09 lesson 04

94
1 1 EP Basic AP Service Learning Service Excellence & Relentless Execution 2 EP Basic AP Service Learning Service Excellence & Relentless Execution Today Menu : 1. CDVR 2. Introduction to Control Panels 3. System Operation/Testing and Adjusting EMCP I (SENR3535 via SIS) EMCP II+ (RENR1200 via SIS) EMCP III (RENR7902 via SIS) 4. TMI web

Upload: rozi54

Post on 14-Apr-2015

108 views

Category:

Documents


2 download

TRANSCRIPT

Page 1: 09 Lesson 04

1

1

EP Basic AP Service Learning

Service Excellence &Relentless Execution

2

EP Basic AP Service Learning

Service Excellence &Relentless Execution

Today Menu:

1. CDVR2. Introduction to Control Panels3. System Operation/Testing and

Adjusting• EMCP I (SENR3535 via SIS)

• EMCP I I+ (RENR1200 via SIS)

• EMCP I I I (RENR7902 via SIS)

4. TMI web

Page 2: 09 Lesson 04

2

3

EP Basic AP Service Learning

Service Excellence &Relentless Execution

Caterpillar Digital Voltage Regulator(CDVR)

Introduction and Specifications

Prepared by Service Traininghttps://psmktg.cat.com/srvtrng/

4

EP Basic AP Service Learning

Service Excellence &Relentless Execution

Foreword

This presentation was prepared by Caterpillar Service Training to be a training overview of the CDVR for Caterpillar generator set service personnel. This presentation provides comparisons to the previous design, DVR, and includes information pertaining to the removal of a DVR and replacement with a new CDVR. As always, the proper service information for the regulators in SIS should be used for the latest specific details for operation, adjustments, programming and troubleshooting.

Page 3: 09 Lesson 04

3

5

EP Basic AP Service Learning

Service Excellence &Relentless Execution

Compatibility – Products Affected

The following product’s standard configuration or available options will be affected. The change will affect PMG generators that have the CDVR as standard or option. Generators that do not have an option for the DVR will not be affected.

6

EP Basic AP Service Learning

Service Excellence &Relentless Execution

Compatibility – Products Affected Con’ t.The following product’s standard configuration or available options will be affected. The change will affect PMG generators that have the CDVR as standard or option. Generators that do not have an option for the DVR will not be affected.

Page 4: 09 Lesson 04

4

7

EP Basic AP Service Learning

Service Excellence &Relentless Execution

Other CDVR Production Information

• The CDVR will replace DVR for low and medium voltage generators and will also replace KCR 760 & KCR 65-12B for high voltage generators. A follow-up announcement will be sent that details product changeover on all affected products.

• The CDVR will be used in all EPG products currently available with a standard or optional CDVR and with high voltage applications where analog regulators are standard with current product.

• 3500 SE Generators will be shipped with a VR-6

• 3500 PM Generators will be shipped with a CDVR

8

EP Basic AP Service Learning

Service Excellence &Relentless Execution

CDVR started production January 2004

Digital Voltage Digital Voltage Regulator or “ DVR”Regulator or “ DVR”

Caterpillar Digital Voltage Caterpillar Digital Voltage Regulator or “ CDVR”Regulator or “ CDVR”

JanuaryJanuary20042004

TransitionTransition

Page 5: 09 Lesson 04

5

9

EP Basic AP Service Learning

Service Excellence &Relentless Execution

DVR from 1994-2003

• Previous design pictured• Called the “DVR” or “Digital

Voltage Regulator”• Manufactured by Magnetek-

Century• Will be discontinued• Replaced with the new

“Caterpillar Digital Voltage Regulator” or “CDVR”

• Six part numbers were used to accommodate SE & PM, 120, 240, and 480 VAC sensing requirements

10

EP Basic AP Service Learning

Service Excellence &Relentless Execution

Caterpillar Digital Voltage Regulator

• New design pictured

• Called the “Caterpillar Digital Voltage Regulator” or abbreviated “CDVR”

• Made by Basler Electric

• Will be used on Caterpillar generator sets and will replace the “DVR”

• January 2004 Production

• Only One Part Number is needed for all applications

• KVAR/PF control included

Page 6: 09 Lesson 04

6

11

EP Basic AP Service Learning

Service Excellence &Relentless Execution

CDVR Publications

• Available on Service Information System (SIS)– RENR7941 Specifications System Operation

Testing & Adjusting Guide

– “CDVR PC Software” is available on SISweb in the download section or on the monthly SIS subscription Flash File CD ROM.

• Available on Electronic Media Center– LEHE3225 Specifications Sheet

– LEXE3226 November 2003 Product News

12

EP Basic AP Service Learning

Service Excellence &Relentless Execution

Part Numbers

• Cat Digital Voltage Regulator (CDVR) - 235-5725

• Connector Part Numbers– P6 plug: 234-1856, P6 seal 246-7013.

– P9 plug: 234-1857, P9 seal 246-7014.

– P12 plug 234-1858, P12 seal 246-7015.

– P6, P9 and P12 Pins : 244-0452.

• Planned part number releases:– Crimping tool: 239-5260.

– Extraction tool: 246-8636.

Page 7: 09 Lesson 04

7

13

EP Basic AP Service Learning

Service Excellence &Relentless Execution

A Brief Look…

• There is no touch pad or display for programming

• PC programming only

• PC software is on SIS

• RS-232 PC connection

• No screw terminals

• 3 Molex connectors

• Bolt pattern like the DVR

• Fault LED Indicator

14

EP Basic AP Service Learning

Service Excellence &Relentless Execution

Why a new Caterpillar Regulator?

• DVR was designed in early 1990’s…– 1990’s technology has fewer features

– Internal components are becoming obsolete

– DVR designed for fewer applications

– Not cost effective to improve present design

• The CDVR has improved transient performance, added standard features such as VAR & PF control, and expanded flexibility for optimizing performance to individual customer applications.

Page 8: 09 Lesson 04

8

15

EP Basic AP Service Learning

Service Excellence &Relentless Execution

Features

• Microprocessor control of three standard modes – Automatic Voltage Regulation (AVR)

– Power Factor Regulation (PF)

– Reactive Power Regulation (VAR)

• Programmable stability settings

• Soft start control with an adjustable time setting in AVR control mode

• Dual Slope Under Frequency (volts/Hertz) regulation

16

EP Basic AP Service Learning

Service Excellence &Relentless Execution

Features

• Three-phase or single-phase generator voltage (RMS) sensing/regulation in AVR mode

• Single-phase generator current sensing for regulation purposes

• Field current and field voltage sensing

• Five contact sensing inputs for system interface

• One common LED for visual indication of Alarm and Shutdown fault conditions

• Ten generator protective functions

Page 9: 09 Lesson 04

9

17

EP Basic AP Service Learning

Service Excellence &Relentless Execution

Features

• Fault Shutdown Driver and Alarm Output Driver for indication of Alarm and Shutdown fault conditions

• Generator paralleling with reactive droop compensation and reactive differential compensation

• Line drop compensation

• Remote communication interface via CAN 2.0B or RS-232

• UL 508 Recognized and CE certified

18

EP Basic AP Service Learning

Service Excellence &Relentless Execution

Modes of Operation Defined

•Automatic Voltage Regulation (AVR)

•Reactive Power (VAR) Regulation

•Power Factor (PF) Regulation

Page 10: 09 Lesson 04

10

19

EP Basic AP Service Learning

Service Excellence &Relentless Execution

Automatic Voltage Regulation Mode

• AVR mode regulates the RMS generator output voltage. The regulator senses the generator output voltage through the sensing leads and then adjusts the dc output excitation current to the generator exciter field. This excitation current maintains the generator terminal voltage at the regulation setpoint.

• This is the basic function of any voltage regulator on a standalone generator set

• AVR mode is the default operating mode and can be disabled by a switch input or the J4 port with CDVR PC Software.

20

EP Basic AP Service Learning

Service Excellence &Relentless Execution

VAR Control Mode

• Reactive or VAR mode regulates “Volt-Amps Reactive” when paralleling with an infinite bus. The CDVR calculates generator VARs from output voltage and droop CT current quantities and adjusts the excitation current to maintain VARs at the programmed setpoint. VAR mode and PF mode are mutually exclusive modes that both work in conjunction with AVR mode.

• VAR mode is enabled by a switch input and the CDVR PC Software. VAR is adjustable from 100 percent absorb to 100 percent generate.

• Typically used when paralleled with utility.

Page 11: 09 Lesson 04

11

21

EP Basic AP Service Learning

Service Excellence &Relentless Execution

Power Factor Control Mode

• PF mode regulates Power Factor when paralleling with an infinite bus. The CDVR calculates PF using the sensed output voltage and current and then adjusts the dc excitation current to maintain PF at theprogrammed setpoint. Again, VAR mode and Power Factor mode are mutually exclusive modes that both work in conjunction with AVR mode.

• PF mode is enabled by a switch input and the J4 port with CDVR PC Software. PF setpoint is adjustable from 0.6 –1.0 lag and 0.6 – 1.0 lead.

• Typically used when paralleled with utility.

22

EP Basic AP Service Learning

Service Excellence &Relentless Execution

Regulation Characteristic. Below the Knee Frequency, the generator voltage follows a decreasing slope based on generator frequency. When generator frequency is between the Knee Frequency and Knee Frequency minus 5 hertz, voltage follows Slope 1. When generator frequency is between the Knee Frequency minus 5 hertz and theUnderfrequency Point, voltage follows Slope 2 down to the Minimum Voltage Setpoint. When generator frequency is below the Minimum Frequency Point, excitation is removed. Programming Decreasing Slope 2 is optional.

0Hz 25 45 55 60Hz

480

VAC

0 Knee Frequency (45-65Hz)

Min. Voltage Setpoint (50-100%)

5 Hz (Not Adjustable)

Decreasing Slope 1 (0-10 V/Hz)

Decreasing Slope 2 (0-10 V/Hz)

Generator Output VoltageMinimum Frequency Point (20-40Hz)

Page 12: 09 Lesson 04

12

23

EP Basic AP Service Learning

Service Excellence &Relentless Execution

10 CDVR Protective Functions

• Generator Overvoltage

• Generator Undervoltage

• Loss of Excitation

• Instantaneous Field Overcurrent

• Over Excitation

• Loss of Sensing Voltage

• Diode Fault Monitor

• Internal CDVR Processor Watchdog Failure

• Internal CDVR Memory Failure

• Fault Reset Switch Closed Too Long

24

EP Basic AP Service Learning

Service Excellence &Relentless Execution

General Specifications

• Voltage Regulation:

– ± 0.25% from no load to full load with < 30% THD

• Temperature Drift:

– Less than ±1% for a 40°C (72°F) change over the ambient operating temperature range.

• Regulator response time:

– Maximum of 10 milliseconds.

• Variable Sense Range:

– 90 to 600 volts.

• Control Power:

– 24Vdc Supply (18 to 30Vdc, 5VA)

Page 13: 09 Lesson 04

13

25

EP Basic AP Service Learning

Service Excellence &Relentless Execution

General Specifications

• Regulator Filtering:– THF 3% per IEC34-1

– TIF of 50 NEMA MG1-22.43

• Harmonic Tolerance:– 0.5% Voltage regulation with up to 40% THD

• Power Dissipation:– 55W Maximum

• Weight:– 1.47 kg (3.24 lbs.)

26

EP Basic AP Service Learning

Service Excellence &Relentless Execution

General Specifications

• Regulator sensing:– True RMS 3-phase sensing is standard. Single phase sensing is

available.

• Configurable Volts/Hz Regulation Characteristic– Two slope ranges adjustable from 0 to 10 V/Hz. See Regulation

Characteristic Illustrations.

• Fine voltage adjust range:– ± 15% Maximum of regulator sensing voltage.

• Regulator voltage gain (line loss compensation)– Adjustable from 0 to 10%.

Page 14: 09 Lesson 04

14

27

EP Basic AP Service Learning

Service Excellence &Relentless Execution

General Specifications

• Reactive droop adjustment:– Adjustable from 0 to 10%.

• Fault detection and identification:– Diagnostics identify operation outside of programmed limits.

Specific fault information is available after the unit has been powered down.

• Over Excitation protection:– Shuts off generator output when excitation current exceeds normal

operating currents for 10 seconds or instantaneous shut-off if output current exceeds approximately 28 Amperes.

28

EP Basic AP Service Learning

Service Excellence &Relentless Execution

General Specifications

• Voltage Regulation Rating– 120 to 15000 VAC

• Generator Excitation Type– PM – Permanent Magnet

– SE – Self Excited

– AREP – Auxiliary Winding Capable

• AC Input Power– Three phase, 80 to 264 VAC, 50 to 400 Hz, 1150VA

– Single phase, 100 to 280 VAC, 50 to 400Hz, 1900 VA

Page 15: 09 Lesson 04

15

29

EP Basic AP Service Learning

Service Excellence &Relentless Execution

General Specifications

• Output Power Maximum Continuous:– 12 Amps DC @ 63VDC – 10 Amps DC @ 125 VDC

• Output Power Maximum Forcing (10 seconds):– 25 Amps DC @ 125 VDC– 20 Amps DC @ 250 VDC

• AC Sensing Voltage:– True RMS three phase or single phase, 90 to 600 VAC, maximum 1 VA

per phase burden.

30

EP Basic AP Service Learning

Service Excellence &Relentless Execution

General Specifications

• Reactive Voltage Droop circuit:

• 5 Amp Current Transformer, maximum 1 VA burden

– Regulator has internal CT burden resistor

• Exciter Field Resistance Range– 3 Ohms minimum, 39 ohms maximum

Page 16: 09 Lesson 04

16

31

EP Basic AP Service Learning

Service Excellence &Relentless Execution

Environmental Specifications

• Operating Temperature:– -40°C to 70°C (-40°F to 158°F)

• Storage Temperature:– -40°C to 85°C (-40°F to 185°F)

• Relative Humidity:– 95% non-condensing 30°C to 60°C

• Salt Fog:– 5% for 48 hours at 38°C (100°F) at 115% of the nominal operating

voltage

32

EP Basic AP Service Learning

Service Excellence &Relentless Execution

Environmental Specifications

• Vibration:– 4.5G (peak) 18-2000Hz in 3 perpendicular planes

• Shock:– Withstands up to 20 g’s in three mutually perpendicular planes.

• Certifications:– CE Approved

– UL 508 Recognized

– CSA Listed

– Meets MIL STD 461C

Page 17: 09 Lesson 04

17

33

EP Basic AP Service Learning

Service Excellence &Relentless Execution

Caterpillar Digital Voltage Regulator(CDVR)

Wiring Connections

Prepared by Service Traininghttps://psmktg.cat.com/srvtrng/

34

EP Basic AP Service Learning

Service Excellence &Relentless Execution

Regulator Connectors and LED

(1) 6-pin connector “P6”

(2) LED Indicator

(3) 12-pin connector “P12”

(4) 9-pin connector “P9”

(5) 9-pin D-sub Connector “J4”

Note: Items 1, 3 & 4 are Molex brand Connector plugs

Page 18: 09 Lesson 04

18

35

EP Basic AP Service Learning

Service Excellence &Relentless Execution

P6 connector pin numbering

���� ���� ����

������������

View as looking at P6 on the regulator plug

36

EP Basic AP Service Learning

Service Excellence &Relentless Execution

P6 Wiring

• Pins 1, 2 & 3: AC power inputs from either SE or PM stator winding

• Pins 4 (-) & 5 (+): DC field voltage output to the generator exciter stator

• Pin 6 should be hard-wired to earth ground with at least a 16AWG copper wire

Page 19: 09 Lesson 04

19

37

EP Basic AP Service Learning

Service Excellence &Relentless Execution

P9 connector pin numbering

���

��

View as looking at P9 on the regulator plug

38

EP Basic AP Service Learning

Service Excellence &Relentless Execution

P9 Wiring• Pins 1, 2 & 3: CANbusdata link

connections

• Pins 4, 5 & 6: Raise and Lower connections for voltage level adjustments in AVR mode, KVAR level in KVAR mode and P.F. level adjustment in P.F. Mode

• Pin 7: Excitation Disable of field voltage to exciter stator

• Pin 8: Fault Shutdown Reset

• Pin 9: VAR/PF mode enable

Page 20: 09 Lesson 04

20

39

EP Basic AP Service Learning

Service Excellence &Relentless Execution

P12 connector pin numbering

�����

������

40

EP Basic AP Service Learning

Service Excellence &Relentless Execution

P12 Wiring

• Pins 1 & 2: droop CT input

• Pins 3 & 6: +/-10 DCV in

• Pin 4: Alarm output

• Pin 5: Fault SD output

• Pins 7 & 8: 24VDC Input

• Pin 9: Alarm and Fault Shutdown Supply Driver

• Pins 10, 11, & 12: Generator AC voltage sensing phases “C” , “B” , and “A” respectively.

Page 21: 09 Lesson 04

21

41

EP Basic AP Service Learning

Service Excellence &Relentless Execution

J4 connector pin numbering

The digital voltage regulator has the capability to communicate with a personal computer or programmable logic controller. The J4 connector of the digital voltage regulator provides an RS-232 port necessary for communication. Pin locations and numbers are shown above.

42

EP Basic AP Service Learning

Service Excellence &Relentless Execution

J4 RS-232 Wiring

The J4 RS-232 port is a 9-pin connector including a pins for Receive, Transmit, common Signal Ground. The common signal ground is NOT a bonding ground and should not be grounded to the case or frame. It is to be connected to the RS-232 device Signal Ground connection point. Cable length should be limited to 15 m (50 ft) maximum for the RS-232 signal wiring

Part 1U-9494 – RS232 cable.

Page 22: 09 Lesson 04

22

43

EP Basic AP Service Learning

Service Excellence &Relentless Execution

Example PMG Diagram

44

EP Basic AP Service Learning

Service Excellence &Relentless Execution

Example PMG Diagram

Required only for Var/PF control. Var/PF permitted with 52a closed, inactive with 52a open.

Page 23: 09 Lesson 04

23

45

EP Basic AP Service Learning

Service Excellence &Relentless Execution

Example PMG Diagram

Excitation is disabled when closed, enabled when open.

46

EP Basic AP Service Learning

Service Excellence &Relentless Execution

Example PMG Diagram

Momentary closure resets any shutdown fault.

Page 24: 09 Lesson 04

24

47

EP Basic AP Service Learning

Service Excellence &Relentless Execution

Example PMG Diagram

S1 (SPDT, spring-return to center-off position) adjusts regulator setpoint or KVAR/PF setpoint when in KVAR/PF mode

48

EP Basic AP Service Learning

Service Excellence &Relentless Execution

Example PMG Diagram

Normally-off, turns on for user alarm or trip.

Page 25: 09 Lesson 04

25

49

EP Basic AP Service Learning

Service Excellence &Relentless Execution

Example PMG Diagram

Analog input voltage between -10 and +10 Vdcprovides adjustment of operating voltage.

50

EP Basic AP Service Learning

Service Excellence &Relentless Execution

Example PMG Diagram

External fuses should be sized to match the PMG and protect the field. Maximum fuse size should be limited to Bussmann type KTK-12.

Page 26: 09 Lesson 04

26

51

EP Basic AP Service Learning

Service Excellence &Relentless Execution

Example PMG Diagram

Three-phase PMG is shown. For single-phase PMG, omit P6-3 connection.

52

EP Basic AP Service Learning

Service Excellence &Relentless Execution

Example PMG Diagram

Sensing potential transformer is required if line voltage exceeds 600 Vac.

Page 27: 09 Lesson 04

27

53

EP Basic AP Service Learning

Service Excellence &Relentless Execution

Example PMG Diagram

Items No.10 are not supplied by Caterpillar.

54

EP Basic AP Service Learning

Service Excellence &Relentless Execution

Example PMG Diagram

When generator rotation is ACB, the connections shown for CTB should be reversed.

Page 28: 09 Lesson 04

28

55

EP Basic AP Service Learning

Service Excellence &Relentless Execution

9

8

CTBGEN

10

9

52 9

P0018-2507-16-03

FIELD OUTPUT

P6-4 (F2,-) P6-5 (F1,+) P6-1

POWER INPUT

P6-2 P6-3

CURRENTSENSING

P12-1 P12-2 P12-10

VOLTAGESENSING

P12-11 P12-12

P9-6

RAISE/LOWERINPUTS

P9-4 P9-5

+/-10 VDCCONTROL INPUT

P12-6 (+) P12-3 (-)

VAR/PFCONTROL

P9-9

EXCITATIONDISABLE

P9-7

FAULTRESET

P9-8 P12-4 (-)

ALARMDRIVER

SHUTDOWNFAULT DRIVER

P12-9 (+) P12-5 (-)

CAT DVR-II

GROUND

P6-6

24 Vdc+ _

24 Vdc CONTROLPOWER

P12-8 (+) P12-7 (-)

1 52a

2 3

S1

4

9

5 5 6

A

B

C

Required only for Var/PF control. Var/PF is active with 52a closed, inactive with 52a open.

Excitation is disabled when closed, enabled when open.

Momentary closure resets any shutdown fault.

S1 (SPDT, spring-return to center-off position) adjusts CAT DVR-II setpoint.

Normally-off, turns on for user alarm or trip.

Analog input voltage between -10 and +10 Vdc provides adjustment of operating setpoint.

External fuses should be sized to match the AREP windings and protect the field. Maximumfuse size should be limited to Bussmann type KTK-12 or equivalent.

Sensing potential transformer is required if line voltage exceeds 660 Vac.

Item not supplied by Caterpillar.

When generator rotation is ACB, the connections shown for CTB should be reversed.

1

2

3

4

5

6

7

8

9

10

9

7

+

Auxiliary WindingsShunt Series

X1 X2 Z1 Z2

AREPWiring

Example

56

EP Basic AP Service Learning

Service Excellence &Relentless Execution

The VR-3 (not shown), VR-6, DVR and new CDVR all have the same bolt pattern and mount in the same location in the generator enclosure.

Mounting

VR-6 DVR CDVR

Page 29: 09 Lesson 04

29

57

EP Basic AP Service Learning

Service Excellence &Relentless Execution

The VR-6 and CDVR both present an electrical shock risk. Terminals and heatsinksare live at potentially lethal voltages when power is applied and for up to 8 minutes after power is removed. This high voltage may cause electrical shock that could result in injury or death. Service by trained personnel only.

Reminder – Live Terminals and Heatsinks

VR-6 CDVR

58

EP Basic AP Service Learning

Service Excellence &Relentless Execution

Wiring Comparisons to the DVR

• Droop CT wiring

• Fault Alarm and Shutdown Output Driver Logic

• VAR/PF enable, fault reset, and excitation disable inputs

• Remote voltage and VAR/PF adjustment

Page 30: 09 Lesson 04

30

59

EP Basic AP Service Learning

Service Excellence &Relentless Execution

Wiring Comparisons to the DVR

DVR

60

EP Basic AP Service Learning

Service Excellence &Relentless Execution

Wiring Comparisons to the DVR

• The DVR uses an 8-ohm resistor with a 1 Amp droop CT or a 1-ohm resistor with a 5 Amp droop CT.

• The CDVR requires a 5 Amp droop CT and no resistor across the CT output.

• Note: CT leads which are not connected to the regulator must be shorted to avoid a potential shock hazard.

DVR

Page 31: 09 Lesson 04

31

61

EP Basic AP Service Learning

Service Excellence &Relentless Execution

Wiring Comparisons to the DVR

• DVR and CDVR have the output driver logic reversed.

• The DVR low side driver outputs for the fault alarm and shutdown are active high (driver output floats when a fault is active).

• The CDVR low side driver outputs for the alarm and shutdown are active low (driver output pulls low when a fault is active).

• A CDVR output is N/O and would energize to close the output circuit upon an alarm or shutdown.

DVR

62

EP Basic AP Service Learning

Service Excellence &Relentless Execution

Wiring Comparisons to the DVR

• The DVR VAR/PF enable, fault reset, and excitation disable inputs activate with +24VDC.

• The CDVR VAR/PF enable, fault reset, and excitation disable inputs require a normally open dry contact to enable the function.

DVR

Page 32: 09 Lesson 04

32

63

EP Basic AP Service Learning

Service Excellence &Relentless Execution

Wiring Comparisons to the DVR

• The DVR utilizes a 10K-ohm potentiometer for remote voltage adjust another for remote VAR/PF adjustments

• The CDVR uses a singlemomentary switch with raise and lower contacts. The switch adjusts voltage in AVR mode and also adjusts VAR or PF if operating in that mode.

DVR

64

EP Basic AP Service Learning

Service Excellence &Relentless Execution

Caterpillar Digital Voltage Regulator(CDVR)

PC Software Installation

Prepared by Service Traininghttps://psmktg.cat.com/srvtrng/

Page 33: 09 Lesson 04

33

65

EP Basic AP Service Learning

Service Excellence &Relentless Execution

CDVR PC Software Download

• The CDVR PC software and an IBM Compatible Personal Computer or Laptop is required for the service technician to program CDVR set points and parameters and to access status indicators and regulator metering functions.

• This Presentation has detailed steps for downloading the PC Software from SIS (Service Information System), establishing communications and programming the CDVR.

66

EP Basic AP Service Learning

Service Excellence &Relentless Execution

CDVR PC Software Download• Navigate to SIS at https://sis.cat.com

Page 34: 09 Lesson 04

34

67

EP Basic AP Service Learning

Service Excellence &Relentless Execution

CDVR PC Software Download

• Click on “Downloads”

68

EP Basic AP Service Learning

Service Excellence &Relentless Execution

CDVR PC Software Download

• Click on “CDVR PC Software.exe”

Page 35: 09 Lesson 04

35

69

EP Basic AP Service Learning

Service Excellence &Relentless Execution

CDVR PC Software Download

• Verify “Save this file to disk” is selected as shown and then click the “OK” button

70

EP Basic AP Service Learning

Service Excellence &Relentless Execution

CDVR PC Software Download

• Select where to save the file. The example shows the file being saved as “CDVR PC Software” to the computer Desktop.

Page 36: 09 Lesson 04

36

71

EP Basic AP Service Learning

Service Excellence &Relentless Execution

CDVR PC Software Download

• The “CDVR PC Software” file will download and a Download Complete box will appear when the download is complete. Click “Close” .

• This file is 6.17MB in size and may take longer with slower network or modem connections.

• This completes the software download.

72

EP Basic AP Service Learning

Service Excellence &Relentless Execution

CDVR PC Software Installation

• Run the file by double-clicking

on the file “CDVR PC Software”

• If the file has not been saved to the desktop, navigate to the folder where it was saved and open the CDVR PC Software program file as shown below.

or

Page 37: 09 Lesson 04

37

73

EP Basic AP Service Learning

Service Excellence &Relentless Execution

CDVR PC Software InstallationCDVR PC Software Installation

• Follow the installation instructions and click “Next” when ready.

74

EP Basic AP Service Learning

Service Excellence &Relentless Execution

CDVR PC Software InstallationCDVR PC Software Installation

• Verify the folder location and click “Next”.

Page 38: 09 Lesson 04

38

75

EP Basic AP Service Learning

Service Excellence &Relentless Execution

CDVR PC Software InstallationCDVR PC Software Installation

• Click “Next”…

76

EP Basic AP Service Learning

Service Excellence &Relentless Execution

CDVR PC Software InstallationCDVR PC Software Installation

• Click “Next”…

Page 39: 09 Lesson 04

39

77

EP Basic AP Service Learning

Service Excellence &Relentless Execution

CDVR PC Software InstallationCDVR PC Software Installation

• Click “Next”

78

EP Basic AP Service Learning

Service Excellence &Relentless Execution

CDVR PC Software InstallationCDVR PC Software Installation

• A window will appear with the bars showing the installation…

Page 40: 09 Lesson 04

40

79

EP Basic AP Service Learning

Service Excellence &Relentless Execution

CDVR PC Software InstallationCDVR PC Software Installation• When the installation is complete click “Finish”

• This completes the software Installation

80

EP Basic AP Service Learning

Service Excellence &Relentless Execution

To start the CDVR PC softwarefollow these four steps. 1. Click the Start button2. Click Programs3. Click Caterpillar Software4. Click Cat PC Software

1

2

3

4

Page 41: 09 Lesson 04

41

81

EP Basic AP Service Learning

Service Excellence &Relentless Execution

CDVR PC SoftwareCDVR PC Software• Startup Screen when the software is launched

82

EP Basic AP Service Learning

Service Excellence &Relentless Execution

What’s needed for communication?

1. Computer with the CDVR Software installed (the computer must meet the minimum requirements in the CDVR Service Manual)

2. Cable to connect the computer to the CDVR RS-232 port. Newer computers may not have an RS-232 port and may require a USB to RS-232 adapter (237-7547). Cables are not provided.

3. 24VDC power to the CDVR input power connections. AC Sensing and/or PMG power voltage is not needed for communication.

Page 42: 09 Lesson 04

42

83

EP Basic AP Service Learning

Service Excellence &Relentless Execution

Caterpillar Digital Voltage Regulator(CDVR)

PC Software Overview

Prepared by Service Traininghttps://psmktg.cat.com/srvtrng/

84

EP Basic AP Service Learning

Service Excellence &Relentless Execution

CDVR Programming Overview

• The next few slides provide only a brief explanation of the CDVR PC Software screens and parameters. The CDVR Service Manual, RENR7941, should be referenced for more detail on the parameters and functions not covered in this overview.

Page 43: 09 Lesson 04

43

85

EP Basic AP Service Learning

Service Excellence &Relentless Execution

CDVR Programming Overview

• “File” pull down menu is used to Open, Save or Print CDVR program configuration (* .DV2) files

86

EP Basic AP Service Learning

Service Excellence &Relentless Execution

CDVR Programming Overview• “Communications” pull down menu is used to connect or disconnect CDVR

communication

Page 44: 09 Lesson 04

44

87

EP Basic AP Service Learning

Service Excellence &Relentless Execution

CDVR Programming Overview• “Screens” pull down menu or the buttons are used to select the five configuration

screens

Both is the same

88

EP Basic AP Service Learning

Service Excellence &Relentless Execution

CDVR Programming Overview

• “Upgrade” pull down is for upgrading the CDVR embedded software

Page 45: 09 Lesson 04

45

89

EP Basic AP Service Learning

Service Excellence &Relentless Execution

CDVR Programming Overview

• “Help” pull down will display the version of PC Software being used. Also shown here.

90

EP Basic AP Service Learning

Service Excellence &Relentless Execution

System Configuration Screen• “Configuration” screen has generator voltage and current output and sensing parameters.

Only fields with a white background can be changed. In this case, “Rated Voltage” has been selected and is high lighted.

The bottom screen bars show the minimum, maximum and step or increment allowed for the selected parameter.

Page 46: 09 Lesson 04

46

91

EP Basic AP Service Learning

Service Excellence &Relentless Execution

System Configuration Screen• “Configuration” screen has generator voltage and current output and sensing parameters.

Rated voltage is changed from 120V to 240V by typing “240” and then the “Enter” key. (Do not use the Tab key). When 240 is entered the Rated KVAR automatically changes from 75 to 150. Fields with a black background cannot be clicked on and changed.

92

EP Basic AP Service Learning

Service Excellence &Relentless Execution

System Configuration Screen

• There are two operating frequency parameters.

“Power Input Freq” is the frequency of the input power. On SE this is the same as the generator operating frequency which is 50 or 60Hz only. For PMG It is the frequency from the PMG exciter stator from 50-400hz.“Frequency” comes from the generator nameplate and will be 50 or 60 Hertz.

Page 47: 09 Lesson 04

47

93

EP Basic AP Service Learning

Service Excellence &Relentless Execution

System Configuration Screen

• Other sensing parameters explained

Sensing Mode can be Three or Single Phase

PT Primary and Secondary voltages

Droop CT is programmed to 600 on the primary. 5 on the secondary is not adjustable so the droop CT ratio is 600:5

94

EP Basic AP Service Learning

Service Excellence &Relentless Execution

System Configuration Screen

• Get From Unit Button

Voltage regulator settings are retrieved by clicking the “Get From Unit” button. This causes the current settings of the CDVR to be displayed on the “settings” screen. This button will be grayed out until the communication is established.

Parameter changes are sent to the CDVR by pressing the Enter key on the PC or by selecting a setting from a pull-down menu. This causes the selected setting displayed on the setting screen to become the active voltage regulator setting.

Page 48: 09 Lesson 04

48

95

EP Basic AP Service Learning

Service Excellence &Relentless Execution

System Configuration Screen

• EEPROM Button

Settings are saved in the CDVR EEPROM (nonvolatile memory). When power is removed, the EEPROM saved settings will be active at power-up. If the settings are changed and sent to the voltage regulator by hitting the enter key, they are not sent to the EEPROM. They will be lost if the CDVR is powered off. When closing communication the software will prompt the user to save the settings to the EEPROM. This question is asked even if no changes were made to the settings. While communicating the user can save changes to the EEPROM anytime by clicking the “EEPROM” button.

96

EP Basic AP Service Learning

Service Excellence &Relentless Execution

System Configuration Screen

• Information for PC Software and CDVR

PC Software version

The CDVR serial number, internal embedded software version and CDVR part number will show in these three boxes

Page 49: 09 Lesson 04

49

97

EP Basic AP Service Learning

Service Excellence &Relentless Execution

Setting Adjustments Screen

• Setpoint Parameters

AVR Voltage is the terminal output voltage of the generator in the AVR mode.

VAR percentage sets VAR level maintained in the VAR mode.

Power Factor sets the PF maintained in the Power Factor mode.

98

EP Basic AP Service Learning

Service Excellence &Relentless Execution

Setting Adjustments Screen• Setpoint Parameters

Load Compensation Mode settings are “Off, Droop, or Line Drop”. “Off” is no voltage droop. “Droop” allows up to 10% droop at full load. “Line Drop” allows voltage to increase up to 10% for line loss compensation.

The Setpoint (%) for “Droop” and “Line Drop” is 0 to 10%.

Page 50: 09 Lesson 04

50

99

EP Basic AP Service Learning

Service Excellence &Relentless Execution

Setting Adjustments Screen

• Startup Parameters Soft Start Mode

Soft Start Bias (%) determines the generator voltage at startup. 0 to 90 may be entered.

Soft Start Time (sec) establishes the length of time for the generatorvoltage to increase to the rated level. 0 to 120 sec. may be entered.

100

EP Basic AP Service Learning

Service Excellence &Relentless Execution

Setting Adjustments Screen

• Startup Parameters Under Frequency Mode

The five programmable Under Frequency Mode parameters determine the CDVR under frequency voltage regulation characteristic curve.

The next slide has a graph of the under frequency voltage regulation characteristic curve and setpoints.

Page 51: 09 Lesson 04

51

101

EP Basic AP Service Learning

Service Excellence &Relentless Execution

0Hz 25 45 55 60Hz

480

VAC

0

Minimum Frequency Point (20-40Hz)

Regulation Characteristic. Below the Knee Frequency, the generator voltage follows a decreasing slope based on generator frequency. When generator frequency is between the Knee Frequency and Knee Frequency minus 5 hertz, voltage follows Slope 1. When generator frequency is between the Knee Frequency minus 5 hertz and theUnderfrequency Point, voltage follows Slope 2 down to the Minimum Voltage Setpoint. When generator frequency is below the Minimum Frequency Point, excitation is removed. Programming Decreasing Slope 2 is optional.

102

EP Basic AP Service Learning

Service Excellence &Relentless Execution

Control Gain Screen

Control Gain

Generators delivered with a CDVR installed will have these parameters set for optimal generator operation. These settings may vary on different packages.

These parameters are covered in detail in the Service Manual and it should be referenced when making changes.

Page 52: 09 Lesson 04

52

103

EP Basic AP Service Learning

Service Excellence &Relentless Execution

Protection Settings Screen

• Protection

The Shutdown Override button can be toggled from DISABLED to ENABLED during set-up or troubleshooting.

If the Fault Reset Switch is held too long the CDVR will take programmed action.

104

EP Basic AP Service Learning

Service Excellence &Relentless Execution

Protection Settings Screen• Protection

Protective settings like Generator Overvoltagehave the following:1. Enable check box,2. Fault Type (Alarm or Shutdown)3. Trip Value (%)4. Time Delay (Sec.)

If output voltage exceeds 135% for 2 seconds, an Alarm condition will activate.

Page 53: 09 Lesson 04

53

105

EP Basic AP Service Learning

Service Excellence &Relentless Execution

Protection Settings Screen• Protection

Excitation (Exciter Stator) current is monitored and if the programmed limits are exceeded the excitation current will be disabled.

Excitation current will also be disabled if the Exciter Diode Monitor or Loss of Sensing limits are exceeded.

106

EP Basic AP Service Learning

Service Excellence &Relentless Execution

Metering, Operation and Alarms Screen

• Metering Password

When the “Metering” button is clicked a password prompt window opens.

This screen has password protection to prohibit an untrained person from changing parameters which may cause damage to the generator or force the generator into an unsafe operating mode.

Page 54: 09 Lesson 04

54

107

EP Basic AP Service Learning

Service Excellence &Relentless Execution

Metering, Operation and Alarms Screen

When the password “cat” is entered, full access is granted.

If “Cancel” is selected the Metering data is available only for viewing. Fields with white backgrounds cannot be changed and the soft buttons will be inactive.

cat

108

EP Basic AP Service Learning

Service Excellence &Relentless Execution

Generator operating parameters values are displayed in green.

Operating Mode is AVR and can be changed to VAR or PF if VAR/PF contact is closed.

Fine Adjustment acts as the raise/lower switch and varies the voltage setpointin AVR mode. This would vary PF/VARs if in the PF/VAR mode.

Metering, Operation and Alarms Screen

Page 55: 09 Lesson 04

55

109

EP Basic AP Service Learning

Service Excellence &Relentless Execution

Setpoint allows the user to change the AVR, VAR or PF level to be maintained while the generator is operating.

Caution: While the generator running, the CDVR will immediately change its regulation to obey the values or buttons changed on this screen. Customer access is discouraged.

Metering, Operation and Alarms Screen

1VDC change cause a 1% AVR volt change or 10% KVAR change or .04 PF change

110

EP Basic AP Service Learning

Service Excellence &Relentless Execution

“Status” will light the soft LED modes that apply when active.

“Contact Inputs” will light when switched inputs are activated.

“Alarms” will light when the alarm is active or if a shutdown has occurred due to an alarm. The hard wired reset switch will reset.

Metering, Operation and Alarms Screen

Page 56: 09 Lesson 04

56

111

EP Basic AP Service Learning

Service Excellence &Relentless Execution

The “Alarm Signal” LED will light if there is an active alarm condition.

When the “Disabled” button is toggled to “Enabled” the CDVR will not allow normal shutdown faults to shutdown excitation for troubleshooting. This must be used carefully to protect the generator from unsafe conditions.

Metering, Operation and Alarms Screen

112

EP Basic AP Service Learning

Service Excellence &Relentless Execution

Summary

This concludes the training overview of the CDVR. This presentation will be updated as needed and available on the Caterpillar Service Training Website at: https://psmktg.cat.com/srvtrng/

Again, the proper service information for the regulators in SIS should be used for the latest specific details for operation, adjustments, programming and troubleshooting.

Page 57: 09 Lesson 04

57

113

EP Basic AP Service Learning

Service Excellence &Relentless Execution

CDVR Laboptional

114

EP Basic AP Service Learning

Service Excellence &Relentless Execution

Control Panels

Page 58: 09 Lesson 04

58

115

EP Basic AP Service Learning

Service Excellence &Relentless Execution

The 3N8900 Type 5

This is the 3N8900 type V control panel. It's been around for a number of years and there are

still many of them in use today. This panel will be covered in detail later. The panel has AC Ammeter,

frequency meter, AC Voltmeter,; Off / Reset, Auto, Start, Stop Engine Control Switch,

Governor Speed Control, Alarm Panel, etc. Four fault lights for Low Oil Pressure,

Excessive Water Temperature, Over Crank, and Over Speed.

116

EP Basic AP Service Learning

Service Excellence &Relentless Execution

Caution VACCaution VACThis is the inside of the Type V control panel. Notice the tapeon the back of the meters.

There is 480 volts on the meters so opening the panel during operation is not recommended.

There is a KVAR controller mounted on this particular one but Cat does not use it any longer.

Page 59: 09 Lesson 04

59

117

EP Basic AP Service Learning

Service Excellence &Relentless Execution

Junction Box

Around 1985 Caterpillar started to standardize the control panels making this “Engine Junction Box"

with all of the electromechanical inputs inside. Oil pressure switches are mounted on the rear of the box and

Water Temperature switches are mounted elsewhere on the engine. Before this box was used, wiring was done

using a schematic without a wire routing diagram or “common” wiring strategy. Cat developed the harness

and a Junction box to make a common wiring for all. This junction box is still being used today not only

in genset applications but also in many industrial and marine as well as other commercial applications.

118

EP Basic AP Service Learning

Service Excellence &Relentless Execution

TDRTDR

ESSESS

EmergEmerg. Stop. StopSw.Sw.Power RelayPower Relay

Hr. MeterHr. Meter

Here is the internal view of the Junction Box. In it are the Engine Speed Switch (ESS), a Time Delay Relay

(TDR), an emergency stop switch, a power relay, and an hour meter. The standard harness is inside of the

corregated plastic conduit. The wires are labeled with a wire code for to make troubleshooting easier.

The box is shock mounted to absorb engine vibration to protect the components inside the junction box.

With out proper shock mounting the small relay contacts inside the ESS and TDR may chatter cause a failure

or shutdown.

Page 60: 09 Lesson 04

60

119

EP Basic AP Service Learning

Service Excellence &Relentless Execution

The 4W8000 with auto start/stop

This electromechanical control panel 4W8000 was used with the engine mounted junction box. It has an

Automatic Stop/Start module with 4 fault lights for Oil Pressure, Water Temperature, Overspeed, and

Overcrank. There is an Emergency Stop switch. The control switch has four positions:. Auto, Manual,

Stop and Reset. The panel also has a Voltmeter, Ammeter, Frequency Meter, Oil Pressure and

Water Temperature gauges, and an optional Alarm Module that warns when some things are about to fail.

If the oil pressure is low, but not too low, it will turn on the low oil pressure alarm light.

120

EP Basic AP Service Learning

Service Excellence &Relentless Execution

EMCP I Engine Control Engine Control ModuleModule

Alarm Alarm ModuleModule AC Meter AC Meter

ModuleModule

Page 61: 09 Lesson 04

61

121

EP Basic AP Service Learning

Service Excellence &Relentless Execution

• In 1987 the Electronic Modular Control Panel (EMCP) was put intoproduction. This was abbreviated as ECMP, not “EMCP I” . Folks later began to call it “EMCP I” when the ECMP II panel was released in the mid-90’s to distinguish between the two.

• The EMCP panel simplified the genset control system by eliminating a lot of wires, senders and switches. The LCD displayed hours, Engine Speed, Battery Voltage, Oil Pressure, and Coolant Temperature. These controls are used in many switchgear applications also.

• This panel needs only one magnetic pick-up, one oil pressure sensor, and one coolant temperature sensor mounted on the engine. The engine junction box was no longer needed.

122

EP Basic AP Service Learning

Service Excellence &Relentless Execution

“ 2 “ 2 PotentiometersPotentiometers

” and Switch” and Switch

Switches Switches and Resistorand Resistor

Alarm Module Set Alarm Module Set point Adjustmentpoint Adjustment

Page 62: 09 Lesson 04

62

123

EP Basic AP Service Learning

Service Excellence &Relentless Execution

• EMCP Panel interior. This EMCP panel was actually cost effective too because the enclosures are very rugged and reliable. To program, the technician needed to remove a rear cover and use switches and a pot to change parameters. Notice the single phase AC meter module. The ECM and AC Meter module are installed in many switchgear applications. The Annunciator is on the left.

• “Pots” and switch are used to program the parameters of the ECM.

• Switches and Resistor are used to program the AC Module voltageand CT Ratios.

• Alarm Module Dc Volt “pot” can be used to adjust the DC Alarm level

124

EP Basic AP Service Learning

Service Excellence &Relentless Execution

EMCP II

This is a picture of the EMCP II GSC. It is the brain of the EMCP II system.

The GSC (Generator Set Control) combines the AC Meter, Annunciator and ECM into one module.

Also added was a Transformer box in the back of the panel for more accurate AC metering of all

three phases. Lights for E-Stop, coolant level and fault lights were added. The “EMCP II” adds even more

features than the EMCP I. If there was a need to program the EMCP I ECM, the technician had to

remove a cover, push buttons and select a rotary switch to the proper position and then do the programming.

All of these switches and pots are on the back of the panel and the display is in the front. The EMCP II GSC

is programmed using the pushbuttons on the front of the panel. The programming password is 13231.

Notice the engine display (on bottom) is a little shorter in length than the generator display (on top).

EMCP II was introduced in 1994.

Page 63: 09 Lesson 04

63

125

EP Basic AP Service Learning

Service Excellence &Relentless Execution

EMCP II+

EMCP II+. The “+” or “Plus” has large displays on the top and bottom of the GSC. In the “Plus” onecan read Kw, Kva, Power Factor, Kw hours, percent of load or percent Kw, etc. The AC metering can display separate phases or totals, average voltage, average frequency and total current. When the customer sees the “ total cur rent” of all three phases he may see the result of 500 Ampsper phase which will show 1500 AMPs. This usually surprises them until it is explained. This works very much like the EMCP II. The “plus” also has Protective Relay functions. There is not a typical relay but it can be programmed for alarm or shutdown parameters such as over current or over voltage to provide industrial grade relay protection. This slide actually shows two alarm modules.

126

EP Basic AP Service Learning

Service Excellence &Relentless Execution

GSCGSC

Alarm Alarm ModuleModule

Customer Customer Alarm Alarm

ModuleModule

ControlsControls

Page 64: 09 Lesson 04

64

127

EP Basic AP Service Learning

Service Excellence &Relentless Execution

EMCP 3EMCP 3

128

EP Basic AP Service Learning

Service Excellence &Relentless Execution

EMCP I & II Control Panel Attachments

Page 65: 09 Lesson 04

65

ALARM MODULESAmberAmber

RedRed

Alarm modules can be used to annunciate low fuel level, outside switch closures, air damper,

air flapper down, battery charger, not in auto, etc. The Annunciator gets information from the EMCP

or EMCP II via a serial data link from the main control panel or from external switches. Changing the

type of Annunciator or its function is a matter of sticking a new graphics film on the front and changing

the jumper wires located in on the rear terminals. There are at least six configurations for these modules.

Any one can be converted to the other usually by changing the jumpers configuration and the film on the

front. Each film has a part number listed on the lower right corner, that part number is for the film and not

the Annunciator. The Annunciator number is located on the rear of the module.

Horn and Alarm silence button are at the bottom as well as the test lamp.

GENERATOR SET

TROUBLE

GENERATOR SET

SUPPLYING LOAD

Remote Annunciators

Page 66: 09 Lesson 04

66

131

EP Basic AP Service Learning

Service Excellence &Relentless Execution

• This is a slightly different version with the same control used as a Remote Annunciator. Shown also an NFPA 110 remote Annunciator which just has a “generator trouble light” , a “generator supplying load light” , a horn, and a horn silence button. An EMCP system can use as many as three Annunciators or remote Annunciator combinations. One can be located on the control panel, and two may be 500 feet away. 1000 feet total of wire is the limitation of the data link because the long run of wires add capacitance which rounds off the edges of the digital serial link pulses. If the serial data link is corrupted or lost the Annunciatorwill flash its lights at a 1/2 hertz cycle.

Remote Annunciators

Customer Interface Module (looks like the relay driver module)

Page 67: 09 Lesson 04

67

133

EP Basic AP Service Learning

Service Excellence &Relentless Execution

This is the Customer Interface Module (CIM) and relay hardware. Instead of activating LEDs from the serial data link like the Annunciator, it receives the data link information to activates relays. Soinstead of turning LEDs on, it turns relays on. The relays can then be used to activate lamps in various locations. A lot of switchgear builders and customers like that because they want to have the lights instead of a single Annunciator with a set number and color of LEDs. One mis-application that happens is that some people wire the relays to trigger a shutdown for a certain fault. It's not intended to be a shutdown because if the generator is running and someonepushes the “ lamp test” button, all of the relays activate and any that can cause a shutdown will shutdown the engine. Also, if there is any problem with the datalink, then the ‘shutdown’ circuit will not work properly or possible in an unsafe manner.

Troubleshooting Tip:

Pin 18 goes in and out on relay board (which may have electrical noise) to terminal 4 on the dark brown terminal brick. If the CIM is shutting down, run the shielded 18 line to terminal 4 skipping the relay board altogether. If there is a a CIM, RDM and an Annunciator all in one system and one loses power, the un-powered unit will pull the data link down and this un-powered unit will be completely dead and the others will have all the lights on.

134

EP Basic AP Service Learning

Service Excellence &Relentless Execution

Customer Communications Module

Customer Communications ModuleCustomer Communications Module

Page 68: 09 Lesson 04

68

135

EP Basic AP Service Learning

Service Excellence &Relentless Execution

The Customer Communications Module (CCM) is simply a ‘ translator box’ . It takes the Cat Data Link output out of the EMCP II and translates it into an RS232 protocol that will communicate with a computer if that computer has the CCM desktop software installed.

In the paralleling class, a CCM is used to start an engine remotely with a modem over a phone line. It is convenient to use a CCM and Laptop PC when running an acceptance test on a generator set. There is a data logger mode so data can be loaded into the PC and put into a spreadsheet to show generator loading data for example. In “Primary Mode” a CCM can monitor four EMCP IIs and four ADEM II ECMs. In “Secondary Mode” one CCM can monitor up to eight EMCP IIs without any ADEM II ECMs. The ADEM II ECMsare sometimes monitored because they too have the Cat Data Link and have detailed engine sensor and operating information.

This does have an internal battery behind the display for internal memory. On the back, it has connections for the RS-232 serial cable for connection to a PC. The Cat Data link connection connects to the GSC Module in the EMCP.

136

EP Basic AP Service Learning

Service Excellence &Relentless Execution

EMCP II and EMCP 3 Control Panel

Attachment

Page 69: 09 Lesson 04

69

137

EP Basic AP Service Learning

Service Excellence &Relentless Execution

PL1000T and PL1000EProduct

138

EP Basic AP Service Learning

Service Excellence &Relentless Execution

PL1000T Package Features

� M5X / M50 Protocol Support (CCM Replacement)

� Cat Data Link Boost

� Embedded Communications Adapter

� CAN Extension Bridge

� J1939 Bridge

� Cat Data Link Tunnel

� Sea Water Temperature and Depth Interface (NMEA-183)

� Global Position System Module Interface (NMEA-183)

� Engine Vision Module Interface Protocol

Page 70: 09 Lesson 04

70

139

EP Basic AP Service Learning

Service Excellence &Relentless Execution

Embedded Communications Adapter

CDL Boost

EVIM GPSIMM5X M50

J1939 Bridge

J1939 Long Distance Extension

CDL Tunnel

PL1000T Cross-Functional Matrix

Modules Previously Required

PL1000T Required

3

3

3

2

4

4

4

1

1

1

2

1

1

1

140

EP Basic AP Service Learning

Service Excellence &Relentless Execution

PL1000E Package Features

� CDL to Modbus Parameter Translation

� J1939 to Modbus Parameter Translation

� Embedded Webserver

� Embedded Communications Adapter

� Cat Data Link Boost

� Caterpillar Communications Tool Kit Configuration

� CDL to Webserver Parameter Translation

� J1939 to Webserver Parameter Translation

Page 71: 09 Lesson 04

71

141

EP Basic AP Service Learning

Service Excellence &Relentless Execution

PL1000E Cross-Functional Matrix

J1939 to Web

CDL to Modbus

J1939 to Modbus

Embedded Web

Server

Embedded Communications

AdapterCDL Boost

CDL to Web

142

EP Basic AP Service Learning

Service Excellence &Relentless Execution

Today Menu:

3. SIS access to System Operation/Testing and Adjusting• EMCP I (SENR3535 via SIS)

• EMCP I I+ (RENR1200 via SIS)

• EMCP I I I (RENR7902 via SIS)4. TMI web

Page 72: 09 Lesson 04

72

143

EP Basic AP Service Learning

Service Excellence &Relentless Execution

TMI and Web Information

144

EP Basic AP Service Learning

Service Excellence &Relentless Execution

TMI on the Web

•• URL: URL: http://http://tmiwebtmiweb.cat.co.cat.comm

•• TMI Web pagesTMI Web pages–– Engine DataEngine Data

–– Generator DataGenerator Data

Page 73: 09 Lesson 04

73

145

EP Basic AP Service Learning

Service Excellence &Relentless Execution

146

EP Basic AP Service Learning

Service Excellence &Relentless Execution

Page 74: 09 Lesson 04

74

147

EP Basic AP Service Learning

Service Excellence &Relentless Execution

TMI on the Web

•• URL: URL: http://http://tmiwebtmiweb.cat.com.cat.com

•• TMI Web pagesTMI Web pages–– Engine DataEngine Data

148

EP Basic AP Service Learning

Service Excellence &Relentless Execution

Page 75: 09 Lesson 04

75

149

EP Basic AP Service Learning

Service Excellence &Relentless Execution

150

EP Basic AP Service Learning

Service Excellence &Relentless Execution

Entry Screen

Page 76: 09 Lesson 04

76

151

EP Basic AP Service Learning

Service Excellence &Relentless Execution

152

EP Basic AP Service Learning

Service Excellence &Relentless Execution

Page 77: 09 Lesson 04

77

153

EP Basic AP Service Learning

Service Excellence &Relentless Execution

Test Cell Results

154

EP Basic AP Service Learning

Service Excellence &Relentless Execution

As Shipped

Page 78: 09 Lesson 04

78

155

EP Basic AP Service Learning

Service Excellence &Relentless Execution

Flash File

156

EP Basic AP Service Learning

Service Excellence &Relentless Execution

Systems Data

Page 79: 09 Lesson 04

79

157

EP Basic AP Service Learning

Service Excellence &Relentless Execution

Physical Data

158

EP Basic AP Service Learning

Service Excellence &Relentless Execution

Water Pump Physical Data

Page 80: 09 Lesson 04

80

159

EP Basic AP Service Learning

Service Excellence &Relentless Execution

Gasket Kit Data

160

EP Basic AP Service Learning

Service Excellence &Relentless Execution

Re-man Parts Data

Page 81: 09 Lesson 04

81

161

EP Basic AP Service Learning

Service Excellence &Relentless Execution

Performance Data

162

EP Basic AP Service Learning

Service Excellence &Relentless Execution

Par Dyno

Page 82: 09 Lesson 04

82

163

EP Basic AP Service Learning

Service Excellence &Relentless Execution

Engine Test Spec.

164

EP Basic AP Service Learning

Service Excellence &Relentless Execution

Component Data

Page 83: 09 Lesson 04

83

165

EP Basic AP Service Learning

Service Excellence &Relentless Execution

Example Component Data

166

EP Basic AP Service Learning

Service Excellence &Relentless Execution

Example Component Data

Page 84: 09 Lesson 04

84

167

EP Basic AP Service Learning

Service Excellence &Relentless Execution

Certify Rerate

168

EP Basic AP Service Learning

Service Excellence &Relentless Execution

TMI on the Web

•• URL: URL: http://http://tmiwebtmiweb.cat.com.cat.com

•• TMI Web pagesTMI Web pages–– Engine DataEngine Data

–– Generator DataGenerator Data

Page 85: 09 Lesson 04

85

5N-5078

Page 86: 09 Lesson 04

86

Select

Page 87: 09 Lesson 04

87

Page 88: 09 Lesson 04

88

Page 89: 09 Lesson 04

89

Page 90: 09 Lesson 04

90

180

EP Basic AP Service Learning

Service Excellence &Relentless Execution

Questions ?

Page 91: 09 Lesson 04

91

181

EP Basic AP Service Learning

Service Excellence &Relentless Execution

Other Useful Electric Power Information available from the Web:

182

EP Basic AP Service Learning

Service Excellence &Relentless Execution

Electronic Media Center

Page 92: 09 Lesson 04

92

Electronic Media Center

Images are not well indexed & may not be described correctly.

Some of the Available Document Catagories

Page 93: 09 Lesson 04

93

185

EP Basic AP Service Learning

Service Excellence &Relentless Execution

Electric Power Quicksize software for Olympian Generator Sets:

https://epd.cat.com/infocast/frames/ep

186

EP Basic AP Service Learning

Service Excellence &Relentless Execution

Page 94: 09 Lesson 04

94

187

EP Basic AP Service Learning

Service Excellence &Relentless Execution

End of Slides End of Slides