© 2012 eaton corporation. all rights reserved. nzm interface module for smartwire-dt monitoring and...

13
© 2012 Eaton Corporation. All rights reserved. NZM Interface Module for SmartWire-DT Monitoring and Control of Circuit Breakers by using the NZM-XSWD-704 module

Upload: bathsheba-mason

Post on 23-Dec-2015

219 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: © 2012 Eaton Corporation. All rights reserved. NZM Interface Module for SmartWire-DT Monitoring and Control of Circuit Breakers by using the NZM-XSWD-704

© 2012 Eaton Corporation. All rights reserved.

NZM Interface Module for SmartWire-DT

Monitoring and Control of Circuit Breakers by using the NZM-XSWD-704 module

Page 2: © 2012 Eaton Corporation. All rights reserved. NZM Interface Module for SmartWire-DT Monitoring and Control of Circuit Breakers by using the NZM-XSWD-704

2 2© 2012 Eaton Corporation. All rights reserved.

The Speaker

Rainer Menden Dipl.-Ing.

Product Manager and Support

Communication Circuit Breakers

Page 3: © 2012 Eaton Corporation. All rights reserved. NZM Interface Module for SmartWire-DT Monitoring and Control of Circuit Breakers by using the NZM-XSWD-704

3 3© 2012 Eaton Corporation. All rights reserved.

NZM circuit breakers - Communication

Modbus RTU

PROFIBUS-DP

DeviceNet CAN

XDMI-612

XPC-Soft

XSWD-704

RMQPKE

Field bus Interface SWD-Communication Energy Metering

XMC-MB

XMC-S0

NZM 2/3/4

Page 4: © 2012 Eaton Corporation. All rights reserved. NZM Interface Module for SmartWire-DT Monitoring and Control of Circuit Breakers by using the NZM-XSWD-704

4 4© 2012 Eaton Corporation. All rights reserved.

NZM as a SWD component in a switchboard

Contactor /

Motor protection

circuit

I/O Modul

RMQ

Front

RMQ Base

Round cable

-Ethernet IP-ModbusTCP

- PROFINET

Gateways- PROFIBUS,CAN

Talking to:

HMI

Page 5: © 2012 Eaton Corporation. All rights reserved. NZM Interface Module for SmartWire-DT Monitoring and Control of Circuit Breakers by using the NZM-XSWD-704

5 5© 2012 Eaton Corporation. All rights reserved.

Areas of Application

Function Benefits•Detection of load peaks -> Optimization of power consumption•Remote control -> Fast reaction time•Fault diagnosis -> Prevention of faults•Power metering -> Cost optimization•Connection to SCADA systems -> Optimized system control

Energy distribution in buildings and industry

OEM Customers who use SWD

Page 6: © 2012 Eaton Corporation. All rights reserved. NZM Interface Module for SmartWire-DT Monitoring and Control of Circuit Breakers by using the NZM-XSWD-704

6 6© 2012 Eaton Corporation. All rights reserved.

Areas of Application Motor Protection –NZM and PKZ as Partners on SmartWire

12A 32A 65A >65A

Total range of motor protection controlled by one network

OEM Customers who use SWD

Page 7: © 2012 Eaton Corporation. All rights reserved. NZM Interface Module for SmartWire-DT Monitoring and Control of Circuit Breakers by using the NZM-XSWD-704

7 7© 2012 Eaton Corporation. All rights reserved.

Function Overview

Load Warnings

Cause of Trip

Remote Control

Currents

Energy counter Value

NZM 2/3/4 SWD Field bus Control level

Circuit Breaker SCADA level

Status

Settings

NZM Coding

ON/OFF

Reset

Page 8: © 2012 Eaton Corporation. All rights reserved. NZM Interface Module for SmartWire-DT Monitoring and Control of Circuit Breakers by using the NZM-XSWD-704

8 8© 2012 Eaton Corporation. All rights reserved.

SmartWire-DT

I/O Interfaces of 704

Motor Operator

Connection cable to NZM is part of NZM-XSWD-704

Energy impulses

XMC-S0

Status of breaker

Opened/closed/tripped

Energy measuring devicewith pulse output S0

Optional

connections

Page 9: © 2012 Eaton Corporation. All rights reserved. NZM Interface Module for SmartWire-DT Monitoring and Control of Circuit Breakers by using the NZM-XSWD-704

9 9© 2012 Eaton Corporation. All rights reserved.

Data Organization

High flexibility through 4 selectable data profiles Additional acyclic access

Profile 13 byte

211 byte

315 byte

431 byte

SWD StatusNZM Status

X X X X

Currents X X X

Energy values X X

NZM set values(rotary switch)

X

NZM breaker data(type,fuction,version)

X

Z cyclic A acyclic

Index

1

2

Page 10: © 2012 Eaton Corporation. All rights reserved. NZM Interface Module for SmartWire-DT Monitoring and Control of Circuit Breakers by using the NZM-XSWD-704

10 10© 2012 Eaton Corporation. All rights reserved.

Number of NZM stations

Data profile 1 2 3 4

Number ofXSWD-704

58 22 15 7

PROFIBUS-DP: Max.58 stations, 242 Byte/String

Data profile

Number ofXSWD-704

1

42

2 3 4

11 8 4

CANOpen: Max.99 stations, 128 Byte/String

Page 11: © 2012 Eaton Corporation. All rights reserved. NZM Interface Module for SmartWire-DT Monitoring and Control of Circuit Breakers by using the NZM-XSWD-704

11 11© 2012 Eaton Corporation. All rights reserved.

SWD Assist: Online Diagnosis via PC

Online access via diagnostic interface of gateway

Read out of current configuration

Display of process values

Display of diagnosis messages

Testing of SWD configuration without PLC

SWD Gateway

Page 12: © 2012 Eaton Corporation. All rights reserved. NZM Interface Module for SmartWire-DT Monitoring and Control of Circuit Breakers by using the NZM-XSWD-704

12 12© 2012 Eaton Corporation. All rights reserved.

Available Sales Tools

Flyer:How to Communicate with your Circuit Breaker SAP:168546 GB

FTP Server:ftp://ftp.moeller.net/CIRCUIT_BREAKER/KOMMUNIKATION/NZM_XSWD_704

Support:Rainer Menden Phone:-492286022334 E-Mail:[email protected]

Daniel Jansen Phone: -492286022260 E-Mail:[email protected]