Climate Control Unit for Telecom Power Presentation
PSBG II - TPBU
The Climate Control Unit (CCU) is designed for the environment control of small to medium outdoor cabinets. It features the control function of fans, heat exchangers, heaters, lightings and detection function of high temperature, low temperature, high water, high humidity, intrusion and smoke/fire. The redundant characteristic also provides the user a most flexible way to meet versatile applications.
Climate Control Unit(CCU ) Descriptions
Outdoor cabinet environment controlAutomatic peripheral devices detectionWide temperature operating range: -40°C ~ +70°CWide input power range: 18 ~ 59VdcCompliant with AC or DC type cooling device, heater and
lighting3 Individual temperature settings for Heater, Cooling 1, 2PWM fan speed control function for Cooling 1, 2User definable alarm functionUser friendly operation interfaces7-segment LED display and LED indicator°C / °F convertible displayHigh / low temperature, high water, high humidity, intrusion
(door open) and smoke/fire alarm functionDIN-rail MountingSafety: cUL, CE
Outdoor System Solutions (Climate Controller)
PDU (Several Configurations)
Rectifier ESR-48/56A
Battery & Base
New Smart CSU (Main Board))
New Smart CSU (Relay Board))
19” Rectifier Shelf (SB-05N/HG A )
160W Heat-exchange
CCU (Climate Control Unit )
RBS2216 Outdoor System Drawing
Add AC Socket
RBS2216 AC Panel Configurations
Changeover Switch
Phase 1 (with Genset Socket & Changeover Switch):
Implementation: from first batch
Genset Socket
Phase 2 (without Genset Socket & Changeover Switch):
Implementation: TBD (Inventory Concern)
AP36
DC LightSmoke Sensor
Humidity Sensor
RBS2216 Lights & Sensors
CCU setting Process
-40 ~ +80 degree CStorage Temperature
EN55022 Class BEMCCULSafety
Remark
-40 ~ +75 degree C0.3 ~ 0.8 Adc
54Vdc at 48V; 27Vdc at 24V19.5dc ~ 60Vdc
Specification/Function
Input Normal Input Input Range
Operational TemperatureInput Current
Item
Electrical specification – Input
Climate Control Unit - CCU (Input specification)
Alarm IndicationItem Alarm Description Type LED 7-Segment
LED1 CCU Fail Alarm Climate Control Unit
shunt down2 Fan 1 Fail Alarm The fan or heat
exchanger that Fan 1port controlled isfailed.
Drycontact
Alarm(red)
3 Fan 2 Fail Alarm The fan or heatexchanger that Fan 2port controlled isfailed.
Drycontact
Alarm(red)
4 Heater Fail Alarm The heater thatHeater port controlledis failed.
Drycontact
Alarm(red)
5 Air Conditioner Fail Alarm The air conditionerthat A/C portcontrolled is failed.
Drycontact
Alarm(red)
6 Intrusion Alarm The door is opened. Drycontact
Alarm(red)
7 High Temperature Alarm The internaltemperature is overthe high limit setting.
Drycontact
Alarm(red)
8 Low Temperature Alarm The internaltemperature is underthe low limit setting.
Drycontact
Alarm(red)
9 High Water Alarm Water level in thecabinet is over thesensor limit.
Drycontact
Alarm(red)
10 Smoke / Fire Alarm Smoke or fire isdetected in thecabinet.
Drycontact
Alarm(red)
11 High Humidity Alarm The humidity in thecabinet is over thesensor limit.
Drycontact
Alarm(red)
Shelter Wall
Inside Shelter Outside Shelter
Fan Tray:• Fan x 2• Control Board• Aluminum Alloy Panel Wall Cutout (464 x 210mm)
CCU with TB Option
Outdoor System Solutions (Alternative-Fan Tray)
28-59 VdcOperating Voltage9
10
8
7
6
5
4
3
2
1
No.
480(W) x 240(H) x 80(D) mmDimensions
YesSpeed Control
58 x 2 = 116WPower Consumption
IP5X for standard fan, water protection code “X”depends on fan’s orientation. The fan can be optional
for IP55 in all orientations.
Ingress Protection
80K Hours@40°C per FanLife Expectancy (MTBF)
446.5 x 2 = 893 CFMAirflow @zero static air pressure
-10 ~ 70°COperating Temperature
Approx. 62 +10Log2 = 65dBANoise
Delta PFB2048LT (200x70mm) x 2pcsFan
SpecificationItem
Outdoor System Solutions (Alternative-Fan Tray)