FieldCare™ Advisory Note

FieldCare

via

HART Multiplexer

Page 2: Fieldcare

Endress+Hauser Process Solutions AG

AN002S/04/en/10.04

Page 2 /16

Table of Contents:

Page

Overview……………………………………………………………………………3

Components………………………………………………………………………...4

Hardware Configuration……………..……………………………………………..4

Wiring……………………………………………………………………………….5

General Description…………………………………………………………………5

Screenshots and Step by Step Instruction………………………………………….6

Final Screenshot from our Tests……………………………………………………16

Additional Notes…………………………………………………………………….16

Please observe all local and national regulations concerning all electrical and process control

regulations.

While all attempts have been made to ensure that the information within is complete and accurate

the Author takes no responsibility for any errors within.

!

!

Page 3: Fieldcare

Endress+Hauser Process Solutions AG

AN002S/04/en/10.04

Page 3 /16

Overview:

Figure #1 – System Overview.

RS232

RS485

4…20mA HART

RNS221

Cerabar S

Page 4: Fieldcare

Endress+Hauser Process Solutions AG

AN002S/04/en/10.04

Page 4 /16

Components:

In the tests we carried out the following components were used.

Description Manufacturer Order No.

KFD2-HMM-16 HART Multiplexer Master Pepperl+Fuchs 52017691

K-HM-26-US Ribbon Cable Pepperl+Fuchs 52017687

FI-DO-R-Y41610 Connecting Board Pepperl+Fuchs 52017690

Software FieldCare Standard Endress+Hauser SFE551-DTAS

Field Devices Pressure Transmitter Endress + Hauser PMC731-U53P6M11G1

RS232 Cable DB9 Female to DB25 Male

AT Modem Cable

www.StarTech.com MC6MF

Converter RS232 to RS485 optical

isolator and converter

Black Box IC1660A

Table #1 – Equipment List.

Hardware Configuration:

• Pepperl+Fuchs HART Multiplexer Master

Power Supply: Permissible operating voltage 20 – 32 V

Operating current 100 mA typical

Dipswitch Settings (#1 – 8): 01000010b (where 1 = ON; 0 = OFF)

• Black Box RS232 to RS485 Optical Converter IC1660A

Power Supply: Wall mounted power supply included 120 VAC to 12VDC

Operating current <500 mA typical

Dipswitch Settings (#1 – 8): 00011110b (where 1 = ON; 0 = OFF)

JP1 (jumper): SD

Page 5: Fieldcare

Endress+Hauser Process Solutions AG

AN002S/04/en/10.04

Page 5 /16

Black Box

IC1660A

Pepperl+Fuchs

KFD2-HMM-16

T- (14)

T+ (15)

Grd (13)

Figure #2 - Wiring diagram of Converter to Multiplexer

General Description:

New installations may require HART multiplexers to enable remote field device management using

FieldCare. Similarly this configuration will work with existing HART Multiplexers with minimal

differences to the procedure.

The HART Multiplexer may be used in conjunction with a PLC or DCS. Pay special attention to

whether the AI or AO cards are already equipped with 250 Ohm HART Communication resistors.

This example will work when the AI or AO card do not have internal HART communication resistors.

The P+F interconnection board FI-DO-Y37023 (E+H SAP# 52017689) is designed to be used with

AI or AO cards that have internal HART communication resistors.

According to RS485 it is possible to have 32 nodes connected with cable distances of about 1200

m. For more facts on RS485 visit http://www.hw.cz/english/docs/rs485/rs485.html

Page 6: Fieldcare

Endress+Hauser Process Solutions AG

AN002S/04/en/10.04

Page 6 /16

Screenshots and Step by Step Instruction:

Step 1: With FieldCare Standard Release 3, version 2.01.00, installed ADD NEW DEVICE, and select

the HART OPC Client Comm DTM as shown.

Figure #2 – Add CommDTM HART OPC Client.

Step 2: The following warning pop-up will occur because the HART OPC Server has not been

connected yet.

Figure #3 – Warning pop-up box.

Page 7: Fieldcare

Endress+Hauser Process Solutions AG

AN002S/04/en/10.04

Page 7 /16

Step 3: With the right mouse button select Additional Functions> Open HART Server.

Figure #4 – Open the HART Server.

Step 4: Configure the HART OPC Server by building the network topology. With the right mouse

button ADD Network…

Figure #5 – Start building the network topology in the HART OPC Server.

Page 8: Fieldcare

Endress+Hauser Process Solutions AG

AN002S/04/en/10.04

Page 8 /16

Step 5: Select the Network type to be Serial Port RS-485.

Figure #6 – Select Network Type.

Step 6: Name the Network (Eg. P+F_MUX), set the Network Properties (Eg. COM1 & Baudrate. Pay

attention to the baudrate settings on the hardware as well!

Figure #7 – Network Properties.

Page 9: Fieldcare

Endress+Hauser Process Solutions AG

AN002S/04/en/10.04

Page 9 /16

Step 7: Add the Multiplexer to the topology using the right mouse button.

Figure #9 – Add the Multiplexer.

Step 8: Configure the Multiplexer settings. Pay attention to the multiplexer dipswitches especially

those for the addressing as this is where you determine what address to set in this step.

Figure #10 – Set the Multiplexer address.

Page 10: Fieldcare

Endress+Hauser Process Solutions AG

AN002S/04/en/10.04

Page 10 /16

Step 9: The following Multiplexer Properties will be displayed after the Server scans the network.

This means you should by now have all of the wiring completed and all interconnections finalized.

No changes to this pop-up window were required in this test setup!

Figure #11 – Default multiplexer properties – No changes were required!

Page 11: Fieldcare

Endress+Hauser Process Solutions AG

AN002S/04/en/10.04

Page 11 /16

Step 10: Using the right mouse button Add Instrument…

Figure #12 – Add instrument.

Step 11: The following default Instrument Properties box pops up! Just click OK. No settings changes

are required.

Figure #13 – Instrument Properties.

Page 12: Fieldcare

Endress+Hauser Process Solutions AG

AN002S/04/en/10.04

Page 12 /16

Step 12: If you have followed the above steps you should similar resulting screens as shown in

Figures 14 & 15 respectively .

Figure #14 – Channel 1 of the P+F Mux is shown. Channel one represents the

terminals 1 + 2 on the interconnection board.

Figure #15 – Shows that a Cerabar S is connected to Channel 1.

Page 13: Fieldcare

Endress+Hauser Process Solutions AG

AN002S/04/en/10.04

Page 13 /16

Step 13: Save the settings just completed by selecting FILE> SAVE As…

Figure #16 – Save the HART OPC Server profile.

Figure #17 – The SAVE As… dialogue box.

Step 14: Close the HART OPC Server, then close the open FieldCare Project. Open a new FieldCare

“Empty Project” then add the CommDTM HART OPC Client. As shown in Figure #2.

Page 14: Fieldcare

Endress+Hauser Process Solutions AG

AN002S/04/en/10.04

Page 14 /16

Step 15: Highlight the HART OPC Client then select CREATE NETWORK. FieldCare will now scan

all of the channels on the connected mux for devices then attach the corresponding DTM as long as

they are available in the DTM catalogue.

Figure #18 – Create a new network.

Figure #19 – First observation after selecting Create Network.

Page 15: Fieldcare

Endress+Hauser Process Solutions AG

AN002S/04/en/10.04

Page 15 /16

Figure #20 – Second observation after selecting Create Network.

Figure #21 – Highlight the new device DTMs found by performing the CREATE

NETWORK scan then toggle them ON.

Page 16: Fieldcare

Endress+Hauser Process Solutions AG

AN002S/04/en/10.04

Page 16 /16

Final Screenshot from our Tests: Select an “On Line” device then double click on it to open the Online Parameterize screen.

Figure #22 – Device Configuration & Plant Asset Management is now possible.

Additional Notes:

Attached at the end of this document are the data sheets for the P+F Mux & the BlackBox RS485

coverter