10 th ANNUAL INDUSTRY WORKSHOP Presented by: Kitchener Building Division November 21, 2013 Kitchener Memorial Auditorium Complex

Upload: others

Post on 28-Aug-2020

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

10th ANNUAL

INDUSTRY WORKSHOP

Presented by:

Kitchener Building Division

November 21, 2013

Kitchener Memorial Auditorium Complex

Page 2: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

2

AGENDA

• Administration – Fees – MMAH Update

• Online Permits Update • Part 6,7,9 & 12

– Code Change Highlights – Permit Applications – Inspection Topics

• Part 3,5 & 6 – Code Change Highlights – Permit Applications

• Questions

Page 3: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

ADMINISTRATION

Tim Benedict Manager of Building – Part 9

Page 4: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

The new development charge rates will apply to all permits issued in 2014

Please note both Kitchener and Regional DC By-laws are under review in 2014

2014 Development Charge Rates

• City of Kitchener (0.9% from 2013)

Single = $9,748.00

Townhouse = $6,733.00

Multiple = $5,524.00

Non-Res = $4.43 sq. ft.

• Region of Waterloo (0.9% from 2013)

Single = $13,288.00

Townhouse = $9,289.00

Multiple = $7,667.00

Non-Res = $9.59 sq. ft.

• School Boards (WRDSB & WCDSB) rates remain unchanged until June 30, 2014

Development Charges

Page 5: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

5

2014 Permit Fees

1.5% increase from 2013 rates • Singles, semis, towns - $1.23/sq.ft.

• Apartment Building - $1.23/sq.ft.

• Interior Finishes - $0.41/sq.ft. (basement finishes & major renovations, all classifications)

• Deck - $110.00 each

• Solar Panels - $ 110.00 for singles and duplex’s

• Residential Revisions - $110.00 (min), will be charged for each revision submitted – A revision changing the model of a house will

result in the cancelation of original permit and a new permit must be applied for.

Page 6: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

6

New Building Code - January 1st, 2014

Ontario Regulation (O.Reg.) 332/12

Themes of this Edition of The Building Code • Support for the economy through promoting

innovation, reducing costs, increasing certainty, and increasing harmonization with National Codes, Servicing Multiple Buildings on One Lot

• Support for enhanced energy and water conservation, greenhouse gas reduction, climate change adaptation, and environmental protection

• Enhanced barrier-free accessibility • Enhanced public health and safety

IMPORTANT

Ministry of Municipal Affairs and Housing Update (MMAH)

Page 7: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

7

• The 2012 Building Code contains “knowledge maintenance” requirements for qualified practitioners

• These replace the requalification requirements set out in the 2006 Code

• Practitioners will have 18 months to successfully complete a knowledge and maintenance exam for a given qualification category, following the release of that exam

• The Ministry will determine the date, no sooner than the date the regulation takes effect, of the release and the qualification categories of Knowledge Maintenance exams

• Options for design, maintenance and delivery of online courses are being explored

• Last day to apply under the 2006 Code is DECEMBER 31, 2013

Ministry of Municipal Affairs and Housing Update (MMAH)

Page 8: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A
Page 9: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

9

ONLINE PERMITS UPDATE

Tim Benedict Manager of Building – Part 9

Page 10: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

10

Online Permits Went LIVE January 2, 2013

• Public Searches

• My Permits (check progress, read status letter, confirm fees, etc…)

• Request Inspection (book or cancel)

• Apply for a Permit (drawings, forms and reports all attached electronically)

• Currently we have 320 registered users

www.kitchener.ca/onlinepermits

* No on-line payment capability at this time *

Page 11: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

11

Online Permits cont’d What’s Happening Now…?

• More types of permits are now available for application online (basement finishes, renovations and garages)

• Electronic plan review has been implemented for all Part 9 residential projects

• As of January 2, 2014 all repeat Builders “Regular Customers” will be required to submit all permit electronically or provide a electronic version of the drawings for submission and review

• All approved permit drawings will be uploading online and it is the Applicant responsibility to print approved drawings to have on site for Building Inspections

Page 12: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

12

PART 6

Tim Benedict Manager of Building – Part 9

Page 13: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

13

6.2.4.3.(12)

Construction and Installation of Ducts and Plenums

(1) Where a supply duct is located in a conditioned space, the ductwork shall be sealed to c Class C seal level in accordance with the SMACNA, “HVAC Duct Construction Standards – Metal and Flexible.”

**Stay tuned, the Ministry is clarifying if this was intended for Single Detached Dwellings**

Part 6 Code Change Highlights

Page 14: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

14

PART 7

Matt Ruetz Municipal Building Official – Part 9

Page 15: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

15

7.2.3.1.

Traps

(3) Except for a floor-mounted service sink, every trap that serves a lavatory, a sink or a laundry tray shall,

(a) … cleanout plug,

(b) … trap dip can be completely removed, or

(c) be provided with a cleanout installed above the floor as close as practical downstream of the trap when the trap is,

(i) installed below the floor, and

(ii) not readily accessible for cleaning as required by Clause (a).

Part 7 Code Change Highlights

Page 16: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

16

7.4.9.2.

Serving Water Closets

(5) No vertical leg of the drainage pipe from a water closet or other fixture that has an integral siphonic flushing action shall exceed 1000mm

Part 7 Code Change Highlights

Page 17: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

17

7.4.9.3.

Size of Fixture Outlet Pipes

(1) … every fixture outlet pipe shall conform to Table 7.4.9.3.

Part 7 Code Change Highlights

Page 18: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

18

7.6.4.1.

Water Supply Fittings

(1) … water to a fixture shall not exceed the maximum flow rates at the test pressures listed for that fitting in Table 7.6.4.1.

(Shower heads reduced from 9.5 to 7.6 L/min)

Part 7 Code Change Highlights

Page 19: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

19

7.6.4.2.

Plumbing Fixtures

(3) In buildings classified as Group C occupancy, the flush cycle for each fixture that is a water closet or urinal shall not exceed the maximum water consumption per flush cycle listed for that fixture in Table 7.6.4.2.B.

Part 7 Code Change Highlights

Page 20: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

20

7.7.1.1.

Non-Potable Connection

(2) Make-up water may be supplied to the non-potable water system by,

(a) a reduced pressure backflow preventer, or

(b) an air gap.

(3) Where a clothes washer is supplied by a rainwater system and a potable water system, the potable water system shall be protected by dual check valve backflow preventers conforming to CAN/CSA-B64.6, “Dual Check Value Backflow Preventers (DuC)” for,

(a) area isolation, and

(b) premise isolation.

Part 7 Code Change Highlights

Page 21: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

21

PART 9

Matt Ruetz Municipal Building Official – Part 9

Page 22: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

22

9.8.1.2.

Stairs, Ramps, Landings, Handrails and Guards in Garages

(1) Except as provided in Sentence 9.8.6.2.(3), stairs, ramps, landings, handrails and guards in a garage that serves a single dwelling unit shall conform to the requirements for stairs, ramps, landings, handrails and guards with a dwelling unit.

Part 9 Code Change Highlights

Page 23: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

23

9.8.4.1.

Dimensions for Risers

Part 9 Code Change Highlights

Page 24: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

24

9.8.4.4.

Uniformity and Tolerances for Risers and Treads

(1) Except as provided in Sentence (2), risers shall be of uniform height in any one flight with a maximum tolerance of,

(a) 5mm between adjacent treads or landings, and

(b) 10mm between the tallest and shortest riser in a flight

(3) Treads shall have uniform run with a maximum tolerance of,

(a) 5mm between adjacent treads, and

(b) 10mm between the deepest and shallowest treads in a flight

(5) The slope of treads shall not exceed 1 in 50

Part 9 Code Change Highlights

Page 25: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

25

9.8.5.2.

Ramp Width (Multi Residential)

(1) Except as provided in Sentence (2), exit ramps and public ramps serving buildings of residential occupancy shall have a clear width of not less than 900mm

Part 9 Code Change Highlights

Page 26: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

26

9.8.7.1.

Required Handrails

(1) Except as provided in Sentence (2) to (4), a handrail shall be installed on stairs and ramps in conformance with Table 9.8.7.1.

Part 9 Code Change Highlights

Page 27: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

27

9.8.7.4.

Height of Handrails

(2) Except as provided in Sentence (3) and (4), the height of handrails on stairs and ramps shall be,

(a) not less than 865mm (2’-10”), and

(b) not more than 965mm (3’-2”)

(4) Handrails installed in addition to required handrails need not comply with Sentence (2)

Part 9 Code Change Highlights

Page 28: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

28

9.8.8.3.

Height of Guards

(5) Except as provided in Sentence (6), the height of guards shall be not less than ,

(a) 920mm (3’-0”) for required exit stairs, and

(b) 1070mm (3’-6”) for around landings

(6) The height of guards for exterior stairs and landings more than 10m above adjacent ground level shall be not less than 1500mm (4’-11”)

9.10.15.5.

Construction of Exposing Building Faces of Houses

Table 9.10.15.5. of the 2006 Building Code and all references to it have been deleted

Part 9 Code Change Highlights

Page 29: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

29

9.9.11.3.

Exit Signs

New requirements for exit signs:

•ISO 3864-1 green pictogram

•ISO 7010 directional symbols

•CSA 22.2 #141 for internally illuminated

•CAN/ULC-S572 for photoluminescent and self-luminous

•Continuous illumination when externally illuminated

•Only emergency lighting allowed on same circuit

Part 9 Code Change Highlights

Page 30: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

30

9.10.16.

Fire Blocks

The references to fire stop(s) have been replaced with fire block(s)

Division A - 1.4.1.2.

Fire Block means a material, component or system that restricts the spread of fire within a concealed space or from a concealed space to an adjacent space

Fire Stop means a system consisting of a material, component and means of support, used to fill gaps between fire separations or between fire separations and other assemblies, or used around items that wholly or partially penetrate a fire separation

Part 9 Code Change Highlights

Page 31: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

31

9.10.19.2.

Sound Patterns of Smoke Alarms

(1) The sound patterns of smoke alarms shall,

(a) meet the temporal patterns of alarm signals, or

(b) be a combination of temporal pattern and voice relay

9.10.19.4.

Power Supply

(1) Except as provided in Sentences (2) and (3), smoke alarms required in Sentence 9.10.9.1.(1) shall,

(c) in case the regular power supply to a smoke alarm is interrupted, be provided with a battery as an alternative power source that can continue to provide power to the smoke alarm for a period of not less than 7 days in the normal condition, followed by 4 minutes of alarm

Part 9 Code Change Highlights

Page 32: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

32

9.10.19.3.

Location of Smoke Alarms

(1) Within dwelling units, sufficient smoke alarms shall be installed so that,

(a) there is at least one smoke alarm installed on each storey , including basements, and

(b) on any storey of a dwelling unit containing sleeping rooms, a smoke alarm is installed,

(i) in each sleeping room, and

(ii) in a location between the sleeping rooms and the remainder of the storey, and if the sleeping rooms are served by a hallway, the smoke alarm shall be located in the hallway

Part 9 Code Change Highlights

Page 33: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

33

9.15.4.2.

Foundation Wall Thickness and Required Lateral Support

(1) Except as required in Sentence (2), the thickness of foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A. for walls not exceeding 3.0m (9’-10”) in unsupported height.

Part 9 Code Change Highlights

Page 34: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

34

9.23.3.5.

Fastening for Sheathing of Subflooring

(5) Where roof sheathing supports are spaced at more than 406mm (16”) o.c., the maximum spacing of fasteners for roof sheathing shall be 150mm (6”) along the edges and intermediate supports

Part 9 Code Change Highlights

Page 35: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

35

9.24.2.1.

Size and Spacing of Studs in Interior Walls

(1)…the size and spacing of steel studs for non-loadbearing interior walls shall conform to Table 9.24.2.1.

Part 9 Code Change Highlights

Page 36: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

36

9.31.4.1.

Required Fixtures

(1) A dwelling unit with a water distribution system shall contain,

(a) a kitchen sink,

(b) a lavatory,

(c) a bathtub or shower stall, and

(d) a water closet or a drainless composting toilet

Part 9 Code Change Highlights

Page 37: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

37

PART 12 & SB 12

Tim Benedict Manager of Building – Part 9

Page 38: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

38

12.3.1.3.

Temperature Control in Dwelling Units

(1) Except where space heating is provided by solid fuel-

burning appliance or ground source heat pump, the indoor air temperature in a dwelling unit shall be controlled by at least one programmable thermostatic control device

(2) The programmable thermostatic control device required in sentence (1) shall;

(a) setting of different air temperatures for at least,

(i) four time periods per day, and

(ii) two different day-types per week

(b) include a manual override, and

(c) allow the setting of the air temperature to,

(i) 13°C or lower in heating mode, and

(ii) 29°C or higher in the cooling mode,

where A/C is provided

Part 12 Code Change Highlights

Page 39: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

39

12.3.1.4.

Hot Water Piping Insulation

(1) Hot water pipes that are vertically connected to a hot

water tank shall have heat traps on both the inlet and outlet piping as close as practical to the tank, except where the tank,

(a) has an integral heat trap, or

(b) serves a recirculating system

Part 12 Code Change Highlights

Page 40: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

40

12.3.1.4.

Hot Water Piping Insulation…continued

(2) The first 2.5m of hot water outlet piping of a hot water

storage tank serving a non-recirculating system shall be insulated to provide a thermal resistance of not less than RSI 0.62 (R 3.5)

(3) The inlet pipe of a hot water storage tank between the heat trap and the tank serving a non-recirculating system shall be insulated to provide a thermal resistance of not less than RSI 0.62 (R 3.5)

Part 12 Code Change Highlights

Page 41: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

41

MR-13-S-23

Ruling of the Minister of Municipal Affairs and Housing

On March 15, 2013 the Ministry revised SB-12 some of the updates included

– Factory Built Modular Homes (mfg. before Jan 1/12)

– Drain Water Heat Recovery Units (Zones 1 & 2)

– Expanded Appendix A

SB 12 Code Change Highlights

Page 42: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

42

2.1.1.2.(10) (11)

Energy Efficiency for Zone 1 Buildings

36% efficient DWHR

- Trade offs in Sentence (10)(a)(c)(d)(e)(f)

46% efficient DWHR

- Trade offs in Sentence (10)(b)

62% efficient DWHR

- Trade offs in Sentence (11)

SB 12 Code Change Highlights

Page 43: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

43

2.1.1.11.

Drain Water Heat Recovery

(1) Where a drain water heat recovery unit is installed to meet the requirements of this Subsection, the unit and its installation shall conform to Sentences (2) to (5)

(2)…DWHR units shall conform to CSA B55.2…

(3)…efficiency of DWHR units determined by CSA B55.1…

SB 12 Code Change Highlights

Page 44: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

44

2.1.1.11.

Drain Water Heat Recovery continued…

(4) A drain water heat recovery unit shall be installed

(a) to receive drain water from all showers or at least two showers where there are two or more showers in a dwelling unit,

(b) in an upright position that does not diverge more than 5 degrees from the veridical

(c) in a position such that the cold water inlet connection is at the bottom of the unit

(d) downstream of a water softener where a water softener is installed, and

(e) in a conditioned space or on the warm side of the dewpoint of the wall assembly

(5)…minimum efficiency of the drain water heat recovery unit shall be not less than 36% when it is tested in accordance with Sentence (3)

SB 12 Code Change Highlights

Page 45: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

45

SB 12 Code Change Highlights

Page 46: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

46

PERMIT

APPLICATIONS

Tim Benedict Manager of Building – Part 9

Page 47: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

47

Permit Applications Residential applications:

• New Applications – Anticipate 10 business days for review of single, semi’s, and towns.

– Day 1 starts the day after a “complete application” is filed.

• Some common reasons permits go On Hold; – Missing Engineered Layouts

(Floors, Roof, Trusses greater than 40’)

– Missing Square Footage for Floor Plans

– HVAC info and EEDS form not matching

• The last day for submitting a complete application to be reviewed in 2013 is December 12, 2013

Page 48: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

At Application…

• If permit drawings indicate elements designed by a Professional Engineer, please provide reports at time of permit application (except for trusses)

• Revising What? Please indicate what elements are being revised (revision fee’s apply)

• When uploading applications, please make sure attached files match the description, saves everyone a lot of time

• Electronic drawings and documents can be uploaded directly from the program they were created in, such as Word, and Excel. Softplan and AutoCad, drawings must be converted to PDF

• Questions, feel free to contact Mandy, Leslie or Christine (519-741-2200)

48

Residential Applications

Page 49: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

Part 12/SB-12 Requirements…

• Accurate Grading to be shown on elevations

• Air Barrier Details (to be submitted with each permit application indicating the air barrier material and location)

• If a prescriptive package requires an HRV, please ensure HRV joins other equipment on the plans

• EEDS form to be submitted for each unit, whether a SFD, townhouse, semi, etc…

49

Residential Applications Continued...

Page 50: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

50

INSPECTION TOPICS

Tim Benedict

Manager of Building – Part 9

Page 51: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

51

Residential Inspections How are things going…?

• Sump pit covers to be left off until inspector has confirmed weeper connections (if at occupancy sealed lids to be fastened after connection confirmed)

• Rigid Insulation(foamed plastics) forming part of a wall assembly to be protected in accordance with 9.10.17.10 (walk outs, look outs, etc…)

• Occupancy Permits, how is electronic working?

• Reminder for inspection, windows stickers to remain on windows until confirmed by inspector (framing/insulation)

Page 52: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

52

Winter Conditions • For safety reasons, inspections will be postponed during

inclement weather (e.g. snow storms). Notification will be given via CBO’s email contact list, Facebook and Twitter

• Keep all stairs and pathways clear from snow and ice.

• Be mindful when using gas powered equipment in enclosed areas. (e.g. basements)

Cold Weather Protection • Concrete footings cannot be placed on frozen ground.

• Concrete footings, walls and slabs shall be protected to ensure a minimum temperature of 10°C for 72 hours after placement. Install tarps or adequate amount of straw for protection.

• All mortar and masonry shall be maintained at 5°C or greater during installation and the temperature shall be maintained for not less than 48 hours after installation.

Page 53: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

53

Before Booking an Inspection • Ensure all work has been completed for inspection,

• Ensure safe access for inspector,

– All required temporary or permanent stair guards around all interior and exterior openings & handrails are in place & properly secured.

– Ladders shall be of sufficient length for the purpose

• Required personnel are on-site (if necessary), and

• When requesting inspection, have permit #, municipal address and inspection code ready.

Booking Inspections 519-741-2761

• Automated call-in for inspections allows same day booking, provided prior to 8:00am.

• Online Booking (after January 1, 2013)

• When booking inspections there is no guarantee for specific time requested.

• If not ready for inspection(s), please ensure it’s cancelled by calling 519-741-2312.

Page 54: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

54

PART 3

Robert Schipper Manager of Building – Part 3

Page 55: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

55

Harmonization and Consistency • The 2012 Building Code enhances harmonization

with the model National Building and Plumbing Codes, including • Editorial changes and updated standard

references, stemming from changes to the model national code.

• Clarifying technical requirements to ensure. consistency and clarity in enforcement.

• Allowing more flexible, performance-oriented methods design and installation of some building elements.

• Changes related to care occupancies that were included in recent model National Building Code.

Code Change Highlights

Page 56: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

56

Energy Conservation Requirements (Large Buildings) • Requiring that large buildings for which building

permits are applied, on or after January 1, 2017. meet an energy efficiency level that is 13% higher than that required in 2012.

• Making a number of energy efficiency changes to the Building Code independent of the 13% increase.

• Similar to the approach with the 2012 energy requirements included in the 2006 Code, MMAH intends to work with the building sector to develop compliance alternatives.

Code Change Highlights

Page 57: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

57

New term Fire block introduced • Fire block: a material, component or system that

restricts the spread of fire within a concealed space or from a concealed space to an adjacent space.

• Fire stop: a system consisting of a material, component and means of support, used to fill gaps between fire separations or between fire separations and other assemblies, or used around items that wholly or partially penetrate a fire separation

Fire stops and Fire blocks

Page 58: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

58

• 3.1.5.3.(2)(c) – combustible roofing materials –

fire stop replaced with fire block

• 3.1.11. – Fire Blocks in concealed spaces – reference to firestopping and fire stops have been replaced with fire blocks

• 3.1.11.2.(2)(c) – Fire Blocks in wall assemblies – wiring, piping and similar services in a concealed wall space are now exempt from flame spread rating requirement (i.e.: FSR 25)

Fire blocks

Page 59: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

59

• 3.1.5.5.(1) & (2) – New Sentence (2) now clarifies

construction requirements for exterior walls limited to 10% unprotected openings.

• If 10% or less, wall construction shall meet requirements of Table 3.2.3.7.

Combustible Components for Exterior walls:

Page 60: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

60

• 3.1.8.8.(6) – Revised to clarify that a duct serving

commercial cooking equipment must be in a vertical or horizontal service space, or be provided with a damper specifically designed for such use, where the duct penetrates a required fire separation.

• NFPA 96 exhaust shall be installed for: grills/fryers, donut machines, boiling meat, preparing soups/stews (20 litre pot or more), domestic cooking range in commercial application.

• NFPA 96 exhaust may not be required for: bake ovens, pizza ovens, conveyor pizza ovens, rotisserie chicken.

• Mechanical P.Eng. Letter required, posted sign.

Fire Dampers waived

Page 61: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

61

• 3.1.8.12.(1) – Revised to permit all doors in fire

separations to use hold-open devices, except for: • Exit stair doors in buildings more than 3

storeys in building height, or • Doors in vestibule fire separation described in

Article 3.3.5.7. (Storage garage)

Hold-Open Devices:

Page 62: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

62

• 3.1.9.1.(4) & (5) – New sentences added:

• No fire stop required at sprinkler pipe

penetrations, if annular space is protected with metal escutcheon plates

• No fire stop required at duct penetrations, if a fire damper is installed in conformance with NFPA 80

Fire Stops:

Page 63: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

63

• 3.1.9.3.(3) - >25mm diameter single conductor

metal sheathed cables with combustible jacketing that penetrates a rated fire separation must now be spaced at least 300mm apart

• 3.1.9.3.(6) – Allows noncombustible electrical outlet box penetrations without the need to provide a fire stop in certain circumstances (i.e.: 100 cm2 each in area)

• 3.1.9.3.(7) – Allows electrical outlet box penetrations on opposite sides of a vertical fire separation to be in the same stud space, or back to back, if a fire stop is provided

Penetrations by Wires, Cables and Outlet boxes:

Page 64: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

64

• 3.1.19.1. – New clearance requirements for above

ground electrical conductors have been provided

• Horizontal clearance measured from the maximum conductor swing to the building: • Not less than 1m for electrical conductors

carrying 750 V or less • Not less than 3m for electrical conductors

carrying 750 V – 46kV • Not less than 3.7m for electrical conductors

carrying 46 kV – 69 kV • Conform to CAN/CSA-C22.3 No.1, “Overhead

Systems”, for >69kV

Clearance to Buildings:

Page 65: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

65

• 3.2.3.1.(5) & (6) - New provisions added that limit

the size of individual unprotected openings in exposing building faces of unsprinklered buildings that have a limiting distance of 2m or less • Greater of Table 3.2.3.1.A or that calculated

formula 0.24[(2 x LD) -1.2]squared • 2m horizontally between openings in the

same room or space • 2m vertically between openings in the same

room or space, and • 2m vertically between openings in another

room or space that is on the same storey

Limiting Distance and Area of Unprotected Openings:

Page 66: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

66

3.2.3.6. - Four new sentences added:

• No projection permitted with LD < 0.45m

• Face of soffit cannot be located closer than 0.45m

from the property line

• Establishes requirements for roof soffits with projections 0.45m – 1.2m (i.e.: protected by sheet steel, drywall, plywood, etc.)

• Combustible finish permitted in combustible construction

Combustible Projections:

Page 67: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

67

• 3.2.3.7. – New easy to read table added for

former sentences (1) to (6)

• 3.2.3.7.(3) – New sentence providing an alternative to the required noncombustible cladding requirement on an exposing building face with more than 10% unprotected openings

• 3.2.3.7.(4) – New sentence providing an alternative to the required noncombustible cladding requirement on an exposing building face with 25% - 50% unprotected openings

• 3.2.3.7.(5) – New sentence providing an alternative to the required noncombustible cladding requirement on an exposing building face with 10% - 25% unprotected openings

Construction of Exposing Building Face:

Page 68: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

68

Continuity of Fire Alarm System: • 3.2.4.2.(6) – New sentence added to clarify that

buildings separated by certain walkways and vestibules are to be treated as separate buildings for the purpose of fire alarm installation and continuity

Commissioning of Life Safety and Fire Protection Systems: • 3.2.4.6. – new article added that requires

integrated life safety and protection systems to be commissioned to operate as a whole

Fire Alarm & Detection Systems

Page 69: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

69

• 3.2.4.12. – New sentence and clause added

requiring smoke detectors in elevator machine rooms or machinery space if a fire alarm system is required. Requires elevators to be recalled when the smoke detector in the machine room or space is actuated

• 3.2.4.12.(5) – In buildings required to be equipped with a fire alarm system, smoke detectors are now required near the entrance to certain walkways (between buildings) or vestibules (under 3.2.6., high buildings)

Smoke and Heat Detectors:

Page 70: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

70

• 3.2.4.22.(3)(a) – Smoke alarms are now also

required within each sleeping room of a dwelling unit

• 3.2.4.22.(5) – Smoke alarms are now required to be provided with a battery as an alternative power supply capable of providing power: • For at least 7 days in normal condition • Followed by 4 minutes of alarm

• 3.2.4.22.(6) & (7) – Smoke detectors are permitted instead of smoke alarms, if the smoke detectors: • Form part of the fire alarm system • Are capable of independently sounding

audible signals within individual suites, and • Installed in conformance with CAN/ULC-S524

and verified as per CAN/ULC-S537

Smoke Alarms:

Page 71: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

71

• 3.2.4.22.(10) & (11) – A manually operated

silencing device must be incorporated within the circuitry of a smoke alarm installed in a dwelling unit (except in suites of residential equipped with smoke detectors

• 3.2.4.22(12) – The sound patterns of smoke alarms are now required to meet the temporal patterns of alarm signals, or be a combination of temporal pattern and voice relay

Smoke Alarms continued:

Page 72: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

72

• 3.2.4.23.(7) – Except in B1 or F1 major

occupancies, voice communication systems are now required in buildings when: • A fire alarm system is required as per 3.2.4. • A two stage system is installed, and • The occupant load of the building exceeds

1000 persons • Voice communication system must be capable

of transmitting pre-recorded, synthesized or live messages

Voice Communication Systems:

Page 73: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

73

• 3.2.7.1.(2) – In addition to the 50 lux average

illumination requirement prescribed, the minimum illumination level must not be less than 10 lux.

Emergency Power Supply Installation:

• 3.2.7.5.(2) - Every emergency power supply must now be equipped with an emergency audible and visual trouble indication

Minimum Lighting Requirements:

Page 74: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

74

• 3.2.9.2.(9) – Standpipe risers must be located in

an exit stair shaft or vertical service space.

• The vertical service space shall be separated from the adjacent floor area by a fire separation having a fire resistance rating conforming to Table 3.6.3.1.

Egress Doorways:

• 3.3.1.5.(2) – New minimum distance requirements between two required egress doors.

• Must be equal to or greater than 1/3 times the maximum diagonal dimension of the room or suite served by the egress doors.

Standpipe System Design:

Page 75: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

75

• 3.3.2.14.(1). – New sentence added for

flammable and combustible liquid storage rooms in assembly occupancies

• These rooms cannot be located above or below the first storey of a building

• 3.3.4.3.(4). – Same new sentence added as above, for residential occupancies when they are not located within a dwelling unit. Also can not have storage room above or below the first storey

Storage Rooms:

Page 76: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

76

3.3.4.10. – Resistance to forced entry

• New article regarding resistance to forced entry

into dwelling units has been added for Part 3 buildings

3.3.4.8. – Protection of Openable windows:

• Previous Article 3.7.2.2. has been removed and this new article identifies protection of openable windows for residential occupancies

• Several revisions: • 1070 mm minimum height above finished

floor (previous 1500) • Heavy duty screen has been removed • Window located less than 1800mm above

floor or ground level on other side (previous 2000mm)

Residential Occupancies:

Page 77: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

77

• 3.3.6. – A new Subsection regarding the design of

hazardous areas has been added for areas in a building that are intended for the storage, handling, use and processing of: • Dangerous goods • Materials that involve a risk of explosion or

high flammability • Materials that are highly reactive

Example New Articles:

• 3.3.6.2. – Storage of explosives • 3.3.6.3. – Indoor storage of compressed gas • 3.3.6.4. – Storage and dispensing rooms for

flammable and combustible liquids • 3.3.6.5. – Tire Storage

Design of Hazardous Areas:

Page 78: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

78

• 3.4.5.1. – Green pictogram and white graphic

symbol (running man) exit signs conforming to ISO standards are now required. Red exit signs have been eliminated.

• Photoluminescent and self-luminous exit signs conforming to CAN/ULC-S572 standard are also permitted. • Must be continuously illuminated if reliant on

an external energy source to energize • Not to be installed in a building within the

scope of 3.2.6. – High Buildings

Exit Signage:

Page 79: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

79

• 3.4.6.5. – Requirements for handrails have been

expanded and clarified

• Handrails installed in addition to required handrails need not comply with handrail height

• Where guards are required, handrails required on landings shall be not more than 1070mm in height

Handrails:

Page 80: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

80

• 3.6.2.8. – Article has been amended to clarify that

emergency power generators are required to be located in a rated fire compartment only when they are located within a building.

• Previous Code: “A generator to supply power for lighting, fire safety and life safety systems shall be located in a room that…”

Emergency Power Installations:

Page 81: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

81

• 3.7.4.15. – Clearances for water closets:

• Except for dwelling units and barrier free

washrooms, a minimum clearance of 380mm is now required in front of all water closets

• 3.7.4.16. – Privacy:

• Water closets, urinals, lavatories, showers and bathtubs shall not be visible from the entrance to the room where the room contains at least: • Two water closets • One water closet and one urinal • One shower stall, or • One bathtub

Plumbing Facilities:

Page 82: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

82

Water Conservation • Requiring newly installed urinals to be high

efficiency (1.9L/flush). • Requiring high efficiency showerheads in

residential occupancies (7.6L/minute).

• Allow for drain less composting toilets w/municipal services.

Code Change Highlights

Page 83: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

83

Property Protection and Health

• Revise the average annual concentration of radon in the Building Code to reflect new national threshold (from 250Bq/m3 to 200Bq/m3).

• Protecting public water supplies from

contamination from “medium hazard” uses(e.g. multi-unit residential buildings, commercial buildings, hotels, manufacturing plants) by requiring a backflow preventers.

Code Change Highlights

Page 84: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

84

Mid-Rise Wood Construction • The 2012 Building Code does not include

changes to permit wood-framed buildings 4 storeys or more. • MMAH is participating in research being

undertaken by the National Research Council (NRC) through staff resources and financial contribution

• The NRC has proposed research on mid-rise

and other wood based construction to support proposed changes to the 2015 edition of the model National Building Code.

Code Change Highlights

Page 85: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

85

PERMIT

APPLICATIONS

Robert Schipper Manager of Building – Part 3

Page 86: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

86

Applications Commercial applications:

• Pre-application meetings available

• Providing required contact and information

• Various forms available on site – Building/Fire design forms, Code Matrix, Energy Efficiency form, etc.

• Provide up-to-date drawings once Site Plan approved

• Timelines – i.e.: Site plan versus building permit application

• Permit fees to be paid prior to permit issuance and prior to work starting on site

**Permit number and address on all submitted info./reports for both plan review and inspections

Page 87: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

87

PART 5

Kelly Lanka Municipal Building Official – Part 3

Page 88: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

Part 5

• Pertains to the separation of environmentally dissimilar spaces.

• Relates to the transfer of heat, air, moisture & sound

• Control of the radon & other gases is addressed by air leakage requirements.

Page 89: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

Structural & Environmental Loads 5.1.4.1.(5)

• This sentence deals with deflection of the backing assembly effecting the cladding performance.

• This sentence now includes a reference to Article 5.2.2.1. where the structural loads are

specified.

Page 90: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

Resistance to Deterioration 5.1.4.2.(1)

Sentence has been amended to clarify that materials must be selected based on:

- the nature & function of materials

- the exposure of the materials, &

- the climate conditions in which the materials will be installed

Page 91: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

Structural Loads & Effects 5.2.2.1.(2)(c)

Earthquake effects need now only be taken into consideration for post-disaster buildings.

Page 92: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

Determination of Wind Load 5.2.2.2.(2)

• Sentence 5.2.2.2.(2) now references all loads not just velocity pressure and gust effect.

• Loads now include external pressure or suction, net specified pressure and exposure factor.

Page 93: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

Air Barrier System Properties 5.4.1.2.(1)(b)

New reference to CAN/ULC-S741 added for air barrier material specifications.

Page 94: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

Deletion from Part 5 5.6.1.2.

Prescriptive requirements for wood shakes & shingles have been deleted from Part 5

Page 95: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

Standards Table 5.10.1.1.

Standards applicable to environmental separators & assemblies exposed to the exterior have been amended. Others have been deleted, such as:

CGSB CAN/CGSB-51.25 Thermal Insulation, Phenolic, Faced

CGSB CAN/CGSB-34.4-M Siding, Asbestos-Cement, Shingles & Clapboards

CGSB CAN/CGSB-34-14-M Sheets, Asbestos-Cement, Decorative

CGSB CAN/CGSB-34.17-m Sheets, Asbestos-Cement, Flat, Semi Compressed

Page 96: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

Windows, Doors & Skylights 5.10.2

New subsection added for windows, doors

and skylights

Page 97: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

Windows, Doors & Skylights Standards 5.10.2.2.

The previously referenced CSA A440 standard has been replaced by the harmonized AAMA/WDMA/CSA 101/I.S.2/A440 standard & the Canadian CSA Supplement CSA A440S1 for North America Fenestration Standards/Specifications for Windows, Doors, & Skylights

Page 98: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

Structural Loads, Air Leakage & Water Penetration 5.10.2.3.

Structural loads, air leakage & water penetration of windows, doors & skylights not within the scope of the standards must be designed & constructed in accordance with Articles 5.1.4.1. (Structural & Environmental Loads) and Sections 5.4 (Air leakage) and 5.6 (Precipitation)

Page 99: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

99

PART 6

Kelly Lanka Municipal Building Official – Part 3

Page 100: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

Scope of Part 6 Change 6.1.1.1.(2)

• Adjustments to existing heating, ventilating or air-conditioning systems are no longer regulated by the Building Code.

• Alterations, repair or component replacements remain within the scope of Part 6.

100

Page 101: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

6.2.1.1.(1)(j),(k)&(l) Good Engineering Practice

Revised:

(j) the CCBFC NRCC 38730, Model National Energy Code of Canada for Buildings 1997

Added:

(k) The CCBFC NRCC 54435, National Energy Code of Canada for Buildings 2011, and

(l) EPA/625/R-92/016, Radon Prevention in the Design and Construction of Schools and Other Large Buildings

101

Page 102: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

Ventilation of Storage & Repair Garages 6.2.2.3.(1)(a)

Upper limit of placement of carbon monoxide detector increased from 1200mm to 1800mm above the floor

102

Page 103: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

Ventilation of Storage & Repair Garages 6.2.2.3.(7)

Decreased exposure level of carbon monoxide to 25 parts per million from 35 parts per million, and nitrogen dioxide limits have been included.

103

Page 104: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

Hazardous Gases, Dusts or Liquids 6.2.2.5.

• New requirements for venting trenches that contain piping for Class I flammable liquids.

• When indoor piping is installed for Class 1 flammable liquids, the trench shall be:

- provided with positive ventilation to the outdoors, OR

- designed to prevent accumulation of flammable vapours

104

Page 105: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

Exhaust Ducts & Outlets 6.2.3.8.(6)

New rules added for venting auxiliary rooms, mechanical rooms & storage rooms through a storage garage, which include:

• these rooms are accessible only from that storage garage

• they have no openings or duct penetrations to adjacent spaces other than that storage garage & other auxiliary mechanical or storage rooms

• exhaust contains no contaminants

• they are provided with CO detection or a light switch interlocked with the operation of the exhaust fan serving the room

105

Page 106: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

Exhaust Ducts & Outlets 6.2.3.8.(15)

Exhaust air requirements for dwelling units have been clarified:

Other than self contained mechanical ventilation serving only one dwelling unit, exhaust air shall be provided in accordance with ANSI/ASHRAE 62.1, “Ventilation for Acceptable Indoor Air Quality”.

106

Page 107: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

Exhaust Dusts & Outlets 6.2.3.8.(18) & (19)

Requirements for collective venting of multiple installations of laundry drying equipment have been introduced to include that the ventilation system:

- be connected to a common exhaust duct that is vented by one central exhaust fan

- incorporate one central lint trap

- include an interlock to activate the central exhaust fan when laundry-drying equipment is in use

- be provided with makeup air, and

- exhaust ducts or vents connected to laundry-drying equipment shall discharge directly to the outdoors.

107

Page 108: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

Ducts in Exits 6.2.3.10

Clarifies that certain ductwork is permitted to penetrate an exit.

Permitted, if the duct:

- is designed for the purposes of 3.2.6., or

- only serves the exit from a dedicated rooftop air makeup unit

108

Page 109: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

Construction & Installation of Ducts & Plenums 6.2.4.3.(11)

Supply & return ducts located in an unconditioned space or outdoors shall have all joints sealed to SMACNA Class A seal level in accordance with the SMACNA “HVAC Duct Construction Standards – Metal & Flexible”.

109

Page 110: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

Construction & Installation of Ducts & Plenums 6.2.4.3.(12)

Supply ducts located in a conditioned space shall have all joints sealed to a Class C seal level in accordance with the SMACNA, “HVAC Duct Construction Standards – Metal & Flexible”.

110

Page 111: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

Concrete Slabs 6.2.4.5.(1)

Warm-air supply systems are no longer required to be installed in concrete slabs

111

Page 112: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

Tempering of Make-up Air 6.2.4.12 (2) & (3)

Tempering of make-up air with electric resistance heating no longer required

112

Page 113: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

Carbon Monoxide Alarms 6.2.12.3.(2)

Installation & conformance to standards now permit

battery operated carbon monoxide alarms in

buildings without electrical power

113

Page 114: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

Ventilation for Laboratories 6.2.13

New subsection added for ventilation design and construction requirements in laboratories

114

Page 115: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

115

PART 9 NON-RESIDENTIAL

Robert Schipper Manager of Building – Part 3

Page 116: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

116

• 9.8.2.1.(3) – width requirements for exit stairs

and public stairs in non-residential buildings have been added: • Based on 8mm per person • But not less than 900mm

Lighting:

• 9.9.12.1.(1) – Lighting requirements amended to

apply to all means of egress, except in dwelling units

• 9.9.12.(2) & 9.9.12.3.(5) – New minimum illumination levels: • Non-emergency lighting 10 lux • Emergency Lighting – 1 lux

Stair Width:

Page 117: 10 ANNUAL INDUSTRY WORKSHOP - Kitchener...foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A

117

9.10.9.6. – Additional types of penetrations detailed:

• All penetrations in firewalls must have a fire stop with a FT rating

• Single conductor wire penetrations to be spaced at least 300mm apart

• No size limit for combustible water distribution pipe penetrations when a fire stop is provided

• No fire stop required for sprinkler piping penetrations when an escutcheon plate is provided

• Fire dampers don’t need a fire stop if installed as per NFPA 80

Penetrations of Fire Separations: