yankee pressure test tappi

Upload: mgmqro

Post on 02-Jun-2018

217 views

Category:

Documents


2 download

TRANSCRIPT

  • 8/10/2019 Yankee Pressure Test TAPPI

    1/4

    Vol. 78, No. 9 Tappi Journal 97

    Yankee Dryers

    The hydrostatic pressure test isperformed by filling the dryerwith water and increasing the pres-

    sure to 1.52.0 times the design pres-sure, depending on the specificpressure-vessel code. The dryer is

    filled and pressurized with waterbecause the potential for explosivefailure of a cracking cylinder during

    this test is greatly reduced with theincompressible medium.

    Hydrostatic testing is a fairly rel-evant testing procedure for a pres-

    sure vessel that will only be exposedto an internal pressure. A Yankeedryer, on the other hand, has a much

    more complicated loading situation.The dryer is pressurized with hot

    steam and cooled on the outside ofthe shell by the wet sheet. This in-

    duces large thermal stresses in theshell. The Yankee dryer is also arotating pressure vessel that is me-

    chanically loaded from the outside

    with the linear load from one or twopress rolls. In Fig. 1, the relative

    magnitude of these loads can be seen.

    In this case, the load from internalpressure is only 23% of the total load.

    These facts reduce the relevancy

    of the hydrostatic testing of a Yan-kee dryer; in some cases, it maycause more harm than good.

    Dryer deformation

    Figure 2illustrates the deformationof the Yankee dryer during the hy-

    drostatic test, which means defor-mation from internal pressure only.

    This load causes a bending momentin the shell and head flange areathat attempts to increase the angle

    between these parts at the flangeinterface.

    Figure 3illustrates the deforma-tion of the Yankee dryer during op-

    erating conditions. The significantdeformation here is the thermal de-

    formation caused by the wet sheeton the shell surface. This reduces

    the diameter and length of the shelland causes a bending moment in theflange corner that decreases the

    angle between the shell and head atthe flange interface.

    Stress distribution

    Figures 4 and 5provide two plots ofthe maximum principal stress in the

    flange area, with the hydrostatic testcondition shown in Fig. 4 and therunning condition in Fig. 5. The dark

    areas in these plots indicate highstresses.

    These plots clearly show that thestress distribution is quite different

    for these two scenarios. During hy-drostatic testing, the high stressesare located on the inside of the shell

    flange and extend into a regionaround the first grooves for a ribbed

    dryer. For the operating condition,the stresses in this area are very low

    and mostly compressive. The hightensile stresses are, in this case,found on the outside of the shell.

    This is an effect of the thermal stress,caused by the temperature differ-

    ence through the shell wall, that cre-

    ates a bending stress in the shellwith compressive stresses on the in-side and tensile stresses on the out-side.

    The hydrostatic test requirementmakes the design of the flange area

    more difficult, as two different loadscenarios must be considered. For

    running conditions, the currentbending forces tend to open a gapbetween the head and shell at the

    Hydrostatic testing of Yankee dryersBengt Unneberg

    ABSTRACT:The hydrostatic pressure testing of a Yankee dryeris performed as a fitness-for-service test made before delivery ofthe Yankee. In some countries, there are also statutoryrequirements for on-site hydrostatic testing after the delivery, aswell as periodic testing of the cylinder during its lifetime.Hydrostatic pressure testing is discussed, and the particular case

    of a Yankee dryer failure during on-site hydrostatic testing isdescribed.

    KEYWORDS:Drum driers (drum dryers), failure, hazards,hydraulic pressure, pressure, test methods, yankee driers (Yankeedryers).

    Unneberg is tissue machinery application engineer, Valmet-Karlstad AB, Box 1014,S-65115 Karlstad, Sweden.

  • 8/10/2019 Yankee Pressure Test TAPPI

    2/4

    98 September 1995 Tappi Journal

    Yankee Dryersouter head radius. This will increasethe risk for crevice corrosion betweenthe shell and head flange.

    The loads during hydrostatic test-ing are just the opposite of those for

    running conditions, so a design com-promise must be developed that

    keeps the deformations within ac-ceptable limits for both. If this is notdone, a gap may develop in the spigot

    fit area on the inside of the flangeconnection at the shell-flange inner

    radius.This gap will only be present dur-

    ing the hydrostatic test, but it maycause permanent deformation thatcould cause problems in the future

    steam leaks, for instance.The hydrostatic test is examining

    the dryer and demanding design con-siderations for a completely differ-

    ent load scenario than what the dryerwill be exposed to during its operat-ing lifetime. The primary justifica-

    tion for a hydrostatic examination isto establish that no major flaws exist

    in the materials of construction andto inspect the dryer for eventual

    leaks.

    On-site hydrostatic testing

    The previous discussion describedhydrostatic testing that is routinely

    performed by the manufacturer be-fore delivery of the Yankee dryer.

    Some countries, such as Italy andRussia, also require an additional

    hydrostatic test after delivery of theYankee to the mill. The purpose ofthis test is to determine whether any

    damage was inflicted during trans-portation to the mill site.

    Some countries also require a hy-drostatic test at regular intervals

    during the lifetime of the dryer. Oth-ers require a hydrostatic test evenafter relatively minor repair work

    on the dryer.These on-site hydrostatic tests in-

    troduce some new concerns aboutthis procedure, since mills normally

    do not have the same control overthe testing process as the manufac-

    turer, which does this procedure rou-tinely.

    These new concerns include: The enormous weight of water

    upwards of 300,000 lb in large Yan-

    keescan require structuralanalysis and additional structuralsupport for the vessel.

    The Yankee cannot sustain theadditional water weight through

    its bearings and, therefore, ar-rangements must be made to sup-

    port this load through the heads.Without proper support of the

    Yankee, it can be irreparably dam-aged.

    Care must be taken to ensure thatthe water used does not carry or

    create deposits that may cause anonuniform barrier to heat trans-fer.

    The monetary costs and downtime

    to perform the structural analy-sis, provide adequate building andYankee support, perform the hy-

    drostatic test, and internally clean

    the Yankee are considerable.

    Case study

    Lets look at a case study from aYankee dryer in a Russian mill as an

    example of the potential danger in-volved with these on-site hydrostatictests.

    On this dryer, the mill had prob-lems with two minor steam leaks be-

    tween the head and shell flanges andwas injecting sealant through pre-

    drilled holes in the head. After thisrepair, the Russian authorities re-

    quired a new hydrostatic test.The Yankee was manufactured in

    1987. The diameter was 5000 mm (195in.), and the shell length was 4850mm (191 in.). The design pressure

    was 900 kPa (130 psi). This dryerwas hydrostatically tested the first

    time at 1350 kPa (196 psi), which is1.5 times design pressure, before de-

    livery. Then, according to Russianrules, it was hydrostatically tested a

    second time after arrival in the mill.This was done in December 1988. InJanuary 1993, steam leaks were

    sealed, and the dryer was hydrostati-cally tested a third time.

    Before filling it with water, theYankee was unloaded from its bear-

    ings and supported with cradles thatwere positioned underneath the shellin the flange area on the front and

    back sides. The water pump that was

    used to fill the dryer had a capacityof 730 L/min at 2100 kPa (190 gal/min at 305 psig) or 420 L/min at 3750

    kPa (111 gal/min at 554 psig).This means a pressure capacity

    was possible of up to 4.2 times the

    maximum allowable working pres-sure of the dryer. A manual pump

    was also installed in the system that,after filling, would be used to increase

    the pressure to its final value.

    1.Yankee loads

  • 8/10/2019 Yankee Pressure Test TAPPI

    3/4

    Vol. 78, No. 9 Tappi Journal 99

    The dryer was made ready for thehydrostatic test but was not filled

    with water because it was gettinglate in the day. Plans were made for

    the testing to be done the next day,and preparations would continue thenext morning. However, during the

    evening, the plant employees began

    to fill the dryer with water to savetime the next day.The filling was initially made

    through the open manhole, which waslocated in the 12 oclock position. Ataround 10 p.m., the manhole cover

    was closed and the filling continued.The air evacuation in this stage was

    done through a 10-mm-diameter holein one of the head-to-shell bolts.

    Abo ut an hou r later, the dryer

    cracked. No personnel were near thedryer at the time.

    It was not known at what volumeor pressure the pump was operating

    when the failure occurred, but a rapidpressure increase is expected whenthe dryer is filled and water starts to

    be evacuated through the 10-mm air-

    venting hole, or if this hole becomesplugged by some foreign material.Later calculations indicated that at

    about 2500 kPa (363 psi) the stressesin the dryer reach a critical level,which is also the pressure level that

    was expected to be created by thepump.

    Here is a list of the resultingcracks in the dryer:

    2.Deformation during hydrostatic test 3.Deformation during operation

    Drive-side journal cracked at in-ner flange radius

    Six journal-to-head bolts brokenon tending side

    Radial cracks at Bolt 135 on tend-ing-side head

    Crack across shell at Bolt 135

    Circumferential crack in tendingside at second groove

    Circumferential crack in drive sideat first groove.

    This list is written in the probableorder in which the cracks developed.

    It suggests that the initial crack prob-ably occurred in the center flange,

    followed by the heads being pushed

    4.Stresses during hydrostatic test 5.Stresses during operation

  • 8/10/2019 Yankee Pressure Test TAPPI

    4/4

    100 September 1995 Tappi Journal

    Yankee Dryers

    out and the breaking of the journal-to-head bolts. From this point, ra-

    dial cracks progressed in the headout to the shell flange, where theaxial crack started and progressed

    over the full width of the cylinder.

    From this axial crack, the two cir-cumferential cracks were initiated.These cracks started close to the

    outer grooves in the shell that is, asshown earlier, one of the areas of

    highest stress during a hydrostatictest.Figure 6 shows the position of

    the crack in the center flange, also avery highly stressed area during a

    hydrostatic test, and the cracks inthe tending-side head.

    6.Cracks in drive-side journal and tending-side head

    Six boltscracked

    Tending-side head

    Drive-side journal

    7.Tending-side cracks in shell

    Second groove

    Tending-side shell

    8.Drive-side cracks in shell

    First groove

    Drive-side shell

    Figures 7 and 8show the crackpattern in the tending side and the

    drive side of the shell.

    Summary

    The case study clearly establishesthe danger inherent in on-site hy-drostatic testing. When we combine

    that danger with the costs associ-ated with hydrostatic testing and

    compare them with the informationgained by performing the tests, therisk and costs are far too high.

    With improved calculation meth-ods and material investigation pro-

    cedures, the value of the on-sitehydrostatic test has changed over

    the years. Global acoustic emissionexamination and a variety of mod-ern and sophisticated local nonde-

    structive testing procedures providegood alternatives to hydrostatic test-

    ing. These examinations should beperformed by experienced, qualifiedtechnicians using a detailed written

    procedure.

    For all these reasons, the YankeeDryer Safety Committee stronglyfeels that in any case where a re-

    quest for an on-site hydrostatic testis made, a discussion should be initi-

    ated with the involved authorities totry to substitute the hydrostatic test-ing with a safer and more appropri-

    ate testing method. TJ

    Received for review July 11, 1994.

    Accepted Nov. 11, 1994.

    Presented at the TAPPI 1994 Engineering Con-ference.