12 catalog sip e7 substation automation

Upload: sherubd

Post on 03-Jun-2018

241 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/12/2019 12 Catalog SIP E7 Substation Automation

    1/33

    Substation Automation Page

    SIPROTEC 4 6MD61 IO-Box 12/3

    SIPROTEC 4 6MD63 bay control unit 12/11

    SIPROTEC 4 6MD66 high-voltage bay control unit 12/13

    12

  • 8/12/2019 12 Catalog SIP E7 Substation Automation

    2/33

  • 8/12/2019 12 Catalog SIP E7 Substation Automation

    3/33

    Substation Automation / 6MD61SIPROTEC 4 6MD61 IO-Box

    12 /3Siemens SIP Edition No. 7

    Description

    The SIPROTEC 4 6MD61 IO-Box enables in a simple, easy wayto enhance the number of binary inputs and outputs in theswitchgear. It can be used directly in the bay together with otherSIPROTEC 4 units and also together with SICAM PAS to serve as acentral process connection.

    The IO-Box is based on the SIPROTEC 6MD63 and 6MD66 series,so it can be easily integrated in systems with other SIPROTEC 4units.

    The IO-Box supports a wide range of demand for additionalbinary inputs (BI) and binary outputs (BO), starting from20 BI+10 BO and going up to 80 BI+53 BO. All importantstandard communication protocols are supported.With IEC 61850-GOOSE communication, a direct informationinterchange with other SIPROTEC units is possible. For simpli-cation and cost reduction, the IO-Box is available only withoutautomation (CFC), without keypad and without display.

    .

    Function overview

    Application Extension of number of inputs and outputs of bay controller Extension of number of inputs and outputs of protection unit Central process connection for SICAM PAS

    Features Standard SIPROTEC hardware for easy conguration with DIGSI

    Full EMC compliance like all other SIPROTEC devices Housing can be used for surface mounting or ush mounting

    (units are always delivered with two mounting rails for surfacemounting. These rails can be dismounted for ush mounting)

    Three types with different amount of inputs and outputsavailable

    Monitoring functions Operational measured values (only 6MD612) Energy metering values (only 6MD612) Time metering of operating hours Self supervision of relay

    Communication interfaces IEC 61850 Ethernet IEC 60870-5-103 protocol PROFIBUS-FMS PROFIBUS-DP Service interface for DIGSI 4 (modem) Front interface for DIGSI4 Time synchronization via IRIG B / DCF77

    Fig. 12/1 SIPROTEC 4 6MD61 IO-Box

    L S P 2 7 9 7

    . e p s

    L S P 2 7 9 5

    - a f p

    . t i f

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    11

    12

    13

    14

    15

  • 8/12/2019 12 Catalog SIP E7 Substation Automation

    4/33

    Substation Automation / 6MD61Application

    12 /4 Siemens SIP Edition No. 7

    Application

    The following gures show the mostimportant applications of the SIPROTECIO-Box 6MD61.

    The conguration shown in Fig. 12/2allows direct GOOSE communicationbetween the SIPROTEC 4 units (6MD66,7SJ63) and the IO-Boxes, independentof the substation controller. Of course,this conguration is also possible withoutsubstation controller. The IO-Box isused as additional digital inputs andmeasurements (measurements only with6MD612), and serves as an additionalcommand output.

    The communication between IO-Box andthe substation controller is established byusing the IEC 61850 standard protocol.

    Fig. 12/3 shows a conguration in whichthe IO-Box is used as a central processconnection in the cubicle of the substa-tion controller. For example, cubiclesignaling lamps or a signaling horn arecontrolled by the command relays of theIO-Box.

    Fig. 12/4 shows the communication forsubstations with no Ethernet protocolused. In this case, all communication linesgo directly to the substation controller.If information from the IO-Box is used forswitchgear interlocking, the interlocking

    logic must be part of the substationcontroller.

    Switchelectrical

    6MD66 7SJ63IO-Box 6MD61 IO-Box 6MD61

    optical

    Bay 2Bay 1

    SICAM PAS substationcontroller

    S I P V 6

    . 0 2 2 e n

    . e p s

    IO-Box 6MD61Switchelectricaloptical

    SICAM PAS substationcontroller

    6MD66 7SA63

    Bay 2Bay 1

    6MD66 7SA63

    S I P V 6

    . 0 2 3 e n

    . e p s

    Fig. 12/2 Conguration with IO-Box in IEC 61850 substation

    Fig. 12/3 IO-Box as central input/output for SICAM PAS substation controller

    Fig. 12/4 Direct connection of IO-Boxes and protection relays to substation controller viastandard protocol

  • 8/12/2019 12 Catalog SIP E7 Substation Automation

    5/33

    Substation Automation / 6MD61Selection and ordering data

    12 /5Siemens SIP Edition No. 7

    Description Order No. Order code

    6MD61 IO-Box 6MD61 - - 0AA0 -

    20 binary inputs, 6 command relays, 4 (2) power relays, 1 live status contact (similar to 6MD634)in 19'' housing33 binary inputs, 14 command relays, 8 (4) power relays, 1 live status contact, 2 x 20 mA, 3 x V , 4 x I ,(similar to 6MD636) in 19'' housing80 binary inputs, 53 command relays, 1 live status contactin 19'' housing

    Current transformer: rated current I nNo analog measured variables1 A2) 5 A2)

    Rated auxiliary voltage (power supply, indication voltage)24 to 48 V DC, threshold binary input 19 V60 V DC, threshold binary input 19 V2) 110 V DC, threshold binary input 88 V2) 220 to 250 V DC, 115 to 230 V AC, threshold binary input 176 V for input No. 8-80for 6MD613 (C-I/O 4), otherwise threshold 88 V2)

    Unit versionSurface-mounting case, without HMI, mounting in low voltage compartment,screw-type terminals (direct wiring / ring lugs), also usable as ush-mounting case

    Region-specic default settings/function versions and language settingsRegion DE, 50 Hz, language: German, changeableRegion World, 50/60 Hz, language: English (GB), changeableRegion US, 60 Hz, ANSI, language: English (US), changeableRegion FR, language: French, changeableRegion World, language: Spanish, changeable

    System interface (on rear of unit, port B)No system port

    IEC 60870-5-103 protocol, electrical RS232IEC 60870-5-103 protocol, electrical RS485IEC 60870-5-103 protocol, optical 820 nm, ST connectorPROFIBUS-FMS Slave, electrical RS485PROFIBUS-FMS Slave, ber, double ring, ST connectorPROFIBUS DP Slave, electrical RS485PROFIBUS-DP Slave, 820 nm ber, double ring, ST connectorsIEC 61850, 100 BaseT (100 Mbit Ethernet electric, double, RJ45 connector)IEC 61850, 100 Mbit Ethernet, ber optic, double, LC connectors

    Function interface (on rear of unit, port C)No function portDIGSI 4, RS232

    DIGSI 4, RS485DIGSI 4, 820 nm ber, ST connector

    ABCDE

    0

    123469999

    01

    23

    234

    5

    F

    1

    2

    3

    015

    L 0 AL 0 BL 0 RL 0 S

    1) Only for position 6 = 22) Thresholds can be changed (jumper) for each binary input between

    19 V and 88 V, for 6MD613 BI No. 8-80 also to 176 V.

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    11

    12

    13

    14

    15

  • 8/12/2019 12 Catalog SIP E7 Substation Automation

    6/33

    Substation Automation / 6MD61Connection diagram

    12 /6 Siemens SIP Edition No. 7

    Fig. 12/5 Connection diagram

  • 8/12/2019 12 Catalog SIP E7 Substation Automation

    7/33

    Substation Automation / 6MD61Connection diagram

    12 /7Siemens SIP Edition No. 7

    Fig. 12/6 Connection diagram

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    11

    12

    13

    14

    15

  • 8/12/2019 12 Catalog SIP E7 Substation Automation

    8/33

    Substation Automation / 6MD61Connection diagram

    12 /8 Siemens SIP Edition No. 7

    Fig. 12/7 Connection diagram, part 1; continued on the following page

  • 8/12/2019 12 Catalog SIP E7 Substation Automation

    9/33

    Substation Automation / 6MD61Connection diagram

    12 /9Siemens SIP Edition No. 7

    Fig. 12/8 Connection diagram part 2

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    11

    12

    13

    14

    15

  • 8/12/2019 12 Catalog SIP E7 Substation Automation

    10/33

    Substation Automation / 6MD61

    2 /10 Siemens SIP Edition No. 7

  • 8/12/2019 12 Catalog SIP E7 Substation Automation

    11/33

    Substation Automation / 6MD63SIPROTEC 4 6MD63 bay control unit

    12 /11Siemens SIP Edition No. 7

    Description

    The 6MD63 bay control unit is a exible, easy-to-use controlunit. It is optimally tailored for medium-voltage applications butcan also be used in high-voltage substations.

    The 6MD63 bay control unit has the same design (look and feel)as the other protection and combined units of the SIPROTEC 4relay series. Conguration is also performed in a standardizedway with the easy-to-use DIGSI 4 conguration tool .

    For operation, a large graphic display with a keyboard is avail-able. The important operating actions are performed in a simpleand intuitive way, e.g. alarm list display or switchgear control.The operator panel can be mounted separately from the relay,if required. Thus, exibility with regard to the mounting positionof the unit is ensured.

    Integrated key-operated switches control the switching authorityand authorization for switching without interlocking.

    Function overview

    Application Optimized for connection to three-position disconnectors Switchgear interlocking interface

    Suitable for redundant master station Automation can be congured easily by graphic meanswith CFC

    Control functions Number of switching devices only limited by number of

    available inputs and outputs Position of switching elements is shown on the graphic display Local/remote switching via key switch Command derivation from an indication 4 freely assignable function keys to speed up frequently

    recurring operator actions Switchgear interlocking isolator/c.-b. Key-operated switching authority Feeder control diagram Measured-value acquisition Signal and command indications P, Q, cos (power factor) and meter-reading calculation Event logging Switching statistics

    Monitoring functions Operational measured values Energy metering values

    Time metering of operating hours Slave pointer Self-supervision of relay

    Communication interfaces System interface

    IEC 61850 Ethernet IEC 60870-5-103 protocol PROFIBUS-FMS DNP 3.0 PROFIBUS-DP MODBUS Service interface for DIGSI 4 (modem)/temperature

    detection (thermo-box) Front interface for DIGSI 4 Time synchronization via IRIG-B/DCF 77

    Fig. 12/9 SIPROTEC 4 6MD63 bay control unit

    L S P 2 3 1 4

    - a f p

    . t i f

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    11

    12

    13

    14

    15

  • 8/12/2019 12 Catalog SIP E7 Substation Automation

    12/33

    Substation Automation / 6MD63Selection and ordering data

    2 /12 Siemens SIP Edition No. 7

    Description Order No. Order code

    6MD63 bay control unit with local control 6MD63 - - AA0 -

    Housing, binary inputs (BI) and outputs (BO), measuring transducerHousing 19, 11 BI, 8 BO, 1 live status contactHousing 19, 24 BI, 11 BO, 4 power relays, 1 live status contactHousing 19, 20 BI, 11 BO, 2 measuring transducer inputs, 4 power relays, 1 live status contactHousing 19, 20 BI, 6 BO, 4 power relays, 1 live status contact1)Housing 19, 37 BI, 14 BO, 8 power relays, 1 live status contactHousing 19, 33 BI, 14 BO, 2 measuring transducer inputs, 8 power relays, 1 live status contactHousing 19, 33 BI, 9 BO, 8 power relays, 1 live status contact1)

    Current transformer I nNo analog measured variables1 A2) 5 A2)

    Rated auxiliary voltage (power supply, indication voltage)24 to 48 V DC, threshold binary input 19 V3) 60 to 125 V DC4), threshold binary input 19 V 3) 110 to 250 V DC4), 115 to 230 V AC, threshold binary input 88 V3)

    Unit versionFor panel surface mounting, plug-in terminal, detached operator panelFor panel surface mounting, 2-tier terminal, top/bottomFor panel surface mounting, screw-type terminal, detached operator panelFor panel ush mounting, plug-in terminal (2/3 pin AMP connector)For panel ush mounting, screw-type terminal (direct connection / ring-type cable lugs)For panel surface mounting, screw-type terminal (direct connection / ring-type cable lugs), without HMIFor panel surface mounting, plug-in terminal without HMI

    Region-specic default settings/function versions and language settingsRegion DE, 50 Hz, IEC, language: German, changeableRegion World, 50/60 Hz, IEC/ANSI, language: English (GB), changeableRegion US, 60 Hz, ANSI, language: English (US), changeableRegion FR, IEC/ANSI, language: French, changeableRegion World, IEC/ANSI, language: Spanish, changeable

    System interface (on rear of unit/Port B)No system portIEC 60870-5-103 protocol, electrical RS232IEC 60870-5-103 protocol, electrical RS485IEC 60870-5-103 protocol, 820 nm ber optic, ST connectorPROFIBUS-FMS Slave, electrical RS485PROFIBUS-FMS Slave, ber optic, single ring, ST connector5)PROFIBUS-FMS Slave, ber optic, double ring, ST connector5)PROFIBUS-DP Slave, RS485PROFIBUS-DP Slave, 820 nm ber optic, double ring, ST connector5)MODBUS, RS485MODBUS, 820 nm ber optic, ST connector5)DNP 3.0, RS485DNP 3.0, 820 nm ber optic, ST connector5)IEC 61850, 100 Mbit Ethernet, electrical, double, RJ45 connectorIEC 61850, 100 Mbit Ethernet, optical, double, LC connector5)

    DIGSI 4 / modem interface (on rear of unit/Port C)No port on rear sideDIGSI 4, electrical RS232DIGSI 4, electrical RS485DIGSI 4, optical 820 nm, ST connector

    MeasuringBasic metering (current, voltage)Slave pointer, mean values, min/max values only for position 7 = 1 and 5

    ABCDEFG

    ABCDE

    0123456999999

    99

    0123

    02

    015

    245

    1234567

    L 0 AL 0 BL 0 DL 0 EL 0 GL 0 H

    L 0 RL 0 S

    1) Only for position 7 = 02) Rated current can be selected by means of jumpers.3) The binary input thresholds can be selected in two stages by means

    of jumpers.

    4) Transition between the two auxiliary voltage ranges can be selectedby means of jumpers.

    5) Not with position 9 = B; if 9 = B; please order 6MD6 unit with

    RS485 port and separate ber-optic converter.

  • 8/12/2019 12 Catalog SIP E7 Substation Automation

    13/33

  • 8/12/2019 12 Catalog SIP E7 Substation Automation

    14/33

    Substation Automation / 6MD66Application

    2 /14 Siemens SIP Edition No. 7

    Application

    Communication

    With regard to communication betweencomponents, particular emphasis isplaced on the SIPROTEC 4 functionsrequired for energy automation. Every data item is time-stamped at its

    source, i.e. where it originates. Information is marked according to

    where it originates from (e.g. if a com-mand originates local or remote)

    The feedback to switching processes isallocated to the commands.

    Communication processes the transferof large data blocks, e.g. le transfers,independently.

    For the reliable execution of a

    command, the relevant signal is rstacknowledged in the unit executingthe command. A check-back indicationis issued after the command has beenenabled (i.e. interlocking check, target= actual check) and executed.

    In addition to the communication inter-faces on the rear of the unit, which areequipped to suit the customers require-ments, the front includes an RS232 inter-face for connection of DIGSI. This is usedfor quick diagnostics as well as for theloading of parameters. DIGSI 4 can readout and represent the entire status of the

    unit online, thus making diagnostics anddocumentation more convenient.

    Control

    The bay control units of the 6MD66 serieshave command outputs and indicationinputs that are particularly suited to therequirements of high-voltage technology.As an example, the 2-pole control of aswitching device is illustrated (see Fig. 12/11). In this example,two poles of the circuit-breaker are closed and 1 pole is open. Allother switching devices (disconnectors, grounding switches) areclosed and open in 1-pole control. A maximum of 14 switchingdevices can be controlled in this manner.

    A complete 2-pole control of all switching devices (seeFig. 12/12) is likewise possible. However more contacts arerequired for this. A maximum of 11 switching devices can becontrolled in this manner.

    A possible method to connect the switching devices to the baycontrol unit 6MD66 is shown in Fig. 12/13. There it is shownhow three switching devices Q0, Q1, and Q2 are connectedusing 1 pole control.

    Fig. 12/11 Connection diagram of the switching devices (circuit-breaker 2 poles closed,1 pole open; disconnector/grounding switch 1 pole)

    Fig. 12/12 2-pole connection diagram of circuit-breakers and disconnectors

  • 8/12/2019 12 Catalog SIP E7 Substation Automation

    15/33

    Substation Automation / 6MD66Functions

    12 /15Siemens SIP Edition No. 7

    Functions

    Switchgear interlockings

    Using the CFC (Continuous Function Chart) available in allSIPROTEC 4 units, the bay interlock conditions can, among otherthings, be conveniently congured graphically in the 6MD66 baycontrol unit. The inter-bay interlock conditions can be checkedvia the inter-relay communication (see next section) to other6MD66 devices. With the introduction of IEC 61850 communica-tion, the exchange of information for interlocking purposesis also possible via Ethernet. This is handled via the GOOSEmessage method. Possible partners are all other bay devices orprotection devices which supportIEC 61850- GOOSE message.

    In the tests prior to command output, the positions of bothkey-operated switches are also taken into consideration. Theupper key-operated switch corresponds to the S5 function (local/remote switch), which is already familiar from the 8TK switch-gear interlock system. The lower key-operated switch effects the

    changeover to non-interlocked command output (S1 function).In the position Interlocking Off the key cannot be withdrawn,with the result that non-operation of the congured interlocks isimmediately evident.

    The precise action of the key-operated switch can be set usingthe parameter switching authority.

    With the integrated function switchgear interlocking there isno need for an external switchgear interlock device.

    Furthermore, the following tests are implemented (parameteriz-able) before the output of a command: Target = Actual, i.e. is the switching device already in the

    desired position?

    Double command lockout, i.e. is another command alreadyrunning? Individual commands, e.g. grounding control can additionally

    be secured using a code.

    Fig. 12/13 Typical connection for 1-pole control

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    11

    12

    13

    14

    15

  • 8/12/2019 12 Catalog SIP E7 Substation Automation

    16/33

    Substation Automation / 6MD66Functions

    2 /16 Siemens SIP Edition No. 7

    Synchronization

    The bay control unit can, upon closingof the circuit-breaker, check whether thesynchronization conditions of both par tialnetworks are met (synchro-check). Thusan additional, external synchronization

    device is not required. The synchroniza-tion conditions can be easily speciedusing the conguration system DIGSI 4.The unit dif ferentiates between synchro-nous and asynchronous networks andreacts differently upon connection:

    In synchronous networks there areminor differences with regard to phaseangle and voltage moduli and so thecircuit-breaker response time does notneed to be taken into consideration. Forasynchronous networks however, thedifferences are larger and the range of theconnection window is traversed at a fasterrate. Therefore it is wise here to take thecircuit-breaker response time into consid-eration. The command is automaticallydated in advance of this time so that thecircuit-breaker contacts close at preciselythe right time.

    Fig. 12/14 illustrates the connection ofthe voltages.

    As is evident from Fig. 12/14, the syn-chronization conditions are tested for onephase. The important parameters forsynchronization are:

    |U min| < | U | < | U max|(Voltage modulus)

    < max (Angle difference)

    f < f max(Frequency difference)

    Using the automation functions availablein the bay control unit, it is possibleto connect various reference voltagesdepending on the setting of a disconnec-tor. Thus in the case of a double busbarsystem, the reference voltage of theactive busbar can be automatically usedfor synchronization (see Fig. 12/15).

    Alternatively the selection of the refer-ence voltage can also take place via relayswitching, if the measurement inputs arealready being used for other purposes.

    Fig. 12/14 Connection of the measured values for synchronization

    Fig. 12/15 Voltage selection for synchronization with duplicate busbar system

    Fig. 12/16 Simultaneous connection of measured values according to a two-wattmeter circuitand synchronization

  • 8/12/2019 12 Catalog SIP E7 Substation Automation

    17/33

    Substation Automation / 6MD66Functions

    12 /17Siemens SIP Edition No. 7

    Synchronization

    The bay control unit offers the optionof storing various parameter sets (upto eight) for the synchronization func-tion and of selecting one of these foroperation. Thus the dif ferent properties

    of several circuit- breakers can be takeninto consideration. These are then usedat the appropriate time. This is relevant ifseveral circuit-breakers with e.g. differentresponse times are to be served by onebay control unit.

    The measured values can be connectedto the bay control unit in accordance withFig. 12/14 (single-phase system) orFig. 12/16 (two-wattmeter circuit).

    The synchronization function can beparameterized via four tabs in DIGSI.

    Fig. 12/17 Power System Data, sheet for parameters of the synchronization function

    Fig. 12/18 General parameters of the synchronization function

    Fig. 12/19 Parameter page for asynchronous networks

    Fig. 12/20 Parameter page for asynchronous networks

    L S P 2 4 9 3 e n

    . t i f

    L S P 2 4 9 6 e n

    . t i f

    L S P 2 4 9 4 e n

    . t i f

    L S P 2 4 9 5 e n

    . t i f

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    11

    12

    13

    14

    15

  • 8/12/2019 12 Catalog SIP E7 Substation Automation

    18/33

    Substation Automation / 6MD66Communication

    2 /18 Siemens SIP Edition No. 7

    Communication

    The device is not only able to communicateto the substation control level via standardprotocol like IEC 61850, IEC 60870-5-103or others. It is also possible to communi-

    cate with other bay devices or protectiondevices. Two possibilities are available.

    Inter-relay-communication

    The function inter-relay-communicationenables the exchange of informationdirectly between 6MD66 bay controllerdevices. The communication is realizedvia Port C of the devices, so it is inde-pendent from the substation communica-tion port B. Port C is equipped with aRS485 interface. For communication overlonger distances, an external converter tober-optic cable can be used.

    An application example for inter-relay-communication is shown in Fig. 12/22.Three 6MD66 devices are used for controlof a 1 circuit-breaker bay. One deviceis assigned to each of the three circuit-breakers. By this means, the redundancyof the primary equipment is also availableon the secondary side. Even if onecircuit-breaker fails, both feeders can besupplied. Control over the entire bay isretained, even if one bay control unit fails.The three bay control units use the inter-relay-communication for interchange ofswitchgear interlocking conditions. Sothe interlocking is working completelyindependent from the substation controllevel.

    IEC 61850-GOOSE

    With the communication standardIEC 61850, a similar function like inter-relay-communication is provided withthe GOOSE communication to otherIEC 61850-devices. Since the standardIEC 61850 is used by nearly all SIPROTECdevices and many devices from othersuppliers, the number of possiblecommunication partners is large.

    The applications for IEC 61850-GOOSE arequite the same as for inter-relay-commu-nication. The most used application is theinterchange of switchgear interlockinginformation between bay devices. GOOSEuses the IEC 61850 substation Ethernet,so no separate communication port is needed.The congurationis shown in Fig. 12/23. The SIPROTEC devices are connectedvia optical Ethernet and grouped by voltage levels (110 kV and20 kV). The devices in the same voltage level can interchangethe substation-wide interlocking information. GOOSE uses thesubstation Ethernet.

    Fig. 12/21 Typical application: 1 circuit-breaker method(disconnector and grounding switch not shown)

    Fig. 12/22 Connection matrix of inter-relay communication in DIGSI 4

    Fig. 12/23 Connection for IEC 61850-GOOSE communication

    Like inter-relay-communication, GOOSE also supplies a statusinformation for supervision of the communication. In case ofinterruption, the respective information is marked as invalid.

    Therefore, non-affected information still can be used for inter-locking, and a maximum functional availability is guaranteed.

    L S P 2 2 2 7 f . t i f

  • 8/12/2019 12 Catalog SIP E7 Substation Automation

    19/33

    Substation Automation / 6MD66Functions

    12 /19Siemens SIP Edition No. 7

    Measured-value processing

    Measured-value processing is imple-mented by predened function modules,which are likewise congured usingDIGSI 4.

    The transducer modules are assigned inthe DIGSI 4 assignment matrix to currentand voltage channels of the bay controlunit. From these input variables, theyform various computation variables (seeTable 12/1).

    The individual transducer modules can beactivated in the functional scope of theunit and will then appear in the DIGSI 4assignment matrix with the input chan-nels and output variables from Table 1.The output variables can then be assignedto the system interface or representedin the measured value window in thedisplay.

    Sample presentation of the measuredvalue display.

    Fig. 12/24 DIGSI 4 Parameter view transducer packets

    Table 12/1 Properties of measured-value processing

    Fig. 12/25

    Name of thetransducer module

    Max. availability oftransducers on theunit (can be set viathe functional scope)

    Required inputchannels

    Calculated variables(= output variables)

    Transducer V x 1 V V , f

    Transducer I x 1 I I , f

    Transducer packet1 phase

    x 3 V , I V , I , P, Q, S, ,cos (PF), sin , f

    Transducer packet3 phase

    x 1 V 1, V 2, V 3, I 1, I 2, I 3 V 0, V 1, V 2, V 3, V 12,V 23, V 31, I 0, I 1, I 2, I 3,

    P, Q, S, , cos (PF),sin , f

    Transducer packettwo-wattmeter circuit

    x 1 V 1, V 2, I 1, I 2 V 12, V 13, I 2, I 3, P, Q, S, , cos (PF), sin , f

    L S P 2 1 8 9 f . t i f

    L S P 2 2 2 8 f . t i f

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    11

    12

    13

    14

    15

  • 8/12/2019 12 Catalog SIP E7 Substation Automation

    20/33

    Substation Automation / 6MD66Functions

    2 /20 Siemens SIP Edition No. 7

    The connection of the input channels canbe chosen without restriction. For thetwo-wattmeter circuit, the interface con-nection should be selected in accordancewith Fig. 12/26. The two-wattmeter circuitenables the complete calculation of athree-phase system with only two voltageand two current transformers.

    Metered values

    For internal metering, the unit cancalculate an energy metered value fromthe measured current and voltage values.If an external meter with a metering pulseoutput is available, the bay control unitcan obtain and process metering pulsesvia an indication input.

    The metered values can be displayed andpassed on to a master unit. A distinctionis made between forward, reverse, activeand reactive power ( kWh, kvarh).

    Automation

    With integrated logic, the user can set, via a graphic interface(CFC, Continuous Function Chart), specic functions for theautomation of switchgear or substation. Functions are activatedvia function keys, binary input or via communication interface.Processing of internal indications or measured values is alsopossible.

    Switching authorization / key-operated switch

    The switching authorization (control authorization) (interlocked/non-interlocked, corresponds to key-operated S1 in the 8TK

    interlock system) and the switching authority (local/remote,corresponds to key-operated S5 for 8TK) can be preset for theSIPROTEC 4 bay control unit using key-operated switches. Theposition of both keys is automatically evaluated by commandprocessing. The key for operation without interlocks cannot beremoved when in the position non-interlocked, such that thismode of operation is immediately recognizable (see also page12/15, Section Switchgear interlockings).

    Every change in the key-operated switch positions is logged.

    Chatter blocking

    Chatter blocking feature evaluates whether, in a conguredperiod of time, the number of status changes of indication inputexceeds a specied gure. If exceeded, the indication input isblocked for a certain period, so that the communication line tothe master unit will not be overloaded by disturbed inputs.

    For every binary input, it is possible to set separately whetherthe chatter blocking should be active or not. The parameters(number of status changes, test time, etc.) can be set once perunit.

    Fig. 12/26 Two-wattmeter circuit (connection to bay control unit)

    Indication / measured value blocking

    To avoid the transmission of information to the master unit dur-ing works on the bay, a transmission blocking can be activated.

    Indication ltering

    Indications can be ltered and delayed.

    Filtering serves to suppress brief changes in potential at theindication input. The indication is passed on only if the indica-tion voltage is still present after a set period of time.The lter time can be set from 0 to 24 hours in 1 ms steps. It isalso possible to set the lter time so that it can, if desired, beretriggered.

    Furthermore, the hardware lter time can be taken into consid-eration in the time stamp; i.e. the time stamp of a message thatis detected as arriving will be predated by the known, constanthardware lter time. This can be set individually for every binaryinput in a 6MD66 bay control unit.

  • 8/12/2019 12 Catalog SIP E7 Substation Automation

    21/33

    Substation Automation / 6MD66Functions

    12 /21Siemens SIP Edition No. 7

    Auto-reclosure (ANSI 79)

    The 6MD66 is equipped with an auto-reclosure function (AR). The functionincludes several operating modes: Interaction with an external device

    for auto-reclosure via binary inputsand binary outputs; also possible withinteraction via IEC 61850-GOOSE

    Control of the internal AR function byexternal protection

    3-pole auto-reclosure for all types offaults; different dead times are availabledepending on the type of the fault

    1-pole auto-reclosure for 1-phase faults,no reclosing for multi-phase faults

    1-pole auto-reclosure for 1-phase faultsand 2-phase faults, no reclosing formulti-phase faults.

    1-pole auto-reclosure for 1-phase and3-pole auto-reclosure for multi-phasefaults

    1-pole auto-reclosure for 1-phase faults and 2-phase faults and3-phase auto-reclosure for multi-phase faults

    Multiple-shot auto-reclosure Interaction with the internal synchro-check Monitoring of the circuit-breaker auxiliary contacts

    In addition to the above-mentioned operating modes, severalother operating principles can be employed by means of theintegrated programmable logic (CFC). Integration of auto-reclosure in the feeder protection allows the line-side voltagesto be evaluated. A number of voltage-dependent supplementary

    functions are thus available: DLC

    By means of dead-line-check (DLC), reclosure is effected onlywhen the line is deenergized (prevention of asynchronousbreaker closure)

    ADTThe adaptive dead time (ADT) is employed only if auto-reclosure at the remote station was successful (reduction ofstress on equipment).

    RDTReduced dead time (RDT) is employed in conjunction withauto-reclosure where no teleprotection method is employed:When faults within the zone extension but external to the pro-

    tected line of a distance protection are switched off for rapidauto-reclosure (RAR), the RDT function decides on the basis ofmeasurement of the return voltage from the remote stationwhich has not tripped whether or not to reduce the dead time.

    Fig. 12/27 Parameterization of time management

    Breaker failure protection (ANSI 50BF)

    The 6MD66 incorporates a two-stage circuit-breaker failureprotection to detect failures of tripping command execution,for example, due to a defective circuit breaker. The currentdetection logic is phase-selective and can therefore also be usedin single-pole tripping schemes. lf the fault current is not inter-rupted after a settable time delay has expired, a retrip commandor a busbar t rip command will be generated. The breaker failureprotection can be initiated by external devices via binary inputsignals or IEC 61850 GOOSE messages.

    Time management

    The 6MD66 bay control units can, like the other units in theSIPROTEC 4 range, be provided with the current time by anumber of different methods: Via the interface to the higher-level system control

    (PROFIBUS FMS or IEC 61850) Via the external time synchronization interface on the rear

    of the unit (various protocols such as IRIG B and DCF77 arepossible)

    Via external minute impulse, assigned to a binary input From another bay control unit by means of inter-relay

    communication Via the internal unit clock.

    Fig. 12/27 illustrates the settings that are possible on the DIGSIinterface.

    L S P 2 2 2 9 f . t i f

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    11

    12

    13

    14

    15

  • 8/12/2019 12 Catalog SIP E7 Substation Automation

    22/33

  • 8/12/2019 12 Catalog SIP E7 Substation Automation

    23/33

    Substation Automation / 6MD66Technical data

    12 /23Siemens SIP Edition No. 7

    Output relay

    Live contact

    Number of command relays,single pole 6MD662

    6MD663

    6MD664

    Switching capacity, commandrelay Make Break Break (at L/R 50 ms) Max. switching voltage

    Max. contact continuous current Max. (short-duration) current for 4 sSwitching capacity,

    live contact ON and OFF Max. switching voltage Max. contact continuous currentMax. make-timeMax. chatter timeMax. break time

    1 NC/NO (can be set via jumper:Factory setting is Break contact,i.e. the contact is normally open butthen closes in the event of an error)

    25, grouping in 2 groups of 4,1 group of 3, 6 groups of 2 and twoungrouped relays35, grouping in 3 groups of 4,1 group of 3, 9 groups of 2 and twoungrouped relays45, grouping 4 groups of 4,1 group of 3, 12 groups of 2 plus twoungrouped relays

    max. 1000 W/ VAmax. 30 VA25 VA250 V

    5 A15 A

    20 W/VA250 V1 A8 ms2.5 ms2 ms

    LED

    Number RUN (green) ERROR (red) Display (red), function can be

    allocated

    1114

    Unit design

    Housing 7XP20

    Type of protection acc. toEN60529 in the surface-mounting

    housing in the ush-mounting housing front rearWeightFlush-mounting housing,integrated local control

    6MD663 6MD664Surface-mounting housing,without local control,with assembly angle 6MD663 6MD664Detached local control

    For dimensions drawings,see part 14

    IP20

    IP51IP20

    approx. 10.5 kgapprox. 11 kg

    approx. 12.5 kgapprox. 13 kgapprox. 2.5 kg

    General unit data

    Analog inputs

    Rated frequency

    Rated current I N

    Rated voltage V N

    Power consumption at I N = 1 A at I N = 5 A Voltage inputsMeasurement range current I Thermal loading capacity

    Measurement range voltage V Max. permitted voltageTransducer inputsMeasurement rangeMax. permitted continuous currentInput resistance,recorded power loss at 24 mA

    50 or 60 Hz (adjustable, dependingon the order number)1 or 5 A (can be changed via plug-in jumper)

    100 V, 110 V, 125 V, 100 V3,110 V3 can be adjusted usingparameters

    < 0.1 VA< 0.5 VA< 0.3 VA with 100 VUp to 1.2 times the rated current12 A continuous, 15 A for 10 s,200 A for 1 sUp to 170 V (rms value)170 V (rms value) continuous

    DC 24 mA DC 250 mA10 1 %5.76 mW

    Power supply

    Rated auxiliary voltages

    Permitted tolerancePermitted ripple of the ratedauxiliary voltagePower consumption Max. at DC 60 to 250 V Max. at DC 24 to 48 V Typical at DC 60 to 250 V Typical at DC 24 to 48 V (typical = 5 relays picked up + live contact active +

    LCD display illuminated +2 interface cards plugged in)

    Bridging time at DC 24 and 60 V at DC 48 and 110 V

    DC 24 to 48 V, DC 60 to 125 V,DC 110 to 250 V-20 % to +20 %15 %

    20 W21.5 W17.5 W18.5 W

    20 ms 50 ms

    Binary inputs

    Number 6MD662 6MD663 6MD664Rated voltage rangePick-up value (range can be setusing jumpers for every binaryinput)Function (allocation)Minimum voltage threshold(presetting) for rated voltage 24, 48, 60 V for rated voltage 110 V for rated voltage 220, 250 VMaximum permitted voltageCurrent consumption, excited for 3 ms

    Permitted capacitive coupling ofthe indication inputsMinimum impulse duration formessage

    355065DC 24 to 250 V (selectable)DC 17, 73 or 154 V

    Can be assigned freely

    DC 17 VDC 73 VDC 154 VDC 300 Vapprox. 1.5 mAapprox. 50 mA to increase pickuptime220 nF

    4.3 ms

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    11

    12

    13

    14

    15

  • 8/12/2019 12 Catalog SIP E7 Substation Automation

    24/33

    Substation Automation / 6MD66Technical data

    2 /24 Siemens SIP Edition No. 7

    Ethernet, electricalConnection for ush-mounting housing/

    surface-mounting housing withdetached operator panel

    Distance

    Test voltage

    Two RJ45 connectors,mounting location B

    Max. 20 m/65.6 ft

    AC 500 V against groundEthernet, opticalConnection for ush-mounting housing/

    surface-mounting housing withdetached operator panel

    Optical wavelengthDistance

    Integrated LC connector for FOconnection, mounting location B

    1300 nm1.5 km/0.9 miles

    Electrical tests

    Specications

    Standards IEC 60255 (product standards)ANSI/IEEE C37.90.0/.1/.2DIN 57435 Part 303For further standards see specictests

    Insulation tests

    StandardsVoltage test (100 % test)All circuits except for auxiliarysupply, binary inputs,communication and time synchro-nization interfacesVoltage test (100 % test)Auxiliary voltage and binaryinputsVoltage test (100 % test)only isolated communication

    and time synchronizationinterfacesSurge voltage test (type test)All circuits except for communi-cation and time synchronizationinterfaces, class III

    IEC 60255-5 and IEC 60870-2-12.5 kV (rms), 50 Hz

    DC 3.5 kV

    500 V (rms value), 50 Hz

    5 kV (peak); 1.2/50 s; 0.5 J;3 positive and 3 negative surgesat intervals of 5 s

    EMC tests for noise immunity; type test

    Standards

    High frequency testIEC 60255-22-1, class IIIand DIN 57435 part 303, class IIIDischarge of static electricityIEC 60255-22-2 class IVEN 61000-4-2, class IVExposure to RF eld, non-modulated IEC 60255-22-3(report), class IIIExposure to RF eld, amplitude-modulated IEC 61000-4-3, class IIIExposure to RF eld, pulse-modulatedIEC 61000-4-3/ ENV 50204, class IIIFast transient interference burstsIEC 60255-22-4, IEC 61000-4-4,class IV

    IEC 60255-6, IEC 60255-22 (productstandards)EN 50082-2 (generic standard)DIN 57 435 Part 3032.5 kV (peak value), 1 MHz; = 15 ms400 pulses per s; duration 2 s

    8 kV contact discharge; 15 kV airdischarge; both polarities; 150 pF; Ri = 330 10 V/m; 27 to 500 MHz

    10 V/m; 80 to 1000 MHz; 80 % AM;1 kHz10 V/m; 900 MHz; repetition frequen-cy 200 Hz; duty cycle 50 %

    4 kV; 5/50 ns; 5 kHz; burst length =15 ms; repetition frequency 300 ms;both polarities; Ri = 50 ;test duration 1 min

    Serial interfaces

    System interfaces

    PROFIBUS FMS,Hardware version depending onOrder No.:PROFIBUS ber optic cable

    Baud rate Optical wave length Permissible path attenuation Distance, bridgeablePROFIBUS RS485 Baud rate Distance, bridgeable

    PROFIBUS RS232 Baud rate Distance, bridgeable

    ST connector

    max 1.5 Mbaud820 nmmax. 8 dB for glassber 62.5/125 mmax. 1.5 km9-pin SUB-D connectormax. 12 Mbaudmax. 1000 m at 93.75 kBaudmax. 100 m at 12 Mbaud9-pin SUB-D connector4800 to 115200 baudmax. 15 m

    Time synchronization DCF77/IRIG B signal

    ConnectionInput voltage levelConnection allocation Pin 1 Pin 2 Pin 3 Pin 4 Pin 7 Pin 8 Pin 5, 9 Pin 6Message type (IRIG B, DCF, etc.)

    9-pin SUB-D connectoreither 5 V, 12 V or 24 V24 V input for minute impulse5 V input for minute impulseReturn conductor for minute impulseReturn conductor for time message5 V input for minute impulse24 V input for time messageScreenNot allocatedCan be adjusted using parameters

    Control interface for RS232 DIGSI 4

    Connection Front side, non-isolated, 9-pinSUB-D connector

    DIGSI 4 interface (rear of unit)

    Fiber optic Baud rate

    Optical wave length Permissible path attenuation

    Distance, bridgeableRS485 Baud rate Distance, bridgeable

    RS232Baud rate

    Distance, bridgeable

    ST connectormax. 1.5 Mbaud

    820 nmmax. 8 dB for glass ber of62.5/125 mmax. 1.5 km9-pin SUB-D connectormax. 12 Mbaudmax. 1000 m at 93.75 kBaudmax. 100 m at 12 MBaud9-pin SUB-D connector4800 to 115200 Baudmax. 15m

    Interface for inter-unit communication

    RS485 Baud rate Distance, bridgeable

    9-pin SUB-D connectormax. 12 Mbaudmax. 1000 m at 93.75 kBaud

    max. 100 m at 12 Mbaud

    Ethernet interface

    IEC 61850 protocol

    Isolated interface for data transfer: to a control center with DIGSI between SIPROTEC 4 relaysTransmission rate

    Port B, 100 Base T acc. toIEEE 802.3

    1000 MBit

  • 8/12/2019 12 Catalog SIP E7 Substation Automation

    25/33

    Substation Automation / 6MD66Technical data

    12 /25Siemens SIP Edition No. 7

    During transportStandardsVibrationIEC 60255-21-1, class 2IEC 60068-2-6

    ShockIEC 60255-21-2, class 1IEC 60068-2-27

    Continuous shockIEC 60255-21-2, class 1IEC 60068-2-29

    IEC 60255-21 and IEC 60068-2Sinusoidal5 to 8 Hz: 7.5 mm amplitude;8 to 150 Hz: 2 g accelerationFrequency sweep 1 octave/min20 cycles in 3 orthogonal axesHalf-sinusoidalAcceleration 15 g , duration 11 ms,3 shockseach in both directions 3 axesHalf-sinusoidalAcceleration 10 g , duration 16 ms,1000 shocks in both directions of the3 axes

    Climatic stress tests

    Temperatures

    StandardsRecommended temperatureduring operationTemporary permissible tempera-ture limit during operation(The legibility of the display maybe impaired above 55 C/131 F)Limit temperature during storageLimit temperature duringtransportStorage and transport withstandard factory packaging

    IEC 60255-6-5 to +55 C 25 to 131 F

    -20 to +70 C -4 to 158 F

    -25 to +55 C -13 to 131 F-25 to +70 C -13 to 158 F

    Humidity

    Permissible humidity stressWe recommend arranging theunits in such a way that they arenot exposed to direct sunlight or

    pronounced temperature changesthat could cause condensation

    Annual average 75 % relativehumidity; on 56 days a year up to93 % relative humidity; condensationduring operation is not permitted

    CE conformity

    The product meets the stipulations of the guideline of the council ofthe European Communities for harmonization of the legal requirementsof the member states on electro-magnetic compatibility (EMC directive2004/108/EEC previous 89/336/EEC) and product use within certainvoltage limits (low-voltage directive 2006/95/EEC previous 73/23/EEC).The product conforms with the international standard of the IEC 60255series and the German national standard DIN VDE 57 435,Part 303. Theunit has been developed and manufactured for use in industrial areas inaccordance with the EMC standard.Further applicable standards: ANSI/IEEE C37.90.0 and C37.90.1This conformity is the result of a test that was performed by Siemens AGin accordance with Article 10 of the directive in conformance withgeneric standards EN 50081-2 and EN 50082-2 for the EMC directive andEN 60255-6 for the low-voltage directive.

    EMC tests for noise immunity; type test (continued)

    High-energy surge voltages(SURGE),IEC 61000-4-5 installation class IIIAuxiliary supply

    Measurement inputs, binary inputsand relay outputsConducted RF, amplitude-modulated IEC 61000-4-6, class IIIMagnetic eld with powerfrequencyIEC 61000-4-8, class IV;IEC 60255-6Oscillatory surge withstandcapabilityANSI/IEEE C37.90.1

    Fast transient surge withstandcapabilityANSI/IEEE C37.90.1

    Radiated electromagnetic interfe-rence ANSI/IEEE C37.90.2Damped oscillationsIEC 60894, IEC 61000-4-12

    Impulse: 1.2/50 s

    common mode: 2 kV; 12 , 9 Fdifferential mode:1 kV; 2 , 18 Fcommon mode: 2 kV; 42 , 0.5 Fdifferential mode: 1 kV; 42 , 0.5 F10 V; 150 kHz to 80 MHz; 80 % AM;1 kHz30 A/m continuous; 300 A/m for3 s; 50 Hz0.5 mT; 50 Hz

    2.5 to 3 kV (peak); 1 to 1.5 MHz

    damped wave; 50 surges per second;duration 2 s; Ri = 150 to 200 4 to 5 kV; 10/150 ns; 50 impulsesper second;both polarities; duration 2 s ;

    Ri = 80 35 V/m; 25 to 1000 MHz

    2.5 kV (peak value), 100 kHzpolarity alternating, 1 MHz, 10 and50 MHz, Ri = 200

    EMC tests for interference emission; type tests

    StandardRadio interference voltage on linesonly auxiliary supplyIEC-CISPR 22Interference eld strengthIEC-CISPR 22

    EN 50081-1 (Basic specication)150 kHz to 30 MHzclass B

    30 to 1000 MHzclass B

    Mechanical dynamic tests

    Vibration, shock stress and seismic vibration

    During operationStandardsVibrationIEC 60255-21-1, class 2IEC 60068-2-6

    ShockIEC 60255-21-2, class 1IEC 60068-2-27

    Vibration during earthquakeIEC 60255-21-2, class 1IEC 60068-3-3

    IEC 60255-21 and IEC 60068-2Sinusoidal10 to 60 Hz: 0.075 mm amplitude;60 to 150 Hz: 1 g accelerationFrequency sweep 1 octave/min20 cycles in 3 orthogonal axesHalf-sinusoidalAcceleration 5 g , duration 11 ms,3 shocks each in both directions ofthe 3 axesSinusoidal1 to 8 Hz: 4 mm amplitude(horizontal axis)1 to 8 Hz: 2 mm amplitude(vertical axis)8 to 35 Hz: 1 g acceleration(horizontal axis)8 to 35 Hz: 0,5 g acceleration(vertical axis)Frequency sweep 1 octave/min1 cycle in 3 orthogonal axes

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    11

    12

    13

    14

    15

  • 8/12/2019 12 Catalog SIP E7 Substation Automation

    26/33

    Substation Automation / 6MD66Selection and ordering data

    2 /26 Siemens SIP Edition No. 7

    Description Order No. Order code

    6MD66 high-voltage bay control unit 6MD662 - - 0 -

    Processor module with power supply, input/output modules with a total of:Number of inputs and outputs35 single-point indications, 22 1-pole single commands,

    3 single commands to common potential, 1 live contact, 3 x current4 x voltage via direct CT inputs, 2 measuring transducer inputs

    Current transformer I N1 A1 A / 150 % I N 1 A / 200 % I N 5 A5 A / 150 % I N 5 A / 200 % I N

    Rated auxiliary voltage (power supply, indication voltage)DC 24 to 48 V, threshold binary input 19 V2) DC 60 V, threshold binary input 19 V2)

    DC 110 V, threshold binary input 88 V2)DC 220 to 250 V, threshold binary input 176 V 2)

    Unit versionFor panel ush mounting, with integr. local operation, HMI, plug-in terminal (2/3-pole AMP socket)For panel ush mounting, with integr. local operation, graphic display,keyboard, screw-type terminals (direct connec./ring-type cable lugs)

    Region-specic default settings / function and language settingsRegion DE, 50Hz, language: German, changeableRegion World, 50/60 Hz, language: English (GB), changeableRegion US, ANSI, language: English (US), changeableRegion World, 50/60 Hz, language: French, changeableRegion World, 50/60 Hz, language: Spanish, changeable

    System interface (on rear of unit, port B)No system interfaceIEC 60870-5-103 protocol, electrical RS485IEC 60870-5-103 protocol, optical 820 nm, ST connectorPROFIBUS-FMS Slave, electrical RS485PROFIBUS-FMS Slave, optical, single ring, ST connectorPROFIBUS-FMS Slave, optical, double ring, ST connectorPROFIBUS-DP Slave, electrical RS485PROFIBUS-DP Slave, 820 nm ber, double ring, ST plugsPROFIBUS-DP Slave, double electrical RS485 (second module on port D)IEC 61850, 100 Mbit Ethernet, electrical, double, RJ45 connectorIEC 61850, 100 Mbit Ethernet, optical, double, LC connector

    Function interface (on rear of unit, port C andD)No function interfaceDIGSI 4, electrical RS232, port CDIGSI 4, electrical RS485, port CDIGSI 4, optical 820 nm, ST connector, port DWith RS485 interface for inter-relay communication, port C and DIGSI 4With RS485 interface for inter-relay communication, port C and DIGSI 4,with optical 820 nm, ST connector, port D

    ABCDE

    02345699999

    01234

    5

    2345

    D

    E

    123567

    L 0 AL 0 BL 1 AL 0 RL 0 S

    1) The binary input thresholds can be selected in two stages by means

    of jumpers.

    seenextpage

  • 8/12/2019 12 Catalog SIP E7 Substation Automation

    27/33

    Substation Automation / 6MD66Selection and ordering data

    12 /27Siemens SIP Edition No. 7

    Description Order No. Order code

    6MD66 high-voltage bay control unit 6MD662 - - 0 -

    Measured-value processingFull measured-value processing and displayNo measured-value processing and no display

    SynchronizationWith synchronizationWithout synchronization

    Protection functionWithout protection functionsWith auto-reclosure (AR)With circuit-breaker failure protectionWith auto-reclosure and circuit-breaker failure protectionWith fault recording

    01234

    AF

    AF

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    11

    12

    13

    14

    15

  • 8/12/2019 12 Catalog SIP E7 Substation Automation

    28/33

    Substation Automation / 6MD66Selection and ordering data

    2 /28 Siemens SIP Edition No. 7

    Description Order No. Order code

    6MD66 high-voltage bay control unit 6MD66 - - 0 -

    Processor module with power supply, input/output modules with a total of:Number of inputs and outputs50 single-point indications, 32 1-pole single commands,

    3 single commands to common potential, 1 live contact,3 x current, 4 x voltage via direct CT inputs2 measuring transducer inputs 365 single-point indications, 42 1-pole single commands,3 single commands to common potential, 1 live contact,3 x current, 4 x voltage via direct CT inputs2 measuring transducer inputs

    Current transformer I N1 A1 A / 150 % I N 1 A / 200 % I N 5 A5 A / 150 % I N 5 A / 200 % I N (for 6MD664)

    Rated auxiliary voltage (power supply, indication voltage)DC 24 to 48 V, threshold binary input 19 V1) DC 60 V, threshold binary input 19 V1)

    DC 110 V, threshold binary input 88 V1)

    DC 220 to 250 V, threshold binary input 176 V 1)

    Unit versionFor panel surface mounting, detached operator panel, for mounting in low-voltage case,screw-type terminals (direct connec./ring-type cable lugs)For panel ush mounting, with integr. local operation, graphic display, keyboard,screw-type terminals (direct connec./ring-type cable lugs)For panel surface mounting, w /o operator unit, for mounting in low-voltage case,screw-type terminals (direct connec./ring-type cable lugs)

    Region-specic default settings / function and language settingsRegion DE, 50 Hz, language: German, changeableRegion World, 50/60 Hz, language: English (GB), changeableRegion US, ANSI, language: English (US), changeableRegion World, 50/60 Hz, language: French, changeableRegion World, 50/60 Hz, language: Spanish, changeable

    System interface (on rear of unit, port B)No system interfaceIEC 60870-5-103 protocol, electrical RS485IEC 60870-5-103 protocol, optical 820 nm, ST connectorPROFIBUS-FMS Slave, electrical RS485PROFIBUS-FMS Slave, optical, single ring, ST connectorPROFIBUS-FMS Slave, optical, double ring, ST connectorPROFIBUS-DP Slave, electrical RS485PROFIBUS-DP Slave, optical 820 nm, double ring, ST connectorPROFIBUS-DP Slave, double electrical RS485 (second module on port D)PROFIBUS-DP Slave, double optical double ring ST (second module on por t D)IEC 61850, 100 Mbit Ethernet, electrical, double, RJ45 connectorIEC 61850, 100 Mbit Ethernet, optical, double, LC connector

    C

    E

    F

    ABCDE

    023456999999

    2345

    3

    4

    123567

    L 0 AL 0 BL 1 AL 1 BL 0 RL 0 S

    1) The binary input thresholds can be selected in two stages by means

    of jumpers.

    see next page

  • 8/12/2019 12 Catalog SIP E7 Substation Automation

    29/33

    Substation Automation / 6MD66Selection and ordering data

    12 /29Siemens SIP Edition No. 7

    Description Order No.

    6MD66 high-voltage bay control unit 6MD66 - - 0

    Function interface (on rear of unit, port C and D)No function interfaceDIGSI 4, electrical RS232, port C

    DIGSI 4, electrical RS485, port CDIGSI 4, optical 820 nm, ST connector, port D1) With RS485 interface for inter-relay communication, port C and DIGSI 4With RS485 interface for inter-relay communication, port C and DIGSI 4,with optical 820 nm, ST connector, port D 1)

    Measured-value processingFull measured-value processing and displayNo measured-value processing and no display 2)

    SynchronizationWith synchronizationWithout synchronization

    Protection functionWithout protection functionsWith auto-reclosure (AR) incl. fault recordingWith circuit-breaker failure protection (BF) incl. fault recordingWith auto-reclosure (AR) and circuit-breaker failure protection (BF) incl. fault recordingFault recording

    1) Not for double PROFIBUS-DP (position 11 =9-L1A or 9-L1B).2) Only for position 16 = 0 (without protection functions).

    01234

    01

    234

    5

    AF

    AF

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    11

    12

    13

    14

    15

  • 8/12/2019 12 Catalog SIP E7 Substation Automation

    30/33

  • 8/12/2019 12 Catalog SIP E7 Substation Automation

    31/33

    Substation Automation / 6MD66Connection diagrams

    12 /31Siemens SIP Edition No. 7

    Fig. 12/33 CPU, C-CPU 2For unit 6MD662*-****1-0AA0 and6MD662*-****2-0AA0(DIGSI interface, electrical,system interface optical or electrical)

    Fig. 12/34 CPU, C-CPU 2For unit 6MD662*-****3-0AA0(DIGSI interface, optical,system interface optical or electrical)

    Fig. 12/35 CPU, C-CPU 2For unit 6MD662*-****4-0AA0(Inter-relay communication interface electrical,system interface optical or electrical)

    Fig. 12/36 CPU, C-CPU 2For unit 6MD662*-****5-0AA0(DIGSI interface, optical,Inter-relay communicationinterface electrical,system interface optical or electrical)

    Bay unit 6MD662

    or

    or

    or 1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    11

    12

    13

    14

    15

  • 8/12/2019 12 Catalog SIP E7 Substation Automation

    32/33

    Substation Automation / 6MD66Connection diagrams

    2 /32 Siemens SIP Edition No. 7

    Fig. 12/37 Module 1,indications, commands

    Fig. 12/39 Module 3,indications, commands

    Fig. 12/40 Module 4,indications, commands

    Fig. 12/41 Module 5,measuring values, commands

    Fig. 12/38 Module 2,indications, commands

    Bay unit 6MD664

  • 8/12/2019 12 Catalog SIP E7 Substation Automation

    33/33

    Substation Automation / 6MD66Connection diagrams

    or

    Fig. 12/42 CPU, C-CPU 2For unit 6MD664*-****1-0AA0and 6MD664*-****2-0AA0(DIGSI interface electric,system interface optical optical or electric)

    Fig. 12/43 CPU, C-CPU 2For unit 6MD664*-****3-0AA0(DIGSI interface optical,system interface optical optical or electric)

    Fig. 12/44 CPU, C-CPU 2For unit 6MD664*-****4-0AA0(Inter-relay communicationinterface electric,system interface optical or electric)

    Fig. 12/45 CPU, C-CPU 2For unit 6MD664*-****5-0AA0(DIGSI interface optical,(Inter-relay communication electric,system interface optical or electric)

    Bay unit 6MD664

    or

    or

    or 1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    11

    12

    13

    14