x-series oemandpanelbuildercomponents · 3circuitbreakers 1 40mx -cw5 3 4circuitbreakers 1 40mx...
TRANSCRIPT
X-SeriesOEM and Panel Builder ComponentsSelection Guide
This guide is applicablefor India only.
X-Series OEM Components
Table of Contents
1. Bulletin 140MX Motor Protection Circuit BreakersProduct Overview .....................................................................................................................1-2
Product Selection .....................................................................................................................1-4
Specifications............................................................................................................................1-6
Time-Current Characteristics .................................................................................................1-11
Dimensions..............................................................................................................................1-13
2. Bulletin 100-CX Contactors104-CX Reversing Contactors
Product Overview .....................................................................................................................2-2
Product Selection .....................................................................................................................2-5
Specifications............................................................................................................................2-8
Dimensions..............................................................................................................................2-13
Bulletin 193-EX Electronic Overload RelaysProduct Overview .....................................................................................................................2-3
Product Selection ...................................................................................................................2-16
Specifications..........................................................................................................................2-17
Dimensions..............................................................................................................................2-18
Bulletin 193-TX1 Bimetal Overload RelaysProduct Overview .....................................................................................................................2-4
Product Selection ...................................................................................................................2-20
Accessories.............................................................................................................................2-21
Specifications..........................................................................................................................2-22
3. Bulletin 100-DX Contactors193-TX Bimetal Overload Relays
Product Overview .....................................................................................................................3-2
Product Selection .....................................................................................................................3-4
Specifications............................................................................................................................3-7
Trip Curves ................................................................................................................................3-9
Dimensions..............................................................................................................................3-11
4. Bulletin 700-CFX Control RelaysProduct Overview .....................................................................................................................4-2
Product Selection .....................................................................................................................4-3
Specifications............................................................................................................................4-5
Dimensions................................................................................................................................4-6
Bulletin 140MX – Motor Protection Circuit BreakersProduct Overview..............................................................................................................................1-2
Product Selection..............................................................................................................................1-4
Specifications ....................................................................................................................................1-6
Time-Current Characteristics..........................................................................................................1-11
Dimensions ......................................................................................................................................1-13
Bulletin 140MX
Motor Protection Circuit BreakersSection Overview
1-1
1
MPCB Functionality:• Manual “ON-OFF” motor control
– kW rated manual motor controller
– Disconnect and isolation of branch circuit
– Long electrical/mechanical life
• Motor overload protection
– Bi-metal, class 10 protection
– Ambient temperature compensated
– Single phase protection
• Short-circuit protection
– Breaking capacity to 65 kA @ 400V
– Exceptional current limiting performance
– Coordinated Type 2 protection with 100-CX contactors
• Status indication and signaling
– Auxiliary contacts (NO/NC) for switch position
– Trip indicating contacts differentiate short circuitand overload fault
– Under-voltage and shunt trip modules
Field Installable Accessories:• Front mount auxiliary contacts
• Side mount auxiliary contacts
• Side mount trip indication contacts:
– Provides signaling to identify motor overloads andshort circuit faults
• Side mount Under-voltage releases
• Side mount shunt trip modules
• Feeder terminal blocks and commoning links
• Lockable circuit breaker operating handle
• Thru-the-door rotary operating kits (IP65)
Ease of Use:• 35 mm DIN rail mounting
• Control modules install without tools
• Combination head terminal screws (cross/slotted)
• Feeder terminal block and commoning links for reduced wiring
• Ideal for use in two component starters
Shunt Trip &Under-voltage
Release Modules
Rotary OperatingMechanism
Auxiliary ContactsFront Mount
140MX-F
140MX-C
Auxiliary ContactsSide Mount
Trip Indicating ContactsSide Mount
1-2
Bulletin 140MX
Motor Protection Circuit BreakersProduct Overview
1
Bulletin 140MX
Motor Protection Circuit BreakersProduct Overview
1-3
Note: This table is for catalog number explanation. It should not be used for configuration purposes.
140MX-C 140MX-F
140MX - C 2 E - C10 (A)
Bulletin/Product Line140MX – MPCBs
Series Letter
Frame SizeC-Frame – 0.1...32 AF-Frame – 10...63 A
Interrupting Rating (400V)2 – Standard
Protection TypeE – Motor
Current Rating
A16 – 0.10...0.16 A
A25 – 0.16...0.25 A
A40 – 0.25...0.40 A
A63 – 0.40...0.63 A
B10 – 0.63...1.0 A
B16 – 1.0...1.6 A
B25 – 1.6...2.5 A
B40 – 2.5...4.0 A
B63 – 4.0...6.3 A
C10 – 6.3...10.0 A
C16 – 10.0...16.0 A
C20 – 16.0...20.0 A
C25 – 20.0...25.0 A
C32 – 25.0...32.0 A
C40 – 32.0...40.0 A
C50 – 40.0...50.0 A
C58 – 50.0...58.0 A
C63 – 58.0...65.0 A
Catalog Number Explanation
1
Bulletin 140MX
Motor Protection Circuit BreakersProduct Selection
1-4
C-Frame — to 15 kW @ 380/400V
Motor RatingAC-3 (kW)
RatedOperationalCurrent
Motor CurrentAdjustmentRange
MagneticTrip Current
Breaking CapacityIcu=Ics (kA)
Catalog Number380/400V Iu (A) (A) (A) 220/230V 380…415V 440V
— 0.16 0.10…0.16 2.2 65 65 65 140MX-C2E-A16
0.06 0.25 0.16…0.25 3.5 65 65 65 140MX-C2E-A25
0.09 0.4 0.25…0.40 5.6 65 65 65 140MX-C2E-A40
0.12 0.63 0.40…0.63 8.8 65 65 65 140MX-C2E-A63
0.25 1 0.63…1.0 14.0 65 65 65 140MX-C2E-B10
0.55 1.6 1.0…1.6 22.4 65 65 65 140MX-C2E-B16
0.75 2.5 1.6…2.5 35.0 65 65 65 140MX-C2E-B25
1.5 4 2.5…4.0 56.0 65 65 65 140MX-C2E-B40
2.2 6.3 4.0…6.3 88.2 65 16 6 140MX-C2E-B63
4 10 6.3…10 140 16 16 6 140MX-C2E-C10
7.5 16 10…16 224 16 16 6 140MX-C2E-C16
9 20 16…20 280 12 12 6 140MX-C2E-C20
12.5 25 20…25 350 12 12 6 140MX-C2E-C25
15 32 25…32 448 12 12 6 140MX-C2E-C32
F-Frame — 7.5...34 kW @ 380/400V
Motor RatingAC-3 (kW)
RatedOperationalCurrent
Motor CurrentAdjustmentRange
Magnetic TripCurrent
Breaking CapacityIcu=Ics (kA)
Catalog Number380/400V Iu (A) (A) (A) 220/230V 380…415V 440V
7.5 16 10…16 224 50 50 45 140MX-F2E-C16
12.5 25 16…25 350 50 50 45 140MX-F2E-C25
15 32 25…32 448 50 50 45 140MX-F2E-C32
20 40 32…40 560 50 50 45 140MX-F2E-C40
25 50 40…50 700 50 50 45 140MX-F2E-C50
30 58 50…58 812 50 50 45 140MX-F2E-C58
34 65 55…65 882 50 50 45 140MX-F2E-C63
140MX-C 140MX-F
Functionality
• Manual “ON-OFF” motor control
• Motor overload protection
• Short-circuit protection
• Status indication and signaling
Approvals
• CE, IEC 60947-2
• CCC, GB14048.2
1
Bulletin 140MX
Motor Protection Circuit BreakersProduct Selection
1-5
Description Type For use withPkg./OrderQuantity
CatalogNumber
Auxiliary ContactsSide Mount 1NO, 1NC 140MX-C & F 5 140MX-C-ASA11
Auxiliary ContactsFront Mount
1NO, 1NC140MX-C & F 5
140MX-C-AFA11
1NO 140MX-C-AFA10
Trip IndicatingContacts
2NO140MX-C & F 2
140MX-C-ASAR10M10
2NC 140MX-C-ASAR01M01
Shunt Trip Modules
110V 50Hz
140MX-C & F 2
140MX-C-SND
220V 50Hz 140MX-C-SNL
230V 50Hz 140MX-C-SNF
380V 50Hz 140MX-C-SNE
400V 50Hz 140MX-C-SNN
24V DC 140MX-C-SNZJ
Under-VoltageRelease Modules
220V 50Hz
140MX-C & F 2
140MX-C-UVL
230V 50Hz 140MX-C-UVF
380V 50Hz 140MX-C-UVE
400V 50Hz 140MX-C-UVN
Rotary Operator KitBlack
140MX-C & F 1140MX-C-DHB
Red/Yellow 140MX-C-DHR
Rotary Operator Kit(MCC) Black 140MX-C & F 1 140MX-C-DHMB
Lockable RotaryHandle (CB Mount) Black 140MX-C & F 1 140MX-C-KB
FeederTerminal Block 140MX-C & F 1 140MX-C-WTE
Commoning Links(w/o Side Accessories)
2 Circuit Breakers
140MX-C 10
140MX-C-W452
3 Circuit Breakers 140MX-C-W453
4 Circuit Breakers 140MX-C-W454
5 Circuit Breakers 140MX-C-W455
Commoning Links(with Side Auxiliary Contacts)
2 Circuit Breakers
140MX-C 10
140MX-C-W542
3 Circuit Breakers 140MX-C-W543
4 Circuit Breakers 140MX-C-W544
5 Circuit Breakers 140MX-C-W545
Commoning Links(with Side Auxiliary
Contacts OR UVR/SNT)
2 Circuit Breakers
140MX-C 10140MX-C-W722
4 Circuit Breakers 140MX-C-W724
1
Bulletin 140MX
Motor Protection Circuit BreakersSpecifications
1-6
Catalog Number Description Function Diagrams Assembly
140MX-C2E-...
Motor ProtectionCircuit Breaker140MX-F2E-...
140MX-C-SAR10M10
Trip IndicatingContacts140MX-C-SAR01M01
140MX-C-ASA11
Auxiliary ContactsSide Mount
140MX-C-AFA11
Auxiliary ContactsFront Mount
140MX-C-SN*
Shunt Trip Modules
140MX-C-UV*
Under Voltage Release
1
Bulletin 140MX
Motor Protection Circuit BreakersSpecifications
1-7
Motor Protection Circuit Breakers 140MX-C 140MX-F
General
Standards IEC/EN 60947, VDE 0660, GB14048, ccc, cE
Climatic Proofing Damp Heat, Constant, to IEC 60068-2-78; Damp Heat, Cyclic, to IEC 60068-2-30
Ambient Temperature Storage ˚C/˚F -25...80 ˚C/-13...176 ˚F -25...70 ˚C/-13...158 ˚F
Open ˚C/˚F -25...55 ˚C/-13...131 ˚F -25...55 ˚C/-13...131 ˚F
Enclosed ˚C/˚F -25...40 ˚C/-13...104 ˚F -25...40 ˚C/-13...104 ˚F
Mounting Position
Direction of Incoming Supply As Required As Required
Degree of Protection Device IP20 IP20
Terminations IP00 IP00
Protection Against Direct Contact Finger and Back-of-Hand Proof Finger and Back-of-Hand Proof
Mechanical Shock Resistance Half-Sinusoidal Shock 10 ms to IEC 60068-2-27 g 25 15
Altitude m 2000 2000
Terminal Capacity Screw Terminals Solid mm2 1 x (1–6); 2 x (1–6) 1 x (1–50); 2 x (1–35)
Flexible with Ferrule to DIN 46228 mm2 1 x (1–6); 2 x (1–6) 1 x (1–35); 2 x (1–35)
Solid or Stranded AWG 18–10 14–2
Specific Tightening Torque forTerminal Screws
Main Cable Nm 1.7 3
Control Circuit Cables Nm 1 1
Main Conducting Paths
Rated Impulse Withstand Voltage Uimp V AC 6000 6000
Overvoltage Category/Pollution Degree III/3 III/3
Rated Operational Voltage Ue V AC 440 440
Rated Uninterrupted Current =Rated Operational Current
Iu = Ie A 25 or Current Setting of theOvercurrent Release
65 Open63 Enclosed
Rated Frequency Hz 40–60 40–60
Current Heat Loss (3 pole at operating temperature) W 6 22
Mechanical Life Operations Mio 0.1 0.03
Electrical Life (AC-3 at 400V) Operations Mio 0.1 0.03
Maximum Operating Frequency Operations Per Hour Ops/h 40 40
Short-Circuit RatingDC kA 60 (up to 140MX-C2E-C16)
40 (up to 140MX-C2E-C20...C32) 60
Motor Switching Capacity AC-3 (up to 440V) A 32 65
DC (up to 250V) A 25 (3 contacts in series) 63 (3 contacts in series)
Releases
Temperature Compensation to IEC/EN 60947, VDE 0660 ˚C/˚F -5...40 ˚C/23...104 ˚F -5...40 ˚C/23...104 ˚F
Operating Range ˚C/˚F -25...55 ˚C/-13...13 ˚F -25...55 ˚C/-13...131 ˚F
Temperature Compensation Residual Error for T>40 ˚C %/K ≤ 0.25 ≤ 0.25
Setting Range of Overload Releases xIu 0.6–1 0.6–1
Short-Circuit Release Fixed xIu 14 14
Short-Circuit Release Tolerance % ±20 ±20
Phase-Failure Sensitivity IEC/EN 60947-4-1, VDE 0660 Part 102
1
Bulletin 140MX
Motor Protection Circuit BreakersSpecifications
1-8
Iu230V
Iq Icu Ics415V
Iq Icu Ics440V
Iq Icu Ics
A kA kA kA A1) kA kA kA A1) kA kA kA A1)
140MX-C With Classification Type “1” and “2”
0.16-1 65 65 65 N 65 65 65 N 65 65 65 N
1.6 65 65 65 N 65 65 65 N 65 65 65 N
2.5 65 65 65 N 65 65 65 N 65 65 65 N
4 65 65 65 N 65 65 65 N 65 65 65 N
6.3 65 65 65 N 16 16 8 50 6 6 3 50
10 16 16 8 50 16 16 8 50 6 6 3 50
12 16 16 8 50 16 16 8 50 6 6 3 50
16 16 16 8 50 16 16 8 50 6 6 3 50
20 12 12 6 50 12 12 6 50 6 6 3 50
25 12 12 6 50 12 12 6 50 6 6 3 50
32 12 12 6 50 12 12 6 50 6 6 3 50
140MX-F With Classification Type “1” and “2”
16 150 150 25 N 150 150 25 N 45 45 25 100
25 150 150 25 N 150 150 25 N 45 45 25 100
32 50 50 25 100 50 50 25 100 45 45 25 100
40 50 50 25 100 50 50 25 100 45 45 25 100
50 50 50 25 100 50 50 25 100 45 45 25 100
58 50 50 25 160 50 50 25 160 45 45 25 160
1) Fuse (AgG/gL) for enhancing the switching capacity of the motor protection circuit breaker to 100 kA.
Motor Protection Circuit Breaker Switching Capacity
• Rated uninterrupted current – Iu
• Rated conditional short-circuit current – Iq (IEC/EN 60947-4-1)
• Rated ultimate short-circuit breaking capacity – Icu (IEC/EN 60947-2)
• Rated operational service short-circuit breaking capacity – Ics (IEC/EN 60947-2)1
Bulletin 140MX
Motor Protection Circuit BreakersSpecifications
1-9
Under-Voltage Release Module — 140MX-C-UV*
Terminal Capacities Solid or FlexibleWire with Ferrule — mm2 1 x (0.75–2.5)
2 x (0.75–2.5)
Solid or Stranded — AWG 1 x (18–14)2 x (18–14)
Rated Operational Voltages V AC Ue 42–480
V DC Ue 24–250
Pick-up Voltage — x Us 0.85–1.1
Drop-out Voltage — x Us 0.7–0.35
Power Consumption Pick-up V AC VA 5
Sealing V AC VA 3
Shunt Trip Module — 140MX-C-SN*
Terminal Capacities Solid or FlexibleWire with Ferrule — mm2 1 x (0.75–2.5)
2 x (0.75–2.5)
Solid or Stranded — AWG 1 x (18–14)2 x (18–14)
Rated Operational Voltages V AC Ue 42–480
V DC Ue 24–250
Operating Range V AC x Us 0.7–1.1
V DC x Us 0.7–1.1
Power Consumption Pick-Up V AC VA 5
Sealing V AC VA 3
Pick-Up V DC W 3
Sealing V DC W 3
1
1-10
1
140MX-C, 140MX-FOne and Two Pole Circuits with AC and DC.
Protection of PVC Insulated Cables againstThermal Overload with Short-CircuitsThe Table Indicates Which Minimum Cable Cross-Sections are Protected byMPCB up to their Rated Conditional Short-Circuit Current, Iq.
Minimum Cross-Section Protected
Bulletin 140MX
Motor Protection Circuit BreakersSpecifications
Bulletin 140MX
Motor Protection Circuit BreakersTime-Current Characteristic
1-11
Time-Current Characteristic
140MX-C 140MX-F
1
1-12
1
140MX-C
140MX-F
Maximum Cut-off Current (380...415V)
Bulletin 140MX
Motor Protection Circuit BreakersTime-Current Characteristic
Bulletin 140MX
Motor Protection Circuit BreakersDimensions
1-13
140MX-C
Standard Operating Handle Lockable Operating Handle 140MX-C-KB
140MX-F
Standard Operating Handle
Lockable Operating Handle 140MX-C-KB
Dimensions are approximate and shown in millimeters.
Dimensions are approximate and shown in millimeters.
1
Bulletin 140MX
Motor Protection Circuit BreakersDimensions
1-14
Door Rotary Operating Handle
140MX-C-DH...
Mounting Depth: 100 to 240 mm fromthe top edge of the mounting rail tothe front edge of the panel door.
Side Mount Auxiliary Contact
140MX-C-ASA...
Shunt Trip/Under-Voltage Releases
140MX-C-UV* and 140MX-C-SN*
Trip-Indicating Auxiliary Contacts
140MX-C-ASAR...
Dimensions are approximate and shown in millimeters.
Dimensions are approximate and shown in millimeters.
1
Bulletin 100-CX Contactors104-CX Reversing Contactors
Product Overview..............................................................................................................................2-2
Product Selection..............................................................................................................................2-5
Specifications ....................................................................................................................................2-8
Dimensions ......................................................................................................................................2-13
Bulletin 193-EX Electronic Overload RelaysProduct Overview..............................................................................................................................2-3
Product Selection............................................................................................................................2-16
Specifications ..................................................................................................................................2-17
Dimensions ......................................................................................................................................2-18
Bulletin 193-TX1 Bimetal Overload RelaysProduct Overview..............................................................................................................................2-4
Product Selection............................................................................................................................2-20
Accessories .....................................................................................................................................2-21
Specifications ..................................................................................................................................2-22
Bulletin 100-CX, 104-CX, 193-EX, 193-TX1
Contactors, Electronic & Bimetal Overload RelaysSection Overview
2-1
2
Bulletin 100-CX, 104-CX, 193-EX, 193-TX1
Contactors, Electronic & Bimetal Overload RelaysProduct Overview
2-2
Note: This table is for catalog number explanation. It should not be used for configuration purposes.
Catalog Number Explanation – 100-CX, 104-CX
100-CX – 09 N 4 00 (A)
Bulletin/Product Line100-CX – DOL Contactors104-CX – Reversing Contactors
Power PolesBlank – 3 Pole4 – 4 Pole
Series Letter
Coil Code – ACK – 24V 50 HzY – 48V 50 HzD – 110V 50 HzKF – 220…230V 50/60 HzN – 380...400V 50 HzG – 415V 50 HzB – 440V 50 Hz
Coil Code – DCZJ – 24VZY – 48VZD – 110ZF – 220V
Current Rating3 Pole – AC3
09
12
18
25
32
38
40
50
65
80
95
Auxiliary Contacts
10 – 1 NO
01 – 1 NC
00 – No Aux.
02 – 2 NC
20 – 2 NO
11 – 1 NO/1 NC
22 – 2 NO/2 NC
100-CX09... 100-CX32... 100-CX65...
2
Bulletin 100-CX, 104-CX, 193-EX, 193-TX1
Contactors, Electronic & Bimetal Overload RelaysProduct Overview
2-3
Catalog Number Explanation – 193-EX
Note: This table is for catalog number explanation. It should not be used for configuration purposes.
193-EX – D A 1 C D (A)
Bulletin/Product Line
193-EX – Electronic OLR
ResetD – ManualE – Auto Control Voltage
D – 110V 50 HzF – 220…230V 50 HzN – 380...400V 50 Hz
Frame SizeC – 9...38 AE – 40...95 A
Trip Class1 – Class 10
Current RatingFrame 1 (0.10...40 A)A – 0.10...0.16 AB – 0.16...0.25 AC – 0.25...0.40 AD – 0.40...0.63E – 0.63...1.0 AF – 1.0...1.6 AG – 1.6...2.5 AH – 2.5...4.0 A
Current RatingFrame 1 (0.10...40 A)J – 4.0...6.0 AK – 5.5...8.0 AL – 7.0...10.0 AM – 9.0...13.0 AN – 12.0...18.0 AO – 17.0...25.0 AP – 23.0...32.0 AQ – 30.0...40.0 A
Current RatingFrame 2 (23...95 A)P – 23.0...32.0 AQ – 30.0...40.0 AR – 37.0...50.0 AS – 48.0...65.0 AT – 55.0...70.0 AU – 63.0...80.0 AV – 80.0...95.0 A
0.1 – 40 A 23 – 95 A
2
2-4
Bulletin 100-CX, 104-CX, 193-EX, 193-TX1
Contactors, Electronic & Bimetal Overload RelaysProduct Overview
Note: This table is for catalog number explanation. It should not be used for configuration purposes.
193-TX1 – A A16 (A)
Bulletin/Product Line
193-TX1 – Bimetal OLR
Series Letter
Current Rating (A)A – 0.1 A…0.9 AB – 1.0 A…9.9 AC – 10 A…99 A
Frame SizeA – 100-CX09…CX18B – 100-CX32…CX38
Catalog Number Explanation – 193-TX1
193-TX1A
2
2-5
Bulletin 100-CX
ContactorsProduct Selection
25 9 2.2 4 4 4 5.5 5.51 0 100-CX09*10 100-CX09*400
0 1 100-CX09*01 —
25 12 3 5.5 5.5 5.5 7.5 7.51 0 100-CX12*10 100-CX12*400
0 1 100-CX12*01 —
32 18 4 7.5 9 9 10 101 0 100-CX18*10 —
0 1 100-CX18*01 —
40 25 5.5 11 11 11 15 151 0 100-CX25*10 100-CX25*400
0 1 100-CX25*01 —
50 32 7.5 15 15 15 18.5 18.51 0 100-CX32*10 —
0 1 100-CX32*01 —
50 38 9 18.5 18.5 18.5 18.5 18.51 0 100-CX38*10 —
0 1 100-CX38*01 —
60 40 11 18.5 22 22 22 30 1 1 100-CX40*11 100-CX40*400
80 50 15 22 25 30 30 33 1 1 100-CX50*11 —
80 65 18.5 30 37 37 37 37 1 1 100-CX65*11 100-CX65*400
125 80 22 37 45 45 55 45 1 1 100-CX80*11 —
125 95 25 45 45 45 55 45 1 1 100-CX95*11 100-CX95*400
Coil Voltage Selection Table: (*) Insert Coil Code
AC50 Hz
24V 48V 110V 220…230V 380…400V 415V 440V
K Y D K F [1] N G B
DC24V 48V 110V 220V — — —
ZJ ZY ZD ZF — — —
Contact Allen-Bradley for other coil voltages.[1] 50/60 Hz
100-CX09... 100-CX32... 100-CX65...
Maximum Ie[A]
Ratings for Switching AC Motors and Non-motor Loads
AC-3, AC-4 Direct-on-Line
kW (50 Hz) 3 Pole 4 Pole
3 Phase Auxiliary Contacts
AC-140 ˚C
AC-360 ˚C
220V230V
380V400V 415V 440V 500V
660V690V NO NC Catalog Number Catalog Number
Functionality
• 9...95 A
• 3 & 4 pole
• AC & DC operated
Approvals
• CE, IEC 60947-4
• CCC, GB14048.2
• TUV2
Bulletin 104-CX
Reversing ContactorsProduct Selection
2-6
25 9 2.2 4 4 4 5.5 5.52 0 104-CX09*20
0 2 104-CX09*02
25 12 3 5.5 5.5 5.5 7.5 7.52 0 104-CX12*20
0 2 104-CX12*02
32 18 4 7.5 9 9 10 102 0 104-CX18*20
0 2 104-CX18*02
40 25 5.5 11 11 11 15 152 0 104-CX25*20
0 2 104-CX25*02
50 32 7.5 15 15 15 18.5 18.52 0 104-CX32*20
0 2 104-CX32*02
50 38 9 18.5 18.5 18.5 18.5 18.52 0 104-CX38*20
0 2 104-CX38*02
60 40 11 18.5 22 22 22 30 2 2 104-CX40*22
80 50 15 22 25 30 30 33 2 2 104-CX50*22
80 65 18.5 30 37 37 37 37 2 2 104-CX65*22
125 80 22 37 45 45 55 45 2 2 104-CX80*22
125 95 25 45 45 45 55 45 2 2 104-CX95*22
Maximum Ie[A]
Ratings for Switching AC Motors
AC-3, AC-4 Reversing
kW (50 Hz) 3 Pole
3 Phase Aux. Contacts
Catalog NumberAC-140˚C
AC-360 ˚C 220V 230V
380V400V 415V 440V 500V 660V 690V NO NC
Coil Voltage Selection Table: (*) Insert Coil Code
AC50 Hz
24V 48V 110V 220…230V 380…400V 415V 440V
K Y D K F [1] N G B
Contact Allen-Bradley for other coil voltages.[1] 50/60 Hz
Functionality
• 9...95 A
• 3 pole reversing
• Mechanical interlock
• Reversing power wiring
• AC operated
Approvals
• CE, IEC 60947-4
• CCC, GB14048.2
104-CX12... 104-CX50...
2
Bulletin 100-CX, 104-CX
Contactor AccessoriesProduct Selection
2-7
Description Type For Use With Pack Qty Catalog Number
Auxiliary ContactsFront Mount – 4 Pole
4 NO
100-CX09...95
1 100-FX40
3 NO/1 NC 1 100-FX31
2 NO/2 NC 1 100-FX22
1 NO/3 NC 1 100-FX13
4 NC 1 100-FX04
Auxiliary ContactsFront Mount – 2 Pole
2 NO
100-CX09...95
1 100-FX20
1 NO/1 NC 1 100-FX11
2 NC 1 100-FX02
Auxiliary ContactsSide Mount – 2 Pole
2 NO
100-CX09...95
1 100-FXS20
1 NO/1 NC 1 100-FXS11
Pneumatic Timer“ON Delay”
0.1...3.0 sec.
700-CFX 1
100-PTXN3
0.1...30 sec. 100-PTXN30
0.1...180 sec. 100-PTXN180
Pneumatic Timer“OFF Delay”
0.1...3.0 sec.
700-CFX 1
100-PTXF3
0.1...30 sec. 100-PTXF30
0.1...180 sec. 100-PTXF180
Surge SuppressorMOV – Plug-in Mount
24...48V AC/DC
100-CX09...95
1 100-FXPM48
50...127V AC/DC 1 100-FXPM127
110...240V AC/DC 1 100-FXPM240
Surge SuppressorMOV – Insert Mount
24...48V AC/DC
100-CX09...95
1 100-FXTM48
50...127V AC/DC 1 100-FXTM127
110...240V AC/DC 1 100-FXTM240
380...415V AC/DC 1 100-FXTM415
Surge SuppressorRC – Insert Mount
24...48V AC
100-CX09...95 1
100-FXTR48
50...127V AC 100-FXTR127
110...240V AC 100-FXTR240
Surge SuppressorDiode – Insert Mount 24...40V DC 100-CX09...95 1 100-FXTD220
Mechanical Interlocks for usein reversing, star-delta andchangeover assemblies
Mechanical Interlockand Assembly Coupler
100-CX09...C38 1 100-MXC00
100-CX40...95 1 100-MXE00
2
Bulletin 100-CX, 104-CX
ContactorsSpecifications
2-8
Contactor Size CX09 CX12 CX18 CX25 CX32 CX38 CX40 CX50 CX65 CX80 CX95
Rated Motor CurrentIe A (AC-3)
400V 9 12 18 25 32 38 40 50 65 80 95
690V 6.6 8.9 12 18 21 21.5 34 39 42 49 49
Thermal Current Ith A (AC-1) 25 25 32 40 50 50 60 80 80 125 125
Insulating Voltage, Ui V 690
Operational Voltage Ue V 380/400/415 660/690
AC-3(6X Make,1X Break)
Electrical Life (Mio) 1.0 1.0 1.0 1.0 0.8 0.8 0.8 0.6 0.6 0.6 0.6
Maximum OperatingFrequency (Ops/h) 1200 1200 1200 1200 600 600 600 600 600 600 600
AC-4(6X Make,6X Break)
Electrical Life (Mio) 0.2 0.2 0.2 0.2 0.2 0.15 0.15 0.15 0.15 0.1 0.1
Maximum OperatingFrequency (Ops/h) 300
OperationalCurrent Ie A
380/400V 3.5 5 7.7 8.5 12 13.9 18.5 24 28 37 44
660/690V 1.5 2 3.8 4.4 7.5 8 9 12 14 17.3 21.3
Auxiliary Contacts
Thermal Current Ith A 10
ElectricalLife 104
AC-15 (360VA)100 80 60
DC-13 (33W)
Minimum Load Connected 24V 10mA
Mechanical Life 104 1,000 800 600
Coil
Operational Voltage Us V AC (50 Hz, 50 Hz/60 Hz, 60 Hz): 24, 48, 110, 220, 380; DC: 24, 48, 110, 220
Pick-up Voltage 85% Us ~ 110% Us
Drop-out Voltage 20% Us ~ 75% Us (AC) 10% Us ~ 75% Us (DC)
AC CoilPower (VA)
Pick-up 76 76 76 110 110 110 230 230 230 230 230
Maintain 9.4 9.4 9.4 11 11 11 32 32 32 32 32
DC CoilPower (W)
Pick-up11 11 11 13 13 13 22 22 22 22 22
Maintain
Terminal
TerminalCapacitymm2
(min/max)
Non-preparedTerminalSoft Cable
1 Wire 1...4 1.5...6 1.5...10 2.5...10 2.5...25 4...50
2 Wires 1...4 1.5...6 1.5...6 2.5...10 2.5...16 4...25
PreparedTerminalSoft Cable
1 Wire 1...4 1...6 1...6 1...10 2.5...25 4...50
2 Wires 1...2.5 1...4 1...4 1.5...6 2.5...10 4...16
Non-preparedTerminalHard Cable
1 Wire 1...4 1.5...6 1.5...6 1.5...10 2.5...25 4...50
2 Wires 1...4 1.5...6 1.5...6 2.5...10 2.5...16 4...25
2
Bulletin 100-CX, 104-CX
ContactorsSpecifications
2-9
Short Circuit Coordination — 25 kA @ 415V
Motor Ratings Motor Protection Circuit Breaker Contactor IEC Coordination
[kW]1500 rpm
[A] Catalog NumberThermal Setting
(A)Magnetic Setting
(A) Catalog NumberCoordination
Level Remark
0.03 0.12 140MX-C2E-A16 0.1 - 0.16 2.2 100-CX09*10 Type “2”
0.06 0.24 140MX-C2E-A25 0.16 - 0.25 3.5 100-CX09*10 Type “2”
0.09 0.33 140MX-C2E-A40 0.25 - 0.4 5.6 100-CX09*10 Type “2”
0.12 0.43 140MX-C2E-A63 0.4 - 0.63 8.8 100-CX09*10 Type “2”
0.18 0.61 140MX-C2E-A63 0.4 - 0.63 8.8 100-CX09*10 Type “2”
0.25 0.80 140MX-C2E-B10 0.63 - 1.0 14.0 100-CX09*10 Type “2”
0.37 1.1 140MX-C2E-B16 1.0 - 1.6 22.4 100-CX09*10 Type “2”
0.55 1.5 140MX-C2E-B16 1.0 - 1.6 22.4 100-CX09*10 Type “2”
0.75 1.9 140MX-C2E-B25 1.6 - 2.5 35.0 100-CX09*10 Type “2”
1.1 2.7 140MX-C2E-B40 2.5 - 4.0 56.0 100-CX09*10 Type “2”
1.5 3.5 140MX-C2E-B40 2.5 - 4.0 56.0 100-CX09*10 Type “2”
2.2 5.0 140MX-C2E-B63 4.0 - 6.3 88.2 100-CX18*10 Type “2” 100-CX Up-sizing
3 6.6 140MX-C2E-C10 6.3 - 10 140 100-CX18*10 Type “2” 100-CX Up-sizing
4 8.5 140MX-C2E-C10 6.3 - 10 140 100-CX18*10 Type “2” 100-CX Up-sizing
5.5 11 140MX-C2E-C16 10 - 16 224 100-CX18*10 Type “2”
7.5 15 140MX-C2E-C16 10 - 16 224 100-CX18*10 Type “2”
10 20 140MX-C2E-C20 20 - 25 280 100-CX25*10 Type “2”
11 22 140MX-C2E-C25 16 - 25 350 100-CX25*10 Type “2”
15 29 140MX-C2E-C32 25 - 32 448 100-CX32*10 Type “2”
18 36 140MX-F2E-C40 32 - 40 560 100-CX38*10 Type “2”
18 36 140MX-F2E-C40 32 - 40 560 100-CX40*10 Type “2”
22 41 140MX-F2E-C50 40 - 50 700 100-CX50*10 Type “2”
30 56 140MX-F2E-C58 50 - 58 812 100-CX65*10 Type “2”
30 56 140MX-F2E-C65 55 - 65 882 100-CX65*10 Type “2”
37 68 140-CMN-9000 63 - 90 1260 100-CX80*10 Type “2”
45 81 140-CMN-9000 63 - 90 1260 100-CX95*10 Type “2”
2
Bulletin 100-CX, 104-CX
ContactorsSpecifications
2-10
Short Circuit Coordination — 50 kA @ 415V
Motor Ratings Motor Protection Circuit Breaker Contactor IEC Coordination
[kW] 1500 rpm [A] Catalog NumberThermal Setting
(A)Magnetic Setting
(A) Catalog NumberCoordination
Level Remark
0.03 0.12 140MX-C2E-A16 0.1 - 0.16 2.2 100-CX09*10 Type “2”
0.06 0.24 140MX-C2E-A25 0.16 - 0.25 3.5 100-CX09*10 Type “2”
0.09 0.33 140MX-C2E-A40 0.25 - 0.4 5.6 100-CX09*10 Type “2”
0.12 0.43 140MX-C2E-A63 0.4 - 0.63 8.8 100-CX09*10 Type “2”
0.18 0.61 140MX-C2E-A63 0.4 - 0.63 8.8 100-CX09*10 Type “2”
0.25 0.80 140MX-C2E-B10 0.63 - 1.0 14.0 100-CX09*10 Type “2”
0.37 1.1 140MX-C2E-B16 1.0 - 1.6 22.4 100-CX09*10 Type “2”
0.55 1.5 140MX-C2E-B16 1.0 - 1.6 22.4 100-CX09*10 Type “2”
0.75 1.9 140MX-C2E-B25 1.6 - 2.5 35.0 100-CX09*10 Type “2”
1.1 2.7 140MX-C2E-B40 2.5 - 4.0 56.0 100-CX09*10 Type “2”
1.5 3.5 140MX-C2E-B40 2.5 - 4.0 56.0 100-CX09*10 Type “2”
2.2 5.0 140MX-C2E-B63 4.0 - 6.3 88.2 100-CX18*10 Type “2” 100-CX Up-sizing
3 6.6 140MX-C2E-C10 6.3 - 10 140 100-CX18*10 Type “2” 100-CX Up-sizing
4 8.5 140MX-C2E-C10 6.3 - 10 140 100-CX18*10 Type “2” 100-CX Up-sizing
5.5 11 140MX-C2E-C16 10 - 16 224 100-CX18*10 Type “2”
7.5 15 140MX-C2E-C16 10 - 16 224 100-CX18*10 Type “2”
10 20 140MX-C2E-C25 16 - 25 350 100-CX25*10 Type “2”
11 22 140MX-C2E-C25 16 - 25 350 100-CX25*10 Type “2”
15 29 140MX-C2E-C32 25 - 32 448 100-CX32*10 Type “2”
18 36 140MX-F2E-C40 32 - 40 560 100-CX38*10 Type “2”
18 36 140MX-F2E-C40 32 - 40 560 100-CX40*10 Type “2”
22 41 140MX-F2E-C50 40 - 50 700 100-CX50*10 Type “2”
30 56 140MX-F2E-C58 50 - 58 812 100-CX65*10 Type “2”
30 56 140MX-F2E-C65 55 - 65 882 100-CX65*10 Type “2”
37 68 140-CMN-9000 63 - 90 1260 100-CX80*10 Type “2”
45 81 140-CMN-9000 63 - 90 1260 100-CX95*10 Type “2”
2
Bulletin 100-CX, 104-CX
ContactorsSpecifications
2-11
2
Renewal Parts:
Description Type For use with Pack Qty. Catalog Number
ACCoils
24V 50 Hz
100-CX09…CX18 &700-CFX 1
100-CX0CK
48V 50 Hz 100-CX0CY
110V 50 Hz 100-CX0CD
220…230V 50/60 Hz 100-CX0CKF
380…410V 50 Hz 100-CX0CN
415V 50 Hz 100-CX0CG
440V 50 Hz 100-CX0CB
24V 50 Hz
100-CX25…CX38 1
100-CX1CK
48V 50 Hz 100-CX1CY
110V 50 Hz 100-CX1CD
220…230V 50/60 Hz 100-CX1CKF
380…410V 50 Hz 100-CX1CN
415V 50 Hz 100-CX1CG
440V 50 Hz 100-CX1CB
24V 50 Hz
100-CX40…CX95 1
100-CX2CK
48V 50 Hz 100-CX2CY
110V 50 Hz 100-CX2CD
220…230V 50/60 Hz 100-CX2CKF
380…410V 50 Hz 100-CX2CN
415V 50 Hz 100-CX2CG
440V 50 Hz 100-CX2CB
Bulletin 100-CX, 104-CX
ContactorsSpecifications
2-12
Dimensions are shown in millimeters.
104-CX Wiring Diagram
104-CX09*20...38*20 104-CX40*22...95*22
104-CX09*02...38*02
2
100-CX Wiring Diagram
100-CX09...38 w/ 1NO AUX 100-CX09...38 w/ 1NC AUX
100-CX40...95 w/ 1NO/1NC AUX 100-CX09...C95* 400
Bulletin 100-CX
ContactorsDimensions
2-13
Dimensions are shown in millimeters.
35m
mDI
Nra
il
Type
Note: C1: 100-CX & 100-FX
100-CX-09, 12
100-CX-18
100-CX-25
100-CX-32, 38
C1 (FX)
100-CX09, 12, 18, 25, 32, 38
AC Operated
Note: C1: 100-CX & 100-FX
T
Type
35m
mD
INra
il
75m
mD
INra
il
100-CX4011, 5011, 6511
100-CX4040, 6540
100-CX8011, 9511
100-CX8040, 9540
C1 (FX)
100-CX40, 50, 65, 80, 95
AC Operated
2
Bulletin 100-CX
ContactorsDimensions
2-14
Note: C1: 100-CX & 100-FX
Type
75m
mD
INra
il
100-CX4011, 5011, 6511
100-CX4040, 6540
100-CX8011, 9511
100-CX9540
C1 (FX)
100-CX40, 50, 65, 80, 95
DC Operated
Dimensions are shown in millimeters.
Type
Note: C1: 100-CX & 100-FX
35m
mDI
Nra
il100-CX09, 12
100-CX18
100-CX25
100-CX32, 38
C1 (FX)
100-CX09, 12, 18, 25, 32, 38
DC Operated
2
Bulletin 104-CX
Reversing ContactorsDimensions
2-15
104-CX40, 65, 80, 95
Unit: mm
75m
mD
INra
ill
Basic model
C1 (FX)
Note: C1: 100-CX & 100-FX
104-CX09, 12
104-CX18
104-CX25
104-CX32, 38
104-CX40, 65
104-CX80, 95
Dimensions are shown in millimeters.
35m
mDI
Nra
il
C1 (FX)
104-CX09, 12, 18, 25, 32, 38
AC Operated
2
Bulletin 193-EX
Electronic Overload RelaysProduct Selection
2-16
Adjustment Range Mounts to Contactor
Manual Reset Auto/Manual Reset
Catalog Number Catalog Number
0.10-0.16 A
100-CX09..38
193-EXDA1C* 193-EXEA1C*
0.16-0.25 A 193-EXDB1C* 193-EXEB1C*
0.25-0.40 A 193-EXDC1C* 193-EXEC1C*
0.40-0.63 A 193-EXDD1C* 193-EXED1C*
0.63-1.0 A 193-EXDE1C* 193-EXEE1C*
1.0-1.6 A 193-EXDF1C* 193-EXEF1C*
1.6-2.5 A 193-EXDG1C* 193-EXEG1C*
2.5-4.0 A 193-EXDH1C* 193-EXEH1C*
4.0-6.0 A 193-EXDJ1C* 193-EXEJ1C*
5.5-8.0 A 193-EXDK1C* 193-EXEK1C*
7.0-10 A 193-EXDL1C* 193-EXEL1C*
9.0-13 A 193-EXDM1C* 193-EXEM1C*
12-18 A 193-EXDN1C* 193-EXEN1C*
17-25 A 193-EXDO1C* 193-EXEO1C*
23-32 A 193-EXDP1C* 193-EXEP1C*
30-40 A 193-EXDQ1C* 193-EXEQ1C*
23-32 A
100-CX40..95
193-EXDP1E* 193-EXEP1E*
30-40 A 193-EXDQ1E* 193-EXEQ1E*
37-50 A 193-EXDR1E* 193-EXER1E*
48-65 A 193-EXDS1E* 193-EXES1E*
55-70 A 193-EXDT1E* 193-EXET1E*
63-80 A 193-EXDU1E* 193-EXEU1E*
80-95 A 193-EXDV1E* 193-EXEV1E*
Supply Voltage Code Table: (*) Insert Supply Voltage (Us) Code
AC (50 Hz)110V 220/230V 380/400V
D F N
Accessories:
Description For Use With Package Quantity Catalog Number
Panel mount adapterfor separate mounting ofthe overload relays, with 35mmDIN rail or panel mount screws
193-EX…C* 1 193-EXPAC
193-EX…E* 1 193-EXPAE
0.1 – 40 A 23 – 95 A
Functionality
• 0.1...95 A
• Electronic motor protection
• Manual or auto reset
• Direct or panel mount
Approvals
• CE, IEC 60947-4
• CCC, GB14048.2
• TUV2
Bulletin 193-EX
Electronic Overload RelaysSpecifications
2-17
The multiple of loaded currentTripping grade 10
The tripping time between the beginning of cold state and the balance among three phasesThe tripping time between the beginning of hot state and the balance among three phases
Class 10 Protection Tripping Characteristic
2
Type 193-EX…C* 193-EX…E*
Current Range Amps 0.1…40A 23…95A
Rated Insulation Voltage V 690V 690V
Operating Voltage V 690V 690V
Operating Frequency Hz 50…60 50…60
Overload Relay Functionality
Trip Class — 10 10
Reset Manual — √ √
Manual/Automatic — √ √
Green LED Indiction Powered — ON ON
Impending Trip — Flash Flash
Tripped — OFF OFF
Phase Loss Protection — 2 secs at 70% phase loss
Phase Unbalance — 4 secs at 50% unbalance
Stop (Red) Button — NC contact opens, NO contact not affected
Test — Reset position to test, NO & NC change state
Power Terminations
Cable Size (Min./Max.)
Stranded Wire w/o Connector mm2 (1) 1.5…10 (1) 4.0…35
Stranded Wire with Connector mm2 (1) 1.0…4.0 (1) 4.0…35
Solid Wire mm2 (1) 1.0…6.0 (1) 4.0…35
Tightening Torque N.m 1.85 9.0
2-18
Bulletin 193-EX
Electronic Overload RelaysDimensions
Type
Type
T
100-CX09, 12
100-CX18
100-CX25
100-CX32
100-CX38
100-CX40, 50, 65
100-CX80, 95
193-EX (0.1...40 A)
Direct Mounted
193-EX (0.1...40 A)
Separate Mount Panel Adapter
193-EX (23...95 A)
Direct Mounted
Dimensions are shown in millimeters.
2
2-19
Bulletin 193-EX
Electronic Overload RelaysDimensions
193-EX (25...95 A)
Separate Mount Panel Adapter
Dimensions are shown in millimeters.
2
2-20
Functionality
• Overload protection Trip Class A
• Phase loss protection
• Ambient temperature compensation
• Auxiliary contact (1 NO and 1 NC)
• Manual/automatic reset
• Optional remote reset solenoidand external reset
• Test release
• Trip indicator
Approvals
• CE, IEC 60947-4
• CCC, GB14048.4
For Use With Setting Range [A] Catalog Number
100-CX09…100-CX18
0.1…0.16 193-TX1AA16
0.16…0.25 193-TX1AA25
0.25…0.40 193-TX1AA40
0.35…0.50 193-TX1AA50
0.45…0.63 193-TX1AA63
0.55…0.80 193-TX1AA80
0.75…1.0 193-TX1AB10
0.90…1.3 193-TX1AB13
1.1…1.6 193-TX1AB16
1.4…2.0 193-TX1AB20
1.8…2.5 193-TX1AB25
2.3…3.2 193-TX1AB32
2.9…4.0 193-TX1AB40
3.5…4.8 193-TX1AB48
4.5…6.3 193-TX1AB63
5.5…7.5 193-TX1AB75
7.2…10 193-TX1AC10
9.0…12.5 193-TX1AC12
11.3…16 193-TX1AC16
15…20 193-TX1AC20
100-CX32…100-CX38
15…20 193-TX1BC20
17.5…21.5 193-TX1BC21
21…25 193-TX1BC25
24.5…30 193-TX1BC30
29…36 193-TX1BC36
33…38 193-TX1BC38
Bulletin 193-TX1
Bimetal Overload RelaysProduct Selection
193-TX1A
2
2-21
Bulletin 193-TX1
Bimetal Overload RelaysAccessories
Description For Use With Package Quantity* Catalog Number
DIN Rail/Panel Mounting AdapterFor separate mounting of overload relaysSnaps on to 35 mm top hat rail
193-TX1AA, 193-TX1AB,193-TX1AC, 193-TX1BC 1 193-TX1APM
Screw AdapterFor screw fixing of the 193-TX1APMpanel adapter (1 required per adapter)
193-TX1APM 10 140M-C-N45
Remote Reset SolenoidFor remote reset of 193-K and193-TX1 overload relays
193-TX1 1 193-T1R⊗
External Reset ButtonFor enclosed, through-the-door resetapplications. Metal construction, IP66,non-illuminated. Refer to the 800Fselection information for additional types.
All 1 800FM-R611
Reset RodLength 142 mm, adjustable range141…159 mm
All 1 800F-ATR08
Reset AdapterExpands the reset target area whenusing an external reset
All 1 193-RA3
[V] 24 48 110 110…120 125 220…240
50/60 Hz KJ KY — KD — KF
DC ZJ ZY ZD — ZS —
* Must be ordered in multiples of package quantity.
⊗ Coil Voltage Codes for Remote Reset Solenoid
2
Catalog Number
Catalog Number
Main Circuits Control Circuits Remote Reset
193-TX1A… 193-TX1BC20…TX1BC25
193-TX1BC30…TX1BC38 193-TX1APM 193-TX1…All 193-TX1R…
Wiring Cross SectionTerminal Type
Terminal Screws M4 M4 M4 M4 M3.5 M3.5
FineStranded with
Ferrule
1 Conductor [mm2]2 Conductors [mm2]
1 x (1.5…4)2 x (1.5…4)
1 x (1.5…4)2 x (1.5…4)
1 x (2.5…10)–
1 x (1.5…10)–
1 x (1…4)2 x (1…4)
1 x (1…2.5)–
Solid orCoarseStranded
1 Conductor [mm2]2 Conductors [mm2]
1 x (1.5…6)2 x (1.5…6)
1 x (1.5…6)2 x (1.5…6)
1 x (2.5…16)–
1 x (1.5…16)–
1 x (1…4)2 x (1…4)
1 x (1…2.5)–
Recommended Torque [N•m] 1.5…2.2 1.5…2.2 2.5…3.5 1.8…2.8 1.2 1.2
Pozidrive Screwdriver Size 2 2 2 2 2 2
Slotted Screwdriver [mm] 0.8 x 5.5 0.8 x 5.5 0.8 x 5.5 0.8 x 5.5 0.8 x 5.5 0.8 x 5.5
Hexagon Socket Screw Size – – – – – –
2-22
Bulletin 193-TX1
Bimetal Overload RelaysSpecifications
Catalog Number 193-TX1…
Rated Isolation Voltage Ui 690V AC
Rated Impulse Withstand Voltage Uimp (between mainpoles and between main poles and auxiliary circuits) 6 kV AC
Rated Impulse Withstand Voltage Uimp(between auxiliary circuits) 4 kV AC
Rated Operating Voltage UeIEC
690V AC
440V AC
UL, CSA 600V AC
Rated Frequencies [Hz] 50/60
Operational Frequencies DC…400 Hz
Power Dissipation 193-TX1A,193-TX1B
Up to 0.4 A 7 W
0.5…20 A 6 W
Catalog Number 193-TX1…
Rated Operating Current Ie
AC-15
24V [A] 4
240V [A] 2
400V [A] 1.6
690V [A] 0.15
DC-13
24V [A] 2
110V [A] 4.
220V [A] 0.25
440V [A] 0.08
Thermal Current Ith 5
Short-CircuitWithstand, Fuse IEC, gL/gG [A] 6
Short-Circuit Withstand, Circuit Breaker ≤1 kA Prospective Short-Circuit-Current [A] 4
Minimum Contact Load for Reliable Operation 15V, 2 mA
Thermal Overload RelaysMain Circuits Control Circuits
2
2-23
Bulletin 193-TX1
Bimetal Overload RelaysSpecifications
Catalog Number 193-TX1…
Type of Overload Relay Bimetallic, Ambient Compensated,Phase Loss Sensitive
Trip Rating (ultimate tripping current) 120% FLA
Phase Loss Sensitivity: Trip Rating at Phase Loss 115% FLA
Trip Class IEC/EN 60947-4-1 10 A
UL 10
Reset Mode Automatic or Manual
Test Release Manual Release of Auxiliary Contacts
Trip Indication By Means of a Flag Visible Through anOpening in the Relay Front
Compensation Temperature Range -20…+60 ˚C (-4…+140 ˚F)
Climatic Conditions
Release Tolerance at -20 ˚C 1.05…1.4 x In
Storage Temperature Range -55…+80 ˚C (-67…+176 ˚F)
Operating Temperature Range -20…+60 ˚C (-4…+140 ˚F)
Air Moisture (storage/operating) 5…95% Relative Humidity,Non-condensing
Vibration
(per IEC/EN 60068-2-6), Service 3 g
IEC/EN 61373 (vibration railways) Category 1, Class B
IEC/EN 60092-504 (vibration ships), Service 0.7 g, all Axes, 2…200 Hz
Shock
(per IEC/EN 68000-2-27), Transport 30 g
IEC/EN 60068-2-27 (shock half-sinus), Service 11 ms > 5 g all Axes
IEC/EN 61373 (shock railways) Category 1, Class B, 5 g 30 ms
Maximum Altitude 2,000 m
Pollution Degree 3
Degree of Protection, with Wires Connected IP2X
Materials RoHS Compliant
Flame Resistivity (outer housing parts) UL-94 V0
Approximate Weight (unpackaged)
193-TX1A, 193-TX1B 0.16…25 A 0.115 kg
193-TX1B 30…38 A 0.155 kg
193-TX1…P 47…90 A 0.415 kg
2
2-24
+ -
+ -
DC
Bulletin 193-TX1
Bimetal Overload RelaysSpecifications
Circuit Diagrams
Trip Characteristics
Catalog Numbers193-TX1AB48…AC25Overload Relays
2
(a)
(b)
Catalog Numbers193-TX1BC20…BC25Overload Relays
(a)
(b)
Catalog Numbers193-TX1BC30…BC38Overload Relays
(a)
(b)
Tripping Time [s]
Multiple of the Set Current [Ie]
Bulletin 100-DX Contactors193-TX Bimetal Overload Relays
Product Overview..............................................................................................................................3-2
Product Selection..............................................................................................................................3-4
Specifications ....................................................................................................................................3-7
Trip Curves.........................................................................................................................................3-9
Dimensions ......................................................................................................................................3-11
Bulletin 100-DX, 193-TX
Contactors & Bimetal Overload RelaysSection Overview
3-1
3
Bulletin 100-DX, 193-TX
Contactors & Bimetal Overload RelaysProduct Overview
3-2
Note: This table is for catalog number explanation. It should not be used for configuration purposes.
100-DX 150 KF 22 (A)
Bulletin/Product LineDX – Large Contactors
Series Letter
Coil Code *KD – 110V 50/60 HzKF – 220V 50/60 HzKL – 230V 50/60 HzKE – 380V 50/60 HzKN – 400V 50/60 HzKG – 415V 50/60 HzKB – 440V 50/60 Hz
Current Rating3 Pole – AC3
115 A
135 A
150 A
180 A
220 A
300 A
Auxiliary Contacts
22 – 2 NO/2 NC
Catalog Number Explanation – 100-DX
100-DX115...135 100-DX150...180 100-DX220...3003
Bulletin 100-DX, 193-TX
Contactors & Bimetal Overload RelaysProduct Overview
3-3
Note: This table is for catalog number explanation. It should not be used for configuration purposes.
193-TXD A 95 (A)
Bulletin/Product Line
TXD – Large Bimetal OLR
Series Letter
Frame SizeA – For use with D115 & D135 ContactorsB – For use with D150 ContactorC – For use with D180 ContactorD – For use with D180 & D220 ContactorsE – For use with D220 & D300 Contactors
Catalog Number Explanation – 193-TX
Max. Current Rating95 – 95 A125 – 125 A160 – 160 A185 – 185 A200 – 200 A240 – 240 A280 – 280 A338 – 338 A
193-TXDA... 193-TXDD... 193-TXDE...3
Bulletin 100-DX
ContactorsProduct Selection
3-4
Maximum Ie[A]
Ratings for Switching AC Motors
AC-3, AC-4 Direct-on-Line
kW (50 Hz) 3 Pole
3 Phase Aux. Contacts
Catalog NumberAC-140 ˚C
AC-360 ˚C 220/230V 380/400V 415V 440V 500V 660/690V NO NC
135 115 30 60 60 60 65 65 2 2 100-DX115*22
150 138 40 75 75 75 75 75 2 2 100-DX135*22
200 150 45 80 80 80 90 100 2 2 100-DX150*22
240 180 55 95 100 110 110 110 2 2 100-DX180*22
260 220 65 120 125 132 132 132 2 2 100-DX220*22
350 300 90 160 160 160 160 200 2 2 100-DX300*22
Coil Voltage Selection Table: (*) Insert Coil Code
AC 110V 220V 230V 380V 400V 415V 440V
50/60 Hz KD KF KL KE KN KG KB
Contact Allen-Bradley for other coil voltages.
Functionality
• 115...300 A – AC-3
• 3 pole
• AC operated
• 2NO/2NC auxiliary contacts
Approvals
• CE, IEC 60947-4
• CCC, GB14048.4
100-DX115...135 100-DX150...180 100-DX220...3003
3-5
Bulletin 100-DX
Contactor AccessoriesProduct Selection
Description Type For use with Pack Qty. Catalog Number
Auxiliary Contacts SideMount – 2 Pole 1 NO/1 NC 100-DX115...300 1 100-DXSA11
Terminal Covers IP20 Finger Safe ProtectionScrew Fixing
100-DX115...135
1
100-DXTC135
100-DX150...180 100-DXTC180
100-DX220...300 100-DXTC300
Mechanical Interlock for usein reversing, star-delta andchangeover assemblies
Mechanical Interlock 100-DX115...300 1 100-DXM00
Accessories:
Renewal Parts:
Description Type For use with Pack Qty. Catalog Number
Coils
110V 50/60 Hz
100-DX115 & 135 1
100-DX4CKD
220V 50/60 Hz 100-DX4CKF
230V 50/60 Hz 100-DX4CKL
380V 50/60 Hz 100-DX4CKE
400V 50/60 Hz 100-DX4CKN
415V 50/60 Hz 100-DX4CKG
440V 50/60 Hz 100-DX4CKB
110V 50/60 Hz
100-DX150 & 180 1
100-DX5CKD
220V 50/60 Hz 100-DX5CKF
230V 50/60 Hz 100-DX5CKL
380V 50/60 Hz 100-DX5CKE
400V 50/60 Hz 100-DX5CKN
415V 50/60 Hz 100-DX5CKG
440V 50/60 Hz 100-DX5CKB
110V 50/60 Hz
100-DX220 & 300 1
100-DX6CKD
220V 50/60 Hz 100-DX6CKF
230V 50/60 Hz 100-DX6CKL
380V 50/60 Hz 100-DX6CKE
400V 50/60 Hz 100-DX6CKN
415V 50/60 Hz 100-DX6CKG
440V 50/60 Hz 100-DX6CKB
3
Bulletin 193-TX
Bimetal Overload Relays & AccessoriesProduct Selection
3-6
Description Functions Adjustment Range For use with Catalog Number
Bimetal Overload Relays
1 N0/1 NC ContactsClass 10
Manual/Auto ResetDirect or Separate Mount
65…95 A
100-DX115...135
193-TXDA95
85…125 A 193-TXDA125
110…160 A 193-TXDA160
65…95 A
100-DX150
193-TXDB95*
85…125 A 193-TXDB125*
110…160 A 193-TXDB160
110…160 A100-DX180
193-TXDC160*
125…185 A 193-TXDC185
110…160 A
100-DX220
193-TXDD160*
125…185 A 193-TXDD185*
175…240 A 193-TXDD240
145…200 A
100-DX300
193-TXDE200*
203…280 A 193-TXDE280
245…336 A 193-TXDE336
193-TXDA... 193-TXDE...
Functionality
• 65...336 A
• Bimetal overload relays
• Direct mount or separate
• Auxiliary & trip contacts
• Manual or auto Reset
• Trip class 10
Approvals
• CE, IEC 60947-4
• CCC, GB14048.4
193-TXDC...
* Special order with extended lead times.
3
Bulletin 100-DX
Contactors & AccessoriesSpecifications
3-7
Contactor Size 100-DX115 100-DX135 100-DX150 100-DX180 100-DX220 100-DX300
Conformance to Standards IEC 60947-4-1, GB947-4
Power Ratings
No. of Poles 3 3 3 3 3 3
Rated Insulation Voltage (Ui) 1000V 1000V 1000V 1000V 1000V 1000V
Rated Impulse Withstand Voltage (Uimp) 8 kV 8 kV 8 kV 8 kV 8 kV 8 kV
Rated Operational Voltage 690V 690V 690V 690V 690V 690V
Rated Operation Current – AC1 (Ie) 135 A 150 A 200 A 240 A 260 A 350 A
Rated Operation Current – AC3 (Ie) 115 A 138 A 150 A 180 A 220 A 300 A
Motor Ratings – AC3 (kW) 220/230V 30 40 45 55 65 90
380/400V 60 75 80 95 120 160
415V 60 75 80 100 125 160
440V 60 75 80 110 132 160
500V 65 75 90 110 132 160
690V 65 75 100 110 132 200
Motor Ratings – AC3 (A) 220/230V 115 138 150 182 225 300
380/400V 115 138 147 179 225 300
415V 105 138 138 182 220 300
440V 105 135 131 178 220 300
500V 93 105 129 156 190 250
690V 75 85 107 118 140 220
Rated Making Capacity 10 x Ie 10 x Ie 10 x Ie 10 x Ie 10 x Ie 10 x Ie
Rated Breaking Capacity 8 x Ie 8 x Ie 8 x Ie 8 x Ie 8 x Ie 8 x Ie
Maximum Operating Rate (AC-3) (Ops/h) 1200 1200 1200 1200 1200 1200
Electrical Life (AC-3) (Mio) 1.0 1.0 1.0 1.0 1.0 1.0
Mechanical Life (Mio) 5.0 5.0 5.0 5.0 5.0 5.0
Weight (Kg) 2.2 2.2 4.1 4.1 6.7 6.7
Control Circuit
Rated Insulation Voltage (Ui) 690V
Rated Operational Voltage 690V
Rated Current (Ith) 10 A
Rated Operational Current AC15
110…120V 6 A
220…240V 3 A
380…415V 1.9 A
440V 1.5 A
500V 1.4 A
Rated Operational Current DC13
125V 0.55 A
250V 0.27 A
Coil Characteristics
Operational Voltage – 50/60 Hz 24…600V
IEC Operating Range 85…110%
Minimum Pick-up Voltage (% Us) 70% 75% 75%
Drop-out Voltage (% Us) 60% 45% 45%
Coil Consumption (Max.) Inrush VA 560 700 1050
Hold-in VA 45 70 70
Power Dissipation (W) 5…12 5…12 9…17 9…17 9…17 9…17
Environmental
Storage Temperature -40…+70 ˚C
Operating Temperature -20…+55 ˚C
Relative Humidity 45…85%
Operating Altitude Below 2,000 m
Operating Position ±30 ˚C
3
Bulletin 193-TX
Bimetal Overlay RelaysSpecifications
3-8
Overload Relay Size 193-TXDA 193-TXDB, TXDC 193-TXDD, TXDE
Conformance to Standards IEC 60947-2, GB947-4
Power Ratings
Current Adjustment Ranges 65...95 A 65...95 A 125...185 A
85...125 A 85...125 A 175...240 A
110...160 A 110...160 A 145...200 A
125...185 A 203...280 A
245...336 A
Mounting Direct X X X
Separate X X X
Suitable for Contactor Mounting 100-DX115, DX135 100-DX150, DX180 100-DX220, DX300
Rated Insulation Voltage Ui 690V 690V 690V
Rated Impulse Voltage Uimp 6 kV 6 kV 6 kV
Protection Characteristics
Trip Class 10 10 10
Reset Mode Manual/Auto Adjustable Manual/Auto Adjustable Manual/Auto Adjustable
Stop Function X X X
Phase Loss Protection X X X
Ambient Temperature Compensation X X X
Control Circuit
Auxiliary Contacts 1 NO + 1 NC 1 NO + 1 NC 1 NO + 1 NC
Auxiliary Contact Ratings AC15
DC13
Ith
24V 6 A 6 A 10 A
110V 6 A 6 A 6 A
220V 3 A 3 A 3 A
380/415V 1.9 A 1.9 A 1.9 A
500V 1.4 A 1.4 A 1.4 A
125V 0.55 A 0.55 A 0.55 A
250V 0.27 A 0.27 A 0.27 A
NO 6 A 6 A 10 A
NC 6 A 6 A 10 A
Termination
Maximum Terminal CapacityAux Contact (2) 2.5 mm2 (2) 2.5 mm2 (2) 2.5 mm2
Power Pole 60 mm2 100 mm3 60…250 mm2
Terminal Hole Size 8.4 mm 8.4 mm / 10.5 mm 10.5 mm
Terminal Bolt M8 M8 / M10 M10
Maximum Terminal TorqueAux. Contact 0.6...0.9 N•m 0.6...0.9 N•m 0.6...0.9 N•m
Power Pole 8.3...11.8 N•m 16.7...24.5 N•m / 17...22.5 N•m
Environmental
Service Temperature -5…+55 ˚C -5...+55 ˚C -5...+55 ˚C
Storage Temperature -40...+70 ˚C -40...+70 ˚C -40...+70 ˚C
Relative Humidity 45...85% 46...85% 47...85%
Altitude < 2,000 m < 2,000 m < 2,000 m
3
Bulletin 193-TX
Bimetal Overlay RelaysTrip Curves
3-9
1x
Multiples of FLA Current Setting
Trip
Tim
e(S
ec)
193-TXDA (3 Phase Protection)
0.1
0.5
1
5
10
Hot Start
Cold Start
50
100
500
1000
2x 3x 4x 5x 6x 7x 8x
3
Bulletin 193-TX
Bimetal Overlay RelaysTrip Curves
3-10
1x
Multiples of FLA Current Setting
Trip
Tim
e(S
ec)
193-TXB, 193-TXC (3 Phase Protection)
0.1
0.5
1
5
10
Hot Start
Cold Start
50
100
500
1000
2x 3x 4x 5x 6x 7x 8x
3
Bulletin 100-DX
ContactorsDimensions
3-11
Dimensions are shown in millimeters.
100-DX115...100-DX135...
100-DX150...100-DX180...
3
Bulletin 100-DX
ContactorsDimensions
3-12 Visit our website: www.ab.com/catalogs
100-DX220...100-DX300...
3
Bulletin 193-TX
Bimetal Overload RelaysDimensions
3-13Visit our website: www.ab.com/catalogs
193-TXDA...
193-TXDB...
100
3
102
6419
105
8010
58
4
RESET STROKE 4mm
33 33
23
100
4.5
102
78
19
105
85.2
10
58
4
RESET STROKE 4mm
33 33
23
3
Bulletin 193-TX
Bimetal Overload RelaysDimensions
3-14 Visit our website: www.ab.com/catalogs
193-TXDC...
94
137
119
4.5
105
85.2
10
33 33
25
46.5
4
RESET STROKE 4mm
79.5
25
193-TXDD...193-TXDE...
48
158.50 136.50
150 185
48
37.30
68 147.20
48
134
48
63.7572.25
3
Bulletin 700-CFX Control RelaysProduct Overview..............................................................................................................................4-2
Product Selection..............................................................................................................................4-3
Specifications ....................................................................................................................................4-5
Dimensions ........................................................................................................................................4-6
Bulletin 700-CFX
Control RelaysSection Overview
4-1
4
Bulletin 700-CFX
Control RelaysProduct Overview
4-2
Note: This table is for catalog number explanation. It should not be used for configuration purposes.
700-CFX – 400 D (A)
Bulletin/Product Line700-CFX – Control Relays
Contact Arrangement400 – 4 NO310 – 3 NO/1 NC220 – 2 NO/2 NC
Series Letter
Control Voltage
K – 24V 50 Hz
D – 110V 50 Hz
KF – 220…230V 50/60 Hz
N – 380...400V 50 Hz
G – 415V 50 Hz
B – 440V 50 Hz
ZJ – 24V DC
Catalog Number Explanation – 700-CFX
700-CFX
4
AC-12 AC-15
Connection Diagrams
Contacts
Catalog Number
Ith [A] Ith [A]
40 ˚C 60 ˚C 24V 110V 230V 415V NO NC
10 5 10 3.5 1.7 .95 4 0 700-CFX400*
10 5 10 3.5 1.7 .95 3 1 700-CFX310*
10 5 10 3.5 1.7 .95 2 2 700-CFX220*
Bulletin 700-CFX
Control RelaysProduct Selection
4-3
700-CFX400*
Coil Voltage Selection Table: (*) Insert Coil Code
AC50 Hz
24V 110V 220…230V 380...400V 415V 440V
K D K F [1] N G B
DC 24V 48V 110V 220V — —
ZJ ZY ZD ZF — —
Contact Allen-Bradley for other control voltages.[1] 50/60 Hz
Functionality
• 4 pole
• AC & DC coils
• Field installed accessories
Approvals
• CE, IEC 60947-5
• CCC, GB14048.5
4
4-4
Bulletin 700-CFX
Control RelaysProduct Selection
Description Type For Use With Pack Qty Catalog Number
Auxiliary ContactsFront Mount – 4 Pole
4 NO
700-CFX
1 100-FX40
3 NO/1 NC 1 100-FX31
2 NO/2 NC 1 100-FX22
1 NO/3 NC 1 100-FX13
4 NC 1 100-FX04
Auxiliary ContactsFront Mount – 2 Pole
2 NO
700-CFX
1 100-FX20
1 NO/1 NC 1 100-FX11
2 NC 1 100-FX02
Auxiliary ContactsSide Mount – 2 Pole
2 NO
700-CFX
1 100-FXS20
1 NO/1 NC 1 100-FXS11
Pneumatic Timer“ON Delay”
0.1...3.0 sec.
700-CFX 1
100-PTXN3
0.1...30 sec. 100-PTXN30
0.1...180 sec. 100-PTXN180
Pneumatic Timer“OFF Delay”
0.1...3.0 sec.
700-CFX 1
100-PTXF3
0.1...30 sec. 100-PTXF30
0.1...180 sec. 100-PTXF180
Surge SuppressorMOV – Plug-in Mount
24...48V AC/DC
700-CFX
1 100-FXPM48
50...127V AC/DC 1 100-FXPM127
110...240V AC/DC 1 100-FXPM240
Surge SuppressorMOV – Insert Mount
24...48V AC/DC
700-CFX
1 100-FXTM48
50...127V AC/DC 1 100-FXTM127
110...240V AC/DC 1 100-FXTM240
380...415V AC/DC 1 100-FXTM415
Surge SuppressorRC – Insert Mount
24...48V AC
700-CFX 1
100-FXTR48
50...127V AC 100-FXTR127
110...240V AC 100-FXTR240
Surge SuppressorDiode – Insert Mount 24...40V DC 700-CFX 1 100-FXTD220
4
4-5
Bulletin 700-CFX
Control RelaysSpecifications
Contactor Size 700-CFX400, 310, 220 (AC) 700-CFX400Z, 310Z, 220Z (DC)
Rated Insulating Voltage, Ui V 690
Rated Working Voltage, Ue V AC 380 DC 220
Set Heating Current Ith A 10
Rated WorkingCurrent Ie A
AC-15 (400V) 0.95
DC-13 (220V) 0.15
Minimum Load Connected (reliable operation) 24V 10 mA
Rated Operating Frequency (Ops/h) 2,400
Mechanical Life (Mio) 10
Electrical Life (Mio) 1.2
Coil Data
Rated Controlling Voltage Us V AC 50 Hz, 50 Hz/60 Hz, 60 Hz24, 48, 110, 220, 380 DC: 24, 48, 110, 220
Pick-up Voltage 85% Us ~ 110% Us
Drop-out Voltage 20% Us ~ 75% Us 10% Us ~ 75% Us
Pick-up Power 76VA 11W
Maintaining Power 9.4VA 11W
Voltage Enduring Capacity 2,500V/1 min.
Switching Time of Permanently Open/Close 1.5 ms
Technical Data
Operational Time NO Making 15 ~ 22 ms NO Opening 5 ~ 15 ms
NC Making 9 ~ 22 ms NC Opening 7 ~ 20 ms
Short Time Withstand Rating 1 s 100 A
500 ms 120 A
100 ms 180 A
Terminal Capacitymm2 Stranded 1 or 2 Wires 2.5
Solid 1 or 2 Wires 4
4
Bulletin 700-CFX
Control RelaysSpecifications & Dimensions
4-6
700-CFX Wiring Diagram (AC & DC)
Dimensions
Type b1 Cmax C1
700-CFX400, 310, 220 (AC) – 84 115
700-CFX400, 310, 220 (DC) 45~50 119 145
700-CFX400... 700-CFX310... 700-CFX220...
C1 + AUX
4
Publication OEMCOMPONENTSIC-SG004A-EN-P – April 2012 Copyright ©2012 Rockwell Automation, Inc. All Rights Reserved. Printed in USA.