28'-0"
27'-4"
24'-0"± 27'-3"
2'-0"
2'-0"
21'-0"±
9'-6"±
26'-10"
26'-6"
5'-0"
ABUT (E) FOOTING
AND MATCH B.O.
FOOTING ELEV
ABUT (E) FOOTING
AND MATCH B.O.
FOOTING ELEV
COLUMN ON CONC
PIER, PER COLUMN
SCHEDULE, TYP
C.J.
C.J.
C.J.
C.J.
C.J.
C.J.
C.J.
C.J.
C.J.
C.J.
C.J.
C.J.
C.J.
C.J.
C.J.
C.J.
C.J.
C.J.
C.J.
C.J.
C.J.
C.J.
C.J.
C.J.
C.J.
C.J.
C.J.
C.J.
C.J.
C.J.
C.J.
C.J.
C.J.
C.J.
C.J.
C.J.
C.J.
C.J.
C.J.
C.J.
C.J.
C.J.
C.J.
C.J.
C.J.
C.J.
C.J.
C.J.
C.J.
C.J.
C.J.
C.J.
C.J.
C.J.
C.J.
C.J.
C.J.
C.J.
C.J.
C.J.
C.J.
C.J.
C.J.
SG1
SG1
C.J
.
CONC FOOTING, PER
COLUMN SCHEDULE,
TYP
1'-0"
TYP
6"
TYP
6"
TYP
1'-0"
TY
P
2'-0"
TY
P
3'-6"
TY
P
6"
TYP
6"
TYP
1'-0"
TY
P
6"
TY
P
6"
TY
P
1'-0"
TYP
6"
TYP
6"
TYP
1'-0"
TY
P
6"
TY
P
6"
TY
P
C.J.
C.J.
C.J.
C.J.
ABUT (E) FOOTING
AND MATCH B.O.
FOOTING ELEV
T.O. WALL
ELEV = 40'-6"
T.O. WALL
ELEV = 40'-6"
T.O. WALL
ELEV = 45'-2"
1'-0"
TYP
T.O. WALL
ELEV = 45'-2"
T.O. WALL
ELEV = 45'-2"
1
S121 S502
2
S121 S502
3
S121 S502
6
S121 S505
7
S121 S505
TYP
OF 7
5'-5"
NO
TE
5
12'-0"
NO
TE
5
5'-10"
NO
TE
5
3'-4"
NO
TE
5
3'-4"
NO
TE
5
1'-10"
NO
TE
5
1'-11"
NO
TE
5
6'-4"
NO
TE
5
12'-9 1/4"
NOTE 5
6'-8 1/2"
NOTE 5
8
S121 S501
TYP
OF 19
3'-4"
NOTE 5
4'-1"
NOTE 5
33'-0"
6
S121 S505
1'-0"
TYP
2'-0"
TYP
3'-6"
TYP
7
S121 S501
T.O. WALL
ELEV = 45'-2"
7
S121 S501
7
S121 S501
7
S121 S501
7
S121 S501
4
S121 S505
TYP OF 17
4'ON
E EI
GHTH
INCH
= O
NE F
OOT
( 1/8"
= 1'
-0" )
08'
16'
04'
8'4'
04'
02'
6"0
02'
6"0
1'6"
6"ON
E QU
ATER
INCH
= O
NE F
OOT
( 1/4"
= 1'
-0" )
THRE
E EI
GHTH
S IN
CH =
ONE
FOO
T ( 3
/8" =
1'-0
" )ON
E HA
LF IN
CH =
ONE
FOO
T ( 1
/2" =
1'-0
" )TH
REE
QUAT
ERS
INCH
= O
NE F
OOT
( 3/4"
= 1'
-0" )
ONE
INCH
= O
NE F
OOT
( 1" =
1'-0
" )ON
E AN
D ON
E HA
LF IN
CHES
= O
NE F
OOT
( 1 1/
2" =
1'-0
" )TH
REE
INCH
ES =
ONE
FOO
T ( 3
" = 1'
-0" )
OKKS Studios, Inc.2 Wisconsin Circle / Suite 820Chevy Chase, MD 20815-7003Tel: (301) 718-0080Fax: (301) 718-9520www.okksstudios.com
Nobis Engineering, Inc.20410 Century Boulevard, Suite 230
Germantown, MD 20874Tel: (301) 528 2010
Woods Peacock Engineering Consultants5250 Cherokee Avenue, Suite 420
Alexandria, VA 22312-2052Tel: (703) 658-4400
Fax: (703) 658-4404
Henry Adams ConsultingEngineers, LLC600 Baltimore Avenue, 4th FloorBaltimore, MD 21204Tel: (410) 296-6500Fax: (410) 296-6501
The Protection Engineering Group2809 Boston Street, Suite 7Baltimore, MD 21224 USA
Tel: (443) 708-4096Fax:
SCHEMATIC DESIGN (30%) SUBMISSION09/11/15DESIGN DEVELOPMENT (60%) SUBMISSION11/23/15CONSTRUCTION DOCUMENTS (90% SUBMISSION)
03/17/16
TMP CAD
PERRY POINT, MD
WAREHOUSE RENOVATION& EXPANSION
03/17/16BID DOCUMENTS SUBMISSION
03/25/15
Professional Certification. I hereby certify that these documentswere prepared or approved by me, and that I am a duly licensedprofessional engineer under the laws of the State of Maryland,License No. 14484, Expiration Date: June 27, 2017.
1
S101 S121
PARTIAL PLAN - ADDITION FOUNDATION/SLAB
1/8" = 1'-0"
NOTES:
1. XX'-XX" DENOTES TOP OF FOOTING ELEVATION. BOTTOM OF FOOTING ELEVATION FOR FOOTINGS ADJACENT TO EXISTING BUILDING SHALL MATCH BOTTOM OF EXISTING FOUNDATIONS.
2. TOP OF SLAB-ON-GRADE ELEVATION = 37'-6"±. TOP OF SLAB-ON-GRADE ELEVATION SHALL MATCH ADJACENT EXISTING TOP OF SLAB-ON-GRADE ELEVATION.
3. SLAB-ON-GRADE MARKED 'SG1' SHALL BE A 6" CONCRETE SLAB PER 1/S503.
4. SEE SHEET S601 FOR COLUMN SCHEDULE AND CONCRETE PIER AND COLUMN FOOTING INFORMATION.
5. COORDINATE DOOR OPENING SIZES AND LOCATIONS WITH ARCHITECTURAL DRAWINGS.
6. SEE ARCHITECTURAL DRAWINGS FOR SIZES AND QUANTITY OF STAIR TREADS AND RISERS.
PARTIAL PLAN - ADDITIONFOUNDATION/SLAB
S121
GRAPHIC SCALE
1/8" = 1'-0"
0 4' 8' 16'
CAUTION: IF THIS DRAWING
IS A REDUCTION, GRAPHIC
SCALES MUST BE USED.
![Page 13: 14012 - VAMC BLDG 360 - CENTRAL elorenz - rlscg.comrlscg.com/site/wp-content/uploads/VA245-16-B-0095-010.pdf · 10.welding electrodes: per table 3.1 of aws d1.1 for the smaw process](https://reader034.vdocuments.us/reader034/viewer/2022052608/5add35567f8b9a213e8c8f07/html5/thumbnails/13.jpg)
21'-0"21'-0"21'-0"21'-0"21'-0"21'-0"21'-0"
27'-4"
28'-0"
28'-0"
27'-4"
24'-0"± 27'-3"
2'-0"
2'-0"
21'-0"±
9'-6"±
26'-10"
26'-6"
5'-0"
(E
) W
12x19
(E
) W
12x19
(E
) W
12x19
(E
) W
18x35
(E
) W
16x26
(E
) W
16x26
(E
) W
16x26
(E
) W
16x26
(E
) W
16x26
(E
) W
16x26
(E
) W
16x26 (14)
(E
) W
16x26 (14)
(E
) W
16x26 (14)
(E
) W
16x26 (14)
(E) W21x44 (38) (E) W27x84 (48)
(E
) W
16x26
(E) W24x55
(E) W16x31
(E) W18x35 (40)
EDGE OF ROOF
DECK, TYP
EDGE OF (E) ROOF
DECK, TYP
COLUMN, PER COLUMN
SCHEDULE, TYP OF 7
COLUMN, PER COLUMN
SCHEDULE, TYP OF 40
W18x76
W18x46
W16x50
W16x50W18x46
W16x50 (S
L)
W16x50 (S
L)
W16x31
W16x31 (S
L)
W16x50 (S
L)
W16x31 (S
L)
(2) L3x3x1/2 KNEE
BRACE, TYP OF 8,
SEE 2/S506
4 EQ SPACES = 16'-0"
1'-0"
4'-0"6 EQ SPACES = 27'-3"
16K
3 (S
L)
16K
3 (S
L)
16K
3 (S
L)
16K
3 (S
L)
18" JS
T
SP
1 (S
L)
16K
3 (S
L)
16K
3 (S
L)
16K
3 (S
L)
16K
3 (S
L)
16K
3 (S
L)
16K
3 (S
L)
16K
3
16" JS
T S
P2
16" JS
T S
P1
16K
3 (S
L)
4'-6" 4'-6"
16K
3 (S
L)
2" EXPANSION
JOINT
SLO
PE
SLO
PE
T.O. STEEL
ELEV = 48'-6"
T.O. STEEL
ELEV = 47'-11"
T.O. STEEL
ELEV = 48'-6"±
34k 23k 35k 13k
25k
25k
45k
67k
8k
8k
6k
6k
39k 28k
8k
8k
6k
6k
6k
7k
6k
6k
BRIDGING, TYP
18" JS
T
SP
2 (S
L)
18" JS
T
SP
3 (S
L)
18" JS
T
SP
4 (S
L)
18" JS
T
SP
1 (S
L)
18" JS
T
SP
2 (S
L)
18" JS
T
SP
3 (S
L)
18" JS
T
SP
4 (S
L)
16" JS
T S
P3
16" JS
T S
P4
6
S122 S507
7
S122 S507
8
S122 S507
6
S122 S507
1'-0"
1'-0"
10"
EDGE OF ROOF DECK
END OF JOIST EXTENSION
AHU, PER MEP DWGS,
NOTES 12, 13, & 14
16" JS
T
SP
5 (S
L)
16" JS
T
SP
5 (S
L)
16" JS
T
SP
5 (S
L)
NOTE 14
4'ON
E EI
GHTH
INCH
= O
NE F
OOT
( 1/8"
= 1'
-0" )
08'
16'
04'
8'4'
04'
02'
6"0
02'
6"0
1'6"
6"ON
E QU
ATER
INCH
= O
NE F
OOT
( 1/4"
= 1'
-0" )
THRE
E EI
GHTH
S IN
CH =
ONE
FOO
T ( 3
/8" =
1'-0
" )ON
E HA
LF IN
CH =
ONE
FOO
T ( 1
/2" =
1'-0
" )TH
REE
QUAT
ERS
INCH
= O
NE F
OOT
( 3/4"
= 1'
-0" )
ONE
INCH
= O
NE F
OOT
( 1" =
1'-0
" )ON
E AN
D ON
E HA
LF IN
CHES
= O
NE F
OOT
( 1 1/
2" =
1'-0
" )TH
REE
INCH
ES =
ONE
FOO
T ( 3
" = 1'
-0" )
OKKS Studios, Inc.2 Wisconsin Circle / Suite 820Chevy Chase, MD 20815-7003Tel: (301) 718-0080Fax: (301) 718-9520www.okksstudios.com
Nobis Engineering, Inc.20410 Century Boulevard, Suite 230
Germantown, MD 20874Tel: (301) 528 2010
Woods Peacock Engineering Consultants5250 Cherokee Avenue, Suite 420
Alexandria, VA 22312-2052Tel: (703) 658-4400
Fax: (703) 658-4404
Henry Adams ConsultingEngineers, LLC600 Baltimore Avenue, 4th FloorBaltimore, MD 21204Tel: (410) 296-6500Fax: (410) 296-6501
The Protection Engineering Group2809 Boston Street, Suite 7Baltimore, MD 21224 USA
Tel: (443) 708-4096Fax:
SCHEMATIC DESIGN (30%) SUBMISSION09/11/15DESIGN DEVELOPMENT (60%) SUBMISSION11/23/15CONSTRUCTION DOCUMENTS (90% SUBMISSION)
03/17/16
TMP CAD
PERRY POINT, MD
WAREHOUSE RENOVATION& EXPANSION
03/17/16BID DOCUMENTS SUBMISSION
03/25/15
Professional Certification. I hereby certify that these documentswere prepared or approved by me, and that I am a duly licensedprofessional engineer under the laws of the State of Maryland,License No. 14484, Expiration Date: June 27, 2017.
1
S102 S122
PARTIAL PLAN - ADDITION LOW ROOF FRAMING
1/8" = 1'-0"
NOTES:
1. EXISTING TOP OF STEEL BEAM ELEVATION = 48'-6"±, UNLESS NOTED OTHERWISE.
2. TOP OF STEEL ELEVATIONS SHALL BE AS NOTED. SLOPE STEEL FRAMING AS REQUIRED BETWEEN TOP OF STEEL ELEVATIONS NOTED.
3. WHERE STEEL FRAMING IS ADJACENT TO EXISTING STEEL FRAMING, TOP OF STEEL JOIST AND TOP OF STEEL BEAM ELEVATIONS SHALL MATCH TOP OF STEEL BEAM ELEVATION OF ADJACENT EXISTING STRUCTURE.
4. FOR BEAMS SUPPORTING STEEL JOISTS, TOP OF STEEL BEAM ELEVATION = -2 1/2" FROM TOP OF STEEL JOIST ELEVATION.
5. ROOF DECK MARKED 'D1' SHALL BE 1 1/2" - 20 GAGE WIDE RIB ROOF DECK.
6. SEE SHEET S601 FOR COLUMN SCHEDULE.
7. LOCATIONS OF BRIDGING, UPLIFT BRIDGING, AND CROSS BRIDGING IS SHOWN SCHEMATICALLY. JOIST MANUFACTURER SHALL DETERMINE FINAL LAYOUT AND INDICATE ON JOIST SHOP DRAWINGS.
8. COORDINATE WITH OTHER DISCIPLINES AND TRADES FOR LOCATIONS AND DIMENSIONS OF OPENINGS, RECESSES, SLEEVES, CONDUITS, AND PIPING. AT LOCATIONS WHERE A LOAD GREATER THAN 50 POUNDS IS
APPLIED TO THE TOP OR BOTTOM CHORD OF A JOIST, PROVIDE JOIST REINFORCING AS NECESSARY PER DETAIL 4/S507.
9. STEEL JOISTS DESIGNATED ON THE PLANS AS SP# SHALL BE DESIGNED FOR THE DEAD, SNOW, AND AHU LOADS SHOWN IN THE SPECIAL JOIST LOAD SCHEDULE, 1/S507. FOR SPECIAL JOISTS WITH A DEPTH
PRECEDING THE DESIGNATION, A JOIST MUST BE PROVIDED WITH THAT DEPTH.
10. VERTICAL REACTIONS SPECIFIED AT BEAM ENDS ARE NOTED #k, ARE FACTORED PER LRFD, IBC 2012, AND ARE IN UNITS OF KIPS. FOR BEAM ENDS WHERE REACTIONS ARE NOT PROVIDED, SEE STRUCTURAL NOTE U3.
11. SEE THE BEAM AXIAL DESIGN LOAD SCHEDULE, 3/S506, FOR BEAM AXIAL DESIGN FORCES FOR BEAMS ALONG BRACED FRAMES.
12. AHU BASIS OF DESIGN OPERATING WEIGHT = 3500 LB. IF ACTUAL WEIGHT IS GREATER, NOTIFY THE COTR IN WRITING FOR GUIDANCE PRIOR TO PROCEEDING.
13. BASIS OF DESIGN AHU CURBS WILL BE CAPABLE OF SUPPORTING THE AHU OPERATING WEIGHT BY SPANNING BETWEEN ROOF JOISTS. IF AHU CURBS ARE NOT CAPABLE OF SPANNING BETWEEN JOISTS, NOTIFY THE
COTR IN WRITING FOR GUIDANCE PRIOR TO PROCEEDING.
14. SEE 5/S507 FOR ADDITIONAL ROOF FRAMING AT ROOF OPENINGS AND BENEATH AHU CURBS. COORDINATE LOCATIONS OF FRAMING AROUND DUCT PENETRATIONS WITH UNIT SPECIFICATIONS, CURB
CONFIGURATIONS, AND THE MECHANICAL DRAWINGS.
PARTIAL PLAN - ADDITIONLOW ROOF FRAMING
S122
GRAPHIC SCALE
1/8" = 1'-0"
0 4' 8' 16'
CAUTION: IF THIS DRAWING
IS A REDUCTION, GRAPHIC
SCALES MUST BE USED.
![Page 14: 14012 - VAMC BLDG 360 - CENTRAL elorenz - rlscg.comrlscg.com/site/wp-content/uploads/VA245-16-B-0095-010.pdf · 10.welding electrodes: per table 3.1 of aws d1.1 for the smaw process](https://reader034.vdocuments.us/reader034/viewer/2022052608/5add35567f8b9a213e8c8f07/html5/thumbnails/14.jpg)
21'-0"21'-0"21'-0"21'-0"21'-0"21'-0"21'-0"
27'-4"
28'-0"
28'-0"
27'-4"
24'-0"± 27'-3"
2'-0"
2'-0"
21'-0"±
9'-6"±
26'-10"
26'-6"
5'-0"
4 EQ SPACES = 21'-0" 4 EQ SPACES = 21'-0" 4 EQ SPACES = 21'-0" 4 EQ SPACES = 21'-0" 4 EQ SPACES = 21'-0" 4 EQ SPACES = 21'-0" 4 EQ SPACES = 21'-0"
16K
4 (S
L)
16K
4 (S
L)
16K
4 (S
L)
16K
4 (S
L)
16K
4 (S
L)
16K
4 (S
L)
16K
4 (S
L)
16K
4 (S
L)
16K
4 (S
L)
16K
4 (S
L)
16K
4 (S
L)
16K
4 (S
L)
16K
4 (S
L)
16K
4 (S
L)
16K
4 (S
L)
16K
4 (S
L)
16K
4 (S
L)
16K
4 (S
L)
16K
4 (S
L)
16K
4 (S
L)
16K
4 (S
L)
16K
4 (S
L)
16K
4 (S
L)
16K
4 (S
L)
16K
4 (S
L)
16K
4 (S
L)
16K
4 (S
L)
16K
4 (S
L)
16K
4 (S
L)
16K
4 (S
L)
16K
4 (S
L)
16K
4 (S
L)
16K
4 (S
L)
16K
4 (S
L)
16K
4 (S
L)
16K
4 (S
L)
16K
4 (S
L)
16K
4 (S
L)
16K
4 (S
L)
16K
4 (S
L)
16K
4 (S
L)
16K
4 (S
L)
16K
4 (S
L)
16K
4 (S
L)
16K
4 (S
L)
16K
4 (S
L)
16K
4 (S
L)
16K
4 (S
L)
16K
4 (S
L)
16K
4 (S
L)
16K
4 (S
L)
16K
4 (S
L)
16K
4 (S
L)
16K
4 (S
L)
16K
4 (S
L)
16K
4 (S
L)
16K
4 (S
L)
16K
4 (S
L)
16K
4 (S
L)
16K
4 (S
L)
16K
4 (S
L)
16K
4 (S
L)
16K
4 (S
L)
16K
4 (S
L)
16K
4 (S
L)
16K
4 (S
L)
16K
4 (S
L)
16K
4 (S
L)
16K
4 (S
L)
16K
4 (S
L)
16K
4 (S
L)
16K
4 (S
L)
16K
4 (S
L)
16K
4 (S
L)
16K
4 (S
L)
16K
4 (S
L)
16K
4 (S
L)
16K
4 (S
L)
16K
4 (S
L)
16K
4 (S
L)
16K
4 (S
L)
16K
4 (S
L)
16K
4 (S
L)
16K
4 (S
L)
(E
) W
16x26
(E
) W
16x26
(E
) W
16x26
(E) W14x30(E) W14x30(E) W14x30(E) W14x30(E) W14x30(E) W14x30
(E) W16x26(E) W16x26(E) W16x26 (E) W16x26
EDGE OF ROOF
DECK, TYP
EDGE OF ROOF
BELOW
EDGE OF (E) ROOF
BELOW
EDGE OF (E) ROOF
DECK, TYP
W16x31
W16x50
W16x31
W16x50
W16x31
W16x50
W16x31
W16x50
W16x31
W16x50
W16x31
W16x50
W16x31
W16x50
W16x50W16x50 W16x50 W16x50 W16x50 W16x50 W16x50
W16x31W16x31 W16x31 W16x31 W16x31 W16x31 W16x31
W16x31 W16x31 W16x31 W16x31 W16x31 W16x31 W16x31
W18x76 (S
L)
W16x31 (S
L)
W18x76 (S
L)
W16x31(S
L)
W16x31 (S
L)
W18x76 (S
L)
W16x31 (S
L)
W18x76(S
L)
W16x31 (S
L)
W18x76 (S
L)
W16x31 (S
L)
W18x76 (S
L)
W16x31 (S
L)
W16x31 (S
L)
COLUMN, PER COLUMN
SCHEDULE TYP OF 40
2" E
XP
AN
SIO
N
JO
IN
T
(2) L3x3x3/8 KNEE
BRACE, TYP OF 48,
SEE 2/S506
T.O. STEEL
ELEV = 63'-11"
T.O. STEEL
ELEV = 63'-4"
T.O. STEEL
ELEV = 63'-11"
T.O. STEEL
ELEV = 63'-4"
T.O. STEEL
ELEV = 63'-11"±
SLO
PE
SLO
PE
8k8k 8k
8k 8k
8k 8k
8k 8k
8k 8k
8k 8k
8k 8k
8k 8k
8k 8k
8k 8k
8k 8k
8k 8k
8k 8k
8k 8k
12k
9k
8k
8k
8k
8k
9k
12k
6k
6k
6k
6k
6k
6k
6k
6k
22k
18k
15k
16k
16k
15k
18k
22k
6k
6k
6k
6k
6k
6k
6k
6k
6k
6k
6k
6k
6k
6k
6k
6k
22k
18k
15k
16k
16k
15k
18k
22k
6k
6k
6k
6k
6k
6k
6k
6k
12k
9k
8k
8k
8k
8k
9k
12k
33k 15k
15k 15k
33k 15k
15k 33k
15k 15k
15k 33k
25k 15k
15k 15k
25k 15k
36 36k
15k 15k
36k 36k
15k 25k
15k 15k
15k 25k
33k 15k
15k 15k
33k 15k
15k 33k
15k 15k
33k15k
BRIDGING, TYP
9
S123 S507
1'-0"
EDGE OF ROOF DECK
END OF JOIST EXTENSION
EDGE OF ROOF DECK
END OF JOIST EXTENSION
1'-0"
1'-0"1'-0"
SLO
PE
SLO
PE
W18x76 (S
L)
W16x31 (S
L)
W18x76 (S
L)
W18x76 (S
L)
W16x31 (S
L)
W18x76 (S
L)
W18x76 (S
L)
W16x31 (S
L)
W18x76 (S
L)
W16x31(S
L)
W18x76 (S
L)
W16x31 (S
L)
W18x76 (S
L)
W16x31(S
L)
W18x76 (S
L)
W16x31 (S
L)
W18x76 (S
L)
W16x31(S
L)
4'ON
E EI
GHTH
INCH
= O
NE F
OOT
( 1/8"
= 1'
-0" )
08'
16'
04'
8'4'
04'
02'
6"0
02'
6"0
1'6"
6"ON
E QU
ATER
INCH
= O
NE F
OOT
( 1/4"
= 1'
-0" )
THRE
E EI
GHTH
S IN
CH =
ONE
FOO
T ( 3
/8" =
1'-0
" )ON
E HA
LF IN
CH =
ONE
FOO
T ( 1
/2" =
1'-0
" )TH
REE
QUAT
ERS
INCH
= O
NE F
OOT
( 3/4"
= 1'
-0" )
ONE
INCH
= O
NE F
OOT
( 1" =
1'-0
" )ON
E AN
D ON
E HA
LF IN
CHES
= O
NE F
OOT
( 1 1/
2" =
1'-0
" )TH
REE
INCH
ES =
ONE
FOO
T ( 3
" = 1'
-0" )
OKKS Studios, Inc.2 Wisconsin Circle / Suite 820Chevy Chase, MD 20815-7003Tel: (301) 718-0080Fax: (301) 718-9520www.okksstudios.com
Nobis Engineering, Inc.20410 Century Boulevard, Suite 230
Germantown, MD 20874Tel: (301) 528 2010
Woods Peacock Engineering Consultants5250 Cherokee Avenue, Suite 420
Alexandria, VA 22312-2052Tel: (703) 658-4400
Fax: (703) 658-4404
Henry Adams ConsultingEngineers, LLC600 Baltimore Avenue, 4th FloorBaltimore, MD 21204Tel: (410) 296-6500Fax: (410) 296-6501
The Protection Engineering Group2809 Boston Street, Suite 7Baltimore, MD 21224 USA
Tel: (443) 708-4096Fax:
SCHEMATIC DESIGN (30%) SUBMISSION09/11/15DESIGN DEVELOPMENT (60%) SUBMISSION11/23/15CONSTRUCTION DOCUMENTS (90% SUBMISSION)
03/17/16
TMP CAD
PERRY POINT, MD
WAREHOUSE RENOVATION& EXPANSION
03/17/16BID DOCUMENTS SUBMISSION
03/25/15
Professional Certification. I hereby certify that these documentswere prepared or approved by me, and that I am a duly licensedprofessional engineer under the laws of the State of Maryland,License No. 14484, Expiration Date: June 27, 2017.
1
S103 S123
PARTIAL PLAN - ADDITION HIGH ROOF FRAMING
1/8" = 1'-0"
NOTES:
1. EXISTING TOP OF STEEL BEAM ELEVATION = 63'-11"±, UNLESS NOTED OTHERWISE.
2. TOP OF STEEL ELEVATIONS SHALL BE AS NOTED. SLOPE STEEL FRAMING AS REQUIRED BETWEEN TOP OF STEEL ELEVATIONS NOTED.
3. WHERE STEEL FRAMING IS ADJACENT TO EXISTING STEEL FRAMING, TOP OF STEEL JOIST AND TOP OF STEEL BEAM ELEVATIONS SHALL MATCH TOP OF STEEL BEAM ELEVATION OF ADJACENT
EXISTING STRUCTURE.
4. FOR BEAMS SUPPORTING STEEL JOISTS, TOP OF STEEL BEAM ELEVATION = -2 1/2" FROM TOP OF STEEL JOIST ELEVATION.
5. ROOF DECK MARKED 'D1' SHALL BE 1 1/2" - 20 GAGE WIDE RIB ROOF DECK.
6. SEE SHEET S601 FOR COLUMN SCHEDULE.
7. LOCATIONS OF BRIDGING, UPLIFT BRIDGING, AND CROSS BRIDGING IS SHOWN SCHEMATICALLY. JOIST MANUFACTURER SHALL DETERMINE FINAL LAYOUT AND INDICATE ON JOIST SHOP
DRAWINGS.
8. COORDINATE WITH OTHER DISCIPLINES AND TRADES FOR LOCATIONS AND DIMENSIONS OF OPENINGS, RECESSES, SLEEVES, CONDUITS, AND PIPING. AT LOCATIONS WHERE A LOAD GREATER
THAN 50 POUNDS IS APPLIED TO THE TOP OR BOTTOM CHORD OF A JOIST, PROVIDE JOIST REINFORCING AS NECESSARY PER DETAIL 4/S507.
9. VERTICAL REACTIONS SPECIFIED AT BEAM ENDS ARE NOTED #k, ARE FACTORED PER LRFD, IBC 2012, AND ARE IN UNITS OF KIPS. FOR BEAM ENDS WHERE REACTIONS ARE NOT PROVIDED, SEE
STRUCTURAL NOTE U3.
10. SEE THE BEAM AXIAL DESIGN LOAD SCHEDULE, 3/S506, FOR BEAM AXIAL DESIGN FORCES FOR BEAMS ALONG BRACED FRAMES.
PARTIAL PLAN - ADDITIONHIGH ROOF FRAMING
S123
GRAPHIC SCALE
1/8" = 1'-0"
0 4' 8' 16'
CAUTION: IF THIS DRAWING
IS A REDUCTION, GRAPHIC
SCALES MUST BE USED.
![Page 15: 14012 - VAMC BLDG 360 - CENTRAL elorenz - rlscg.comrlscg.com/site/wp-content/uploads/VA245-16-B-0095-010.pdf · 10.welding electrodes: per table 3.1 of aws d1.1 for the smaw process](https://reader034.vdocuments.us/reader034/viewer/2022052608/5add35567f8b9a213e8c8f07/html5/thumbnails/15.jpg)
4'ON
E EI
GHTH
INCH
= O
NE F
OOT
( 1/8"
= 1'
-0" )
08'
16'
04'
8'4'
04'
02'
6"0
02'
6"0
1'6"
6"ON
E QU
ATER
INCH
= O
NE F
OOT
( 1/4"
= 1'
-0" )
THRE
E EI
GHTH
S IN
CH =
ONE
FOO
T ( 3
/8" =
1'-0
" )ON
E HA
LF IN
CH =
ONE
FOO
T ( 1
/2" =
1'-0
" )TH
REE
QUAT
ERS
INCH
= O
NE F
OOT
( 3/4"
= 1'
-0" )
ONE
INCH
= O
NE F
OOT
( 1" =
1'-0
" )ON
E AN
D ON
E HA
LF IN
CHES
= O
NE F
OOT
( 1 1/
2" =
1'-0
" )TH
REE
INCH
ES =
ONE
FOO
T ( 3
" = 1'
-0" )
OKKS Studios, Inc.2 Wisconsin Circle / Suite 820Chevy Chase, MD 20815-7003Tel: (301) 718-0080Fax: (301) 718-9520www.okksstudios.com
Nobis Engineering, Inc.20410 Century Boulevard, Suite 230
Germantown, MD 20874Tel: (301) 528 2010
Woods Peacock Engineering Consultants5250 Cherokee Avenue, Suite 420
Alexandria, VA 22312-2052Tel: (703) 658-4400
Fax: (703) 658-4404
Henry Adams ConsultingEngineers, LLC600 Baltimore Avenue, 4th FloorBaltimore, MD 21204Tel: (410) 296-6500Fax: (410) 296-6501
The Protection Engineering Group2809 Boston Street, Suite 7Baltimore, MD 21224 USA
Tel: (443) 708-4096Fax:
SCHEMATIC DESIGN (30%) SUBMISSION09/11/15DESIGN DEVELOPMENT (60%) SUBMISSION11/23/15CONSTRUCTION DOCUMENTS (90% SUBMISSION)
03/17/16
TMP CAD
PERRY POINT, MD
WAREHOUSE RENOVATION& EXPANSION
03/17/16BID DOCUMENTS SUBMISSION
03/25/15
Professional Certification. I hereby certify that these documentswere prepared or approved by me, and that I am a duly licensedprofessional engineer under the laws of the State of Maryland,License No. 14484, Expiration Date: June 27, 2017.
PARTIAL FRAMING PLANS
S401
T.O. (E) SOG
ELEV = 33'-6"±
(E) 12" CONC
WALL
12" CONC WALL BELOW
21'-0"±
1
S401 S504
2
S401 S504
8" CMU WALL BELOW
8" CMU WALL BELOW
8" CMU WALL BELOW
(E) 12" CONC WALL BELOW
T.O. SLAB
ELEV = 37'-6"±
NOTE 1
(E) 8" CMU WALL
(E) CONC FOOTING,
TYP
(E) STEEL COLUMN,
TYP OF 4
NOTES:
1. T.O. SLAB SHALL MATCH TOP OF SLAB ELEVATION OF ADJACENT EXISTING STRUCTURE.
2. SLAB MARKED 'S1' SHALL BE A 6" CONCRETE SLAB. SEE SHEET S504 FOR REINFORCING.
1
S111 S401
RAISED SLAB PARTIAL FRAMING PLAN
SCALE: 1/4" = 1'-0"
GRAPHIC SCALE
1/4" = 1'-0"
0 2' 4' 8'
CAUTION: IF THIS DRAWING
IS A REDUCTION, GRAPHIC
SCALES MUST BE USED.
![Page 16: 14012 - VAMC BLDG 360 - CENTRAL elorenz - rlscg.comrlscg.com/site/wp-content/uploads/VA245-16-B-0095-010.pdf · 10.welding electrodes: per table 3.1 of aws d1.1 for the smaw process](https://reader034.vdocuments.us/reader034/viewer/2022052608/5add35567f8b9a213e8c8f07/html5/thumbnails/16.jpg)
4'ON
E EI
GHTH
INCH
= O
NE F
OOT
( 1/8"
= 1'
-0" )
08'
16'
04'
8'4'
04'
02'
6"0
02'
6"0
1'6"
6"ON
E QU
ATER
INCH
= O
NE F
OOT
( 1/4"
= 1'
-0" )
THRE
E EI
GHTH
S IN
CH =
ONE
FOO
T ( 3
/8" =
1'-0
" )ON
E HA
LF IN
CH =
ONE
FOO
T ( 1
/2" =
1'-0
" )TH
REE
QUAT
ERS
INCH
= O
NE F
OOT
( 3/4"
= 1'
-0" )
ONE
INCH
= O
NE F
OOT
( 1" =
1'-0
" )ON
E AN
D ON
E HA
LF IN
CHES
= O
NE F
OOT
( 1 1/
2" =
1'-0
" )TH
REE
INCH
ES =
ONE
FOO
T ( 3
" = 1'
-0" )
OKKS Studios, Inc.2 Wisconsin Circle / Suite 820Chevy Chase, MD 20815-7003Tel: (301) 718-0080Fax: (301) 718-9520www.okksstudios.com
Nobis Engineering, Inc.20410 Century Boulevard, Suite 230
Germantown, MD 20874Tel: (301) 528 2010
Woods Peacock Engineering Consultants5250 Cherokee Avenue, Suite 420
Alexandria, VA 22312-2052Tel: (703) 658-4400
Fax: (703) 658-4404
Henry Adams ConsultingEngineers, LLC600 Baltimore Avenue, 4th FloorBaltimore, MD 21204Tel: (410) 296-6500Fax: (410) 296-6501
The Protection Engineering Group2809 Boston Street, Suite 7Baltimore, MD 21224 USA
Tel: (443) 708-4096Fax:
SCHEMATIC DESIGN (30%) SUBMISSION09/11/15DESIGN DEVELOPMENT (60%) SUBMISSION11/23/15CONSTRUCTION DOCUMENTS (90% SUBMISSION)
03/17/16
TMP CAD
PERRY POINT, MD
WAREHOUSE RENOVATION& EXPANSION
03/17/16BID DOCUMENTS SUBMISSION
03/25/15
Professional Certification. I hereby certify that these documentswere prepared or approved by me, and that I am a duly licensedprofessional engineer under the laws of the State of Maryland,License No. 14484, Expiration Date: June 27, 2017.
SECTIONS AND DETAILS
S501
3"
CLR
2"
CLR
PER COLUMN SCHEDULE
DOWELS, WITH STANDARD
HOOK, TO MATCH
PIER VERTICAL
REINFORCING
1" NON-SHRINK GROUT
SEE PLAN/SCHEDULE FOR
PIER SIZE AND REINFORCING
C
L
COLUMN, PER SCHEDULE
REINFORCING, PER
COLUMN SCHEDULE
NOTE:
1. SEE DETAIL 6/S503 FOR SLAB ISOLATION JOINT PLAN.
1
4
" ISOLATION JOINT
MATERIAL, PER SPECS
3"
CLR
BASE PLATE AND ANCHOR
BOLTS, PER COLUMN SCHEDULE
8
S501 S501
TYPICAL INTERIOR COLUMN FOOTING
NOT TO SCALE
1
S501 S506
FTG WIDTH
SEE PLAN
WALL FOOTING
CORNER DETAIL
LONGITUDINAL REINF
TRANSVERSE REINF
LAP SPLICE
TYP
WALL FOOTING
INTERSECTION DETAIL
WALL FOOTING,
PER PLAN
WALL, PER
PLAN
LONGITUDINAL REINF
3"
CLR
1
S501 S501
TYPICAL WALL FOOTING REINFORCEMENT DETAIL
NOT TO SCALE
"2D", 2'-0" MIN
TRANSVERSE REINF
LONGITUDINAL REINF
WITH STANDARD
HOOK
6" MIN
FTG THICKNESS
(1'-0" MIN)
PROFILE
F.S. F.S.
PLAN DETAIL
WALL FOOTING,
PER PLAN
WALL,
PER PLAN
2"
CLR
1'-0"
MIN
NOTE:
1. FOOTING STEP LOCATIONS AS SHOWN ON FOUNDATION PLAN ARE FOR BIDDING PURPOSES ONLY. FINAL STEP LOCATION IS
TO BE DETERMINED IN FIELD BY CONTRACTOR USING THE FOUNDATION PLAN, SPECIFICATIONS AND FIELD CONDITIONS.
2
S501 S501
TYPICAL STEPPED FOOTING DETAIL
NOT TO SCALE
PIPE SLEEVE,
NOTE 3
NOTE:
1. SEE PLUMBING, MECHANICAL, OR ELECTRICAL DRAWINGS FOR UTILITY LOCATIONS AND
ELEVATIONS.
2. COORDINATE SLOPE WITH OSHA REGULATIONS AND GEOTECH REPORT.
3. THE INNER DIAMETER OF THE PIPE SLEEVE SHALL BE A MINIMUM OF 2" GREATER THAN THE OUTER
DIAMETER OF THE UTILITY, ALL AROUND.
WALL FOOTING,
PER PLAN
FOR H ≤ 4'
CONCRETE FOOTING, SEE
TYPICAL STEPPED WALL
FOOTING DETAIL
1'-0"
MIN
WALL BEYOND, PER
PLAN
NOTE 2
3
S501 S501
TYPICAL SITE UTILITY LESS THAN 4' DEEP
NOT TO SCALE
LEAN CONCRETE
FILL OR #57 STONE
PIPE SLEEVE, NOTE 3
NOTE:
1. SEE PLUMBING, MECHANICAL, OR ELECTRICAL DRAWINGS FOR UTILITY LOCATIONS AND
ELEVATIONS.
2. COORDINATE SLOPE WITH OSHA REGULATIONS AND GEOTECH REPORT.
3. THE INNER DIAMETER OF THE PIPE SLEEVE SHALL BE A MINIMUM OF 2" GREATER THAN THE
OUTER DIAMETER OF THE UTILITY, ALL AROUND.
WALL FOOTING, PER
PLAN
FOR H > 4'
1'-0" 1'-0"
WALL BEYOND, PER
PLAN
4
S501 S501
TYPICAL SITE UTILITY GREATER THAN 4' DEEP
NOT TO SCALE
WALL, PER PLAN
(2) ADDED #4 X EXCAVATION
WIDTH PLUS 10'-0" LOCATE 2"
CLEAR FROM TOP OF FOOTING
AND CENTERED ON THE
EXCAVATION
CONCRETE FOOTING,
PER PLAN
PIPE SLEEVE
UTILITY PIPE
LEAN CONCRETE FILL OR #57 STONE
NOTE:
1. LINE PIPE SLEEVE WITH 1" MIN COMPRESSIBLE MATERIAL
5
S501 S501
TYPICAL SECTION
AT UTILITY BELOW FOOTING WALL
NOT TO SCALE
WATERPROOFING AND
DRAINAGE BOARD PER
ARCH DWGS
SUBDRAINAGE
PIPE, NOTE 3
GRANULAR FILL, PER
STRUCTURAL NOTE Q3
SLAB-ON-GRADE,
PER PLAN
VAPOR BARRIER
CONCRETE WALL,
PER PLAN
PERMEABLE
GEOTEXTILE
FABRIC,
NOTE 2
FILTER MATERIAL,
NOTE 1
NOTES:
1. FILTER MATERIAL SHALL CONFORM TO THE GRADATION REQUIREMENTS FOR AASHTO
M-43, NO. 7.
2. PERMEABLE FABRIC SHALL HAVE EQUIVALENT OPENING SIZE NOT LARGER THAN NO.
70 U.S. STANDARD SIEVE SIZE.
3. SUBDRAINAGE PIPING SHALL BE 4" DIAMETER SLOTTED CORRUGATED POLYETHYLENE
(PE) TUBING ACCORDING TO ASTM F-405 WITH MAXIMUM
1
8
" SLOT WIDTH. PIPE SHALL
EXTEND TO A STORM SEWER OR SUITABLE GRAVITY OUTLET.
BACKFILL
CONCRETE FOUNDATION,
PER PLAN
6
S501 S501
FOUNDATION DRAIN DETAIL
NOT TO SCALE
#4@12"O.C.,
E.W., E.F.
#4@12"O.C., T&B
(3)#4 CONT, T&B
EQ EQ
3" CLR
TYP
2'-0"
1'-0"
7
S121 S501
TYPICAL WALL SECTION
SCALE: 3/4" = 1'-0"
SLAB-ON-GRADE,
PER PLAN
DOWELS TO MATCH
WALL REINF
1/4" ISOLATION JOINT
MATERIAL, PER SPECS
METAL WALL PANEL,
PER ARCH DWGS
GRAPHIC SCALE
3/4" = 1'-0"
0 2' 3'1'
CAUTION: IF THIS DRAWING
IS A REDUCTION, GRAPHIC
SCALES MUST BE USED.
![Page 17: 14012 - VAMC BLDG 360 - CENTRAL elorenz - rlscg.comrlscg.com/site/wp-content/uploads/VA245-16-B-0095-010.pdf · 10.welding electrodes: per table 3.1 of aws d1.1 for the smaw process](https://reader034.vdocuments.us/reader034/viewer/2022052608/5add35567f8b9a213e8c8f07/html5/thumbnails/17.jpg)
4'ON
E EI
GHTH
INCH
= O
NE F
OOT
( 1/8"
= 1'
-0" )
08'
16'
04'
8'4'
04'
02'
6"0
02'
6"0
1'6"
6"ON
E QU
ATER
INCH
= O
NE F
OOT
( 1/4"
= 1'
-0" )
THRE
E EI
GHTH
S IN
CH =
ONE
FOO
T ( 3
/8" =
1'-0
" )ON
E HA
LF IN
CH =
ONE
FOO
T ( 1
/2" =
1'-0
" )TH
REE
QUAT
ERS
INCH
= O
NE F
OOT
( 3/4"
= 1'
-0" )
ONE
INCH
= O
NE F
OOT
( 1" =
1'-0
" )ON
E AN
D ON
E HA
LF IN
CHES
= O
NE F
OOT
( 1 1/
2" =
1'-0
" )TH
REE
INCH
ES =
ONE
FOO
T ( 3
" = 1'
-0" )
OKKS Studios, Inc.2 Wisconsin Circle / Suite 820Chevy Chase, MD 20815-7003Tel: (301) 718-0080Fax: (301) 718-9520www.okksstudios.com
Nobis Engineering, Inc.20410 Century Boulevard, Suite 230
Germantown, MD 20874Tel: (301) 528 2010
Woods Peacock Engineering Consultants5250 Cherokee Avenue, Suite 420
Alexandria, VA 22312-2052Tel: (703) 658-4400
Fax: (703) 658-4404
Henry Adams ConsultingEngineers, LLC600 Baltimore Avenue, 4th FloorBaltimore, MD 21204Tel: (410) 296-6500Fax: (410) 296-6501
The Protection Engineering Group2809 Boston Street, Suite 7Baltimore, MD 21224 USA
Tel: (443) 708-4096Fax:
SCHEMATIC DESIGN (30%) SUBMISSION09/11/15DESIGN DEVELOPMENT (60%) SUBMISSION11/23/15CONSTRUCTION DOCUMENTS (90% SUBMISSION)
03/17/16
TMP CAD
PERRY POINT, MD
WAREHOUSE RENOVATION& EXPANSION
03/17/16BID DOCUMENTS SUBMISSION
03/25/15
Professional Certification. I hereby certify that these documentswere prepared or approved by me, and that I am a duly licensedprofessional engineer under the laws of the State of Maryland,License No. 14484, Expiration Date: June 27, 2017.
SECTIONS AND DETAILS
S502
1
S121 S502
COMBINED COLUMN FOOTING DETAIL
SCALE: 3/4" = 1'-0"
2'-0"2'-0" 2'-6"
6'-6"
(6) #6 BOTTOM
BARS, E.W.
CONC PIER, TYP OF 2
CONC WALL, TYP
3" CLR
TYP
NOTES:
1. SEE COLUMN SCHEDULE ON SHEET S601 FOR SIZES OF CONCRETE PIERS.
TRANSVERSE WALL
FOOTING REINF, PER
7/S501, TYP
LONGITUDINAL WALL FOOTING
REINF, PER 7/S501, TYP.
CONTINUE REINF THROUGH
COMBINED FOOTING.
3
S121 S502
COMBINED COLUMN FOOTING DETAIL
SCALE: 3/4" = 1'-0"
2'-0"2'-0" 2'-6"
6'-6"
(5) #6 BOTTOM
BARS, E.W.
CONC PIER, TYP OF 2
CONC WALL, TYP
3" CLR
TYP
NOTES:
1. SEE COLUMN SCHEDULE ON SHEET S601 FOR SIZES OF CONCRETE PIERS.
TRANSVERSE WALL
FOOTING REINF, PER
7/S501, TYP
LONGITUDINAL WALL FOOTING
REINF, PER 7/S501, TYP.
CONTINUE REINF THROUGH
COMBINED FOOTING.
2
S121 S502
COMBINED COLUMN FOOTING DETAIL
SCALE: 3/4" = 1'-0"
2'-0"2'-6" 3'-6"
8'-0"
(9) #6 BOTTOM
BARS, E.W.
CONC PIER, TYP OF 2
CONC WALL, TYP
3" CLR
TYP
NOTES:
1. SEE COLUMN SCHEDULE ON SHEET S601 FOR SIZES OF CONCRETE PIERS.
TRANSVERSE WALL
FOOTING REINF, PER
7/S501, TYP
LONGITUDINAL WALL FOOTING
REINF, PER 7/S501, TYP.
CONTINUE REINF THROUGH
COMBINED FOOTING.
GRAPHIC SCALE
3/4" = 1'-0"
0 2' 3'1'
CAUTION: IF THIS DRAWING
IS A REDUCTION, GRAPHIC
SCALES MUST BE USED.
![Page 18: 14012 - VAMC BLDG 360 - CENTRAL elorenz - rlscg.comrlscg.com/site/wp-content/uploads/VA245-16-B-0095-010.pdf · 10.welding electrodes: per table 3.1 of aws d1.1 for the smaw process](https://reader034.vdocuments.us/reader034/viewer/2022052608/5add35567f8b9a213e8c8f07/html5/thumbnails/18.jpg)
4'ON
E EI
GHTH
INCH
= O
NE F
OOT
( 1/8"
= 1'
-0" )
08'
16'
04'
8'4'
04'
02'
6"0
02'
6"0
1'6"
6"ON
E QU
ATER
INCH
= O
NE F
OOT
( 1/4"
= 1'
-0" )
THRE
E EI
GHTH
S IN
CH =
ONE
FOO
T ( 3
/8" =
1'-0
" )ON
E HA
LF IN
CH =
ONE
FOO
T ( 1
/2" =
1'-0
" )TH
REE
QUAT
ERS
INCH
= O
NE F
OOT
( 3/4"
= 1'
-0" )
ONE
INCH
= O
NE F
OOT
( 1" =
1'-0
" )ON
E AN
D ON
E HA
LF IN
CHES
= O
NE F
OOT
( 1 1/
2" =
1'-0
" )TH
REE
INCH
ES =
ONE
FOO
T ( 3
" = 1'
-0" )
OKKS Studios, Inc.2 Wisconsin Circle / Suite 820Chevy Chase, MD 20815-7003Tel: (301) 718-0080Fax: (301) 718-9520www.okksstudios.com
Nobis Engineering, Inc.20410 Century Boulevard, Suite 230
Germantown, MD 20874Tel: (301) 528 2010
Woods Peacock Engineering Consultants5250 Cherokee Avenue, Suite 420
Alexandria, VA 22312-2052Tel: (703) 658-4400
Fax: (703) 658-4404
Henry Adams ConsultingEngineers, LLC600 Baltimore Avenue, 4th FloorBaltimore, MD 21204Tel: (410) 296-6500Fax: (410) 296-6501
The Protection Engineering Group2809 Boston Street, Suite 7Baltimore, MD 21224 USA
Tel: (443) 708-4096Fax:
SCHEMATIC DESIGN (30%) SUBMISSION09/11/15DESIGN DEVELOPMENT (60%) SUBMISSION11/23/15CONSTRUCTION DOCUMENTS (90% SUBMISSION)
03/17/16
TMP CAD
PERRY POINT, MD
WAREHOUSE RENOVATION& EXPANSION
03/17/16BID DOCUMENTS SUBMISSION
03/25/15
Professional Certification. I hereby certify that these documentswere prepared or approved by me, and that I am a duly licensedprofessional engineer under the laws of the State of Maryland,License No. 14484, Expiration Date: June 27, 2017.
SECTIONS AND DETAILS
S503
10
S503 S503
PEDESTRIAN BOLLARD DETAIL
NOT TO SCALE
NOTES:
1. PROVIDE DECORATIVE BOLLARD COVER PER
ARCHITECTURAL DRAWINGS.
2'-0"Ø
PIPE 6 STD., CONCRETE
FILLED
(E) 6"± CONC SOG
CONCRETE FOUNDATION
REINFORCED W/ (6) #5 VERT
AND 3# TIES @ 12" O.C.
SLAB-ON-GRADE
SECTIONSLAB MARK REINFORCING DESCRIPTION
4" CONCRETE SLAB-ON-GRADE,
REINFORCED AS INDICATED, OVER 4"
GRANULAR FILL
#4 @ 12"
O.C., E.W.
SG1
VAPOR BARRIER
1
S503 S503
SLAB-ON-GRADE SECTION
NOT TO SCALE
2
S503 S503
SLAB-ON-GRADE CONTRACTION/CONTROL
JOINT DETAIL
NOT TO SCALE
3"
CLR
3"
CLR
NOTES:
1. SEE SLAB-ON-GRADE SECTION 1/S503 FOR SLAB
REINFORCING AND INFORMATION NOT SHOWN.
SAW CUT JOINT, SEE
DETAIL 4/S503
VAPOR BARRIER
INTERRUPT BARS AT
JOINT LOCATIONS
SLAB-ON-GRADE,
PER PLAN
3
S503 S503
SLAB-ON-GRADE DOWELED
CONSTRUCTION JOINT DETAIL
NOT TO SCALE
3"
MAX
3"
MAX
VAPOR BARRIER
NOTE:
1. SEE SLAB-ON-GRADE SECTION 1/S503 FOR SLAB
REINFORCING AND INFORMATION NOT SHOWN.
INTERRUPT BARS AT
JOINT LOCATIONS
DOWELS, PER
SLAB-ON-GRADE DOWEL
SCHEDULE, 5/S503
SLAB-ON-GRADE,
PER PLAN
4
S503 S503
SAW CUT JOINT DETAIL
NOT TO SCALE
1
8
" MAX FOR SEMI-RIGID JOINT SEALANT
1
4
" FOR ELASTOMERIC JOINT SEALANT
JOINT SEALER AND
BACKER ROD,
PER SPECIFICATIONS
NOTE:
1. SAW CUT SHALL BE MADE WITH AN ULTRA EARLY ENTRY SAW AND CUT
WITHIN 2 HOURS AFTER FINISHING AND PRIOR TO FINAL SET.
7
S503 S503
EDGE OF SLAB ISOLATION JOINT DETAIL
NOT TO SCALE
CONCRETE WALL,
PER PLAN
1
4
" ISOLATION JOINT
MATERIAL, PER SPECS
#4 CONT W/ CORNER DOWELS
#4 DOWELS AT 12" O.C.
2'-0"
SLAB-ON-GRADE,
PER PLAN
FINISHED GRADE
OR PAVEMENT,
PER CIVIL DWGS
#4 @ 12" O.C.,
E.W., E.F.
EQ
SLAB-ON-GRADE,
PER PLAN
CONCRETE FOOTING,
PER PLAN
#4 VERTICAL DOWEL,
W/STANDARD HOOK,
@ 12" O.C., TYP OF 2
PER PLAN
AT THRESHOLD, ADD #4 BARS
@ 12" O.C., 3'-0" LONG,
CENTERED IN DOOR OPENING
8
S503 S503
TYPICAL SECTION AT EDGE OF SLAB
NOT TO SCALE
9
S503 S503
TYPICAL HOUSEKEEPING PAD
NOT TO SCALE
#4 @ 12" O.C.
NOTE 2 NOTE 2
SLAB-ON-GRADE,
PER PLAN
#4 DOWELS @
12" O.C.
DRILL AND EPOXY
#4 DOWELS INTO
SLAB AT 12" O.C., 4"
EMBEDMENT
ROUGHEN SURFACE
AND APPLY EPOXY
BONDING AGENT
NOTES:
1. COORDINATE HOUSEKEEPING PAD SIZE AND LOCATION WITH APPROVED MECHANICAL
SHOP DRAWINGS.
2. PROVIDE A MINIMUM 6" CLEAR DISTANCE BETWEEN EQUIPMENT AND EDGE OF CURB.
MEP EQUIPMENT
NOTE 1
6
S503 S503
TYPICAL ISOLATION JOINT AT COLUMN
NOT TO SCALE
90°
ISOLATION JOINT,
TYP
CONTROL JOINT
PER PLAN, TYP
INTERIOR COLUMN
EXTERIOR
COLUMN
ISOLATION JOINT,
TYP
5
S503 S503
SLAB-ON-GRADE DOWEL SCHEDULE
NOT TO SCALE
DOWEL SIZE AND SPACING FOR
ROUND, SQUARE, AND
RECTANGULAR DOWELS
DOWEL DIMENSIONS AND SPACING
SLAB
DEPTH
5" TO 6"
ROUND SQUARE RECTANGULAR
3
4
" x 14"
@ 12" O.C.
3
4
" x 14"
@ 14" O.C.
3
8
" x 2" x 12"
@ 19" O.C.
7" TO 8"
1" x 16"
@ 12" O.C.
1
2
" x 2
1
2
" x 12"
@ 18" O.C.
1" x 16"
@ 14" O.C.
DOWEL SIZE AND SPACING FOR
DIAMOND-SHAPED LOAD PLATES
DIAMOND LOAD PLATE
DIMENSIONS AND SPACING
SLAB
DEPTH
5" TO 6"
1
4
" x 4
1
2
" x 4
1
2
" @ 18" O.C.
7" TO 8"
3
8
" x 4
1
2
" x 4
1
2
" @ 18" O.C.
NOTES:
1. LIGHTLY GREASE ONE END OF DOWEL PROVIDE COMPRESSIBLE MATERIAL ON VERTICAL FACES OF SQUARE AND
RECTANGULAR BARS.
2. DO NOT LOCATE GREASED DOWELS, DOWELS WRAPPED IN COMPRESSIBLE MATERIAL, OR DIAMOND PLATES
WITHIN 12" OF SLAB JOINT INTERSECTION.
3. DOWELS AND PLATES SHALL BE EITHER ASTM A615 OR ASTM A36 STEEL.
![Page 19: 14012 - VAMC BLDG 360 - CENTRAL elorenz - rlscg.comrlscg.com/site/wp-content/uploads/VA245-16-B-0095-010.pdf · 10.welding electrodes: per table 3.1 of aws d1.1 for the smaw process](https://reader034.vdocuments.us/reader034/viewer/2022052608/5add35567f8b9a213e8c8f07/html5/thumbnails/19.jpg)
4'ON
E EI
GHTH
INCH
= O
NE F
OOT
( 1/8"
= 1'
-0" )
08'
16'
04'
8'4'
04'
02'
6"0
02'
6"0
1'6"
6"ON
E QU
ATER
INCH
= O
NE F
OOT
( 1/4"
= 1'
-0" )
THRE
E EI
GHTH
S IN
CH =
ONE
FOO
T ( 3
/8" =
1'-0
" )ON
E HA
LF IN
CH =
ONE
FOO
T ( 1
/2" =
1'-0
" )TH
REE
QUAT
ERS
INCH
= O
NE F
OOT
( 3/4"
= 1'
-0" )
ONE
INCH
= O
NE F
OOT
( 1" =
1'-0
" )ON
E AN
D ON
E HA
LF IN
CHES
= O
NE F
OOT
( 1 1/
2" =
1'-0
" )TH
REE
INCH
ES =
ONE
FOO
T ( 3
" = 1'
-0" )
OKKS Studios, Inc.2 Wisconsin Circle / Suite 820Chevy Chase, MD 20815-7003Tel: (301) 718-0080Fax: (301) 718-9520www.okksstudios.com
Nobis Engineering, Inc.20410 Century Boulevard, Suite 230
Germantown, MD 20874Tel: (301) 528 2010
Woods Peacock Engineering Consultants5250 Cherokee Avenue, Suite 420
Alexandria, VA 22312-2052Tel: (703) 658-4400
Fax: (703) 658-4404
Henry Adams ConsultingEngineers, LLC600 Baltimore Avenue, 4th FloorBaltimore, MD 21204Tel: (410) 296-6500Fax: (410) 296-6501
The Protection Engineering Group2809 Boston Street, Suite 7Baltimore, MD 21224 USA
Tel: (443) 708-4096Fax:
SCHEMATIC DESIGN (30%) SUBMISSION09/11/15DESIGN DEVELOPMENT (60%) SUBMISSION11/23/15CONSTRUCTION DOCUMENTS (90% SUBMISSION)
03/17/16
TMP CAD
PERRY POINT, MD
WAREHOUSE RENOVATION& EXPANSION
03/17/16BID DOCUMENTS SUBMISSION
03/25/15
Professional Certification. I hereby certify that these documentswere prepared or approved by me, and that I am a duly licensedprofessional engineer under the laws of the State of Maryland,License No. 14484, Expiration Date: June 27, 2017.
SECTIONS AND DETAILS
S504
20'-4"
(E) 8" CMU WALL
CONT L3-1/2x3-1/2x1/4 W/ 1/2"Ø
ADHESIVE ANCHORS @ 18"
O.C., EACH SIDE OF SLAB
2
S401 S504
RAISED SLAB SECTION
SCALE: 3/8" = 1'-0"
NOTES:
1. T.O. SLAB SHALL MATCH TOP OF SLAB ELEVATION OF ADJACENT EXISTING STRUCTURE.
T.O. SLAB
ELEV = 37'-6"±
NOTE 1
T.O. (E) SOG
ELEV = 33'-6"±
1
S401 S504
RAISED SLAB SECTION
SCALE: 3/8" = 1'-0"
20'-4"±
DEMOLISH TOP 6" OF (E)
CONC WALL TO ALLOW
CONC SLAB TO SIT ON TOP
OF WALL
#4 @ 12" O.C., E.W.
#4 @ 12" O.C., E.W.
4'-11"±4'-11" 5'-3"5'-3"
T.O. SLAB
ELEV = 37'-6"±
NOTE 1
T.O. (E) SOG
ELEV = 33'-6"±
NOTES:
1. T.O. SLAB SHALL MATCH TOP OF SLAB ELEVATION OF ADJACENT EXISTING STRUCTURE.
2. DOWEL VERTICAL WALL REINFORCING AND DOWELS INTO EXISTING CONCRETE WALL WITH ADHESIVE OR GROUT.
C
L
WALLC
L
WALLC
L
WALL
1'-0"
1 1/2" CLR
TYP
(E) 12" CONC WALL
#4 DOWELS @ 12" O.C.
3'-6"
3'-9"
#4 DOWELS @ 12" O.C.
3'-6"
9"
GRAPHIC SCALE
0 4' 6'
3/8" = 1'-0"
2'
CAUTION: IF THIS DRAWING
IS A REDUCTION, GRAPHIC
SCALES MUST BE USED.
3
S504 S504
TYPICAL MASONRY WALL
BOND ANGLE PLAN OR DETAIL
NOT TO SCALE
MASONRY INFILL,
PER PLAN
(E) MASONRY
WALL
L4x3x1/4" CONT WITH 3/4"Ø
MASONRY ADHESIVE
ANCHORS AT 24" O.C.
EMBEDDED 4 1/4" INTO SOLID
MASONRY ONLY, NOTE 2
NOTES
1. THIS DETAIL APPLIES AT ALL WALL INFILL AND ALL CMU
WALLS THAT ABUT EXISTING, AND AT EACH SIDE (TOP,
SIDES, AND BOTTOM) OF PENETRATION TO BE INFILLED.
2. WHERE EXISTING STEEL LINTELS ARE ENCOUNTERED AT
TOP OF PENETRATION, WELD ANGLE TO LINTEL WITH 3/16"
FILLET WELDS, 2" LONG @ 12" O.C., BOTH SIDES OF ANGLE.
4
S111 S504
ROLL-UP DOOR LINTEL SECTION
NOT TO SCALE
NOTES:
1. PROVIDE BEARING PLATE WIDTH TO MATCH WALL
THICKNESS.
2. VERTICAL PLATES SHALL BE 3/16" PLATES AT 16" ON
CENTER, MAXIMUM.
3. HUNG PLATE SHALL BE CONTINUOUS 3/8" PLATES WITH
WIDTHS = WALL WIDTH - 1/2".
4. SEE DETAIL 5/S504 FOR MASONRY LINTEL BEARING
DETAIL.
LINTEL, PER PLAN
SOLID MASONRY
INFILL
VERTICAL ⅊,NOTE 2
3/8" BEARING
⅊, NOTE 1
(E) MASONRY WALL,
PER PLAN
HUNG ⅊, NOTE 3
8" BRG,
MIN
2'-8"
NOTE 1
SOLID MASONRY
INFILL
DOOR OR WALL
OPENING, PER PLAN
VERTICAL AND HUNG
⅊, PER 4/S504
8"x6"x1/2"
BEARING ⅊
LINTEL, PER PLAN
(2) L2x2x1/4 x 0'-4"
LONG MASONRY
WEB ANGLES
NOTES:
1. IF WALL DIMENSIONS DO NOT ALLOW 2'-8" GROUT
CONDITION, GROUT SOLID VERTICALLY TO FLOOR LEVEL.
GROUT MASONRY
CELLS SOLID
(E) MASONRY WALL,
PER PLAN
3 SIDES
5
S504 S504
MASONRY LINTEL BEARING DETAIL
NOT TO SCALE
X X XX X X
6
S111 S504
RECESSED FLOOR SCALE SLAB SECTION
SCALE: 1" = 1'-0"
NOTES:
1. SAW CUT AND REMOVE PORTION OF EXISTING CONCRETE SLAB-ON-GRADE.
2. COORDINATE DIMENSIONS WITH FLOOR SCALE MANUFACTURER.
5'-0 1/2"
NOTE 2
6" 4'-0 1/2" CLR
BETWEEN ANGLES, NOTE 2
6"
(E) CONC SLAB-ON-GRADE,
NOTE 1
T.O. SLAB
ELEV = 37'-6"±
#4 U-SHAPED BARS
@ 12" O.C., E.W.
#4 CONT AROUND PERIMETER,
W/ CORNER BARS
ANGLE AND HEADED
STUD PER FLOOR SCALE
MANUFACTURER, TYP
#4 DOWELS @ 12" O.C.
DOWEL INTO (E) SLAB W/
ADHESIVE OR GROUT, TYP
4" 6"
8
S111 S504
(E) TRENCH DRAIN INFILL SECTION
SCALE: 1" = 1'-0"
NOTES:
1. PROVIDE CONTROL JOINTS PER 2/S503 TO MATCH EXISTING SLAB-ON-GRADE CONTROL JOINT LOCATIONS.
1'-6"±
4"±
1'-6"±
T.O. SLAB
ELEV = 37'-6"±
1'-0"±1'-0"± 2'-0"±
(E) CONC TRENCH
DRAIN STRUCTURE
CONC TRENCH INFILL W/
(6)#4 CONT, TYP OF 2
X X X
7
S111 S504
(E) CURB AND SLAB DEMO AND INFILL SECTION
SCALE: 1" = 1'-0"
NOTES:
1. SAW CUT AND REMOVE EXISTING CONCRETE SLAB-ON-GRADE AND CURB TO THE EXTENT SHOWN ON PLAN.
(E) CONC WALL
T.O. SLAB
ELEV = 37'-6"±
#4 U-SHAPED BARS
@ 12" O.C., E.W.
(E) SLAB SUBGRADE
#4 DOWELS @ 12" O.C.
AROUND PERIMETER OF INFILL
SLAB. DOWEL INTO (E) SLAB W/
ADHESIVE OR GROUT, TYP
6" 1'-0"
(E) CONC SLAB-ON-
GRADE, NOTE 1
6'-8"±
1/4" ISLOATION JOINT
MATERIAL, PER SPECS
9
S504 S504
TYPICAL HOUSEKEEPING PAD - ELEVATED SLAB
NOT TO SCALE
#4 @ 12" O.C.
NOTE 2 NOTE 2
(E) CONC ON
MTL DECK
#4 DOWELS @
12" O.C.
DRILL AND EPOXY
#4 DOWELS INTO
SLAB AT 12" O.C., 2"
EMBEDMENT
ROUGHEN SURFACE
AND APPLY EPOXY
BONDING AGENT
NOTES:
1. COORDINATE HOUSEKEEPING PAD SIZE AND LOCATION WITH APPROVED MEP SHOP
DRAWINGS.
2. PROVIDE A MINIMUM 6" CLEAR DISTANCE BETWEEN EQUIPMENT AND EDGE OF CURB.
X X X X X X X X X X X X X X
MEP EQUIPMENT
NOTE 1
![Page 20: 14012 - VAMC BLDG 360 - CENTRAL elorenz - rlscg.comrlscg.com/site/wp-content/uploads/VA245-16-B-0095-010.pdf · 10.welding electrodes: per table 3.1 of aws d1.1 for the smaw process](https://reader034.vdocuments.us/reader034/viewer/2022052608/5add35567f8b9a213e8c8f07/html5/thumbnails/20.jpg)
4'ON
E EI
GHTH
INCH
= O
NE F
OOT
( 1/8"
= 1'
-0" )
08'
16'
04'
8'4'
04'
02'
6"0
02'
6"0
1'6"
6"ON
E QU
ATER
INCH
= O
NE F
OOT
( 1/4"
= 1'
-0" )
THRE
E EI
GHTH
S IN
CH =
ONE
FOO
T ( 3
/8" =
1'-0
" )ON
E HA
LF IN
CH =
ONE
FOO
T ( 1
/2" =
1'-0
" )TH
REE
QUAT
ERS
INCH
= O
NE F
OOT
( 3/4"
= 1'
-0" )
ONE
INCH
= O
NE F
OOT
( 1" =
1'-0
" )ON
E AN
D ON
E HA
LF IN
CHES
= O
NE F
OOT
( 1 1/
2" =
1'-0
" )TH
REE
INCH
ES =
ONE
FOO
T ( 3
" = 1'
-0" )
OKKS Studios, Inc.2 Wisconsin Circle / Suite 820Chevy Chase, MD 20815-7003Tel: (301) 718-0080Fax: (301) 718-9520www.okksstudios.com
Nobis Engineering, Inc.20410 Century Boulevard, Suite 230
Germantown, MD 20874Tel: (301) 528 2010
Woods Peacock Engineering Consultants5250 Cherokee Avenue, Suite 420
Alexandria, VA 22312-2052Tel: (703) 658-4400
Fax: (703) 658-4404
Henry Adams ConsultingEngineers, LLC600 Baltimore Avenue, 4th FloorBaltimore, MD 21204Tel: (410) 296-6500Fax: (410) 296-6501
The Protection Engineering Group2809 Boston Street, Suite 7Baltimore, MD 21224 USA
Tel: (443) 708-4096Fax:
SCHEMATIC DESIGN (30%) SUBMISSION09/11/15DESIGN DEVELOPMENT (60%) SUBMISSION11/23/15CONSTRUCTION DOCUMENTS (90% SUBMISSION)
03/17/16
TMP CAD
PERRY POINT, MD
WAREHOUSE RENOVATION& EXPANSION
03/17/16BID DOCUMENTS SUBMISSION
03/25/15
Professional Certification. I hereby certify that these documentswere prepared or approved by me, and that I am a duly licensedprofessional engineer under the laws of the State of Maryland,License No. 14484, Expiration Date: June 27, 2017.
SECTIONS AND DETAILS
S505
6
S121 S505
RETAINING WALL SECTION
NOT TO SCALE
3" CLR
TYP
6'-6"
2" CLR
TYP
1'-0"
2'-0"
DOWEL TO MATCH
WALL REINF
#6@12" O.C.
VERT REINF
#4@12" O.C.
HORIZ REINF
3'-6"
SLAB-ON-GRADE,
PER PLAN
#6@12" O.C.
T&B
CONT #4@12"
O.C. T&B
1/4" ISOLATION JOINT
MATERIAL, PER SPECS
METAL WALL PANEL,
PER ARCH DWGS
LAP
SPLICE
STANDARD
HOOK
STANDARD
HOOK
PER
PLAN
PER
PLAN
STANDARD HOOK 'd',
SEE WALL HOOK
SCHEDULE
CORNER REINF
MATCH HORIZ REINF
PER PLAN AND
WALL SCHEDULE
T-INTERSECTIONOUTSIDE CORNER
0"
LAP
SPLICE
U-BARS SIZE & SPACING
TO MATCH HORIZONTAL
REINFORCING
1
S505 S505
TYPICAL CONCRETE DOUBLE
REINFORCED WALL PLAN DETAILS
NOT TO SCALE
#4 x 4'-0" LONG DOWELS
CENTERED IN WALL, SPACING TO
MATCH HORIZONTAL
REINFORCING
CONTROL JOINT
CONSTRUCTION JOINT
WALL REINFORCING
CHAMFER
WALL REINFORCING,
DISCONTINUOUS AT
JOINT
KEY 0.1tx0.2t, MIN
MAXIMUM JOINT SPACING IS 25'-0"
NOTE:
1. PLACEMENT OF CONCRETE BETWEEN ADJACENT SECTIONS OF WALL
SHALL BE SEPARATED BY 48 HOURS MINIMUM.
2"
2"
EARTH SIDE/ EXTERIOR FACE
INSIDE / INTERIOR FACE
EARTH SIDE/ EXTERIOR FACE
INSIDE / INTERIOR FACE
WATERSTOP, PER
SPECIFICATIONS
0.1t
2
S505 S505
TYPICAL WALL JOINT DETAILS
NOT TO SCALE
2"
FOOTING DOWEL SCHEDULE
b
(in)
a
(in)
BAR NO.
#3 18 6
#4 24 8
#5 30 10
#6 36 12
a
#7 42 14
#8 48 16
3
S505 S505
FOOTING
DOWEL SCHEDULE
NOT TO SCALE
3" CLR
TYP
FOOTING REINF, PER
COLUMN SCHEDULE
WALL REINF
TIES, PER COLUMN
SCHEDULE
PIER REINFORCING, PER
COLUMN SCHEDULE
DOWELS TO MATCH
VERTICAL WALL
REINF
DOWELS TO MATCH
PIER REINF
1
4
" ISOLATION JOINT
MATERIAL, PER SPECS
SLAB-ON-GRADE,
PER PLAN
WALL REINF, CONTINUE
THROUGH PIER
FTG SIZE AND REINF
PER COL SCHEDULE
T.O. SLAB
SEE PLAN
5
S505 S505
4
S121 S505
WALL/PIER SECTION
SCALE: 3/4" = 1'-0"
COLUMN, PER SCHEDULE
BASE PLATE AND
ANCHOR BOLTS, PER
COLUMN SCHEDULE
1" NON-SHRINK GROUT
1
S505 S506
WALL FOOTING
REINF, CONTINUE
THROUGH PIER
FILL WITH MASTIC
CAULKING OR
RUBBER STRIP
STOP HORIZONTAL
REINFORCING @
CONTROL JOINT
t/4
t
PER PLAN
VERTICAL REINF, PER
COLUMN SCHEDULE
TIES AND CROSS TIES
PER COLUMN
SCHEDULE,
ALTERNATE CROSS
TIES, CENTER
REINFORCING ON
GRIDLINE
INTERSECTION
WALL REINF, CONTINUE
THROUGH PIER
AT CONTROL JOINT
BETWEEN CONTROL
JOINTS
t
PER PLAN
5
S505 S505
WALL/PIER INTERFACE DETAIL
SCALE: 3/4" = 1'-0"
GRAPHIC SCALE
3/4" = 1'-0"
0 2' 3'1'
CAUTION: IF THIS DRAWING
IS A REDUCTION, GRAPHIC
SCALES MUST BE USED.
7
S121 S505
WALL/PIER SECTION AT EXISTING BUILDING
NOT TO SCALE
4'-0"
SQUARE
2'-6"±
(E) CONC WALL
(E) CONC WALL FTG
NOTES:
1. SEE 4/S505 FOR INFORMATION NOT SHOWN
DOWELS TO MATCH
VERTICAL WALL
REINF
(4) #6
(2) #6
(3) #6
DOWELS TO MATCH
PIER REINF
![Page 21: 14012 - VAMC BLDG 360 - CENTRAL elorenz - rlscg.comrlscg.com/site/wp-content/uploads/VA245-16-B-0095-010.pdf · 10.welding electrodes: per table 3.1 of aws d1.1 for the smaw process](https://reader034.vdocuments.us/reader034/viewer/2022052608/5add35567f8b9a213e8c8f07/html5/thumbnails/21.jpg)
4'ON
E EI
GHTH
INCH
= O
NE F
OOT
( 1/8"
= 1'
-0" )
08'
16'
04'
8'4'
04'
02'
6"0
02'
6"0
1'6"
6"ON
E QU
ATER
INCH
= O
NE F
OOT
( 1/4"
= 1'
-0" )
THRE
E EI
GHTH
S IN
CH =
ONE
FOO
T ( 3
/8" =
1'-0
" )ON
E HA
LF IN
CH =
ONE
FOO
T ( 1
/2" =
1'-0
" )TH
REE
QUAT
ERS
INCH
= O
NE F
OOT
( 3/4"
= 1'
-0" )
ONE
INCH
= O
NE F
OOT
( 1" =
1'-0
" )ON
E AN
D ON
E HA
LF IN
CHES
= O
NE F
OOT
( 1 1/
2" =
1'-0
" )TH
REE
INCH
ES =
ONE
FOO
T ( 3
" = 1'
-0" )
OKKS Studios, Inc.2 Wisconsin Circle / Suite 820Chevy Chase, MD 20815-7003Tel: (301) 718-0080Fax: (301) 718-9520www.okksstudios.com
Nobis Engineering, Inc.20410 Century Boulevard, Suite 230
Germantown, MD 20874Tel: (301) 528 2010
Woods Peacock Engineering Consultants5250 Cherokee Avenue, Suite 420
Alexandria, VA 22312-2052Tel: (703) 658-4400
Fax: (703) 658-4404
Henry Adams ConsultingEngineers, LLC600 Baltimore Avenue, 4th FloorBaltimore, MD 21204Tel: (410) 296-6500Fax: (410) 296-6501
The Protection Engineering Group2809 Boston Street, Suite 7Baltimore, MD 21224 USA
Tel: (443) 708-4096Fax:
SCHEMATIC DESIGN (30%) SUBMISSION09/11/15DESIGN DEVELOPMENT (60%) SUBMISSION11/23/15CONSTRUCTION DOCUMENTS (90% SUBMISSION)
03/17/16
TMP CAD
PERRY POINT, MD
WAREHOUSE RENOVATION& EXPANSION
03/17/16BID DOCUMENTS SUBMISSION
03/25/15
Professional Certification. I hereby certify that these documentswere prepared or approved by me, and that I am a duly licensedprofessional engineer under the laws of the State of Maryland,License No. 14484, Expiration Date: June 27, 2017.
SECTIONS AND DETAILS
S506
1
S501 S506
BASEPLATE PLAN DETAIL
S505
NOT TO SCALE
(4) HEADED ANCHOR
BOLTS, PER COLUMN
SCHEDULE
COLUMN, PER
COLUMN SCHEDULE
B
PER SCHEDULE
1 1/2" 1 1/2"
BASEPLATE, PER
COLUMN SCHEDULE
GRAPHIC SCALE
0
1" = 1'-0"
1' 2'1/2'
CAUTION: IF THIS DRAWING
IS A REDUCTION, GRAPHIC
SCALES MUST BE USED.
BEAM, PER PLAN
ROOF DECK, PER PLAN
T.O. STEEL
PER PLAN
3'-0"
COLUMN, PER
COLUMN
SCHEDULE
W.P.
W.P.
KNEE BRACE,
PER PLAN
NOTES:
1. OTHER BEAMS AND KNEE BRACES NOT SHOWN, WHERE APPLICABLE,
FOR CLARITY. SEE PLAN FOR FRAMING LOCATIONS AND QUANTITIES.
2
S506 S506
ROOF KNEE BRACE
CONNECTION DETAIL
SCALE: 1" = 1'-0"
SHEAR CONNECTION
TO BE DESIGNED BY
STEEL FABRICATOR
L6x3x3/8 x
10" LONG
3
S506 S506
BEAM AXIAL DESIGN LOAD SCHEDULE
NOT TO SCALE
BRACED FRAME
GRID
BEAM AXIAL DESIGN LOAD SCHEDULE
7
9a
d'
c
NOTES:
1. DESIGN BEAM TO COLUMN CONNECTIONS
ALONG THE SPECIFIED GRIDLINES FOR
THE AXIAL TENSION AND COMPRESSION
FORCES PROVIDED.
2. LOADS PROVIDED ARE FACTORED PER
LRFD, IBC 2012, AND ARE IN UNITS OF
KIPS.
3. SEE PLANS FOR VERTICAL REACTIONS.
1', 8'
COMPRESSION
(k)
19
TENSION (k)
14
8
7
24
50
8
2
8
8
3', 6'
b, d3647
26 37
![Page 22: 14012 - VAMC BLDG 360 - CENTRAL elorenz - rlscg.comrlscg.com/site/wp-content/uploads/VA245-16-B-0095-010.pdf · 10.welding electrodes: per table 3.1 of aws d1.1 for the smaw process](https://reader034.vdocuments.us/reader034/viewer/2022052608/5add35567f8b9a213e8c8f07/html5/thumbnails/22.jpg)
4'ON
E EI
GHTH
INCH
= O
NE F
OOT
( 1/8"
= 1'
-0" )
08'
16'
04'
8'4'
04'
02'
6"0
02'
6"0
1'6"
6"ON
E QU
ATER
INCH
= O
NE F
OOT
( 1/4"
= 1'
-0" )
THRE
E EI
GHTH
S IN
CH =
ONE
FOO
T ( 3
/8" =
1'-0
" )ON
E HA
LF IN
CH =
ONE
FOO
T ( 1
/2" =
1'-0
" )TH
REE
QUAT
ERS
INCH
= O
NE F
OOT
( 3/4"
= 1'
-0" )
ONE
INCH
= O
NE F
OOT
( 1" =
1'-0
" )ON
E AN
D ON
E HA
LF IN
CHES
= O
NE F
OOT
( 1 1/
2" =
1'-0
" )TH
REE
INCH
ES =
ONE
FOO
T ( 3
" = 1'
-0" )
OKKS Studios, Inc.2 Wisconsin Circle / Suite 820Chevy Chase, MD 20815-7003Tel: (301) 718-0080Fax: (301) 718-9520www.okksstudios.com
Nobis Engineering, Inc.20410 Century Boulevard, Suite 230
Germantown, MD 20874Tel: (301) 528 2010
Woods Peacock Engineering Consultants5250 Cherokee Avenue, Suite 420
Alexandria, VA 22312-2052Tel: (703) 658-4400
Fax: (703) 658-4404
Henry Adams ConsultingEngineers, LLC600 Baltimore Avenue, 4th FloorBaltimore, MD 21204Tel: (410) 296-6500Fax: (410) 296-6501
The Protection Engineering Group2809 Boston Street, Suite 7Baltimore, MD 21224 USA
Tel: (443) 708-4096Fax:
SCHEMATIC DESIGN (30%) SUBMISSION09/11/15DESIGN DEVELOPMENT (60%) SUBMISSION11/23/15CONSTRUCTION DOCUMENTS (90% SUBMISSION)
03/17/16
TMP CAD
PERRY POINT, MD
WAREHOUSE RENOVATION& EXPANSION
03/17/16BID DOCUMENTS SUBMISSION
03/25/15
Professional Certification. I hereby certify that these documentswere prepared or approved by me, and that I am a duly licensedprofessional engineer under the laws of the State of Maryland,License No. 14484, Expiration Date: June 27, 2017.
SECTIONS AND DETAILS
S507
4
S507 S507
JOIST REINFORCING
ELEVATION DETAIL
NOT TO SCALE
NOTE 1
STEEL JOIST, PER
PLAN
ADDITIONAL (2)
L1
1
2
x1
1
2
x
1
4
" BRACE
AS REQUIRED
PER NOTE 1
NOTE 1
ADDITIONAL (2)
L1
1
2
x1
1
2
x
1
4
" BRACE AS
REQUIRED PER NOTE 1
NOTES:
1. ANGLE BRACE MUST BE ADDED TO JOIST WHEN A CONCENTRATED LOAD GREATER THAN 50
POUNDS IS PLACED, OR HUNG, ON THE JOIST MORE THAN 6" AWAY FROM A PANEL POINT.
2. LIMIT THE CONCENTRATED LOAD TO 250 POUNDS.
3. ROOF SUPPORT ANGLE AND ANGLE SUPPORT BRACKET NOT SHOWN FOR CLARITY. SEE
DETAIL 5/S507.
4. ATTACHMENTS MUST BE CONCENTRIC TO THE CHORD.
TYP
3
16
ROOF DECK,
PER PLAN
1
S507 S507
SPECIAL JOIST LOAD SCHEDULE
NOT TO SCALE
MARK
DEAD LOAD
(PLF)
SNOW LOAD
(PLF)
SPECIAL JOIST LOAD SCHEDULE
SP1 95 290
DEAD LOAD
SNOW LOAD
SP2
SP4
SEE PLAN
SP3
95 221
95 152
95 90
NOTES:
1. SNOW LOADS LISTED INCLUDE SNOW DRIFT LOADING. SNOW LOADS
PROVIDED ARE GREATER THAN CODE REQUIRED ROOF LIVE LOAD AND
THEREFORE CONTROL DESIGN.
2. SEE STRUCTURAL NOTES FOR WIND UPLIFT LOADING REQUIREMENTS.
3. LOADS PROVIDED ARE UNFACTORED & CALCULATED IN ACCORDANCE
WITH IBC, REFERENCED IN THE STRUCTURAL NOTES.
4. WEB CONFIGURATION SHOWN IS SCHEMATIC. ACTUAL CONFIGUATION
MAY VARY FROM THAT SHOWN.
5. DIMENSIONS DENOTED WITH AN * SHALL BE COORDINATED WITH THE
AHU SELECTED AND SHALL BE ADJUSTED AS NECESSARY.SP5 101 90
AHU LOAD 1
L1 (LB)
-
-
600
AHU CRUB 1
C1
15'-1" * 6'-1" *
-
-
-
-
-
-
-
-
-
-
AHU CURB 1
C1
AHU CURB 2
C2
GRID 2
c
GRID 1
d'
-
-
-
-
-
-
-
-
AHU LOAD 2
L2 (LB)
AHU CRUB 2
C2
-
-
600
-
-
AHU LOAD 2 (L2)AHU LOAD 1 (L1)
2
S507 S507
K SERIES JOIST
BEARING ON BEAM DETAIL
NOT TO SCALE
1
2
" CLR
MIN
2
1
2
"
MIN
2
1
2
"
MIN
BEAM, PER PLAN
FOR "bf" > 5
1
2
"
ALIGN JOISTS
FOR "bf" < 5
1
2
"
STAGGER JOISTS
NOTES:
1. COORDINATE WITH PLANS, SECTIONS, AND DETAILS FOR JOIST SIZE AND
END CONDITIONS
2. PROVIDE TWO KICKERS PER BEAM, ONE EACH SIDE, LOCATED AT THE
MID-SPAN OF THE BEAM. WHERE A JOIST DOES NOT OCCUR AT
MID-SPAN, PLACE KICKERS AT NEAREST JOIST TO MID-SPAN.
3. STEEL DECK NOT SHOWN FOR CLARITY, SEE PLAN FOR SIZE AND TYPE.
STEEL JOIST,
PER PLAN
STEEL JOIST, PER PLAN
L2x2x
3
16
KICKER,
SEE NOTE 2
PLACE AS CLOSE TO PANEL
POINT AS POSSIBLE. FASTEN
TO BEAM AND JOIST W/
3
16
"
FILLET WELDS.
3
S507 S507
K SERIES JOIST TO
COLUMN CONNECTION DETAIL
NOT TO SCALE
COLUMN, PER
COLUMN
SCHEDULE
2
1
2
"
MIN
1/2" THICK
STEEL PLATE
STEEL JOIST,
PER PLAN
1
2
"
1
2
"
NOTES:
1. STEEL DECK NOT SHOWN FOR CLARITY, SEE PLAN FOR SIZE AND
TYPE.
2. PROVIDE 2
1
2
" MINIMUM JOIST BEARING ON STEEL CAP PLATE.
3. PROVIDE JOIST ANCHORAGE TO CAP PLATE PER SJI.
5
S507 S507
TYPICAL METAL ROOF DECK
FRAMING AT OPENING
NOT TO SCALE
'B'
NOTES:
1. COORDINATE OPENING LOCATION AND QUANTITY W/ ARCHITECTURAL AND
MECHANICAL DRAWINGS.
2. ANGLE SIZE BASED ON LARGER OF 'A' OR 'B'.
3. IF OPENING FRAMING IS NOT SUPPORTED DIRECTLY AT A STEEL JOIST
PANEL POINT, REINFORCE STEEL JOISTS PER DETAIL 4/S507.
L3x3x
1
4
FOR OPENINGS 2'-0" OR
SMALLER
L4x4x
1
4
FOR OPENINGS 2'-1"
THRU 4'-0" MAX
L6x4x
5
16
(LLV) FOR OPENINGS
4'-1" THRU 6'-0" MAX
C6x10.5 FOR OPENINGS 6'-1"
THRU 8'-0" MAX
C8x11.5 FOR OPENINGS 8'-1"
THRU 10'-0" MAX
STEEL
BEAM OR
JOIST
STEEL
BEAM OR
JOIST
5A
S507 S507
SECTION
NOT TO SCALE
6
S122 S507
ROOF JOINT AT (E) LOW ROOF
SCALE: 1-1/2" = 1'-0"
STEEL JOIST, PER PLAN
1'-0"
OVERLAP
ROOF DECK, PER PLAN
L8x6x3/4 x 0'-6" LONG, LLH(E) STEEL BEAM
(E) ROOF DECK
2 1/2"
MIN
7
S122 S507
ROOF JOINT AT (E) LOW ROOF
SCALE: 1-1/2" = 1'-0"
1'-0"
OVERLAP
(E) ROOF DECK
(E) STEEL BEAM
ROOF DECK, PER PLAN
8
S122 S507
EXPANSION JOINT AT LOW ROOF
SCALE: 1-1/2" = 1'-0"
2" EXPANSION
JOINT
ROOF DECK, PER PLAN
BEAM, PER PLAN
WALL PANEL, PER ARCH DWGS
GRAPHIC SCALE
CAUTION: IF THIS DRAWING
IS A REDUCTION, GRAPHIC
SCALES MUST BE USED.
0
1-1/2" = 1'-0"
1' 1 1/2'1/2'
9
S123 S507
EXPANSION JOINT AT HIGH ROOF
SCALE: 1-1/2" = 1'-0"
1'-0"
OVERLAP
2" EXPANSION
JOINT
STEEL JOIST, PER PLAN
ROOF DECK, PER PLAN
BEAM, PER PLAN
ROOF DECK TO MATCH
(E) ROOF DECK PROFILE
IF NEEDED TO FILL GAP
(E) STEEL BEAM
(E) ROOF DECK
SEE PLAN
![Page 23: 14012 - VAMC BLDG 360 - CENTRAL elorenz - rlscg.comrlscg.com/site/wp-content/uploads/VA245-16-B-0095-010.pdf · 10.welding electrodes: per table 3.1 of aws d1.1 for the smaw process](https://reader034.vdocuments.us/reader034/viewer/2022052608/5add35567f8b9a213e8c8f07/html5/thumbnails/23.jpg)
4'ON
E EI
GHTH
INCH
= O
NE F
OOT
( 1/8"
= 1'
-0" )
08'
16'
04'
8'4'
04'
02'
6"0
02'
6"0
1'6"
6"ON
E QU
ATER
INCH
= O
NE F
OOT
( 1/4"
= 1'
-0" )
THRE
E EI
GHTH
S IN
CH =
ONE
FOO
T ( 3
/8" =
1'-0
" )ON
E HA
LF IN
CH =
ONE
FOO
T ( 1
/2" =
1'-0
" )TH
REE
QUAT
ERS
INCH
= O
NE F
OOT
( 3/4"
= 1'
-0" )
ONE
INCH
= O
NE F
OOT
( 1" =
1'-0
" )ON
E AN
D ON
E HA
LF IN
CHES
= O
NE F
OOT
( 1 1/
2" =
1'-0
" )TH
REE
INCH
ES =
ONE
FOO
T ( 3
" = 1'
-0" )
OKKS Studios, Inc.2 Wisconsin Circle / Suite 820Chevy Chase, MD 20815-7003Tel: (301) 718-0080Fax: (301) 718-9520www.okksstudios.com
Nobis Engineering, Inc.20410 Century Boulevard, Suite 230
Germantown, MD 20874Tel: (301) 528 2010
Woods Peacock Engineering Consultants5250 Cherokee Avenue, Suite 420
Alexandria, VA 22312-2052Tel: (703) 658-4400
Fax: (703) 658-4404
Henry Adams ConsultingEngineers, LLC600 Baltimore Avenue, 4th FloorBaltimore, MD 21204Tel: (410) 296-6500Fax: (410) 296-6501
The Protection Engineering Group2809 Boston Street, Suite 7Baltimore, MD 21224 USA
Tel: (443) 708-4096Fax:
SCHEMATIC DESIGN (30%) SUBMISSION09/11/15DESIGN DEVELOPMENT (60%) SUBMISSION11/23/15CONSTRUCTION DOCUMENTS (90% SUBMISSION)
03/17/16
TMP CAD
PERRY POINT, MD
WAREHOUSE RENOVATION& EXPANSION
03/17/16BID DOCUMENTS SUBMISSION
03/25/15
Professional Certification. I hereby certify that these documentswere prepared or approved by me, and that I am a duly licensedprofessional engineer under the laws of the State of Maryland,License No. 14484, Expiration Date: June 27, 2017.
COLUMN SCHEDULE
S601
COLUMN SCHEDULE
14"x13"x3/4"
(8) #8
24"x24"
37'-0"
SIZE
TOP ELEVATION
VERTICAL STEEL
PIER TIES
SIZE
REINFORCING
(BOT. E.W. - U.N.O.)
BASE PLATE
SIZE (N x B x tp)
FOOTING LOAD (KIPS)
ELEV = 32'-0"
FOUNDATION
ELEV = 37'-6"
GROUND FLOOR
ELEV = 48'-6", U.N.O.
LOW ROOF
ELEV = 63'-11", U.N.O.
HIGH ROOF
MARK A-7
#3@12 O.C.
ANCHORS 3/4"Ø
1
S601 S601
COLUMN SCHEDULE
NOT TO SCALE
a-1' a-3' a-6'b-1', d-1'
c-7 c-8a c-9a c-1' d'-7 d'-8a d'-9a
49 15 26 26 25 4651 50 82
ELEV = 63'-4"
b-3', b-6',
d-3', d-6'
ELEV = 63'-4"
b-2', b-7',
d-2', d-7'
ELEV = 63'-4"
b-4', d-4'
ELEV = 63'-4"
ELEV = 47'-11"
69
ELEV = 47'-11"
33
ELEV = 47'-11"
25 44
c-2', c-4', c-7'
40
c-3', c-6'
42 45 16
20"x16"x1/2" 21"x21"x1/2" 21"x21"x1/2" 20"x16"x1/2" 21"x21"x1/2"20"x16"x1/2" 20"x16"x1/2" 14"x13"x3/4" 14"x13"x3/4" 14"x13"x3/4" 20"x16"x1/2" 21"x21"x1/2"16"x14"x1/2" 14"x13"x3/4" 14"x13"x3/4" 14"x13"x3/4"
24"x24"
45'-2"
24"x24"
45'-2"
24"x24"
37'-0"
24"x24"
45'-2"
24"x24"
37'-0"
24"x24"
37'-0"
24"x24"
37'-0"
24"x24"
37'-0"
24"x24"
37'-0"
24"x24"
40'-6"
24"x24"
45'-2"
24"x24"
37'-0"
24"x24"
37'-0"
24"x24"
40'-6"
24"x24"
40'-6"
24"x24"
40'-6"
c-8'
25
20"x16"x1/2"
24"x24"
37'-0"
d-8'
25
ELEV = 63'-4"
20"x16"x1/2"
24"x24"
45'-2"
b-8'
25
ELEV = 63'-4"
20"x16"x1/2"
24"x24"
37'-0"
COMBINED
FOOTING
PER DETAIL
1/S502
COMBINED
FOOTING
PER DETAIL
2/S502
COMBINED
FOOTING
PER DETAIL
3/S502
COMBINED
FOOTING
PER DETAIL
1/S502
COMBINED
FOOTING
PER DETAIL
2/S502
COMBINED
FOOTING
PER DETAIL
3/S502
4'-0"x4'-0"
x1'-0"
(4) #6 E.W.
4'-0"x4'-0"
x1'-0"
(4) #6 E.W.
4'-0"x4'-0"
x1'-0"
(4) #6 E.W.
5'-0"x5'-0"
x1'-0"
(4) #6 E.W.
5'-0"x5'-0"
x1'-0"
(4) #6 E.W.
5'-0"x5'-0"
x1'-0"
(4) #6 E.W.
5'-0"x5'-0"
x1'-0"
(4) #6 E.W.
6'-0"x6'-0"
x1'-0"
(5) #6 E.W.
5'-0"x5'-0"
x1'-0"
(4) #6 E.W.
6'-0"x6'-0"
x1'-0"
(5) #6 E.W.
6'-0"x6'-0"
x1'-0"
(5) #6 E.W.
a-8'
15
20"x16"x1/2"
24"x24"
37'-0"
a-2'
21
16"x14"x1/2"
24"x24"
45'-2"
a-4', a-5', a-7'
21
16"x14"x1/2"
24"x24"
37'-0"
4'-0"x4'-0"
x1'-0"
(4) #6 E.W.
e-1', e-8'
e-2', e-4',
e-5', e-7'
15 21
20"x16"x1/2" 16"x14"x1/2"
24"x24"
45'-2"
24"x24"
45'-2"
4'-0"x4'-0"
x1'-0"
(4) #6 E.W.
e-3', e-6'
26
21"x21"x1/2"
24"x24"
45'-2"
4'-0"x4'-0"
x1'-0"
(4) #6 E.W.
SEE DETAIL
7/S505
SEE DETAIL
7/S505
SEE DETAIL
7/S505
SEE DETAIL
7/S505
SEE DETAIL
7/S505
SEE DETAIL
7/S505
3/4"Ø 3/4"Ø 3/4"Ø 3/4"Ø 3/4"Ø 3/4"Ø 3/4"Ø 3/4"Ø3/4"Ø 3/4"Ø 3/4"Ø 3/4"Ø 3/4"Ø 3/4"Ø 3/4"Ø 3/4"Ø3/4"Ø 3/4"Ø 3/4"Ø 3/4"Ø 3/4"Ø 3/4"Ø 3/4"Ø 3/4"Ø3/4"Ø
(8) #8
#3@12 O.C.
(8) #8
#3@12 O.C.
(8) #8
#3@12 O.C.
(8) #8
#3@12 O.C.
(8) #8
#3@12 O.C.
(8) #8
#3@12 O.C.
(8) #8
#3@12 O.C.
(8) #8
#3@12 O.C.
(8) #8
#3@12 O.C.
(8) #8
#3@12 O.C.
(8) #8
#3@12 O.C.
(8) #8
#3@12 O.C.
(8) #8
#3@12 O.C.
(8) #8
#3@12 O.C.
(8) #8
#3@12 O.C.
(8) #8
#3@12 O.C.
(8) #8
#3@12 O.C.
(8) #8
#3@12 O.C.
(8) #8
#3@12 O.C.
(8) #8
#3@12 O.C.
(8) #8
#3@12 O.C.
(8) #8
#3@12 O.C.
(8) #8
#3@12 O.C.
(8) #8
#3@12 O.C.
(8) #8
#3@12 O.C.
PER COL
SCHEDULE
1 1/2"
CLR
TIES, PER COLUMN
SCHEDULE
VERTICAL REINF,
SEE COLUMN SCHEDULE
NOTE:
1. CONSECUTIVE CROSS TIES MUST HAVE HOOKS ON
ALTERNATE SIDES
2. VERTICAL SPACING OF CROSSTIES SHALL MATCH
THE TIE SPACING SHOWN IN THE COLUMN SCHEDULE.
CROSSTIE,
NOTE 1
2
S601 S601
CONCRETE PIER
TYPICAL 8 BAR PLAN DETAIL
NOT TO SCALE