Profibus Process Event, ABB, May 2008

Component SelectionWhat components there are available

What components to use & where

Into the real world

Some rules

Hazardous area

Minimum configuration

Profibus Process Event, ABB, May 2008

PSU CPU

Mas

ter1

Mas

ter2

Mas

ter3

Remote I/O etc.

Profibus DP

Basic configuration always uses Profibus DP

Profibus Process Event, ABB, May 2008

The Master controls all cyclic communicationsThe Master is configured using a software tool for your PLC/DCSUse a .gsd file as the common interface between all devices and the masterYou can have more than one master on a network

A slave is locked to a cyclic master

Profibus Process Event, ABB, May 2008

Slave1

Slave4

Slave3

Slave2

Master

Cyclic Data Transfer

Cyclic operation:

M S1, S1 MM S2, S2 MM S3, S3 MM S4, S4 MM S1, S1 MM S2, S2 M

etc.

Single master system

© Manchester Metropolitan University

Profibus Process Event, ABB, May 2008

Slave1

Master

Slave4

Slave3

Slave2

Slave5

1Master

2

Cyclic Data Transfer

Token

Cyclic operation:M1 S1, S1 M1M1 S2, S2 M1M1 S4, S4 M1M1 token M2

M2 S3, S3 M2M2 S5, S5 M2M2 token M1M1 S1, S1 M1M1 S2, S2 M1

etc.

Token

Dual master system

Token

Token

Token

© Manchester Metropolitan University

Profibus Process Event, ABB, May 2008

For Process Automation devices youneed a converter between DP & PADP uses RS485

Different converters exist. Simple couplers or link modulesEach has its areas of use, benefits and disadvantages

PA uses Manchester Bus Power

Profibus Process Event, ABB, May 2008

Conversion between RS485 and Manchester Bus Powered communications

© Manchester Metropolitan University

0

-9mA

time

Current/mA

+9mA

1 1 0 0

Profibus PA Manchester Bus Powered multi-drop

4To7

volts

Profibus DPRS485 multi-drop

Coupler

or lin

k mod

ule

Profibus Process Event, ABB, May 2008

PSU CPU

Mas

ter1

Mas

ter2

Mas

ter3

Remote I/O etc.

PROFIBUS-PA

Link module allows non-unique addressing, uses one address on the bus for all PA devices and allows full baud rate

Coupler uses unique addressing, no address on the bus but fixed baud rate

SK3 coupler uses unique addressing, no address on the bus but full baud rate is available

Powered termination.

Profibus Process Event, ABB, May 2008

Simple coupler (P&F / Siemens)

15 ms15 ms

15 ms

PROFIBUS-DP

PROFIBUS-PA

For 31 devices approximately half a second cycle time

Master class 1Master class 2

© Endress & Hauser

Unique addressing only

Profibus Process Event, ABB, May 2008

• Two variants of the DP/PA Coupler: Ex and Non-Ex

• Converts the signals from DP (RS 485) to PA (IEC 61158-2)

• Transparent to master and slave

• No configuration necessary

• Fixed baud rate of 45.45 or 93.75 kBit/s on DP network

• Contains termination (one end) for the Profibus PA bus

• Powers the PA field devices

Profibus Process Event, ABB, May 2008

15 ms15 ms

15 ms

PROFIBUS-PA

Link

1 ms

PROFIBUS-DP up to 12 Mbit/s

T SEG ~ 500 msec

Link module (Siemens)

© Endress & Hauser

Non-unique addressing

Master class 1

12 13 etc

12 13 14

Profibus Process Event, ABB, May 2008

• The LINK contains at least one IM157 module and one DP/PA coupler

the Link acts as a DP-Slave to the DP-Masterthe Link acts as a master to the PA-Slavesmax. I/O range for all PA devices:

244 Byte Input + 244 Byte Output

• Address range on PROFIBUS-DP between 0-125

• Address range for slaves on PROFIBUS-PA from 3-125

• Up to 5 DP/PA couplers can be connected to one IM157 module•Remember the 244 byte limit

• 9.6 kBit/s to 12 Mbit/s (standard bus parameters)

• GSD generator required when used outside a Siemens environment

Profibus Process Event, ABB, May 2008© Endress & Hauser

Link moduleIM 157 1..5 DP/PA Coupler(s)

Profibus Process Event, ABB, May 2008

Where now?Profibus PA can go 1900 metres inthe field with up to 31 slaves

Current limiting devices can be employed to protect segmentsThis enables a highly flexible systemto be created

Junction boxes are often used to distribute PA around the plant

Profibus Process Event, ABB, May 2008

PSU CPU

Mas

ter1

Mas

ter2

Mas

ter3

Remote I/O

Limits apply on spur lengths Spurs can be protected

Profibus Process Event, ABB, May 2008

Possible faults in a PROFIBUS PA segment

failure effect estim. of harm

1 breakdown of PA Coupler breakdown of up to 31 devices

2 short-circuit / wire break on backbone breakdown of up to 31 devices

3 short-circuit / wire break on spur breakdown of typ. 1-4 devices

4 missing bus termination disturbance of communication

max. 31 devices per coupler

IM 157 redundant

DP/PA coupler, non redundant

23 backbone

spur

...

bus termination

PROFIBUS DPPROFIBUS PA

1

spur

4

© Endress & Hauser

Profibus Process Event, ABB, May 2008

Redundant systems

Offers a safe and reliable system for critical plant

Using special devices the PA segmentcan be maintained even under faultconditions

Profibus Process Event, ABB, May 2008

Fault tolerant PROFIBUS PA - Overview

PRO

FIB

US

DP

IM 157, redundant

DP/PA coupler, redundant

AFS

M

PROFIBUS PA

PRO

FIB

US

DP

AFD

M

PROFIBUS PA

DP/PA coupler, redundant

IM 157, redundant

© Siemens Ltd

Profibus Process Event, ABB, May 2008

Hazardous areaVery simple to do – you can self-certify

Hazardous area components available

Allows a flexible approach as in a safe area

FISCO, FINCO, ENTITY all supported

Profibus Process Event, ABB, May 2008

Hazardous area•Max 1000 metres (EEx ia)•Max 10 devices (current limited)•Max 60 metre spur lengths•Max 100 mA link module supply•Vo < Vi•Io < Ii FISCO parameters•Po < Pi (Fieldbus Intrinsically safe COncept

Limitation of device capacitance and inductance: Ci < 5 nF, Li < 10 µH

•One source of power (i.e. device is a passive current sink)•Must use FISCO approved devices.

FISCO - Rules Overview

Profibus Process Event, ABB, May 2008

PSU CPU

Mas

ter1

Mas

ter2

Mas

ter3

Remote I/O

EEXia

Using FISCO rules you need a special coupler or link module

Maximum of 8 to 10 devices

Maximum of 1000 metres using type A cable

Safe area

Hazardous area

Profibus Process Event, ABB, May 2008

FieldBarrier from Pepperl+Fuchs

Cover forEx e Terminals

4 Spurs withCable Glands

Ex i Terminals

LEDsSwitchable FieldbusTermination Resistor

Trunk In withCable Glands

Trunk Out withCable Glands

GroundingPoint

© Pepperl & Fuchs Ltd

Profibus Process Event, ABB, May 2008

PSU CPU

Mas

ter1

Mas

ter2

Mas

ter3

Remote I/O

EEXe

Field Barrier

Limit on the numberof devices on a segment is 110mA

Using a field barrier meansyou do not need a hazardous area coupler so can have the full 400mA available Safe area

Hazardous area

EEX ia

Profibus Process Event, ABB, May 2008

I.SNon-I.SNumber of spurs

60m120m1-1260m90m13-1460m60m15-1860m30m19-241m1m24-32

DP (Decentralised Peripheral)

Networks

PA (PROCESS Automation)Networks

PA segment length is 1900 metres including

spurs

DP is distance limitedPA tends to be current limited

Profibus Process Event, ABB, May 2008

Turck

Other field devices

Profibus Process Event, ABB, May 2008

• 9-pin DIN is standard way to connect Profibus DP devices together.

• Outdoor equipment generally cable-glanded and hard-wired.

• Wide choice of Cable to suit each application.

• PA has 4 pin M12 plugs and sockets

Connectors

Profibus Process Event, ABB, May 2008

Bus with spurs - components

Profibus Process Event, ABB, May 2008

Weidmüller PROFIBUS PA

© Endress & Hauser

Profibus Process Event, ABB, May 2008

Weidmüller PROFIBUS PA

Non EX

Siemens PROFIBUS PA

Profibus Process Event, ABB, May 2008

Selection of over-voltage protection

Dehn+Söhne

© Endress & Hauser

Profibus Process Event, ABB, May 2008

Power Hub Advanced Diagnostic Module

• Power Hub based Diagnostic Module• Upgrade option for existing

installations• Monitors Power Hub related functions

and Physical Layer health• Supports 4 Fieldbus Segments• Summary Alarm Relay Output• Status LED´s for

– Bulk power health– Segment health– Communication activity

Bulk power health

- Segment health- Communication activity

© Endress & Hauser

Profibus Process Event, ABB, May 2008

ProfiHub: Freedom for DP-Network Topology• 5 Galvanic isolated channels

(segments).• Suitable for RS 485 based networks

(PROFIBUS DP, DP-V1, DP-V2 and MPI).

• Transmission speeds: 9,6 Kbit/s …12 Mbit/s.

• Each channel complies to the DP -RS 485 specification.

• Integrated termination facility for each channel and trunk line.

• IP 65 classification.• Each channel can serve 1 up to 31

devices.• No limit in serial placement or

cascading of ProfiHubs.ProfiHub B5

ProfiHub A5

Profibus Process Event, ABB, May 2008

ProfiHub: Freedom for DP-Network Topology

• Large networks with star and tree topology• No limit in the cascading of ProfiHubs

RS485

Profibus Process Event, ABB, May 2008

Fuse

:x2.

1b-1

23/1

24Fu

se:x

2.1b

-123

/124

Fibre Optic topologies

Segment 1

Fuse

:x2.

1b-1

23/1

24

T

FIBRE-OPTIC

REPEATER

DP

FO

A

Fuse

:x2.

1b-1

23/1

24

T

FIBRE-OPTIC

REPEATER

DP

FO

A

Fuse

:x2.

1b-1

23/1

24

T

FIBRE-OPTIC

REPEATER

DP

FO

A

Segment 2 Segment 3

Profibus Process Event, ABB, May 2008

Fibre Optic topologies

Fuse

:x2.

1b-1

23/1

24Fu

se:x

2.1b

-123

/124

Fuse

:x2.

1b-1

23/1

24Fu

se:x

2.1b

-123

/124

Profibus Process Event, ABB, May 2008