10017 - ei - 1 - hilti.com · 10017 - ei - 1 drawn: typical details td-ei-gp122-c notes: 1. this...

7
ELEVATION (SCALE 5/8"=1'-0") ISOMETRIC (SCALE 5/8"=1'-0") Qty.* Description Item No.* Piece Mark 2 GIRDER MIQ-90 2119866 1 2 GIRDER MIQ-90 2119866 2 2 MIQC-C90 BASE PLATE 2120144 3 4 MIQC-90-HT-V 2134818 4 ** MIQM 3/8" WING NUT 2183584 5 2 END CAP - MIA-EC-90 432077 6 8 USE APPROPRIATE HILTI ANCHOR VARIES 7 1 1 2 2 3 3 4 4 5 5 6 6 A A B B C C D D E E F F C:\Hilti Vault\Designs\Projects\10000 Internal Projects\10017 Typicals\E&I STANDS\TD-E All loading and design criteria supplied by customer is assumed accurate. Only the stated Design Assumptions were considered, and must be verified by the responsible Engineer of Record (EOR). The basis of Hilti component and connection design is the published data in the current Hilti Technical Guide, including material and cross-section properties, allowable load values, factors of safety, methods of calculation, and limiting factors. The EOR must verify suitability for any specific application, and the capacity of the supportive structure to receive the shown configuration and associated reaction loads. Modification to components and/or design may alter performance and must be evaluated by the EOR. PROJECT NUMBER: PAPER SIZE: ANSI A DESIGNED: CHECKED: REVIEWED: OMO GAB BAP JWP PROJECT NAME: PROJECT DESCRIPTION: ELECTRICAL & INSTRUMENTATION PANEL STAND REVISION HISTORY PROJECT JOB SHEET 10017 EI 1 - - DRAWN: TYPICAL DETAILS TD-EI-GP121-C W 7 1 1 4 6 3 S S S S H H 1 AS REQ'D AS REQ'D S 2 5 2 NO: DESCRIPTION: DATE: A NOT FOR CONSTRUCTION 10/06/2017 NOTES: 1. THIS DRAWING REPRESENTS A COMMON CONFIGURATION FOR THIS APPLICATION. THE ELECTRICAL AND INSTRUMENTATION SUPPORT IS LOAD RATED AND DIMENSIONALLY LIMITED BASED ON HILTI -PUBLISHED STATIC LOAD DATA AND DESIGN METHODOLOGIES, AND GENERIC, NON-PROJECT SPECIFIC DESIGN ASSUMPTIONS. THE ENGINEERING OF RECORD SHALL EVALUATE THIS SUPPORT TO DETERMINE ITS SUITABILITY FOR THE ACTUAL, PROJECT SPECIFIC DESIGN CRITERIA AND REQUIREMENTS. 2. ALL LOADS ASSUMED TO ACT AT THE CENTER OF THE HORIZONTAL SUPPORT BEAMS, NO ECCENTRIC LOADS INCLUDED. PANEL/INSTRUMENT CONNECTION HARDWARE MUST BE CHECKED SEPARATELY. 3. DESIGN ASSUMPTIONS: IBC 2012 BUILDING CODE; SEE TABLE FOR DESIGN LOADS (STATIC U.N.O.). 4. REFER TO COMPONENT MANUFACTURER'S IFU'S FOR REQUIRED INSTALLATION INFORMATION. 5. FOR APPLICABLE CONCRETE OR STEEL ANCHOR DESIGN CONTACT HILTI OR THE PROJECT SITE ENGINEER OF RECORD. Longitudinal Transverse V e r t i c a l LRFD, lbs ASD, lbs Transverse Longitudinal Transverse Longitudinal Max H1, in 42 400 340 280 100 78 Max H, in Max W, in 48 A. RATED FOR 200 LBS FACTORED VERTICAL LOAD (LRFD). B. RATED FOR 200 LBS ALLOWABLE VERTICAL LOAD (ASD). C. ANCHOR CAPACITY NOT CONSIDERED. ** ASSUME 4 PER PANEL GENERIC PANEL CONFIGURATION. PANEL BY OTHERS

Upload: leduong

Post on 25-Jan-2019

223 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: 10017 - EI - 1 - hilti.com · 10017 - ei - 1 drawn: typical details td-ei-gp122-c notes: 1. this drawing represents a common configuration for this application. the electrical and

ELEVATION

(SCALE 5/8"=1'-0")

ISOMETRIC

(SCALE 5/8"=1'-0")

Qty.*DescriptionItem No.*Piece Mark

2GIRDER MIQ-9021198661

2GIRDER MIQ-9021198662

2MIQC-C90 BASE PLATE21201443

4MIQC-90-HT-V21348184

**MIQM 3/8" WING NUT21835845

2END CAP - MIA-EC-904320776

8USE APPROPRIATE HILTI ANCHORVARIES7

1

1

2

2

3

3

4

4

5

5

6

6

A A

B B

C C

D D

E E

F F

C:\Hilti Vault\Designs\Projects\10000 Internal Projects\10017 Typicals\E&I STANDS\TD-EI-GP121-C\TD-EI-GP121-C.dwg

All loading and design criteria supplied by customer is assumed accurate. Only the stated Design

Assumptions were considered, and must be verified by the responsible Engineer of Record (EOR).

The basis of Hilti component and connection design is the published data in the current Hilti

Technical Guide, including material and cross-section properties, allowable load values, factors of

safety, methods of calculation, and limiting factors. The EOR must verify suitability for any specific

application, and the capacity of the supportive structure to receive the shown configuration and

associated reaction loads. Modification to components and/or design may alter performance and

must be evaluated by the EOR.

PROJECT NUMBER:PAPER SIZE:

ANSI A

DESIGNED:CHECKED: REVIEWED:

OMOGAB BAP JWP

PROJECT NAME:

PROJECT DESCRIPTION:

ELECTRICAL & INSTRUMENTATION

PANEL STAND

REVISION HISTORY

PROJECT JOB SHEET

10017 EI 1- -

DRAWN:

TYPICAL DETAILS

TD-EI-GP121-C

W

7

1 1

4

6

3

H

H1

AS

REQ'D

AS REQ'D

2

5

2

NO: DESCRIPTION: DATE:

A NOT FOR CONSTRUCTION

10/06/2017

NOTES:

1. THIS DRAWING REPRESENTS A COMMON CONFIGURATION FOR THIS APPLICATION. THE ELECTRICAL AND INSTRUMENTATION SUPPORT IS LOAD RATED AND

DIMENSIONALLY LIMITED BASED ON HILTI -PUBLISHED STATIC LOAD DATA AND DESIGN METHODOLOGIES, AND GENERIC, NON-PROJECT SPECIFIC DESIGN

ASSUMPTIONS. THE ENGINEERING OF RECORD SHALL EVALUATE THIS SUPPORT TO DETERMINE ITS SUITABILITY FOR THE ACTUAL, PROJECT SPECIFIC DESIGN

CRITERIA AND REQUIREMENTS.

2. ALL LOADS ASSUMED TO ACT AT THE CENTER OF THE HORIZONTAL SUPPORT BEAMS, NO ECCENTRIC LOADS INCLUDED. PANEL/INSTRUMENT CONNECTION HARDWARE

MUST BE CHECKED SEPARATELY.

3. DESIGN ASSUMPTIONS: IBC 2012 BUILDING CODE; SEE TABLE FOR DESIGN LOADS (STATIC U.N.O.).

4. REFER TO COMPONENT MANUFACTURER'S IFU'S FOR REQUIRED INSTALLATION INFORMATION.

5. FOR APPLICABLE CONCRETE OR STEEL ANCHOR DESIGN CONTACT HILTI OR THE PROJECT SITE ENGINEER OF RECORD.

L

o

n

g

i

t

u

d

i

n

a

l

T

r

a

n

s

v

e

r

s

e

Vertical

LRFD,

lbs

ASD,

lbs

Transverse

Longitudinal

Transverse

Longitudinal

Max H1, in

42

400

340

280

100

78

Max H, in

Max W, in

48

A. RATED FOR 200 LBS FACTORED VERTICAL LOAD (LRFD).

B. RATED FOR 200 LBS ALLOWABLE VERTICAL LOAD (ASD).

C. ANCHOR CAPACITY NOT CONSIDERED.

** ASSUME 4 PER PANEL

GENERIC PANEL CONFIGURATION.

PANEL BY OTHERS

Page 2: 10017 - EI - 1 - hilti.com · 10017 - ei - 1 drawn: typical details td-ei-gp122-c notes: 1. this drawing represents a common configuration for this application. the electrical and

ELEVATION

(SCALE 5/8"=1'-0")

ISOMETRIC

(SCALE 5/8"=1'-0")

Qty.*DescriptionItem No.*Piece Mark

2MIC-C90-DH WELDED BRACKET21746821

2GIRDER MIQ-9021198662

4CONNECTOR MIQC-90-MI-V21402583

**MIQM 3/8" WING NUT21835844

2END CAP - MIA-EC-904320775

8USE APPROPRIATE HILTI ANCHORVARIES6

1

1

2

2

3

3

4

4

5

5

6

6

A A

B B

C C

D D

E E

F F

C:\Hilti Vault\Designs\Projects\10000 Internal Projects\10017 Typicals\E&I STANDS\TD-EI-GP122-C\TD-EI-GP122-C.dwg

All loading and design criteria supplied by customer is assumed accurate. Only the stated Design

Assumptions were considered, and must be verified by the responsible Engineer of Record (EOR).

The basis of Hilti component and connection design is the published data in the current Hilti

Technical Guide, including material and cross-section properties, allowable load values, factors of

safety, methods of calculation, and limiting factors. The EOR must verify suitability for any specific

application, and the capacity of the supportive structure to receive the shown configuration and

associated reaction loads. Modification to components and/or design may alter performance and

must be evaluated by the EOR.

PROJECT NUMBER:PAPER SIZE:

ANSI A

DESIGNED:CHECKED: REVIEWED:

OMOGAB BAP JWP

PROJECT NAME:

PROJECT DESCRIPTION:

ELECTRICAL & INSTRUMENTATION

PANEL STAND

REVISION HISTORY

PROJECT JOB SHEET

10017 EI 1- -

DRAWN:

TYPICAL DETAILS

TD-EI-GP122-C

NOTES:

1. THIS DRAWING REPRESENTS A COMMON CONFIGURATION FOR THIS APPLICATION. THE ELECTRICAL AND INSTRUMENTATION SUPPORT IS LOAD RATED AND

DIMENSIONALLY LIMITED BASED ON HILTI -PUBLISHED STATIC LOAD DATA AND DESIGN METHODOLOGIES, AND GENERIC, NON-PROJECT SPECIFIC DESIGN

ASSUMPTIONS. THE ENGINEERING OF RECORD SHALL EVALUATE THIS SUPPORT TO DETERMINE ITS SUITABILITY FOR THE ACTUAL, PROJECT SPECIFIC DESIGN

CRITERIA AND REQUIREMENTS.

2. ALL LOADS ASSUMED TO ACT AT THE CENTER OF THE HORIZONTAL SUPPORT BEAMS, NO ECCENTRIC LOADS INCLUDED. PANEL/INSTRUMENT CONNECTION HARDWARE

MUST BE CHECKED SEPARATELY.

3. DESIGN ASSUMPTIONS: IBC 2012 BUILDING CODE; SEE TABLE FOR DESIGN LOADS (STATIC U.N.O.).

4. REFER TO COMPONENT MANUFACTURER'S IFU'S FOR REQUIRED INSTALLATION INFORMATION.

5. FOR APPLICABLE CONCRETE OR STEEL ANCHOR DESIGN CONTACT HILTI OR THE PROJECT SITE ENGINEER OF RECORD.

6

5

H

AS

REQ'D

2

4

W

AS REQ'D

11

2

3

H1

A. RATED FOR 200 LBS FACTORED VERTICAL LOAD (LRFD).

B. RATED FOR 200 LBS ALLOWABLE VERTICAL LOAD (ASD).

C. ANCHOR CAPACITY NOT CONSIDERED.

LRFD,

lbs

ASD,

lbs

Transverse

Longitudinal

Transverse

Longitudinal

Max H1, in

42

900

1520

580

1040

78

Max H, in

Max W, in

48

L

o

n

g

i

t

u

d

i

n

a

l

T

r

a

n

s

v

e

r

s

e

Vertical

NO: DESCRIPTION: DATE:

A NOT FOR CONSTRUCTION

10/06/2017

** ASSUME 4 PER PANEL

GENERIC PANEL CONFIGURATION.

PANEL BY OTHERS.

Page 3: 10017 - EI - 1 - hilti.com · 10017 - ei - 1 drawn: typical details td-ei-gp122-c notes: 1. this drawing represents a common configuration for this application. the electrical and

ELEVATION

(SCALE 3/8"=1'-0")

ISOMETRIC

(SCALE 3/8"=1'-0")

Qty.*DescriptionItem No.*Piece Mark

2GIRDER MIQ-9021198661

2GIRDER MIQ-9021198662

2MIQC-C90 BASE PLATE21201443

4CONNECTOR MIQC-90-MI-V21402584

**MIQM 3/8" WING NUT21835845

2END CAP - MIA-EC-904320776

8USE APPROPRIATE HILTI ANCHORVARIES7

1

1

2

2

3

3

4

4

5

5

6

6

A A

B B

C C

D D

E E

F F

All loading and design criteria supplied by customer is assumed accurate. Only the stated Design

Assumptions were considered, and must be verified by the responsible Engineer of Record (EOR).

The basis of Hilti component and connection design is the published data in the current Hilti

Technical Guide, including material and cross-section properties, allowable load values, factors of

safety, methods of calculation, and limiting factors. The EOR must verify suitability for any specific

application, and the capacity of the supportive structure to receive the shown configuration and

associated reaction loads. Modification to components and/or design may alter performance and

must be evaluated by the EOR.

PROJECT NUMBER:PAPER SIZE:

ANSI A

DESIGNED:CHECKED: REVIEWED:

OMOGAB IDP JWP

PROJECT NAME:

PROJECT DESCRIPTION:

ELECTRICAL & INSTRUMENTATION

PANEL STAND

REVISION HISTORY

PROJECT JOB SHEET

10017 EI 1- -

DRAWN:

TYPICAL DETAILS

TD-EI-GP123-C

H

W

4

2

6

7

3

MIQM WING NUT

1

4

AS REQ'D

2

1

H1

5

NO: DESCRIPTION: DATE:

A NOT FOR CONSTRUCTION

10/06/2017

NOTES:

1. THIS DRAWING REPRESENTS A COMMON CONFIGURATION FOR THIS APPLICATION. THE ELECTRICAL AND INSTRUMENTATION SUPPORT IS LOAD RATED AND

DIMENSIONALLY LIMITED BASED ON HILTI -PUBLISHED STATIC LOAD DATA AND DESIGN METHODOLOGIES, AND GENERIC, NON-PROJECT SPECIFIC DESIGN

ASSUMPTIONS. THE ENGINEERING OF RECORD SHALL EVALUATE THIS SUPPORT TO DETERMINE ITS SUITABILITY FOR THE ACTUAL, PROJECT SPECIFIC DESIGN

CRITERIA AND REQUIREMENTS.

2. ALL LOADS ASSUMED TO ACT AT THE CENTER OF THE HORIZONTAL SUPPORT BEAMS, NO ECCENTRIC LOADS INCLUDED. PANEL/INSTRUMENT CONNECTION HARDWARE

MUST BE CHECKED SEPARATELY.

3. DESIGN ASSUMPTIONS: IBC 2012 BUILDING CODE; SEE TABLE FOR DESIGN LOADS (STATIC U.N.O.).

4. REFER TO COMPONENT MANUFACTURER'S IFU'S FOR REQUIRED INSTALLATION INFORMATION.

5. FOR APPLICABLE CONCRETE OR STEEL ANCHOR DESIGN CONTACT HILTI OR THE PROJECT SITE ENGINEER OF RECORD.

A. RATED FOR 200 LBS FACTORED VERTICAL LOAD (LRFD).

B. RATED FOR 200 LBS ALLOWABLE VERTICAL LOAD (ASD).

C. ANCHOR CAPACITY NOT CONSIDERED.

LRFD,

lbs

ASD,

lbs

Transverse

Longitudinal

Transverse

Longitudinal

Max H1, in

42

400

200

280

140

78

Max H, in

Max W, in

48

** ASSUME 4 PER PANEL

L

o

n

g

i

t

u

d

i

n

a

l

T

r

a

n

s

v

e

r

s

e

Vertical

GENERAL PANEL CONFIGURATION.

PANEL BY OTHERS.

Page 4: 10017 - EI - 1 - hilti.com · 10017 - ei - 1 drawn: typical details td-ei-gp122-c notes: 1. this drawing represents a common configuration for this application. the electrical and

ELEVATION

(SCALE 1/4"=1'-0")

ISOMETRIC

(SCALE 1/4"=1'-0")

Qty.*DescriptionItem No.*Piece Mark

2BRACKET MIC-C90-DH-2000 *21746821

4GIRDER MIQ-9021198662

8CONNECTOR MIQC-90-MI-V21402583

**MIQM 3/8" WING NUT21835844

2END CAP - MIA-EC-904320775

8USE APPROPRIATE HILTI ANCHORVARIES6

1

1

2

2

3

3

4

4

5

5

6

6

A A

B B

C C

D D

E E

F F

All loading and design criteria supplied by customer is assumed accurate. Only the stated Design

Assumptions were considered, and must be verified by the responsible Engineer of Record (EOR).

The basis of Hilti component and connection design is the published data in the current Hilti

Technical Guide, including material and cross-section properties, allowable load values, factors of

safety, methods of calculation, and limiting factors. The EOR must verify suitability for any specific

application, and the capacity of the supportive structure to receive the shown configuration and

associated reaction loads. Modification to components and/or design may alter performance and

must be evaluated by the EOR.

PROJECT NUMBER:PAPER SIZE:

ANSI A

DESIGNED:CHECKED: REVIEWED:

OMOGAB IDP JWP

PROJECT NAME:

PROJECT DESCRIPTION:

ELECTRICAL & INSTRUMENTATION

PANEL STAND

REVISION HISTORY

PROJECT JOB SHEET

10017 EI 1- -

DRAWN:

TYPICAL DETAILS

TD-EI-GP125-C

H

W

3

4

5

6

MIQM WING NUT

2

3

AS REQ'D

2

2

2

H1

H2

H3

NOTES:

1. THIS DRAWING REPRESENTS A COMMON CONFIGURATION FOR THIS APPLICATION. THE ELECTRICAL AND INSTRUMENTATION SUPPORT IS LOAD RATED AND

DIMENSIONALLY LIMITED BASED ON HILTI -PUBLISHED STATIC LOAD DATA AND DESIGN METHODOLOGIES, AND GENERIC, NON-PROJECT SPECIFIC DESIGN

ASSUMPTIONS. THE ENGINEERING OF RECORD SHALL EVALUATE THIS SUPPORT TO DETERMINE ITS SUITABILITY FOR THE ACTUAL, PROJECT SPECIFIC DESIGN

CRITERIA AND REQUIREMENTS.

2. ALL LOADS ASSUMED TO ACT AT THE CENTER OF THE HORIZONTAL SUPPORT BEAMS, NO ECCENTRIC LOADS INCLUDED. PANEL/INSTRUMENT CONNECTION HARDWARE

MUST BE CHECKED SEPARATELY.

3. DESIGN ASSUMPTIONS: IBC 2012 BUILDING CODE; SEE TABLE FOR DESIGN LOADS (STATIC U.N.O.).

4. REFER TO COMPONENT MANUFACTURER'S IFU'S FOR REQUIRED INSTALLATION INFORMATION.

5. FOR APPLICABLE CONCRETE OR STEEL ANCHOR DESIGN CONTACT HILTI OR THE PROJECT SITE ENGINEER OF RECORD.

L

o

n

g

i

t

u

d

i

n

a

l

T

r

a

n

s

v

e

r

s

e

Vertical

LRFD,

lbs

ASD,

lbs

Transverse

Longitudinal

Transverse

Longitudinal

Max H3, in

18

1600

1840

1100

1120

42

Max H2, in

Max H1, in

54

Max H, in

Max W, in

78

84

A. RATED FOR 800 LBS FACTORED VERTICAL LOAD (LRFD).

B. RATED FOR 800 LBS ALLOWABLE VERTICAL LOAD (ASD).

C. ANCHOR CAPACITY NOT CONSIDERED.

** ASSUME 4 PER PANEL

GENERIC PANEL CONFIGURATION.

PANELS BY OTHERS.

NO: DESCRIPTION: DATE:

1 NOT FOR CONSTRUCTION

10/06/2017

1 1

Page 5: 10017 - EI - 1 - hilti.com · 10017 - ei - 1 drawn: typical details td-ei-gp122-c notes: 1. this drawing represents a common configuration for this application. the electrical and

ELEVATION

(SCALE 3/8"=1'-0")

ISOMETRIC

(SCALE 3/8"=1'-0")

Qty.*DescriptionItem No.*Piece Mark

2BRACKET MIC-C90-DH-200021746821

2GIRDER MIQ-9021198662

2GIRDER MIQ-9021198663

4CONNECTOR MIQC-90-MI-V21402584

2CONNECTOR MIC-U-MA3048065

2CONNECTOR MIC-CU-MAH CONCRETE21746646

2END CAP - MIA-EC-904320777

**MIQM 3/8" WING NUT21835848

12USE APPROPRIATE HILTI ANCHORVARIES9

1

1

2

2

3

3

4

4

5

5

6

6

A A

B B

C C

D D

E E

F F

All loading and design criteria supplied by customer is assumed accurate. Only the stated Design

Assumptions were considered, and must be verified by the responsible Engineer of Record (EOR).

The basis of Hilti component and connection design is the published data in the current Hilti

Technical Guide, including material and cross-section properties, allowable load values, factors of

safety, methods of calculation, and limiting factors. The EOR must verify suitability for any specific

application, and the capacity of the supportive structure to receive the shown configuration and

associated reaction loads. Modification to components and/or design may alter performance and

must be evaluated by the EOR.

PROJECT NUMBER:PAPER SIZE:

ANSI A

DESIGNED:CHECKED: REVIEWED:

OMOGAB IDP JWP

PROJECT NAME:

PROJECT DESCRIPTION:

ELECTRICAL & INSTRUMENTATION

PANEL STAND

REVISION HISTORY

PROJECT JOB SHEET

10017 EI 1- -

DRAWN:

TYPICAL DETAILS

TD-EI-GP138-C

H

4

8

7

7

1

5

6

MIQM WING NUT

2

4

9

AS REQ'D

W

H1

GENERIC PANEL CONFIGURATION.

PANELS BY OTHERS.

3

NO: DESCRIPTION: DATE:

A NOT FOR CONSTRUCTION

10/09/2017

L

o

n

g

i

t

u

d

i

n

a

l

T

r

a

n

s

v

e

r

s

e

Vertical

** ASSUME 4 PER PANEL

NOTES:

1. THIS DRAWING REPRESENTS A COMMON CONFIGURATION FOR THIS APPLICATION. THE ELECTRICAL AND INSTRUMENTATION SUPPORT IS LOAD RATED AND

DIMENSIONALLY LIMITED BASED ON HILTI -PUBLISHED STATIC LOAD DATA AND DESIGN METHODOLOGIES, AND GENERIC, NON-PROJECT SPECIFIC DESIGN

ASSUMPTIONS. THE ENGINEERING OF RECORD SHALL EVALUATE THIS SUPPORT TO DETERMINE ITS SUITABILITY FOR THE ACTUAL, PROJECT SPECIFIC DESIGN

CRITERIA AND REQUIREMENTS.

2. ALL LOADS ASSUMED TO ACT AT THE CENTER OF THE HORIZONTAL SUPPORT BEAMS, NO ECCENTRIC LOADS INCLUDED. PANEL/INSTRUMENT CONNECTION HARDWARE

MUST BE CHECKED SEPARATELY.

3. DESIGN ASSUMPTIONS: IBC 2012 BUILDING CODE; SEE TABLE FOR DESIGN LOADS (STATIC U.N.O.).

4. REFER TO COMPONENT MANUFACTURER'S IFU'S FOR REQUIRED INSTALLATION INFORMATION.

5. FOR APPLICABLE CONCRETE OR STEEL ANCHOR DESIGN CONTACT HILTI OR THE PROJECT SITE ENGINEER OF RECORD.

LRFD,

lbs

ASD,

lbs

Transverse

Longitudinal

Transverse

Longitudinal

Max H1, in

42

840

4680

600

3120

78

Max H, in

Max W, in

120

A. RATED FOR 600 LBS FACTORED VERTICAL LOAD (LRFD).

B. RATED FOR 600 LBS ALLOWABLE VERTICAL LOAD (ASD).

C. ANCHOR CAPACITY NOT CONSIDERED.

1

2

Page 6: 10017 - EI - 1 - hilti.com · 10017 - ei - 1 drawn: typical details td-ei-gp122-c notes: 1. this drawing represents a common configuration for this application. the electrical and

ELEVATION

(SCALE 3/8"=1'-0")

ISOMETRIC

(SCALE 3/8"=1'-0")

Qty.*DescriptionItem No.*Piece Mark

2BRACKET MIC-C90-D-2000H 21746821

2GIRDER MIQ-9021198662

2GIRDER MIQ-9021198663

4CONNECTOR MIQC-90-MI-V21402584

2CONNECTOR MIC-U-MA3048065

2CONNECTOR MIC-CU-MAH CONCRETE21746646

2END CAP - MIA-EC-904320777

**MIQM 3/8" WING NUT21835848

11USE APPROPRIATE HILTI ANCHORVARIES9

1

1

2

2

3

3

4

4

5

5

6

6

A A

B B

C C

D D

E E

F F

All loading and design criteria supplied by customer is assumed accurate. Only the stated Design

Assumptions were considered, and must be verified by the responsible Engineer of Record (EOR).

The basis of Hilti component and connection design is the published data in the current Hilti

Technical Guide, including material and cross-section properties, allowable load values, factors of

safety, methods of calculation, and limiting factors. The EOR must verify suitability for any specific

application, and the capacity of the supportive structure to receive the shown configuration and

associated reaction loads. Modification to components and/or design may alter performance and

must be evaluated by the EOR.

PROJECT NUMBER:PAPER SIZE:

ANSI A

DESIGNED:CHECKED: REVIEWED:

OMOGAB IDP JWP

PROJECT NAME:

PROJECT DESCRIPTION:

ELECTRICAL & INSTRUMENTATION

PANEL STAND

REVISION HISTORY

PROJECT JOB SHEET

10017 EI 1- -

DRAWN:

TYPICAL DETAILS

TD-EI-GP141-C

H

5

6

MIQM WING NUT

H1

4

2

7

3

GENERIC PANEL CONFIGURATION.

PANEL BY OTHERS.

W

AS REQ'D

1

2

1

9

8

L

o

n

g

i

t

u

d

i

n

a

l

T

r

a

n

s

v

e

r

s

e

Vertical

** ASSUME 4 PER PANEL

A. RATED FOR 200 LBS FACTORED VERTICAL LOAD (LRFD).

B. RATED FOR 200 LBS ALLOWABLE VERTICAL LOAD (ASD).

C. ANCHOR CAPACITY NOT CONSIDERED.

NO: DESCRIPTION: DATE:

A NOT FOR CONSTRUCTION

10/09/2017

LRFD,

lbs

ASD,

lbs

Transverse

Longitudinal

Transverse

Longitudinal

Max H1, in

42

920

4800

580

3320

78

Max H, in

Max W, in

48

NOTES:

1. THIS DRAWING REPRESENTS A COMMON CONFIGURATION FOR THIS APPLICATION. THE ELECTRICAL AND INSTRUMENTATION SUPPORT IS LOAD RATED AND

DIMENSIONALLY LIMITED BASED ON HILTI -PUBLISHED STATIC LOAD DATA AND DESIGN METHODOLOGIES, AND GENERIC, NON-PROJECT SPECIFIC DESIGN

ASSUMPTIONS. THE ENGINEERING OF RECORD SHALL EVALUATE THIS SUPPORT TO DETERMINE ITS SUITABILITY FOR THE ACTUAL, PROJECT SPECIFIC DESIGN

CRITERIA AND REQUIREMENTS.

2. ALL LOADS ASSUMED TO ACT AT THE CENTER OF THE HORIZONTAL SUPPORT BEAMS, NO ECCENTRIC LOADS INCLUDED. PANEL/INSTRUMENT CONNECTION HARDWARE

MUST BE CHECKED SEPARATELY.

3. DESIGN ASSUMPTIONS: IBC 2012 BUILDING CODE; SEE TABLE FOR DESIGN LOADS (STATIC U.N.O.).

4. REFER TO COMPONENT MANUFACTURER'S IFU'S FOR REQUIRED INSTALLATION INFORMATION.

5. FOR APPLICABLE CONCRETE OR STEEL ANCHOR DESIGN CONTACT HILTI OR THE PROJECT SITE ENGINEER OF RECORD.

Page 7: 10017 - EI - 1 - hilti.com · 10017 - ei - 1 drawn: typical details td-ei-gp122-c notes: 1. this drawing represents a common configuration for this application. the electrical and

ELEVATION

(SCALE 1/4"=1'-0")

ISOMETRIC

(SCALE 1/4"=1'-0")

Qty.*DescriptionItem No.*Piece Mark

3BRACKET MIC-C90-DH-2000 21746821

8GIRDER MIQ-9021198662

3GIRDER MIQ-9021198663

12CONNECTOR MIQC-90-MI-V21402584

3CONNECTOR MIC-U-MA3048065

3CONNECTOR MIC-CU-MAH CONCRETE21746646

**MIQM 3/8" WING NUT21835847

18USE APPROPRIATE HILTI ANCHORVARIES8

3END CAP - MIA-EC-904320779

4TOOTHED PLATE MIA-TP30570710

1

1

2

2

3

3

4

4

5

5

6

6

A A

B B

C C

D D

E E

F F

All loading and design criteria supplied by customer is assumed accurate. Only the stated Design

Assumptions were considered, and must be verified by the responsible Engineer of Record (EOR).

The basis of Hilti component and connection design is the published data in the current Hilti

Technical Guide, including material and cross-section properties, allowable load values, factors of

safety, methods of calculation, and limiting factors. The EOR must verify suitability for any specific

application, and the capacity of the supportive structure to receive the shown configuration and

associated reaction loads. Modification to components and/or design may alter performance and

must be evaluated by the EOR.

PROJECT NUMBER:PAPER SIZE:

ANSI A

DESIGNED:CHECKED: REVIEWED:

OMOGAB IDP JWP

PROJECT NAME:

PROJECT DESCRIPTION:

ELECTRICAL & INSTRUMENTATION

PANEL STAND

REVISION HISTORY

PROJECT JOB SHEET

10017 EI 1- -

DRAWN:

TYPICAL DETAILS

TD-EI-GP146-C

H

MIQM WING NUT

H1

H2

H3

410

GENERIC PANEL CONFIGURATION.

PANELS BY OTHERS.

3

6

5

W

EQ. EQ.

AS REQ'D

7

2

2

2

2

2

2

2

2

1 1

1

8

9

4 4

NO: DESCRIPTION: DATE:

A NOT FOR CONSTRUCTION

10/06/2017

** ASSUME 4 PER PANEL

L

o

n

g

i

t

u

d

i

n

a

l

T

r

a

n

s

v

e

r

s

e

Vertical

LRFD,

lbs

ASD,

lbs

Transverse

Longitudinal

Transverse

Longitudinal

Max H3, in

18

1800

5400

1680

3700

42

Max H2, in

Max H1, in

54

Max H, in

Max W, in

78

120

NOTES:

1. THIS DRAWING REPRESENTS A COMMON CONFIGURATION FOR THIS APPLICATION. THE ELECTRICAL AND INSTRUMENTATION SUPPORT IS LOAD RATED AND

DIMENSIONALLY LIMITED BASED ON HILTI -PUBLISHED STATIC LOAD DATA AND DESIGN METHODOLOGIES, AND GENERIC, NON-PROJECT SPECIFIC DESIGN

ASSUMPTIONS. THE ENGINEERING OF RECORD SHALL EVALUATE THIS SUPPORT TO DETERMINE ITS SUITABILITY FOR THE ACTUAL, PROJECT SPECIFIC DESIGN

CRITERIA AND REQUIREMENTS.

2. ALL LOADS ASSUMED TO ACT AT THE CENTER OF THE HORIZONTAL SUPPORT BEAMS, NO ECCENTRIC LOADS INCLUDED. PANEL/INSTRUMENT CONNECTION HARDWARE

MUST BE CHECKED SEPARATELY.

3. DESIGN ASSUMPTIONS: IBC 2012 BUILDING CODE; SEE TABLE FOR DESIGN LOADS (STATIC U.N.O.).

4. REFER TO COMPONENT MANUFACTURER'S IFU'S FOR REQUIRED INSTALLATION INFORMATION.

5. FOR APPLICABLE CONCRETE OR STEEL ANCHOR DESIGN CONTACT HILTI OR THE PROJECT SITE ENGINEER OF RECORD.

A. RATED FOR 1600 LBS FACTORED VERTICAL LOAD (LRFD).

B. RATED FOR 1600 LBS ALLOWABLE VERTICAL LOAD (ASD).

C. ANCHOR CAPACITY NOT CONSIDERED.