yst steam turbine drive centrifugal liquid chillers

30
WIRING DIAGRAMS CONTRACTOR _________________________ PURCHASER _____________________________________________ ORDER NO. ____________________________ JOB NAME ________________________________________________ JCI CONTRACT NO. _____________________ LOCATION ________________________________________________ JCI ORDER NO. _________________________ ENGINEER _______________________________________________ REFERENCE DATE ________ APPROVAL DATE ________ CONSTRUCTION DATE _______ New Release Form: 160.67-PW7 (219) MODEL YST STEAM TURBINE DRIVE CENTRIFUGAL CHILLER WITH OPTIVIEW™ CONTROL CENTER Issue Date: February 28, 2019 JOB DATA: YST CHILLER MODEL NO. ________________________________________________________ NO. OF UNITS _____________ STEAM TURBINE MODEL_________________________________________________________ OIL PUMP MOTOR _____________ VOLTS, 3-PHASE, _____________ Hz, _____________FLA REMARKS: –––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––– –––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––– –––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––– –––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––– –––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––– –––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––– –––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––– –––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––– –––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––– –––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––– –––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––– –––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––– –––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––– ––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––

Upload: others

Post on 08-Nov-2021

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: YST Steam Turbine Drive Centrifugal Liquid Chillers

WIRING DIAGRAMS

CONTRACTOR _________________________ PURCHASER _____________________________________________ ORDER NO. ____________________________ JOB NAME ________________________________________________ JCI CONTRACT NO. _____________________ LOCATION ________________________________________________ JCI ORDER NO. _________________________ ENGINEER _______________________________________________

REFERENCE DATE ________ APPROVAL DATE ________ CONSTRUCTION DATE _______

New Release Form: 160.67-PW7 (219)

MODEL YST STEAM TURBINE DRIVE CENTRIFUGAL CHILLER WITH

OPTIVIEW™ CONTROL CENTER

Issue Date: February 28, 2019

JOB DATA:

YST CHILLER MODEL NO. ________________________________________________________

NO. OF UNITS _____________

STEAM TURBINE MODEL_________________________________________________________

OIL PUMP MOTOR _____________ VOLTS, 3-PHASE, _____________ Hz, _____________FLA

REMARKS:

––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––

Page 2: YST Steam Turbine Drive Centrifugal Liquid Chillers

JOHNSON CONTROLS2

FORM 160.67-PW7 ISSUE DATE: 2/28/2019

This equipment is a relatively complicated apparatus. During installation, operation maintenance or service, individuals may be exposed to certain components or conditions including, but not limited to: refrigerants, materials under pressure, rotating components, and both high and low voltage. Each of these items has the potential, if misused or handled improperly, to cause bodily injury or death. It is the obligation and respon-sibility of operating/service personnel to identify and recognize these inherent hazards, protect themselves, and proceed safely in completing their tasks. Failure to comply with any of these requirements could result in serious damage to the equipment and the property in

IMPORTANT!READ BEFORE PROCEEDING!

GENERAL SAFETY GUIDELINES

which it is situated, as well as severe personal injury or death to themselves and people at the site.

This document is intended for use by owner-authorized rigging, installation, and operating/service personnel. It is expected that these individuals possess independent training that will enable them to perform their assigned tasks properly and safely. It is essential that, prior to performing any task on this equipment, this individual shall have read and understood the on-product labels, this document and any referenced materials. This in-dividual shall also be familiar with and comply with all applicable industry and governmental standards and regulations pertaining to the task in question.

SAFETY SYMBOLSThe following symbols are used in this document to alert the reader to specific situations:

Indicates a possible hazardous situation which will result in death or serious injury if proper care is not taken.

Indicates a potentially hazardous situa-tion which will result in possible injuries or damage to equipment if proper care is not taken.

Identifies a hazard which could lead to damage to the machine, damage to other equipment and/or environmental pollu-tion if proper care is not taken or instruc-tions and are not followed.

Highlights additional information useful to the technician in completing the work being performed properly.

External wiring, unless specified as an optional connection in the manufacturer’s product line, is not to be connected inside the control cabinet. Devices such as relays, switches, transducers and controls and any external wiring must not be installed inside the micro panel. All wiring must be in accor-dance with Johnson Controls’ published specifications and must be performed only by a qualified electrician. Johnson Controls will NOT be responsible for damage/problems resulting from improper connections to the controls or application of improper control signals. Failure to follow this warn-ing will void the manufacturer’s warranty and cause serious damage to property or personal injury.

Page 3: YST Steam Turbine Drive Centrifugal Liquid Chillers

JOHNSON CONTROLS 3

FORM 160.67-PW7 ISSUE DATE: 2/28/2019

CHANGEABILITY OF THIS DOCUMENT

In complying with Johnson Controls’ policy for con-tinuous product improvement, the information con-tained in this document is subject to change without notice. Johnson Controls makes no commitment to update or provide current information automatically to the manual or product owner. Updated manuals, if applicable, can be obtained by contacting the nearest Johnson Controls Service office or accessing the John-son Controls QuickLIT website at http://cgproducts.johnsoncontrols.com.

It is the responsibility of rigging, lifting, and operating/ service personnel to verify the applicability of these documents to the equipment. If there is any question

regarding the applicability of these documents, rig-ging, lifting, and operating/service personnel should verify whether the equipment has been modified and if current literature is available from the owner of the equipment prior to performing any work on the chiller.

CHANGE BARSRevisions made to this document are indicated with a line along the left or right hand column in the area the revision was made. These revisions are to technical information and any other changes in spelling, gram-mar or formatting are not included.

MANUAL DESCRIPTION FORM NUMBER

Operation Manual - Model YST Steam Turbine Drive Centrifugal Liquid Chiller with OptiView™ Control Center Design Level F and G 160.67-O1

Wiring Diagram - Field Control Modifications MaxE™ Model YST Chillers (Style F) 160.67-PW2

Wiring Diagram - Model YST Steam Turbine Drive Centrifugal Liquid Chillers Floor Mounted Steam Condenser Design Level F and G 160.67-PW4

Wiring Diagram - Model YST Steam Turbine Drive Centrifugal Liquid Chillers Top Mount Steam Con-denser Design Level F and G 160.67-PW5

ASSOCIATED LITERATURE

Page 4: YST Steam Turbine Drive Centrifugal Liquid Chillers

JOHNSON CONTROLS4

FORM 160.67-PW7 ISSUE DATE: 2/28/2019

THIS PAGE INTENTIONALLY LEFT BLANK.

Page 5: YST Steam Turbine Drive Centrifugal Liquid Chillers

JOHNSON CONTROLS 5

FORM 160.67-PW7 ISSUE DATE: 2/28/2019

LEGEND

LABEL DESCRIPTIONCS Start/Stop Control SwitchDS Disconnect Switch

FCV Solenoid Or Electrically Actuated Ball Valve

FLA Full Load AmpsFU Fuse

HGBP Hot Gas Bypass Valve (TCV-100A)

HTR 3-Phase Thermostatically Controlled 3000 Watt Oil Heater at Line Voltage

HW HotwellK7, K8, K13,K14, K17, K18

Relays Mounted on YORK I/O Board

LCV Level Control Valve Actuator (LCV-113)LE Level Transducer (0-5 VDC Output)

LSH High Level SwitchLT Level Transmitter (4-20 MA DC Output)M Contactor/Motor Starter

MOV Metal Oxide VaristorMP Manual Motor Protector

MP_A Manual Motor Protector Auxiliary Contact (see note 19)

MP_S Manual Motor Protector Signaling Contact (see note 25)

MPU Magnetic Pickup

PE Pressure Tranducer (0.5-4.5 VDC Output)

PGD Proximity Gap Distance (ZE-142)

PT Pressure Transmitter (4-20 MA DC Out-put)

PRV Pre-Rotation Vanes (TCV-100)

PSHH-112A Compr. Disch. High Press. Cutout, Hard-wired

PWM Pulse Width ModulatedR Control Relay

RES ResistorSC Speed ControlSS Speed SwitchST Speed Transmitter (4-20 MA DC Output)T Transformer

TB1, TB3, TB5, TB7

Terminal Block Factory Wiring -

TB2, TB4 Terminal BlockField Connection -

TB6 Terminal Block - Field (bottom) Factory (top)

LABEL DESCRIPTION

TB7 Terminal Block - Field (left) Factory (right)

TB8 Terminal Block in Power Panel, Factory -

TB9 Terminal Block in Steam Condenser Junction Box -

TE Resistance Temperature Sensing Element

VE Vibration Proximity ProbeVGD Variable Geometry DiffuserVMS Vane Motor Closed Limit SwitchVT Vibration TransmitterZS Limit Switch

Field WiringFactory WiringCircuit Board or Enclosure BoundaryJack (J1, J2, .....)Plug (P1, P2, ....)Wire entrance Hole in Control PanelOption (when supplied by YORK)Mechanical LinkageShielded CableMetal Oxide Varistor

SUPR Transient SuppressorGround

035-26593-000SHT. 2 OF 11REV. H

Page 6: YST Steam Turbine Drive Centrifugal Liquid Chillers

JOHNSON CONTROLS6

FORM 160.67-PW7 ISSUE DATE: 2/28/2019

NOTES1. This wiring diagram describes the standard elec-

tronic control scheme for use with a steam turbine drive. For details of field control modifications, refer to Product Form 160.67-PW2.

2. Field wiring to be in accordance with the National Electrical Code as well as all applicable codes and specifications. Refer to Form 160.67-PW5 (Top Mount Steam Condenser) and Form 160.67-PW4 (Floor Mount Steam Condenser) for field wiring connections.

3. Numbers along the left side of the diagram are line identification numbers. The number along the right side indicates the line number location of relay contacts. An underlined contact location signifies a normally closed contact.

4. Main Control Panel Class 1 field wiring terminal connection points are indicated by numbers with-in a rectangle i.e. 15 . Main Control Panel factory wiring terminal connection points are indicated by numbers within a triangle i.e. 5 . Component Terminal connection points are indicated by num-bers within a circle i.e. CI . Numbers adjacent to circuit lines are the circuit identification numbers. Power Panel wiring terminal connection points are indicated by numbers within a hexagon i.e . L1 . Steam Condenser junction box wiring termi-nal connection points are indicated by numbers within a diamond i.e. 80 .

5. To cycle unit ON and OFF automatically and pro-vide a controlled shutdown. Install a cycling de-vice between terminals 1 & 13 . (Line 33A) (see Note 9). If a cycling device is installed, jumper must be removed between terminals 1 & 13 .

6. Fuse sizes and motor overload setpoints depend on voltage of single point power supply. See chart on field connection diagram on door of panel.

7. To stop unit and not permit it to start again, after a controlled shutdown install a stop device between terminals 1 & 8 (Line 32A) (see Note 9). A remote start-stop switch may be connected to ter-minals 1 , 7 ,& 8 . (Line 32A) (see Note 9). Re-mote switches are operative only in the "remote" operating mode.

8. Contact rating is 5 amps resistive at 120 volts AC or 240 volts AC.

9. Device contact rating to be 5 milliamperes at 115 volts AC.

10. Three phase power must be properly phased. L1, L2, & L3 corresponding to phase sequence A, B, & C.

11. Contact rating is 5 Amps resistive at 250 volts AC & 30 volts DC 2 Amp inductive (.4 PF) at 250 volts AC & 30 volts DC.

12. Each 115 VAC field-connected inductive load I.E. relay coil, motor starter coil, etc. shall have a transient suppressor wired in parallel with its coil, physically located at the coil. Spare transient sup-pressor and control circuit fuses are supplied in a bag attached to the green ground screw in the lower left corner of the control panel.

13. Turbine auxiliary oil pump, oil cooler, oil sensors & turbine oil safety logic are supplied only on turbines with pressurized lubrication.

14. If optional chilled and condenser liquid low pres-sure differential switches are installed, panel must be configured for "digital" flow sensor. Refer to Form 160.67-O1.

15. Refer to Operators Manual for a detailed descrip-tion of chiller operation & all wanring/shutdown operating points.

16. Do NOT apply voltage on field wiring terminal blocks TB4 or TB6. All 115 volt AC power is fed from terminals 1 & 2.

17. Do NOT apply voltage on field instrument wiring terminal block TB7. All instrument loop power is supplied from terminals 325, 327, & 329 .

18. YST chillers are supplied with automatic starting as standard. Manual starting is not recommended and will be supplied by special quote only.

19. Manual motor protector auxiliary contact is open when operator is in the OFF position, closed when operator is in the ON or any tripped position.

20. Liquid injection solenoid is supplied on K3, K4, & K7 compressors only.

21. Optional wiring between the chiller terminal box and the floor mounted steam condensor is sup-plied by the factory for installation in conduit by the electrical installation contractor.

22. For standard top mounted steam condensor cables 28, 30, and 42 are connected directly to devices shown after the steam condensor is installed in the field.

Page 7: YST Steam Turbine Drive Centrifugal Liquid Chillers

JOHNSON CONTROLS 7

FORM 160.67-PW7 ISSUE DATE: 2/28/2019

23. For standard top mounted steam condenser, the harnesses from the main junction box and power panel are connected directly to the steam condens-er box after the steam condenser is installed in the field.

24. For inlet steam pressures up to 200 PSIG, PT-170 Range is 0-300 PSIG and PT-172 Range is 0-100 PSIG. For inlet steam pressures above 200 PSIG, PT-170 Range is 0-500 PSIG and PT-172 Range is 0-150 PSIG.

25. Manual motor protector signaling contact is closed when operator is in the off or on position, open when operator is in any tripped position. Trips may be caused by thermal overload, short circuit, under-voltage, or shunt.

NOTES (CONT'D)

Page 8: YST Steam Turbine Drive Centrifugal Liquid Chillers

JOHNSON CONTROLS8

FORM 160.67-PW7 ISSUE DATE: 2/28/2019

ELEMENTARY DIAGRAM

LD28558

035-26593-000SHT. 1 OF 11REV. H

FIGURE 1 - ELEMENTARY DIAGRAM

Page 9: YST Steam Turbine Drive Centrifugal Liquid Chillers

JOHNSON CONTROLS 9

FORM 160.67-PW7 ISSUE DATE: 2/28/2019

ELEMENTARY DIAGRAM (CONT'D)

LD28559

035-26593-000SHT. 1 OF 11REV. H

FIGURE 2 - ELEMENTARY DIAGRAM

Page 10: YST Steam Turbine Drive Centrifugal Liquid Chillers

JOHNSON CONTROLS10

FORM 160.67-PW7 ISSUE DATE: 2/28/2019

LD28560

FIGURE 3 - ELEMENTARY DIAGRAM

ELEMENTARY DIAGRAM

Page 11: YST Steam Turbine Drive Centrifugal Liquid Chillers

JOHNSON CONTROLS 11

FORM 160.67-PW7 ISSUE DATE: 2/28/2019

LD28561

035-26593-000SHT. 2 of 11REV. H

FIGURE 3 - ELEMENTARY DIAGRAM (CONT'D)

ELEMENTARY DIAGRAM (CONT'D)

Page 12: YST Steam Turbine Drive Centrifugal Liquid Chillers

JOHNSON CONTROLS12

FORM 160.67-PW7 ISSUE DATE: 2/28/2019

LD28562

035-26593-000SHT. 3 OF 11REV. H

FIGURE 4 - ELEMENTARY DIAGRAM

ELEMENTARY DIAGRAM

Page 13: YST Steam Turbine Drive Centrifugal Liquid Chillers

JOHNSON CONTROLS 13

FORM 160.67-PW7 ISSUE DATE: 2/28/2019

035-26593-000SHT. 3 OF 11REV. H

LD28563

FIGURE 5 - ELEMENTARY DIAGRAM

ELEMENTARY DIAGRAM (CONT'D)

Page 14: YST Steam Turbine Drive Centrifugal Liquid Chillers

JOHNSON CONTROLS14

FORM 160.67-PW7 ISSUE DATE: 2/28/2019

MICROBOARD DIAGRAM

LD28564

FIGURE 6 - MICROBOARD DIAGRAM

Page 15: YST Steam Turbine Drive Centrifugal Liquid Chillers

JOHNSON CONTROLS 15

FORM 160.67-PW7 ISSUE DATE: 2/28/2019

LD28564

MICROBOARD DIAGRAM (CONT'D)

035-26593-000SHT. 4 OF 11REV. H

LD28565

FIGURE 6 - MICROBAORD DIAGRAM (CONT'D)

Page 16: YST Steam Turbine Drive Centrifugal Liquid Chillers

JOHNSON CONTROLS16

FORM 160.67-PW7 ISSUE DATE: 2/28/2019

ELEMENTARY DIAGRAM

LD28566

035-26593SHT. 5 of 11REV. H

FIGURE 7 - ELEMENTARY DIAGRAM

Page 17: YST Steam Turbine Drive Centrifugal Liquid Chillers

JOHNSON CONTROLS 17

FORM 160.67-PW7 ISSUE DATE: 2/28/2019

THIS PAGE INTENTIONALLY LEFT BLANK.

Page 18: YST Steam Turbine Drive Centrifugal Liquid Chillers

JOHNSON CONTROLS18

FORM 160.67-PW7 ISSUE DATE: 2/28/2019

ELEMENTARY DIAGRAM

LD28567

FIGURE 8 - ELEMENTARY DIAGRAM

LD28568

035-26593-000SHT. 6 OF 11REV. H

Page 19: YST Steam Turbine Drive Centrifugal Liquid Chillers

JOHNSON CONTROLS 19

FORM 160.67-PW7 ISSUE DATE: 2/28/2019

LD28567

ELEMENTARY DIAGRAM

LD28568

035-26593-000SHT. 6 OF 11REV. H

FIGURE 8 - ELEMENTARY DIAGRAM (CONT'D)

Page 20: YST Steam Turbine Drive Centrifugal Liquid Chillers

JOHNSON CONTROLS20

FORM 160.67-PW7 ISSUE DATE: 2/28/2019

ELEMENTARY DIAGRAM

LD28569

FIGURE 9 - ELEMENTARY DIAGRAM

LD28570

035-26593-000SHT. 7 OF 11REV. H

Page 21: YST Steam Turbine Drive Centrifugal Liquid Chillers

JOHNSON CONTROLS 21

FORM 160.67-PW7 ISSUE DATE: 2/28/2019

LD28569

ELEMENTARY DIAGRAM

LD28570

035-26593-000SHT. 7 OF 11REV. H

FIGURE 9 - ELEMENTARY DIAGRAM (CONT'D)

Page 22: YST Steam Turbine Drive Centrifugal Liquid Chillers

JOHNSON CONTROLS22

FORM 160.67-PW7 ISSUE DATE: 2/28/2019

ELEMENTARY DIAGRAM

LD28571

FIGURE 10 - ELEMENTARY DIAGRAM

LD28572

035-26593-000SHT. 8 OF 11REV. H

Page 23: YST Steam Turbine Drive Centrifugal Liquid Chillers

JOHNSON CONTROLS 23

FORM 160.67-PW7 ISSUE DATE: 2/28/2019

LD28571

ELEMENTARY DIAGRAM

LD28572

035-26593-000SHT. 8 OF 11REV. H

FIGURE 10 - ELEMENTARY DIAGRAM (CONT'D)

Page 24: YST Steam Turbine Drive Centrifugal Liquid Chillers

JOHNSON CONTROLS24

FORM 160.67-PW7 ISSUE DATE: 2/28/2019

ELEMENTARY DIAGRAM

LD28573

ZS-149

FIGURE 11 - ELEMENTARY DIAGRAM

LD28574

035-26593-000SHT. 9 of 11REV. H

Page 25: YST Steam Turbine Drive Centrifugal Liquid Chillers

JOHNSON CONTROLS 25

FORM 160.67-PW7 ISSUE DATE: 2/28/2019

LD28573

ZS-149

ELEMENTARY DIAGRAM

LD28574

035-26593-000SHT. 9 of 11REV. H

FIGURE 11 - ELEMENTARY DIAGRAM (CONT'D)

Page 26: YST Steam Turbine Drive Centrifugal Liquid Chillers

JOHNSON CONTROLS26

FORM 160.67-PW7 ISSUE DATE: 2/28/2019

ELEMENTARY DIAGRAM

LD28575

FIGURE 12 - ELEMENTARY DIAGRAM

Page 27: YST Steam Turbine Drive Centrifugal Liquid Chillers

JOHNSON CONTROLS 27

FORM 160.67-PW7 ISSUE DATE: 2/28/2019

LD28575

ELEMENTARY DIAGRAM

LD28576

035-26593-000SHT. 10 OF 11REV. H

FIGURE 12 - ELEMENTARY DIAGRAM (CONT'D)

Page 28: YST Steam Turbine Drive Centrifugal Liquid Chillers

JOHNSON CONTROLS28

FORM 160.67-PW7 ISSUE DATE: 2/28/2019

ELEMENTARY DIAGRAM

LD28577

FIGURE 13 - ELEMENTARY DIAGRAM

LD28578

035-26593-000SHT 11 OF 11REV. H

Page 29: YST Steam Turbine Drive Centrifugal Liquid Chillers

JOHNSON CONTROLS 29

FORM 160.67-PW7 ISSUE DATE: 2/28/2019

LD28577

ELEMENTARY DIAGRAM

LD28578

035-26593-000SHT 11 OF 11REV. H

FIGURE 13 - ELEMENTARY DIAGRAM (CONT'D)

Page 30: YST Steam Turbine Drive Centrifugal Liquid Chillers

5000 Renaissance Drive, New Freedom, Pennsylvania USA 17349 1-800-524-1330 Subject to change without notice. Printed in USACopyright © by Johnson Controls 2019 www.johnsoncontrols.com ALL RIGHTS RESERVEDForm 160.67-PW7(219)Issue Date: February 28, 2019 NEW RELEASE