04 3 climate control unit

14
Climate Control Unit for Telecom Power Presentation PSBG II - TPBU

Upload: dinh-cong-thien-taydo-university

Post on 15-May-2015

134 views

Category:

Business


1 download

TRANSCRIPT

Page 1: 04 3 climate control unit

Climate Control Unit for Telecom Power Presentation

PSBG II - TPBU

Page 2: 04 3 climate control unit

The Climate Control Unit (CCU) is designed for the environment control of small to medium outdoor cabinets. It features the control function of fans, heat exchangers, heaters, lightings and detection function of high temperature, low temperature, high water, high humidity, intrusion and smoke/fire. The redundant characteristic also provides the user a most flexible way to meet versatile applications.

Climate Control Unit(CCU ) Descriptions

Page 3: 04 3 climate control unit

Outdoor cabinet environment controlAutomatic peripheral devices detectionWide temperature operating range: -40°C ~ +70°CWide input power range: 18 ~ 59VdcCompliant with AC or DC type cooling device, heater and

lighting3 Individual temperature settings for Heater, Cooling 1, 2PWM fan speed control function for Cooling 1, 2User definable alarm functionUser friendly operation interfaces7-segment LED display and LED indicator°C / °F convertible displayHigh / low temperature, high water, high humidity, intrusion

(door open) and smoke/fire alarm functionDIN-rail MountingSafety: cUL, CE

Outdoor System Solutions (Climate Controller)

Page 4: 04 3 climate control unit

PDU (Several Configurations)

Rectifier ESR-48/56A

Battery & Base

New Smart CSU (Main Board))

New Smart CSU (Relay Board))

19” Rectifier Shelf (SB-05N/HG A )

160W Heat-exchange

CCU (Climate Control Unit )

Page 5: 04 3 climate control unit

RBS2216 Outdoor System Drawing

Page 6: 04 3 climate control unit

Add AC Socket

RBS2216 AC Panel Configurations

Changeover Switch

Phase 1 (with Genset Socket & Changeover Switch):

Implementation: from first batch

Genset Socket

Phase 2 (without Genset Socket & Changeover Switch):

Implementation: TBD (Inventory Concern)

AP36

Page 7: 04 3 climate control unit

DC LightSmoke Sensor

Humidity Sensor

RBS2216 Lights & Sensors

Page 8: 04 3 climate control unit

CCU setting Process

Page 9: 04 3 climate control unit

-40 ~ +80 degree CStorage Temperature

EN55022 Class BEMCCULSafety

Remark

-40 ~ +75 degree C0.3 ~ 0.8 Adc

54Vdc at 48V; 27Vdc at 24V19.5dc ~ 60Vdc

Specification/Function

Input Normal Input Input Range

Operational TemperatureInput Current

Item

Electrical specification – Input

Climate Control Unit - CCU (Input specification)

Page 10: 04 3 climate control unit

Alarm IndicationItem Alarm Description Type LED 7-Segment

LED1 CCU Fail Alarm Climate Control Unit

shunt down2 Fan 1 Fail Alarm The fan or heat

exchanger that Fan 1port controlled isfailed.

Drycontact

Alarm(red)

3 Fan 2 Fail Alarm The fan or heatexchanger that Fan 2port controlled isfailed.

Drycontact

Alarm(red)

4 Heater Fail Alarm The heater thatHeater port controlledis failed.

Drycontact

Alarm(red)

5 Air Conditioner Fail Alarm The air conditionerthat A/C portcontrolled is failed.

Drycontact

Alarm(red)

6 Intrusion Alarm The door is opened. Drycontact

Alarm(red)

7 High Temperature Alarm The internaltemperature is overthe high limit setting.

Drycontact

Alarm(red)

8 Low Temperature Alarm The internaltemperature is underthe low limit setting.

Drycontact

Alarm(red)

9 High Water Alarm Water level in thecabinet is over thesensor limit.

Drycontact

Alarm(red)

10 Smoke / Fire Alarm Smoke or fire isdetected in thecabinet.

Drycontact

Alarm(red)

11 High Humidity Alarm The humidity in thecabinet is over thesensor limit.

Drycontact

Alarm(red)

Page 11: 04 3 climate control unit

Shelter Wall

Inside Shelter Outside Shelter

Fan Tray:• Fan x 2• Control Board• Aluminum Alloy Panel Wall Cutout (464 x 210mm)

CCU with TB Option

Outdoor System Solutions (Alternative-Fan Tray)

Page 12: 04 3 climate control unit

28-59 VdcOperating Voltage9

10

8

7

6

5

4

3

2

1

No.

480(W) x 240(H) x 80(D) mmDimensions

YesSpeed Control

58 x 2 = 116WPower Consumption

IP5X for standard fan, water protection code “X”depends on fan’s orientation. The fan can be optional

for IP55 in all orientations.

Ingress Protection

80K Hours@40°C per FanLife Expectancy (MTBF)

446.5 x 2 = 893 CFMAirflow @zero static air pressure

-10 ~ 70°COperating Temperature

Approx. 62 +10Log2 = 65dBANoise

Delta PFB2048LT (200x70mm) x 2pcsFan

SpecificationItem

Outdoor System Solutions (Alternative-Fan Tray)

Page 13: 04 3 climate control unit

Q & A

Page 14: 04 3 climate control unit