wr2 series g10 2nd · 2019. 2. 6. · hic circuit (hic: heat inter-changer) - - drawing external...
TRANSCRIPT
2 - 423
WR2 SERIES G10 2nd
HEAT SOURCE UNITS
HEAT SOURCE UNITSI.WR2 SERIES
1. SPECIFICATIONS........................................................................................................................................... 2 - 424
2. EXTERNAL DIMENSIONS .............................................................................................................................. 2 - 431
3. CENTER OF GRAVITY ................................................................................................................................... 2 - 433
4. ELECTRICAL WIRING DIAGRAMS ................................................................................................................ 2 - 434
5. SOUND LEVELS ............................................................................................................................................. 2 - 435
6. CAPACITY TABLES ........................................................................................................................................ 2 - 4376-1. Correction by temperature ....................................................................................................................... 2 - 4376-2. Correction by total indoor......................................................................................................................... 2 - 4456-3. Correction by refrigerant piping length..................................................................................................... 2 - 4496-4. Correction by port counts of the BC controller ......................................................................................... 2 - 4506-5. Operation temperature range .................................................................................................................. 2 - 451
7. SYSTEM DESIGN GUIDE............................................................................................................................... 2 - 4527-1. Designing of water circuit system ............................................................................................................ 2 - 4527-2. Water piping work .................................................................................................................................... 2 - 464
8. OPTIONAL PARTS.......................................................................................................................................... 2 - 4668-1. JOINT ...................................................................................................................................................... 2 - 4668-2. OUTDOOR TWINNING KIT..................................................................................................................... 2 - 4678-3. JOINT KIT "CMY-R160-J1" FOR BC CONTROLLER ............................................................................. 2 - 468
1. SPECIFICATIONS G10 2nd
HEAT SOURCE UNITS 2 - 424
WR
2
I.WR2 SERIES1. SPECIFICATIONS
Model PQRY-P200YHM-A PQRY-P250YHM-A Power source 3-phase 4-wire 380-400-415V 50/60Hz 3-phase 4-wire 380-400-415V 50/60Hz
Cooling capacity *1 kW 22.4 28.0
(Nominal) *1 kcal / h 19,300 24,100*1 BTU / h 76,400 95,500
Power input kW 3.96 5.51
Current input A 6.6-6.3-6.1 9.3-8.8-8.5EER kW / kW 5.65 5.08
Temp. range of Indoor W.B. 15.0 ~ 24.0°C(59 ~ 75°F) 15.0 ~ 24.0°C(59 ~ 75°F)
cooling Circulating water °C 10.0 ~ 45.0°C(50 ~ 113°F) 10.0 ~ 45.0°C(50 ~ 113°F) Heating capacity *2 kW 25.0 31.5
(Nominal) *2 kcal / h 21,500 27,100
*2 BTU / h 85,300 107,500Power input kW 4.12 5.80
Current input A 6.9-6.6-6.3 9.7-9.3-8.9
COP kW / kW 6.06 5.43
Temp. range of Indoor D.B. 15.0 ~ 27.0°C(59 ~ 81°F) 15.0 ~ 27.0°C(59 ~ 81°F) heating Circulating water °C 10.0 ~ 45.0°C(50 ~ 113°F) 10.0 ~ 45.0°C(50 ~ 113°F)
Indoor unit Total capacity 50 ~ 150 % of heat source unit capacity 50 ~ 150 % of heat source unit capacity
connectable Model / Quantity P15 ~ P250 / 1 ~ 20 P15 ~ P250 / 1 ~ 25 Sound pressure level (measured in anechoic room) dB <A> 47 49
Refrigerant High pressure mm (in.) 15.88(5/8) Brazed 19.05(3/4) Brazed
piping diameter Low pressure mm (in.) 19.05(3/4) Brazed 22.2(7/8) BrazedCirculating water Water flow rate m3 / h 5.76 5.76
L / min 96 96
cfm 3.4 3.4Pressure drop kPa 17 17
Operating volume range m3 / h 4.5 ~ 7.2 4.5 ~ 7.2
Compressor Type x Quantity Inverter scroll hermetic compressor Inverter scroll hermetic compressor
Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION AC&R Works, MITSUBISHI ELECTRIC CORPORATION
Starting method Inverter InverterMotor output kW 4.6 6.3
Case heater kW 0.035(240 V) 0.035(240 V)
Lubricant MEL32 MEL32 External finish Acrylic painted steel plate Acrylic painted steel plate
External dimension HxWxD mm 1,160(1,100 without legs) x 880 x 550 1,160(1,100 without legs) x 880 x 550
in. 45-11/16(43-5/16 without legs) x 34-11/16 x 21-11/16 45-11/16(43-5/16 without legs) x 34-11/16 x 21-11/16
Protection devices High pressure protection High pressure sensor, High pressure switch at 4.15MPa (601 psi)
High pressure sensor, High pressure switch at 4.15MPa (601 psi)
Inverter circuit (COMP.) Over-heat protection, Over-current protection Over-heat protection, Over-current protectionCompressor Over-heat protection Over-heat protection
Refrigerant Type x original charge R410A x 5.0kg (12lbs) R410A x 5.0kg (12lbs)
Control Indoor LEV and BC controller Indoor LEV and BC controller Net weight kg (lbs) 181(400) 181(400)
Heat exchanger plate type plate type
Water volume in plate I 5.0 5.0Water pressure Max. MPa 2.0 2.0
HIC circuit (HIC: Heat Inter-Changer) - -
Drawing External KB94T146 KB94T146Wiring KE94C302 KE94C302
Standard attachment Document Installation Manual Installation Manual
Accessory Refrigerant conn. pipe Refrigerant conn. pipe Optional parts Joint: CMY-Y102SS-G2,CMY-Y102LS-G2,CMY-Y202S-G2,
CMY-R160-J1Joint: CMY-Y102SS-G2,CMY-Y102LS-G2,CMY-Y202S-G2,
CMY-R160-J1
BC controller: CMB-P104, 105, 106, 108, 1010, 1013,1016V-G1
BC controller: CMB-P104, 105, 106, 108, 1010, 1013, 1016V-G1
Main BC controller: CMB-P108,1010,1013,1016V-GA1Sub BC controller: CMB-P104,108V-GB1,CMB-P1016V-HB1
Main BC controller: CMB-P108,1010,1013,1016V-GA1Sub BC controller: CMB-P104,108V-GB1,CMB-P1016V-HB1
Remarks .Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the Installation Manual..Due to continuing improvement, above specifications may be subject to change without notice..The ambient temperature of the heat source unit needs to be kept below 40°C D.B..The ambient relative humidity of the heat source unit needs to be kept below 80%..The heat source Unit should not be installed at outdoor..Be sure to mount a strainer (more than 50 meshes) at the water inlet piping of the unit..Be sure to provide interlocking for the unit operation and water circuit.
Notes: Unit converter
1. Nominal cooling conditions (subject to JIS B8615-2) kcal/h =kW x 860Indoor: 27°CDB/19°CWB (81°FDB/66°FWB), Water temperature: 30°C (86°F) BTU/h =kW x 3,412
Pipe length: 7.5m (24-9/16ft.), Level difference: 0m (0ft.) cfm =m3/min x 35.31
2. Nominal heating conditions (subject to JIS B8615-2) lbs =kg/0.4536Indoor: 20°CDB (68°FDB), Water temperature: 20°C (68°F)
Pipe length: 7.5m (24-9/16ft.), Level difference: 0m (0ft.) *The specification data is
subject to rounding variation.
2 - 425
1. SPECIFICATIONS G10 2nd
HEAT SOURCE UNITS
WR
2
Model PQRY-P300YHM-A Power source 3-phase 4-wire 380-400-415V 50/60Hz Cooling capacity *1 kW 33.5 (Nominal) *1 kcal / h 28,800
*1 BTU / h 114,300Power input kW 7.44Current input A 12.5-11.9-11.5EER kW / kW 4.50
Temp. range of Indoor W.B. 15.0 ~ 24.0°C(59 ~ 75°F) cooling Circulating water °C 10.0 ~ 45.0°C(50 ~ 113°F) Heating capacity *2 kW 37.5 (Nominal) *2 kcal / h 32,300
*2 BTU / h 128,000Power input kW 8.15Current input A 13.7-13.0-12.5COP kW / kW 4.60
Temp. range of Indoor D.B. 15.0 ~ 27.0°C(59 ~ 81°F) heating Circulating water °C 10.0 ~ 45.0°C(50 ~ 113°F) Indoor unit Total capacity 50 ~ 150 % of heat source unit capacity connectable Model / Quantity P15 ~ P250 / 1 ~ 30 Sound pressure level (measured in anechoic room) dB <A> 50 Refrigerant High pressure mm (in.) 19.05(3/4) Brazed piping diameter Low pressure mm (in.) 22.2(7/8) BrazedCirculating water Water flow rate m3 / h 5.76
L / min 96cfm 3.4
Pressure drop kPa 17Operating volume range m3 / h 4.5 ~ 7.2
Compressor Type x Quantity Inverter scroll hermetic compressorManufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATIONStarting method InverterMotor output kW 7.4Case heater kW 0.035(240 V)Lubricant MEL32
External finish Acrylic painted steel plate External dimension HxWxD mm 1,160(1,100 without legs) x 880 x 550
in. 45-11/16(43-5/16 without legs) x 34-11/16 x 21-11/16 Protection devices High pressure protection High pressure sensor, High pressure switch at 4.15MPa (601 psi)
Inverter circuit (COMP.) Over-heat protection, Over-current protectionCompressor Over-heat protection
Refrigerant Type x original charge R410A x 5.0kg (12lbs)Control Indoor LEV and BC controller
Net weight kg (lbs) 181(400) Heat exchanger plate type
Water volume in plate I 5.0Water pressure Max. MPa 2.0
HIC circuit (HIC: Heat Inter-Changer) - Drawing External KB94T146
Wiring KE94C302 Standard attachment Document Installation Manual
Accessory Refrigerant conn. pipe Optional parts Joint: CMY-Y102SS-G2,CMY-Y102LS-G2,CMY-Y202S-G2,CMY-R160-J1
BC controller: CMB-P104, 105, 106, 108, 1010, 1013, 1016V-G1Main BC controller: CMB-P108,1010,1013,1016V-GA1
Sub BC controller: CMB-P104,108V-GB1,CMB-P1016V-HB1 Remarks .Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the Installation Manual.
.Due to continuing improvement, above specifications may be subject to change without notice..The ambient temperature of the heat source unit needs to be kept below 40°C D.B..The ambient relative humidity of the heat source unit needs to be kept below 80%..The heat source Unit should not be installed at outdoor..Be sure to mount a strainer (more than 50 meshes) at the water inlet piping of the unit..Be sure to provide interlocking for the unit operation and water circuit.
Notes: Unit converter
1. Nominal cooling conditions (subject to JIS B8615-2) kcal/h =kW x 860
Indoor: 27°CDB/19°CWB (81°FDB/66°FWB), Water temperature: 30°C (86°F) BTU/h =kW x 3,412Pipe length: 7.5m (24-9/16ft.), Level difference: 0m (0ft.) cfm =m3/min x 35.31
2. Nominal heating conditions (subject to JIS B8615-2) lbs =kg/0.4536
Indoor: 20°CDB (68°FDB), Water temperature: 20°C (68°F)Pipe length: 7.5m (24-9/16ft.), Level difference: 0m (0ft.) *The specification data is
subject to rounding variation.
1. SPECIFICATIONS G10 2nd
HEAT SOURCE UNITS 2 - 426
WR
2
Model PQRY-P400YSHM-A Power source 3-phase 4-wire 380-400-415V 50/60Hz Cooling capacity *1 kW 45.0 (Nominal) *1 kcal / h 38,700
*1 BTU / h 153,500Power input kW 8.32Current input A 14.0-13.3-12.8EER kW / kW 5.40
Temp. range of Indoor W.B. 15.0 ~ 24.0°C(59 ~ 75°F) cooling Circulating water °C 10.0 ~ 45.0°C(50 ~ 113°F) Heating capacity *2 kW 50.0 (Nominal) *2 kcal / h 43,000
*2 BTU / h 170,600Power input kW 8.65Current input A 14.6-13.8-13.3COP kW / kW 5.78
Temp. range of Indoor D.B. 15.0 ~ 27.0°C(59 ~ 81°F) heating Circulating water °C 10.0 ~ 45.0°C(50 ~ 113°F) Indoor unit Total capacity 50 ~ 150 % of heat source unit capacity connectable Model / Quantity P15 ~ P250 / 1 ~ 40 Sound pressure level (measured in anechoic room) dB <A> 50 Refrigerant High pressure mm (in.) 22.2(7/8) Brazed piping diameter Low pressure mm (in.) 28.58(1-1/8) Brazed Set Model Model PQRY-P200YHM-A PQRY-P200YHM-ACirculating water Water flow rate m3 / h 5.76 + 5.76
L / min 96 + 96cfm 3.4 + 3.4
Pressure drop kPa 17 17Operating volume range m3 / h 4.5 + 4.5 ~ 7.2 + 7.2
Compressor Type x Quantity Inverter scroll hermetic compressor Inverter scroll hermetic compressorManufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION AC&R Works, MITSUBISHI ELECTRIC CORPORATIONStarting method Inverter InverterMotor output kW 4.6 4.6Case heater kW 0.035(240 V) 0.035(240 V)Lubricant MEL32 MEL32
External finish Acrylic painted steel plate Acrylic painted steel plate External dimension HxWxD mm 1,160(1,100 without legs) x 880 x 550 1,160(1,100 without legs) x 880 x 550
in. 45-11/16(43-5/16 without legs) x 34-11/16 x 21-11/16 45-11/16(43-5/16 without legs) x 34-11/16 x 21-11/16
Protection devices High pressure protection High pressure sensor, High pressure switch at 4.15MPa (601 psi)
High pressure sensor, High pressure switch at 4.15MPa (601 psi)
Inverter circuit (COMP.) Over-heat protection, Over-current protection Over-heat protection, Over-current protectionCompressor Over-heat protection Over-heat protection
Refrigerant Type x original charge R410A x 5.0kg (12lbs) R410A x 5.0kg (12lbs)Control Indoor LEV and BC controller
Net weight kg (lbs) 181(400) 181(400) Heat exchanger plate type plate type
Water volume in plate I 5.0 5.0Water pressure Max. MPa 2.0 2.0
HIC circuit (HIC: Heat Inter-Changer) - - Pipe between unit and High pressure mm (in.) 19.05(3/4) Brazed 19.05(3/4) Brazed distributor Low pressure mm (in.) - 22.2(7/8) Brazed Drawing External KB94T147
Wiring KE94C302 KE94C302 Standard attachment Document Installation Manual
Accessory Refrigerant conn. pipe Optional parts Heat Source Twinning kit: CMY-Q100VBK
Joint: CMY-Y102SS-G2,CMY-Y102LS-G2,CMY-Y202S-G2,CMY-R160-J1Main BC controller: CMB-P108,1010,1013,1016V-GA1
Sub BC controller: CMB-P104,108V-GB1,CMB-P1016V-HB1 Remarks .Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the Installation Manual.
.Due to continuing improvement, above specifications may be subject to change without notice..The ambient temperature of the heat source unit needs to be kept below 40°C D.B..The ambient relative humidity of the heat source unit needs to be kept below 80%..The heat source Unit should not be installed at outdoor..Be sure to mount a strainer (more than 50 meshes) at the water inlet piping of the unit..Be sure to provide interlocking for the unit operation and water circuit..The heat source twinning kit (low pressure) should be connected to the low pressure side of the heat source unit.If the connected units are of different capacities, the heat source twinning kit (low pressure) should be installed in the unit with the largest capacity.
Notes: Unit converter
1. Nominal cooling conditions (subject to JIS B8615-2) kcal/h =kW x 860
Indoor: 27°CDB/19°CWB (81°FDB/66°FWB), Water temperature: 30°C (86°F) BTU/h =kW x 3,412Pipe length: 7.5m (24-9/16ft.), Level difference: 0m (0ft.) cfm =m3/min x 35.31
2. Nominal heating conditions (subject to JIS B8615-2) lbs =kg/0.4536
Indoor: 20°CDB (68°FDB), Water temperature: 20°C (68°F)Pipe length: 7.5m (24-9/16ft.), Level difference: 0m (0ft.) *The specification data is
subject to rounding variation.
2 - 427
1. SPECIFICATIONS G10 2nd
HEAT SOURCE UNITS
WR
2
Model PQRY-P450YSHM-A Power source 3-phase 4-wire 380-400-415V 50/60Hz Cooling capacity *1 kW 50.0 (Nominal) *1 kcal / h 43,000
*1 BTU / h 170,600Power input kW 9.94Current input A 16.7-15.9-15.3EER kW / kW 5.03
Temp. range of Indoor W.B. 15.0 ~ 24.0°C(59 ~ 75°F) cooling Circulating water °C 10.0 ~ 45.0°C(50 ~ 113°F) Heating capacity *2 kW 56.0 (Nominal) *2 kcal / h 48,200
*2 BTU / h 191,100Power input kW 10.42Current input A 17.5-16.7-16.1COP kW / kW 5.37
Temp. range of Indoor D.B. 15.0 ~ 27.0°C(59 ~ 81°F) heating Circulating water °C 10.0 ~ 45.0°C(50 ~ 113°F) Indoor unit Total capacity 50 ~ 150 % of heat source unit capacity connectable Model / Quantity P15 ~ P250 / 1 ~ 45 Sound pressure level (measured in anechoic room) dB <A> 51 Refrigerant High pressure mm (in.) 22.2(7/8) Brazed piping diameter Low pressure mm (in.) 28.58(1-1/8) Brazed Set Model Model PQRY-P250YHM-A PQRY-P200YHM-ACirculating water Water flow rate m3 / h 5.76 + 5.76
L / min 96 + 96cfm 3.4 + 3.4
Pressure drop kPa 17 17Operating volume range m3 / h 4.5 + 4.5 ~ 7.2 + 7.2
Compressor Type x Quantity Inverter scroll hermetic compressor Inverter scroll hermetic compressorManufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION AC&R Works, MITSUBISHI ELECTRIC CORPORATIONStarting method Inverter InverterMotor output kW 6.3 4.6Case heater kW 0.035(240 V) 0.035(240 V)Lubricant MEL32 MEL32
External finish Acrylic painted steel plate Acrylic painted steel plate External dimension HxWxD mm 1,160(1,100 without legs) x 880 x 550 1,160(1,100 without legs) x 880 x 550
in. 45-11/16(43-5/16 without legs) x 34-11/16 x 21-11/16 45-11/16(43-5/16 without legs) x 34-11/16 x 21-11/16
Protection devices High pressure protection High pressure sensor, High pressure switch at 4.15MPa (601 psi)
High pressure sensor, High pressure switch at 4.15MPa (601 psi)
Inverter circuit (COMP.) Over-heat protection, Over-current protection Over-heat protection, Over-current protectionCompressor Over-heat protection Over-heat protection
Refrigerant Type x original charge R410A x 5.0kg (12lbs) R410A x 5.0kg (12lbs)Control Indoor LEV and BC controller
Net weight kg (lbs) 181(400) 181(400) Heat exchanger plate type plate type
Water volume in plate I 5.0 5.0Water pressure Max. MPa 2.0 2.0
HIC circuit (HIC: Heat Inter-Changer) - - Pipe between unit and High pressure mm (in.) 19.05(3/4) Brazed 19.05(3/4) Brazed distributor Low pressure mm (in.) - 22.2(7/8) Brazed Drawing External KB94T147
Wiring KE94C302 KE94C302 Standard attachment Document Installation Manual
Accessory Refrigerant conn. pipe Optional parts Heat Source Twinning kit: CMY-Q100VBK
Joint: CMY-Y102SS-G2,CMY-Y102LS-G2,CMY-Y202S-G2,CMY-R160-J1Main BC controller: CMB-P108,1010,1013,1016V-GA1
Sub BC controller: CMB-P104,108V-GB1,CMB-P1016V-HB1 Remarks .Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the Installation Manual.
.Due to continuing improvement, above specifications may be subject to change without notice..The ambient temperature of the heat source unit needs to be kept below 40°C D.B..The ambient relative humidity of the heat source unit needs to be kept below 80%..The heat source Unit should not be installed at outdoor..Be sure to mount a strainer (more than 50 meshes) at the water inlet piping of the unit..Be sure to provide interlocking for the unit operation and water circuit..The heat source twinning kit (low pressure) should be connected to the low pressure side of the heat source unit.If the connected units are of different capacities, the heat source twinning kit (low pressure) should be installed in the unit with the largest capacity.
Notes: Unit converter
1. Nominal cooling conditions (subject to JIS B8615-2) kcal/h =kW x 860
Indoor: 27°CDB/19°CWB (81°FDB/66°FWB), Water temperature: 30°C (86°F) BTU/h =kW x 3,412Pipe length: 7.5m (24-9/16ft.), Level difference: 0m (0ft.) cfm =m3/min x 35.31
2. Nominal heating conditions (subject to JIS B8615-2) lbs =kg/0.4536
Indoor: 20°CDB (68°FDB), Water temperature: 20°C (68°F)Pipe length: 7.5m (24-9/16ft.), Level difference: 0m (0ft.) *The specification data is
subject to rounding variation.
1. SPECIFICATIONS G10 2nd
HEAT SOURCE UNITS 2 - 428
WR
2
Model PQRY-P500YSHM-A Power source 3-phase 4-wire 380-400-415V 50/60Hz Cooling capacity *1 kW 56.0 (Nominal) *1 kcal / h 48,200
*1 BTU / h 191,100Power input kW 11.57Current input A 19.5-18.5-17.8EER kW / kW 4.84
Temp. range of Indoor W.B. 15.0 ~ 24.0°C(59 ~ 75°F) cooling Circulating water °C 10.0 ~ 45.0°C(50 ~ 113°F) Heating capacity *2 kW 63.0 (Nominal) *2 kcal / h 54,200
*2 BTU / h 215,000Power input kW 12.06Current input A 20.3-19.3-18.6COP kW / kW 5.22
Temp. range of Indoor D.B. 15.0 ~ 27.0°C(59 ~ 81°F) heating Circulating water °C 10.0 ~ 45.0°C(50 ~ 113°F) Indoor unit Total capacity 50 ~ 150 % of heat source unit capacity connectable Model / Quantity P15 ~ P250 / 1 ~ 50 (Connectable branch pipe number is max. 48.) Sound pressure level (measured in anechoic room) dB <A> 52 Refrigerant High pressure mm (in.) 22.2(7/8) Brazed piping diameter Low pressure mm (in.) 28.58(1-1/8) Brazed Set Model Model PQRY-P250YHM-A PQRY-P250YHM-ACirculating water Water flow rate m3 / h 5.76 + 5.76
L / min 96 + 96cfm 3.4 + 3.4
Pressure drop kPa 17 17Operating volume range m3 / h 4.5 + 4.5 ~ 7.2 + 7.2
Compressor Type x Quantity Inverter scroll hermetic compressor Inverter scroll hermetic compressorManufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION AC&R Works, MITSUBISHI ELECTRIC CORPORATIONStarting method Inverter InverterMotor output kW 6.3 6.3Case heater kW 0.035(240 V) 0.035(240 V)Lubricant MEL32 MEL32
External finish Acrylic painted steel plate Acrylic painted steel plate External dimension HxWxD mm 1,160(1,100 without legs) x 880 x 550 1,160(1,100 without legs) x 880 x 550
in. 45-11/16(43-5/16 without legs) x 34-11/16 x 21-11/16 45-11/16(43-5/16 without legs) x 34-11/16 x 21-11/16
Protection devices High pressure protection High pressure sensor, High pressure switch at 4.15MPa (601 psi)
High pressure sensor, High pressure switch at 4.15MPa (601 psi)
Inverter circuit (COMP.) Over-heat protection, Over-current protection Over-heat protection, Over-current protectionCompressor Over-heat protection Over-heat protection
Refrigerant Type x original charge R410A x 5.0kg (12lbs) R410A x 5.0kg (12lbs)Control Indoor LEV and BC controller
Net weight kg (lbs) 181(400) 181(400) Heat exchanger plate type plate type
Water volume in plate I 5.0 5.0Water pressure Max. MPa 2.0 2.0
HIC circuit (HIC: Heat Inter-Changer) - - Pipe between unit and High pressure mm (in.) 19.05(3/4) Brazed 19.05(3/4) Brazed distributor Low pressure mm (in.) - 22.2(7/8) Brazed Drawing External KB94T147
Wiring KE94C302 KE94C302 Standard attachment Document Installation Manual
Accessory Refrigerant conn. pipe Optional parts Heat Source Twinning kit: CMY-Q100VBK
Joint: CMY-Y102SS-G2,CMY-Y102LS-G2,CMY-Y202S-G2,CMY-R160-J1Main BC controller: CMB-P108,1010,1013,1016V-GA1
Sub BC controller: CMB-P104,108V-GB1,CMB-P1016V-HB1 Remarks .Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the Installation Manual.
.Due to continuing improvement, above specifications may be subject to change without notice..The ambient temperature of the heat source unit needs to be kept below 40°C D.B..The ambient relative humidity of the heat source unit needs to be kept below 80%..The heat source Unit should not be installed at outdoor..Be sure to mount a strainer (more than 50 meshes) at the water inlet piping of the unit..Be sure to provide interlocking for the unit operation and water circuit..The heat source twinning kit (low pressure) should be connected to the low pressure side of the heat source unit.If the connected units are of different capacities, the heat source twinning kit (low pressure) should be installed in the unit with the largest capacity.
Notes: Unit converter
1. Nominal cooling conditions (subject to JIS B8615-2) kcal/h =kW x 860
Indoor: 27°CDB/19°CWB (81°FDB/66°FWB), Water temperature: 30°C (86°F) BTU/h =kW x 3,412Pipe length: 7.5m (24-9/16ft.), Level difference: 0m (0ft.) cfm =m3/min x 35.31
2. Nominal heating conditions (subject to JIS B8615-2) lbs =kg/0.4536
Indoor: 20°CDB (68°FDB), Water temperature: 20°C (68°F)Pipe length: 7.5m (24-9/16ft.), Level difference: 0m (0ft.) *The specification data is
subject to rounding variation.
2 - 429
1. SPECIFICATIONS G10 2nd
HEAT SOURCE UNITS
WR
2
Model PQRY-P550YSHM-A Power source 3-phase 4-wire 380-400-415V 50/60Hz Cooling capacity *1 kW 63.0 (Nominal) *1 kcal / h 54,200
*1 BTU / h 215,000Power input kW 13.60Current input A 22.9-21.8-21.0EER kW / kW 4.63
Temp. range of Indoor W.B. 15.0 ~ 24.0°C(59 ~ 75°F) cooling Circulating water °C 10.0 ~ 45.0°C(50 ~ 113°F) Heating capacity *2 kW 69.0 (Nominal) *2 kcal / h 59,300
*2 BTU / h 235,400Power input kW 14.65Current input A 24.7-23.4-22.6COP kW / kW 4.70
Temp. range of Indoor D.B. 15.0 ~ 27.0°C(59 ~ 81°F) heating Circulating water °C 10.0 ~ 45.0°C(50 ~ 113°F) Indoor unit Total capacity 50 ~ 150 % of heat source unit capacity connectable Model / Quantity P15 ~ P250 / 2 ~ 50 (Connectable branch pipe number is max. 48.) Sound pressure level (measured in anechoic room) dB <A> 52.5 Refrigerant High pressure mm (in.) 28.58(1-1/8) Brazed piping diameter Low pressure mm (in.) 28.58(1-1/8) Brazed Set Model Model PQRY-P300YHM-A PQRY-P250YHM-ACirculating water Water flow rate m3 / h 5.76 + 5.76
L / min 96 + 96cfm 3.4 + 3.4
Pressure drop kPa 17 17Operating volume range m3 / h 4.5 + 4.5 ~ 7.2 + 7.2
Compressor Type x Quantity Inverter scroll hermetic compressor Inverter scroll hermetic compressorManufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION AC&R Works, MITSUBISHI ELECTRIC CORPORATIONStarting method Inverter InverterMotor output kW 7.4 6.3Case heater kW 0.035(240 V) 0.035(240 V)Lubricant MEL32 MEL32
External finish Acrylic painted steel plate Acrylic painted steel plate External dimension HxWxD mm 1,160(1,100 without legs) x 880 x 550 1,160(1,100 without legs) x 880 x 550
in. 45-11/16(43-5/16 without legs) x 34-11/16 x 21-11/16 45-11/16(43-5/16 without legs) x 34-11/16 x 21-11/16
Protection devices High pressure protection High pressure sensor, High pressure switch at 4.15MPa (601 psi)
High pressure sensor, High pressure switch at 4.15MPa (601 psi)
Inverter circuit (COMP.) Over-heat protection, Over-current protection Over-heat protection, Over-current protectionCompressor Over-heat protection Over-heat protection
Refrigerant Type x original charge R410A x 5.0kg (12lbs) R410A x 5.0kg (12lbs)Control Indoor LEV and BC controller
Net weight kg (lbs) 181(400) 181(400) Heat exchanger plate type plate type
Water volume in plate I 5.0 5.0Water pressure Max. MPa 2.0 2.0
HIC circuit (HIC: Heat Inter-Changer) - - Pipe between unit and High pressure mm (in.) 19.05(3/4) Brazed 19.05(3/4) Brazed distributor Low pressure mm (in.) - 22.2(7/8) Brazed Drawing External KB94T147
Wiring KE94C302 KE94C302 Standard attachment Document Installation Manual
Accessory Refrigerant conn. pipe Optional parts Heat Source Twinning kit: CMY-Q100VBK
Joint: CMY-Y102SS-G2,CMY-Y102LS-G2,CMY-Y202S-G2,CMY-R160-J1Main BC controller: CMB-P108,1010,1013,1016V-GA1
Sub BC controller: CMB-P104,108V-GB1,CMB-P1016V-HB1 Remarks .Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the Installation Manual.
.Due to continuing improvement, above specifications may be subject to change without notice .The ambient temperature of the heat source unit needs to be kept below 40°C D.B. .The ambient relative humidity of the heat source unit needs to be kept below 80%. .The heat source Unit should not be installed at outdoor. .Be sure to mount a strainer (more than 50 meshes) at the water inlet piping of the unit. .Be sure to provide interlocking for the unit operation and water circuit. .The heat source twinning kit (low pressure) should be connected to the low pressure side of the heat source unit.If the connected units are of different capacities, the heat source twinning kit (low pressure) should be installed in the unit with the largest capacity.
Notes: Unit converter
1. Nominal cooling conditions (subject to JIS B8615-2) kcal/h =kW x 860
Indoor: 27°CDB/19°CWB (81°FDB/66°FWB), Water temperature: 30°C (86°F) BTU/h =kW x 3,412Pipe length: 7.5m (24-9/16ft.), Level difference: 0m (0ft.) cfm =m3/min x 35.31
2. Nominal heating conditions (subject to JIS B8615-2) lbs =kg/0.4536
Indoor: 20°CDB (68°FDB), Water temperature: 20°C (68°F)Pipe length: 7.5m (24-9/16ft.), Level difference: 0m (0ft.) *The specification data is
subject to rounding variation.
1. SPECIFICATIONS G10 2nd
HEAT SOURCE UNITS 2 - 430
WR
2
Model PQRY-P600YSHM-A Power source 3-phase 4-wire 380-400-415V 50/60Hz Cooling capacity *1 kW 69.0 (Nominal) *1 kcal / h 59,300
*1 BTU / h 235,400Power input kW 15.62Current input A 26.3-25.0-24.1EER kW / kW 4.41
Temp. range of Indoor W.B. 15.0 ~ 24.0°C(59 ~ 75°F) cooling Circulating water °C 10.0 ~ 45.0°C(50 ~ 113°F) Heating capacity *2 kW 76.5 (Nominal) *2 kcal / h 65,800
*2 BTU / h 261,000Power input kW 17.12Current input A 28.9-27.4-26.4COP kW / kW 4.46
Temp. range of Indoor D.B. 15.0 ~ 27.0°C(59 ~ 81°F) heating Circulating water °C 10.0 ~ 45.0°C(50 ~ 113°F) Indoor unit Total capacity 50 ~ 150 % of heat source unit capacity connectable Model / Quantity P15 ~ P250 / 2 ~ 50 (Connectable branch pipe number is max. 48.) Sound pressure level (measured in anechoic room) dB <A> 53 Refrigerant High pressure mm (in.) 28.58(1-1/8) Brazed piping diameter Low pressure mm (in.) 28.58(1-1/8) Brazed Set Model Model PQRY-P300YHM-A PQRY-P300YHM-ACirculating water Water flow rate m3 / h 5.76 + 5.76
L / min 96 + 96cfm 3.4 + 3.4
Pressure drop kPa 17 17Operating volume range m3 / h 4.5 + 4.5 ~ 7.2 + 7.2
Compressor Type x Quantity Inverter scroll hermetic compressor Inverter scroll hermetic compressorManufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION AC&R Works, MITSUBISHI ELECTRIC CORPORATIONStarting method Inverter InverterMotor output kW 7.4 7.4Case heater kW 0.035(240 V) 0.035(240 V)Lubricant MEL32 MEL32
External finish Acrylic painted steel plate Acrylic painted steel plate External dimension HxWxD mm 1,160(1,100 without legs) x 880 x 550 1,160(1,100 without legs) x 880 x 550
in. 45-11/16(43-5/16 without legs) x 34-11/16 x 21-11/16 45-11/16(43-5/16 without legs) x 34-11/16 x 21-11/16
Protection devices High pressure protection High pressure sensor, High pressure switch at 4.15MPa (601 psi)
High pressure sensor, High pressure switch at 4.15MPa (601 psi)
Inverter circuit (COMP.) Over-heat protection, Over-current protection Over-heat protection, Over-current protectionCompressor Over-heat protection Over-heat protection
Refrigerant Type x original charge R410A x 5.0kg (12lbs) R410A x 5.0kg (12lbs)Control Indoor LEV and BC controller
Net weight kg (lbs) 181(400) 181(400) Heat exchanger plate type plate type
Water volume in plate I 5.0 5.0Water pressure Max. MPa 2.0 2.0
HIC circuit (HIC: Heat Inter-Changer) - - Pipe between unit and High pressure mm (in.) 19.05(3/4) Brazed 19.05(3/4) Brazed distributor Low pressure mm (in.) - 22.2(7/8) Brazed Drawing External KB94T147
Wiring KE94C302 KE94C302 Standard attachment Document Installation Manual
Accessory Refrigerant conn. pipe Optional parts Heat Source Twinning kit: CMY-Q100VBK
Joint: CMY-Y102SS-G2,CMY-Y102LS-G2,CMY-Y202S-G2,CMY-R160-J1Main BC controller: CMB-P108,1010,1013,1016V-GA1
Sub BC controller: CMB-P104,108V-GB1,CMB-P1016V-HB1
Remarks .Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the Installation Manual. .Due to continuing improvement, above specifications may be subject to change without notice. .The ambient temperature of the heat source unit needs to be kept below 40°C D.B. .The ambient relative humidity of the heat source unit needs to be kept below 80%. .The heat source Unit should not be installed at outdoor. .Be sure to mount a strainer (more than 50 meshes) at the water inlet piping of the unit. .Be sure to provide interlocking for the unit operation and water circuit. .The heat source twinning kit (low pressure) should be connected to the low pressure side of the heat source unit.If the connected units are of different capacities, he heat source twinning kit (low pressure) should be installed in the unit with the largest capacity.
Notes: Unit converter 1. Nominal cooling conditions (subject to JIS B8615-2) kcal/h =kW x 860
Indoor: 27°CDB/19°CWB (81°FDB/66°FWB), Water temperature: 30°C (86°F) BTU/h =kW x 3,412
Pipe length: 7.5m (24-9/16ft.), Level difference: 0m (0ft.) cfm =m3/min x 35.31 2. Nominal heating conditions (subject to JIS B8615-2) lbs =kg/0.4536
Indoor: 20°CDB (68°FDB), Water temperature: 20°C (68°F)
Pipe length: 7.5m (24-9/16ft.), Level difference: 0m (0ft.) *The specification data issubject to rounding variation.
2 - 431
2. EXTERNAL DIMENSIONS G10 2nd
HEAT SOURCE UNITS
WR
2
2. EXTERNAL DIMENSIONS
Ser
vice
spa
ce(fr
ont s
ide)
Servi
ce sp
ace
(fron
t side
)
Top
view
550
6060
20
74
1160(60)
The
spac
e fo
rco
ntro
l box
repl
acem
ent
450
600
170
350
725
600450
170
1100550 (530)
(102
)(5
3)
506 (503~509)
470 (467~473)
834
720
1100
141213240
2 x
2-14
x 2
0 O
val h
ole
140
75
608
563
584
83 58
121226234
18
78 168
433 54
8
(550)2222
4040
550
880
2 x
2-14
x 2
0 O
val h
ole
(Inst
alla
tion
supp
ort h
ole)
(880
)
8080 23
23
Con
trol b
ox
Ser
vice
pane
l
(Inst
alla
tion
supp
ort h
ole
pitc
h) (M
ount
ing
pitc
h)
(Installation support hole pitch)
(Mounting pitch)
88
7654
3 2
Refrig
eran
t ser
vice
valve
<Lo
w pr
essu
re>
Refrig
eran
t ser
vice
valve
<Hi
gh pr
essu
re>
1
(fron
t and
bac
k, 2
poi
nts)
Not
e 8*
Det
acha
ble
leg
880
ø45
Kno
ckou
t hol
e
ø34
Kno
ckou
t hol
eø5
2 or ø
27 K
nock
out h
ole
For p
ipes
For w
ires
For t
rans
miss
ion ca
bles
Fron
t thr
ough
hol
e
Fron
t thr
ough
hol
eFr
ont t
hrou
gh h
ole
Fron
t thr
ough
hol
e
140
x 77
Knoc
kout
hole
ø65 o
r ø40
Kno
ckou
t hole
(Uses
when
twinn
ing kit
(optio
nal
parts
) is m
ounte
d.)
Fron
t thr
ough
hol
e
ø22.
2 Br
azed
ø19.
05 B
raze
d
ø19.
05 B
raze
dø1
5.88
Bra
zed
Low
pre
ssur
eH
igh
pres
sure
Con
nect
ion
spec
ifica
tions
for
the
refri
gera
nt s
ervi
ce v
alve
PQ
RY-
P30
0YH
M-A
PQ
RY-
P25
0YH
M-A
PQ
RY-
P20
0YH
M-A
Mod
el
Con
nect
ing
pipe
spe
cific
atio
ns
*2 *1
*2 *2
*1.E
xpan
d th
e fie
ld p
ipes
and
con
nect
dire
ctly
to th
e va
lve.
*2.C
onne
ct b
y us
ing
the
conn
ectin
g pi
pes
that
are
sup
plie
d.
Fig.
BFi
g. A
Wat
er p
ipe
Dra
in p
ipe
inle
tou
tlet
Rc1
-1/2
Scr
ewR
c1-1
/2 S
crew
Rc3
/4 S
crew
<Acc
esso
ries>
·Ref
riger
ant (
high
pre
ssur
e) c
onn.
pip
e ···
···1
pc.
(P20
0 ; P
acka
ged
in th
e ac
cess
ory
kit)
·Ref
riger
ant (
low
pre
ssur
e) c
onn.
pip
e ···
··1 p
c.(P
200/
P25
0 ; P
acka
ged
in th
e ac
cess
ory
kit)
Not
e 1.
Clo
se a
hol
e of
the
wat
er p
ipin
g, th
e re
frige
rant
pip
ing,
th
e po
wer
sup
ply,
and
the
cont
rol w
iring
and
unu
sed
knoc
kout
h
oles
with
the
putty
etc
. so
as n
ot to
infil
trate
rain
wat
er
etc
. (fie
ld e
rect
ion
wor
k)N
ote
2. A
t the
tim
e of
pro
duct
shi
pmen
t, th
e fro
nt s
ide
pipi
ng
spe
cific
atio
n se
rves
as
the
loca
l dra
inag
e co
nnec
tion.
W
hen
conn
ectin
g on
the
rear
sid
e, p
leas
e re
mov
e th
e
rear
sid
e pl
ug s
ealin
g co
rks,
and
atta
ch a
fron
t sid
e.
Ens
ure
ther
e is
no
leak
afte
r the
atta
chm
ent h
as b
een
fitte
d.N
ote
3. T
ake
notic
e of
ser
vice
spa
ce a
s Fi
g. A
. (In
cas
e of
sin
gle
in
stal
latio
n, 6
00m
m o
r mor
e of
bac
k sp
ace
as fr
ont s
pace
m
akes
eas
ier a
cces
s w
hen
serv
icin
g th
e un
it fro
m re
ar s
ide)
Not
e 4.
If w
ater
pip
es o
r ref
riger
ant p
ipes
stre
tch
upw
ard,
re
quire
d sp
ace
for s
ervi
ce a
nd m
aint
enan
ce d
ue to
repl
acem
ent o
f con
trol b
ox is
sho
wn
in F
ig. B
.N
ote
5. E
nviro
nmen
tal c
ondi
tion
for i
nsta
llatio
n; -2
0~40
°C (D
B)
a
s in
door
inst
alla
tion.
Not
e 6.
In c
ase
the
tem
pera
ture
aro
und
the
heat
sou
rce
unit
has
p
ossi
bilit
y to
dro
p un
der 0
°C, b
e ca
refu
l for
the
follo
win
g
poi
nt to
pre
vent
the
pipe
bur
st b
y th
e w
ater
pip
e fre
eze-
up.
·
Circ
ulat
e th
e w
ater
all
the
time
even
if th
e he
at s
ourc
e
un
it is
not
in o
pera
tion.
·
Dra
in th
e w
ater
from
insi
de o
f the
hea
t sou
rce
unit
whe
n
th
e he
at s
ourc
e un
it w
ill n
ot o
pera
te fo
r a lo
ng te
rm.
Not
e 7.
Ens
ure
that
the
drai
n pi
ping
is d
ownw
ard
with
a p
itch
of
m
ore
than
1/1
00.
Not
e 8.
The
det
acha
ble
leg
can
be re
mov
ed a
t site
.N
ote
9. A
t bra
zing
of p
ipes
, wra
p th
e re
frige
rant
ser
vice
val
ve
w
ith w
et c
loth
and
kee
p th
e te
mpe
ratu
re o
f
refri
gera
nt s
ervi
ce v
alve
und
er 1
20°C
.
Spe
cific
atio
nsU
sage
NO
.
PQRY-P200, 250, 300YHM-AUnit : mm
2. EXTERNAL DIMENSIONS G10 2nd
HEAT SOURCE UNITS 2 - 432
WR
2
1100
550
1780
880
880
20
ce
d
To B
C c
ontro
ller
To B
C c
ontro
ller
ba
Twin
ning
pip
e (H
igh
pres
sure
)<o
ptio
nal p
arts
>
Twin
ning
pip
e(L
ow p
ress
ure)
<opt
iona
l par
ts>
Hig
hpr
essu
reLo
wpr
essu
rec
or e
d
P25
0P
200
P30
0
Uni
t m
odel
Twin
ning
pip
e ~
Hea
t sou
rce
unit
(fron
t and
bac
k, 2
poi
nts)
Det
acha
ble
leg
CM
Y-Q
100V
BK
PQRY
-P60
0YSH
M-A
PQRY
-P30
0YHM
-APQ
RY-P
300Y
HM-A
Not
e 1.
Con
nect
the
pipe
s as
sho
wn
in th
e fig
ure
abov
e. R
efer
to th
e ta
ble
belo
w fo
r the
pip
e si
ze.
2.
The
det
acha
ble
leg
can
be re
mov
ed a
t site
.
3. T
win
ning
pip
e (H
igh
pres
sure
) sho
uld
not b
e til
ted
mor
e th
an 1
5 de
gree
s fro
m th
e gr
ound
.
4. S
ee th
e In
stal
latio
n M
anua
l for
the
deta
ils o
f Tw
inni
ng p
ipe
inst
alla
tion.
PQRY
-P25
0YHM
-APQ
RY-P
250Y
HM-A
PQRY
-P50
0YSH
M-A
Low
press
ure
Twin
ning
pip
e co
nnec
tion
size
Heat
Sou
rce
unit
1Co
mpo
nent
unit
nam
e
Pac
kage
uni
t nam
e
BC
con
trolle
r ~Tw
inni
ng p
ipe
a b
PQRY
-P40
0YSH
M-A
PQRY
-P20
0YHM
-APQ
RY-P
200Y
HM-A
High
pres
sure
Twin
ning
pip
e K
it (o
ptio
nal p
arts
)He
at S
ourc
e un
it 2
PQRY
-P45
0YSH
M-A
PQRY
-P25
0YHM
-APQ
RY-P
200Y
HM-A
ø19.
05ø2
2.2
PQRY
-P55
0YSH
M-A
PQRY
-P30
0YHM
-APQ
RY-P
250Y
HM-A
116060
ø28.
58ø2
2.2
ø28.
58
Hea
t Sou
rce
unit
2H
eat S
ourc
e un
it 1
PQRY-P400,450,500,550,600YSHM-AUnit : mm
2 - 433
3. CENTER OF GRAVITY G10 2nd
HEAT SOURCE UNITS
WR
2
3. CENTER OF GRAVITY
PQRY-P200,250,300YHM-A
Model X Y Z423(16-11/16) 253(10)423(16-11/16) 253(10)
524(20-11/16)524(20-11/16)
PQRY-P200YHM-A
423(16-11/16) 253(10) 524(20-11/16)PQRY-P300YHM-APQRY-P250YHM-A
Unit : mm[in.]
1100
(43-
5/16
)60
(2-6
/16)
550(21-11/16)880(34-11/16)
506(19-15/16)
YX
Z
1160
(45-
11/1
6)
80(3-3/16)
720(28-6/16)
4. ELECTRICAL WIRING DIAGRAMS G10 2nd
HEAT SOURCE UNITS 2 - 434
WR
2
4. ELECTRICAL WIRING DIAGRAMS
~
CNAC
4
31
CN83
CNOU
T2 43
21
65
CNPW
42
1
75
CN51
0ye
llow
CN50
9blu
e3
CNOU
T1ye
llow
blue
yellow
red
orange
41
1 2 3 4 5 6
6 5 4 3 2 1
CNLV
ELE
VINV
tTH
812
CN99
2ye
llow
12
4
blue
CN63
PW
MF1
SV4d
156X1
2156
SV4b
SV7b
SV7a
3
DCL
t
M1M2
SV1a
Z3
21
-+
C5
SC-L1
SC-L2
SC-W
1Z5
R1R2R3
C3 C2F3 F2 F1Z1
Z2
R5D1
R4 R6C1
7
Diod
eBr
idge
C7C8C9C10
C4
C1
C6
TB1
L
F4 AC25
0V6.3
A T black
white
red
31 CN3
green
TB24
TB23
TB22
TB21
CN1B
41
31
CN1A
UU
U
F1,F2
,F3AC
250V
6.3A T
UZ4
DSA
CN2
6 5 3 1
UZNR0
1
U
+
31
CN5
red3
CN4
blue
1
C100
R1R5
black
red2 4
31
72C bla
ckred
SC-P
1SC
-P2
4CN
1 1
CN6
21CN
412
CN2
157 1CN
TYP
black
C1 RSH1
t THHS
FT-P
FT-N
P N
++++
++++
R34
C30
C32
C34
C36
R30
R32
C31
C33
C35
C37
R31
R33
black
white
redR3
5
CT3
SC-L3
IGBT
SC-U
SC-V
CT12
CT22
redwh
itebla
ck
black
white
red
UV
W
TP2
TP1
TB7
SM2
M1TB3
13
CN04
redCN
102
4321
CNS2
yello
w
2154
32CN
ITred
1
63H1
P
3 1CN
TYP2
black
Z24
3 2 1
Z25
CNTY
P5gre
en
CNTY
P4gre
en4 2 1
CN21
3red CN
990
2 1
TH7
TH5
t t
21 363
LS
63HS
121 3
THIN
V
tTH
4
3 2 1CN
202
red CN20
123 1
CN21
5bla
ck2 1
CN21
121
red CNIT
yello
wCN
S25
12
34
14
14
CN41
CN40
CN10
2 43
21
CN3D 1
23
blue
CN3N 1
23
yello
w C
N3K 1
2CN
ACred
21
3
F01
AC25
0V3.1
5A T
6 3 1
SV9
X09
CN50
8bla
ck
SV4a
X08
X07
1356
CN50
7red
6 5 3 1
CN50
6
X13
X05
3 121
S4a
CN50
4gre
enX0
4
X03
CH11
3 1CN
503
blue
2 1CN
502
X02
12
CNAC
2bla
ck
65 72C
12CN
72red
31
CNDC
pink
12CN
T01
13
1221
CN80
1ye
llow
CNT0
2CN
4
CN2
7 5 1
SW1ON
OFF 1 10
SW2ON
OFF 1 10
SW3ON
OFF 1 10
SW4ON
OFF 1 10
ONOF
F 1 10SW
5
543
12V
1CN
51SWU2
SWU1
10's
digit
1's digit
<Sym
bol e
xpla
natio
n>
*1.
Sing
le-d
otte
d lin
es in
dica
te w
iring
no
t sup
plie
d w
ith th
e un
it.*2
. D
ot-d
ash
lines
indi
cate
the
cont
rol
bo
x bo
unda
ries.
*3.
Ref
er to
the
Dat
a bo
ok fo
r con
nect
ing
in
put/o
utpu
t sig
nal c
onne
ctor
s.*4
. D
aisy
-cha
in te
rmin
als
(TB3
) on
the
he
at s
ourc
e un
its in
the
sam
e
refri
gera
nt s
yste
m to
geth
er.
*5.
Fast
on te
rmin
als
have
a lo
ckin
g
func
tion.
Mak
e su
re th
e te
rmin
als
ar
e se
cure
ly lo
cked
in p
lace
afte
r
inse
rtion
. Pre
ss th
e ta
b on
the
te
rmin
als
to re
mov
ed th
em.
*6.
Con
trol b
ox h
ouse
s hi
gh-v
olta
ge p
arts
.
Befo
re in
spec
ting
the
insi
de o
f the
co
ntro
l box
, tur
n of
f the
pow
er, k
eep
th
e un
it of
f for
at l
east
10
min
utes
,
and
conf
irm th
at th
e vo
ltage
bet
wee
n
FT-P
and
FT-
N o
n IN
V Bo
ard
has
drop
ped
to
20V
DC
or l
ess.
*7.
Ref
er to
the
Dat
a bo
ok fo
r wiri
ng
te
rmin
al b
lock
for P
ump
Inte
rlock
(TB8
).
Out
let t
emp.
det
ect o
f hea
t ex
chan
ger f
or in
verte
rTH
INV
Wat
er o
utle
t tem
pera
ture
TH8
Hea
t exc
hang
er c
apac
ity c
ontro
lSV
7a, b
Hea
t exc
hang
er c
apac
ity c
ontro
lSV
4a, b
, d
Hea
t exc
hang
er fo
r inv
erte
rLE
VIN
V
For o
peni
ng/c
losi
ng th
e by
pass
circ
uit u
nder
the
O/S
Fan
mot
or (R
adia
tor p
anel
)M
F1SV
1a
For o
peni
ng/c
losi
ng th
e by
pass
circ
uit
Sole
noid
valv
e
Z24,
25
Ther
mis
tor
Ope
ratio
n O
N s
igna
l, Pu
mp
Inte
rlock
Dis
char
ge p
ipe
tem
pera
ture
ACC
inle
t pip
e te
mpe
ratu
reW
ater
inle
t tem
pera
ture
IGBT
tem
pera
ture
Func
tion
setti
ng c
onne
ctor
THH
S
TH7
TH5
TH4
TB8
Pow
er s
uppl
y
Expl
anat
ion
Indo
or/H
eat s
ourc
e tra
nsm
issi
onca
ble
Cen
tral c
ontro
l tra
nsm
issi
onca
ble
Term
inal
bloc
k
TB7
TB3
TB1Sy
mbo
l
DC
reac
tor
DC
LLi
near
expa
nsio
nva
lve
Sole
noid
valv
e
CT1
2, 2
2, 3
CH
11C
rank
case
hea
ter (
for h
eatin
g th
e co
mpr
esso
r)C
urre
nt s
enso
r (AC
)M
agne
tic re
lay
(inve
rter m
ain
circ
uit)
72C
Low
pre
ssur
eH
igh
pres
sure
Hig
h pr
essu
re p
rote
ctio
n fo
r the
heat
sou
rce
unit
Pres
sure
switc
hPr
essu
rese
nsor
63LS
63H
1Sym
bol
Expl
anat
ion
4-w
ay v
alve
21S4
aSV
9
63H
S1
RELA
Y Bo
ard
Noise
Filte
r
INV
Boar
d
M-N
ET B
oard
Cont
rol B
oard
*7
*5
*6
*4OFF
ON
*3
LED1
Unit a
ddre
ssse
tting
LED1
Disp
layse
tting
Func
tion
settin
g
Comp
ress
or O
N/OF
F ou
tput
Erro
r dete
ction
outpu
t
TB7 P
ower
selec
ting
conn
ector
LED3
:Lit w
hen p
ower
ed
LED2
:CPU
in op
erati
on
CPU
pow
ersu
pply
circ
uit
Pow
er fa
ilure
dete
ctio
n ci
rcui
t
*3
M-N
ET p
ower
supp
ly c
ircui
t
Cen
tral c
ontro
ltra
nsm
issi
onca
ble
Indo
or/
Hea
t sou
rce
trans
mis
sion
cabl
e
LED
1:Po
wer
sup
ply
to In
door
/Hea
t sou
rce
trans
mis
sion
line
M
° °° ° °
M
Pum
p In
terlo
ckO
pera
tion
ON
sig
nal
M
otor
(Com
pres
sor)
MS 3~
1TB
82
34
°
LED
1 : N
orm
al o
pera
tion(
lit)
/ E
rror(b
link)
L3L2
L1
NL3
L2L1
NL3
L2L1
Powe
r Sou
rce
3N~
50/6
0Hz
380/
400/
415V
N
PQRY-P200, 250, 300YHM-A
2 - 435
5. SOUND LEVELS G10 2nd
HEAT SOURCE UNITS
WR
2
5. SOUND LEVELS
1m
1m
Measurementlocation
Measurement conditionPQRY-P200,250,300YHM-A
63 125 250 500 1k 2k 4k 8k dB(A)Standard 50/60Hz 65.0 55.5 49.0 44.0 42.5 39.5 43.5 36.5 50.0Low noise mode 50/60Hz 60.5 53.0 47.5 43.0 38.0 37.0 40.5 28.5 47.0When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operationfrom Low noise mode automatically in the case that the operation condition is severe.
10
20
30
40
50
60
70
80
90
63 125 250 500 1k 2k 4k 8k
NC-40
NC-30
NC-20
NC-60
NC-50
NC-70
Octave band central frequency (Hz)
Oct
ave
band
sou
nd le
vel (
dB)
Approximate minimumaudible limit oncontinuous noise
Stand 50/60HzLow 50/60Hz
Sound level of PQRY-P300YHM-A
63 125 250 500 1k 2k 4k 8k dB(A)Standard 50/60Hz 60.5 53.0 47.5 43.0 38.0 37.0 40.5 28.5 47.0Low noise mode 50/60Hz 56.5 50.0 44.0 39.5 36.0 34.5 36.5 28.5 44.0When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operationfrom Low noise mode automatically in the case that the operation condition is severe.
10
20
30
40
50
60
70
80
90
63 125 250 500 1k 2k 4k 8k
NC-40
NC-30
NC-20
NC-60
NC-50
NC-70
Octave band central frequency (Hz)
Oct
ave
band
sou
nd le
vel (
dB)
Approximate minimumaudible limit oncontinuous noise
Stand 50/60HzLow 50/60Hz
Sound level of PQRY-P200YHM-A
63 125 250 500 1k 2k 4k 8k dB(A)Standard 50/60Hz 61.0 54.0 48.0 43.5 42.0 39.0 43.0 32.5 49.0Low noise mode 50/60Hz 60.5 53.0 47.5 43.0 38.0 37.0 40.5 28.5 47.0When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operationfrom Low noise mode automatically in the case that the operation condition is severe.
10
20
30
40
50
60
70
80
90
63 125 250 500 1k 2k 4k 8k
NC-40
NC-30
NC-20
NC-60
NC-50
NC-70
Octave band central frequency (Hz)
Oct
ave
band
sou
nd le
vel (
dB)
Approximate minimumaudible limit oncontinuous noise
Stand 50/60HzLow 50/60Hz
Sound level of PQRY-P250YHM-A
5. SOUND LEVELS G10 2nd
HEAT SOURCE UNITS 2 - 436
WR
2
1m
1m
Measurementlocation
Measurement conditionPQRY-P400,450,500,550,600YSHM-A
63 125 250 500 1k 2k 4k 8k dB(A)Standard 50/60Hz 64.0 57.0 51.0 46.5 45.0 42.0 46.0 35.5 52.0Low noise mode 50/60Hz 62.5 56.0 50.0 46.0 42.0 40.5 42.5 31.5 50.0When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operationfrom Low noise mode automatically in the case that the operation condition is severe.
10
20
30
40
50
60
70
80
90
63 125 250 500 1k 2k 4k 8k
NC-40
NC-30
NC-20
NC-60
NC-50
NC-70
Octave band central frequency (Hz)
Oct
ave
band
sou
nd le
vel (
dB)
Approximate minimumaudible limit oncontinuous noise
Stand 50/60HzLow 50/60Hz
Sound level of PQRY-P500YSHM-A
63 125 250 500 1k 2k 4k 8k dB(A)Standard 50/60Hz 63.5 56.0 50.5 46.0 41.0 40.0 43.5 31.5 50.0Low noise mode 50/60Hz 61.0 54.5 47.5 43.5 38.5 37.0 38.0 30.0 47.0When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operationfrom Low noise mode automatically in the case that the operation condition is severe.
10
20
30
40
50
60
70
80
90
63 125 250 500 1k 2k 4k 8k
NC-40
NC-30
NC-20
NC-60
NC-50
NC-70
Octave band central frequency (Hz)
Oct
ave
band
sou
nd le
vel (
dB)
Approximate minimumaudible limit oncontinuous noise
Stand 50/60HzLow 50/60Hz
Sound level of PQRY-P400YSHM-A
63 125 250 500 1k 2k 4k 8k dB(A)Standard 50/60Hz 66.5 58.0 51.5 46.5 45.5 42.5 46.5 38.0 52.5Low noise mode 50/60Hz 62.5 56.0 50.0 46.0 42.0 40.5 42.5 31.5 50.0When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operationfrom Low noise mode automatically in the case that the operation condition is severe.
10
20
30
40
50
60
70
80
90
63 125 250 500 1k 2k 4k 8k
NC-40
NC-30
NC-20
NC-60
NC-50
NC-70
Octave band central frequency (Hz)
Oct
ave
band
sou
nd le
vel (
dB)
Approximate minimumaudible limit oncontinuous noise
Stand 50/60HzLow 50/60Hz
Sound level of PQRY-P550YSHM-A
63 125 250 500 1k 2k 4k 8k dB(A)Standard 50/60Hz 63.5 56.5 50.5 46.0 43.5 41.0 45.0 34.0 51.0Low noise mode 50/60Hz 62.0 55.0 49.5 44.5 41.5 40.5 40.0 31.5 49.0When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operationfrom Low noise mode automatically in the case that the operation condition is severe.
10
20
30
40
50
60
70
80
90
63 125 250 500 1k 2k 4k 8k
NC-40
NC-30
NC-20
NC-60
NC-50
NC-70
Octave band central frequency (Hz)
Oct
ave
band
sou
nd le
vel (
dB)
Approximate minimumaudible limit oncontinuous noise
Stand 50/60HzLow 50/60Hz
Sound level of PQRY-P450YSHM-A
63 125 250 500 1k 2k 4k 8k dB(A)Standard 50/60Hz 68.0 58.5 52.0 47.0 45.5 42.5 46.5 39.5 53.0Low noise mode 50/60Hz 62.5 56.0 50.0 46.0 42.0 40.5 42.5 31.5 50.0When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operationfrom Low noise mode automatically in the case that the operation condition is severe.
10
20
30
40
50
60
70
80
90
63 125 250 500 1k 2k 4k 8k
NC-40
NC-30
NC-20
NC-60
NC-50
NC-70
Octave band central frequency (Hz)
Oct
ave
band
sou
nd le
vel (
dB)
Approximate minimumaudible limit oncontinuous noise
Stand 50/60HzLow 50/60Hz
Sound level of PQRY-P600YSHM-A
2 - 437
6. CAPACITY TABLES G10 2nd
HEAT SOURCE UNITS
WR
2
6. CAPACITY TABLES6-1. Correction by temperatureCITY MULTI could have various capacities at different designing temperatures. Using the nominal cooling/heating capacity values and the ratios below, the capacity can be found for various temperatures.
Inlet-water temp. [°C]
Rat
io
Rat
ioR
atio
Intake air temp. (Room temp.) [°CWB] Water-volume [m3/h]
Water-volume [m3/h]
Wat
er-p
ress
ure
drop
[kPa
]
Water-volume [m3/h]
Wat
er-p
ress
ure
drop
[kPa
]
Inlet-water temp. [°C]
Rat
io
Rat
io
Water-volume [m3/h]
Rat
io
Intake air temp. (Room temp.) [°CDB]
CapacityInput
CapacityInput
CapacityInput
CapacityInput
CapacityInput
CapacityInput
Inlet-water temp. Water volume
Intake air temp.
Inlet-water temp. Water volume
Intake air temp.
Water-pressure drop
Water-pressure drop
NominalCoolingCapacityInput
kW 22.476,400
3.92BTU/hkW
PQHY-P200YHM-A22.4
76,4003.96
PQRY-P200YHM-A
NominalHeatingCapacityInput
kW 25.085,300
4.12BTU/hkW
PQHY-P200YHM-A25.0
85,3004.12
PQRY-P200YHM-A
04 5 6 7 8
10
20
30
04 5 6 7 8
10
20
30
0.7
0.6
0.8
0.9
1.0
1.1
1.2
1.3
1.4
10 15 20 25 30 35 40 45
0.7
0.6
0.8
0.9
1.0
1.1
1.2
1.3
1.4
10 15 20 25 30 35 40 45
0.9
0.95
1
1.05
1.1
4.5 5.0 5.5 6.0 6.5 7.0 7.5
0.9
0.95
1
1.05
1.1
4.5 5.0 5.5 6.0 6.5 7.0 7.5
0.7
0.8
0.9
1.0
1.1
1.2
1615 17 18 19 20 21 22 23 24
0.7
0.8
0.9
1.0
1.1
1.2
2715 16 17 18 19 20 21 22 23 24 25 26
6. CAPACITY TABLES G10 2nd
HEAT SOURCE UNITS 2 - 438
WR
2
Inlet-water temp. [°C]
Rat
io
Rat
ioR
atio
Intake air temp. (Room temp.) [°CWB] Water-volume [m3/h]
Water-volume [m3/h]
Wat
er-p
ress
ure
drop
[kPa
]
Water-volume [m3/h]
Wat
er-p
ress
ure
drop
[kPa
]
Inlet-water temp. [°C]
Rat
io
Rat
io
Water-volume [m3/h]
Rat
io
Intake air temp. (Room temp.) [°CDB]
CapacityInput
CapacityInput
CapacityInput
CapacityInput
CapacityInput
CapacityInput
Inlet-water temp. Water volume
Intake air temp.
Inlet-water temp. Water volume
Intake air temp.
Water-pressure drop
Water-pressure drop
NominalCoolingCapacityInput
kW 28.095,500
5.45BTU/hkW
PQHY-P250YHM-A28.0
95,5005.51
PQRY-P250YHM-A
NominalHeatingCapacityInput
kW 31.5107,500
5.80BTU/hkW
PQHY-P250YHM-A31.5
107,5005.80
PQRY-P250YHM-A
04 5 6 7 8
10
20
30
04 5 6 7 8
10
20
30
0.7
0.6
0.8
0.9
1.0
1.1
1.2
1.3
1.4
10 15 20 25 30 35 40 45
0.7
0.6
0.8
0.9
1.0
1.1
1.2
1.3
1.4
10 15 20 25 30 35 40 45
0.9
0.95
1
1.05
1.1
4.5 5.0 5.5 6.0 6.5 7.0 7.5
0.9
0.95
1
1.05
1.1
4.5 5.0 5.5 6.0 6.5 7.0 7.5
0.7
0.8
0.9
1.0
1.1
1.2
1615 17 18 19 20 21 22 23 24
0.7
0.8
0.9
1.0
1.1
1.2
2715 16 17 18 19 20 21 22 23 24 25 26
2 - 439
6. CAPACITY TABLES G10 2nd
HEAT SOURCE UNITS
WR
2
Inlet-water temp. [°C]
Rat
io
Rat
ioR
atio
Intake air temp. (Room temp.) [°CWB] Water-volume [m3/h]
Water-volume [m3/h]
Wat
er-p
ress
ure
drop
[kPa
]
Water-volume [m3/h]
Wat
er-p
ress
ure
drop
[kPa
]
Inlet-water temp. [°C]
Rat
io
Rat
io
Water-volume [m3/h]
Rat
io
Intake air temp. (Room temp.) [°CDB]
CapacityInput
CapacityInput
CapacityInput
CapacityInput
CapacityInput
CapacityInput
Inlet-water temp. Water volume
Intake air temp.
Inlet-water temp. Water volume
Intake air temp.
Water-pressure drop
Water-pressure drop
NominalCoolingCapacityInput
kW 33.5114,300
7.36BTU/hkW
PQHY-P300YHM-A33.5
114,3007.44
PQRY-P300YHM-A
NominalHeatingCapacityInput
kW 37.5128,000
8.15BTU/hkW
PQHY-P300YHM-A37.5
128,0008.15
PQRY-P300YHM-A
04 5 6 7 8
10
20
30
04 5 6 7 8
10
20
30
0.7
0.6
0.8
0.9
1.0
1.1
1.2
1.3
1.4
10 15 20 25 30 35 40 45
0.7
0.6
0.8
0.9
1.0
1.1
1.2
1.3
1.4
10 15 20 25 30 35 40 45
0.9
0.95
1
1.05
1.1
4.5 5.0 5.5 6.0 6.5 7.0 7.5
0.9
0.95
1
1.05
1.1
4.5 5.0 5.5 6.0 6.5 7.0 7.5
0.7
0.8
0.9
1.0
1.1
1.2
1615 17 18 19 20 21 22 23 24
0.7
0.8
0.9
1.0
1.1
1.2
2715 16 17 18 19 20 21 22 23 24 25 26
6. CAPACITY TABLES G10 2nd
HEAT SOURCE UNITS 2 - 440
WR
2
Inlet-water temp. [°C]
Rat
io
Rat
ioR
atio
Intake air temp. (Room temp.) [°CWB] Water-volume [m3/h (/unit)]
Water-volume [m3/h (/unit)]
Wat
er-p
ress
ure
drop
[kPa
]
Water-volume [m3/h (/unit)]
Wat
er-p
ress
ure
drop
[kPa
]
*The drawing indicates characteristic per unit.
*The drawing indicates characteristic per unit.
Inlet-water temp. [°C]
Rat
io
Rat
io
Water-volume [m3/h (/unit)]
Rat
io
Intake air temp. (Room temp.) [°CDB]
CapacityInput
CapacityInput
CapacityInput
CapacityInput
CapacityInput
CapacityInput
Inlet-water temp. Water volume*
Intake air temp.
Inlet-water temp. Water volume*
Intake air temp.
Water-pressure drop*
Water-pressure drop*
NominalCoolingCapacityInput
kW 45.0153,500
8.25BTU/hkW
PQHY-P400YSHM-A45.0
153,5008.32
PQRY-P400YSHM-A
NominalHeatingCapacityInput
kW 50.0170,600
8.65BTU/hkW
PQHY-P400YSHM-A50.0
170,6008.65
PQRY-P400YSHM-A
04 5 6 7 8
10
20
30
04 5 6 7 8
10
20
30
0.7
0.6
0.8
0.9
1.0
1.1
1.2
1.3
1.4
10 15 20 25 30 35 40 45
0.7
0.6
0.8
0.9
1.0
1.1
1.2
1.3
1.4
10 15 20 25 30 35 40 45
0.9
0.95
1
1.05
1.1
4.5 5.0 5.5 6.0 6.5 7.0 7.5
0.9
0.95
1
1.05
1.1
4.5 5.0 5.5 6.0 6.5 7.0 7.5
0.7
0.8
0.9
1.0
1.1
1.2
1615 17 18 19 20 21 22 23 24
0.7
0.8
0.9
1.0
1.1
1.2
2715 16 17 18 19 20 21 22 23 24 25 26
2 - 441
6. CAPACITY TABLES G10 2nd
HEAT SOURCE UNITS
WR
2
Inlet-water temp. [°C]
Rat
io
Rat
ioR
atio
Intake air temp. (Room temp.) [°CWB] Water-volume [m3/h (/unit)]
Water-volume [m3/h (/unit)]
Wat
er-p
ress
ure
drop
[kPa
]
Water-volume [m3/h (/unit)]
Wat
er-p
ress
ure
drop
[kPa
]
*The drawing indicates characteristic per unit.
*The drawing indicates characteristic per unit.
Inlet-water temp. [°C]
Rat
io
Rat
io
Water-volume [m3/h (/unit)]
Rat
io
Intake air temp. (Room temp.) [°CDB]
CapacityInput
CapacityInput
CapacityInput
CapacityInput
CapacityInput
CapacityInput
Inlet-water temp. Water volume*
Intake air temp.
Inlet-water temp. Water volume*
Intake air temp.
Water-pressure drop*
Water-pressure drop*
NominalCoolingCapacityInput
kW 50.0170,600
9.84BTU/hkW
PQHY-P450YSHM-A50.0
170,6009.94
PQRY-P450YSHM-A
NominalHeatingCapacityInput
kW 56.0191,100
10.42BTU/hkW
PQHY-P450YSHM-A56.0
191,10010.42
PQRY-P450YSHM-A
04 5 6 7 8
10
20
30
04 5 6 7 8
10
20
30
0.7
0.6
0.8
0.9
1.0
1.1
1.2
1.3
1.4
10 15 20 25 30 35 40 45
0.7
0.6
0.8
0.9
1.0
1.1
1.2
1.3
1.4
10 15 20 25 30 35 40 45
0.9
0.95
1
1.05
1.1
4.5 5.0 5.5 6.0 6.5 7.0 7.5
0.9
0.95
1
1.05
1.1
4.5 5.0 5.5 6.0 6.5 7.0 7.5
0.7
0.8
0.9
1.0
1.1
1.2
1615 17 18 19 20 21 22 23 24
0.7
0.8
0.9
1.0
1.1
1.2
2715 16 17 18 19 20 21 22 23 24 25 26
6. CAPACITY TABLES G10 2nd
HEAT SOURCE UNITS 2 - 442
WR
2
Inlet-water temp. [°C]
Rat
io
Rat
ioR
atio
Intake air temp. (Room temp.) [°CWB] Water-volume [m3/h (/unit)]
Water-volume [m3/h (/unit)]
Wat
er-p
ress
ure
drop
[kPa
]
Water-volume [m3/h (/unit)]
Wat
er-p
ress
ure
drop
[kPa
]
*The drawing indicates characteristic per unit.
*The drawing indicates characteristic per unit.
Inlet-water temp. [°C]
Rat
io
Rat
io
Water-volume [m3/h (/unit)]
Rat
io
Intake air temp. (Room temp.) [°CDB]
CapacityInput
CapacityInput
CapacityInput
CapacityInput
CapacityInput
CapacityInput
Inlet-water temp. Water volume*
Intake air temp.
Inlet-water temp. Water volume*
Intake air temp.
Water-pressure drop*
Water-pressure drop*
NominalCoolingCapacityInput
kW 56.0191,100
11.45BTU/hkW
PQHY-P500YSHM-A56.0
191,10011.57
PQRY-P500YSHM-A
NominalHeatingCapacityInput
kW 63.0215,000
12.06BTU/hkW
PQHY-P500YSHM-A63.0
215,00012.06
PQRY-P500YSHM-A
04 5 6 7 8
10
20
30
04 5 6 7 8
10
20
30
0.7
0.6
0.8
0.9
1.0
1.1
1.2
1.3
1.4
10 15 20 25 30 35 40 45
0.7
0.6
0.8
0.9
1.0
1.1
1.2
1.3
1.4
10 15 20 25 30 35 40 45
0.9
0.95
1
1.05
1.1
4.5 5.0 5.5 6.0 6.5 7.0 7.5
0.9
0.95
1
1.05
1.1
4.5 5.0 5.5 6.0 6.5 7.0 7.5
0.7
0.8
0.9
1.0
1.1
1.2
1615 17 18 19 20 21 22 23 24
0.7
0.8
0.9
1.0
1.1
1.2
2715 16 17 18 19 20 21 22 23 24 25 26
2 - 443
6. CAPACITY TABLES G10 2nd
HEAT SOURCE UNITS
WR
2
*The drawing indicates characteristic per unit.
*The drawing indicates characteristic per unit.
Inlet-water temp. [°C]
Rat
io
Rat
ioR
atio
Intake air temp. (Room temp.) [°CWB] Water-volume [m3/h (/unit)]
Water-volume [m3/h (/unit)]
Wat
er-p
ress
ure
drop
[kPa
]
Water-volume [m3/h (/unit)]
Wat
er-p
ress
ure
drop
[kPa
]
Inlet-water temp. [°C]
Rat
io
Rat
io
Water-volume [m3/h (/unit)]
Rat
io
Intake air temp. (Room temp.) [°CDB]
CapacityInput
CapacityInput
CapacityInput
CapacityInput
CapacityInput
CapacityInput
Inlet-water temp. Water volume*
Intake air temp.
Inlet-water temp. Water volume*
Intake air temp.
Water-pressure drop*
Water-pressure drop*
NominalCoolingCapacityInput
kW 63.0215,000
13.46BTU/hkW
PQHY-P550YSHM-A63.0
215,00013.60
PQRY-P550YSHM-A
NominalHeatingCapacityInput
kW 69.0235,400
14.65BTU/hkW
PQHY-P550YSHM-A69.0
235,40014.65
PQRY-P550YSHM-A
04 5 6 7 8
10
20
30
04 5 6 7 8
10
20
30
0.7
0.6
0.8
0.9
1.0
1.1
1.2
1.3
1.4
10 15 20 25 30 35 40 45
0.7
0.6
0.8
0.9
1.0
1.1
1.2
1.3
1.4
10 15 20 25 30 35 40 45
0.9
0.95
1
1.05
1.1
4.5 5.0 5.5 6.0 6.5 7.0 7.5
0.9
0.95
1
1.05
1.1
4.5 5.0 5.5 6.0 6.5 7.0 7.5
0.7
0.8
0.9
1.0
1.1
1.2
1615 17 18 19 20 21 22 23 24
0.7
0.8
0.9
1.0
1.1
1.2
2715 16 17 18 19 20 21 22 23 24 25 26
6. CAPACITY TABLES G10 2nd
HEAT SOURCE UNITS 2 - 444
WR
2
*The drawing indicates characteristic per unit.
*The drawing indicates characteristic per unit.
Inlet-water temp. [°C]
Rat
io
Rat
ioR
atio
Intake air temp. (Room temp.) [°CWB] Water-volume [m3/h (/unit)]
Water-volume [m3/h (/unit)]
Wat
er-p
ress
ure
drop
[kPa
]
Water-volume [m3/h (/unit)]
Wat
er-p
ress
ure
drop
[kPa
]
Inlet-water temp. [°C]
Rat
io
Rat
io
Water-volume [m3/h (/unit)]
Rat
io
Intake air temp. (Room temp.) [°CDB]
CapacityInput
CapacityInput
CapacityInput
CapacityInput
CapacityInput
CapacityInput
Inlet-water temp. Water volume*
Intake air temp.
Inlet-water temp. Water volume*
Intake air temp.
Water-pressure drop*
Water-pressure drop*
NominalCoolingCapacityInput
kW 69.0235,400
15.48BTU/hkW
PQHY-P600YSHM-A69.0
235,40015.62
PQRY-P600YSHM-A
NominalHeatingCapacityInput
kW 76.5261,000
17.12BTU/hkW
PQHY-P600YSHM-A76.5
261,00017.12
PQRY-P600YSHM-A
04 5 6 7 8
10
20
30
04 5 6 7 8
10
20
30
0.7
0.6
0.8
0.9
1.0
1.1
1.2
1.3
1.4
10 15 20 25 30 35 40 45
0.7
0.6
0.8
0.9
1.0
1.1
1.2
1.3
1.4
10 15 20 25 30 35 40 45
0.9
0.95
1
1.05
1.1
4.5 5.0 5.5 6.0 6.5 7.0 7.5
0.9
0.95
1
1.05
1.1
4.5 5.0 5.5 6.0 6.5 7.0 7.5
0.7
0.8
0.9
1.0
1.1
1.2
1615 17 18 19 20 21 22 23 24
0.7
0.8
0.9
1.0
1.1
1.2
2715 16 17 18 19 20 21 22 23 24 25 26
2 - 445
6. CAPACITY TABLES G10 2nd
HEAT SOURCE UNITS
WR
2
6-2. Correction by total indoorCITY MULTI system have different capacities and inputs when many combinations of indoor units with different total capacities are connected. Using following tables, the maximum capacity can be found to ensure the system is installed with enough capacity for a particular application.
Cap
acity
(kW
)In
put(k
W)
Total capacity of indoor units
10.0
10.0
20.0
30.0
40.0
50.0
0.0
5.0
100 200 300 400
100 200 300 400 500
Cap
acity
(kW
)In
put(k
W)
Total capacity of indoor units
10.0
20.0
30.0
40.0
50.0
0.0
5.0
10.0
PQRY-P200YHM-A
PQRY-P250YHM-A
CoolingHeating
P200
CoolingHeating
P250
6. CAPACITY TABLES G10 2nd
HEAT SOURCE UNITS 2 - 446
WR
2
PQRY-P300YHM-A
PQRY-P400YSHM-A
100 200 300 400 500
Cap
acity
(kW
)In
put(k
W)
Total capacity of indoor units
10.0
20.0
30.0
40.0
50.0
0.0
5.0
10.0
CoolingHeating
P300
100 200 300 400 500 600 700
Cap
acity
(kW
)In
put(k
W)
Total capacity of indoor units
20.0
30.0
40.0
50.0
60.0
0.0
2.50
7.50
10.0
5.00
CoolingHeating
P400
2 - 447
6. CAPACITY TABLES G10 2nd
HEAT SOURCE UNITS
WR
2
200 300 400 500 600 700 800
Cap
acity
(kW
)In
put(k
W)
Total capacity of indoor units
30.0
40.0
50.0
60.0
70.0
0.0
5.0
15.0
20.0
10.0
CoolingHeating
P500
200 300 400 500 600 700 800
Cap
acity
(kW
)In
put(k
W)
Total capacity of indoor units
30.0
40.0
50.0
60.0
70.0
0.0
5.0
15.0
20.0
10.0
CoolingHeating
P450
PQRY-P450YSHM-A
PQRY-P500YSHM-A
6. CAPACITY TABLES G10 2nd
HEAT SOURCE UNITS 2 - 448
WR
2
Cap
acity
(kW
)In
put(k
W)
Total capacity of indoor units
50.0
40.0
30.0
20.0
60.0
70.0
80.0
90.0
0.0
10.0
200 300 400 500 600 700 800 900
CoolingHeating
P550
PQRY-P550YSHM-A
PQRY-P600YSHM-A
Cap
acity
(kW
)In
put(k
W)
Total capacity of indoor units
50.0
40.0
30.0
20.0
60.0
70.0
80.0
90.0
0.0
10.0
300 400 500 600 700 800 900 1000
CoolingHeating
P600
2 - 449
6. CAPACITY TABLES G10 2nd
HEAT SOURCE UNITS
WR
2
6-3. Correction by refrigerant piping lengthCITY MULTI systems can have extended piping lengths if certain limitations are followed, but cooling/heating capacity could be reduced. Using following correction factor by equivalent piping length shown at 6-3-1 and 6-3-2, capacity can be found. 6-3-3 shows how to obtain the equivalent piping length.
6-3-1. Cooling capacity correction
Piping equivalent length (m)
1
0.90
0.80
0.95
0.85
0.75
0.65
0.70
Coo
ling
capa
city
cor
rect
ion
fact
or
PQRY-P200YHM-A100
150
200300
0 20 40 60 80 100 120 140 160 180
Total capacity of indoor unit
Piping equivalent length (m)
1
0.90
0.80
0.95
0.85
0.75
0.65
0.70
Coo
ling
capa
city
cor
rect
ion
fact
or
0 20 40 60 80 100 120 140 160 180
PQRY-P450YSHM-A225
338
450675
Total capacity of indoor unit
Piping equivalent length (m)
1
0.90
0.80
0.95
0.85
0.75
0.65
0.70
Coo
ling
capa
city
cor
rect
ion
fact
or
0 20 40 60 80 100 120 140 160 180
PQRY-P250YHM-A125
188
250375
Total capacity of indoor unit
Piping equivalent length (m)
1
0.90
0.80
0.95
0.85
0.75
0.65
0.70
Coo
ling
capa
city
cor
rect
ion
fact
or
0 20 40 60 80 100 120 140 160 180
PQRY-P500YSHM-A250
375
500750
Total capacity of indoor unit
Piping equivalent length (m)
1
0.90
0.80
0.95
0.85
0.75
0.65
0.70
Coo
ling
capa
city
cor
rect
ion
fact
or
0 20 40 60 80 100 120 140 160 180
PQRY-P300YHM-A150
225
300450
Total capacity of indoor unit
Piping equivalent length (m)
1
0.90
0.80
0.95
0.85
0.75
0.65
0.70
Coo
ling
capa
city
cor
rect
ion
fact
or
0 20 40 60 80 100 120 140 160 180
PQRY-P550YSHM-A275
413
550825
Total capacity of indoor unit
Piping equivalent length (m)
1
0.90
0.80
0.95
0.85
0.75
0.65
0.70
Coo
ling
capa
city
cor
rect
ion
fact
or
0 20 40 60 80 100 120 140 160 180
PQRY-P400YSHM-A200
300
400600
Total capacity of indoor unit
Piping equivalent length (m)
1
0.90
0.80
0.95
0.85
0.75
0.65
0.70
Coo
ling
capa
city
cor
rect
ion
fact
or
0 20 40 60 80 100 120 140 160 180
PQRY-P600YSHM-A300
450
600900
Total capacity of indoor unit
6. CAPACITY TABLES G10 2nd
HEAT SOURCE UNITS 2 - 450
WR
2
6-3-2. Heating capacity correction
6-3-3. How to obtain the equivalent piping length
6-4. Correction by port counts of the BC controllerIndoor unit sizes P200 and P250 must be connected to 2 ports on the BC controller.Indoor unit sizes from P100 to P140 should normally be connected to 2 ports on the BC controller (set BC controller DIP-SW 4-6 to its ON position).In cases whereby indoor unit sizes from P100 to P140 are connected to only 1port on the BC controller (set BC controller DIP-SW 4-6 to its OFF position), the cooling capacity of the indoor unit should be multiplied by a correction factor of 0.97.
Piping equivalent length (m)
1
0.90
0.80
0.95
0.85
0.75
0.65
0.70
Hea
ting
capa
city
cor
rect
ion
fact
or
0 20 40 60 80 100 120 140 160 180
PQRY-P200YHM-A
Piping equivalent length (m)
1
0.90
0.80
0.95
0.85
0.75
0.65
0.70
Hea
ting
capa
city
cor
rect
ion
fact
or
0 20 40 60 80 100 120 140 160 180
PQRY-P400, 450, 500YSHM-A
Piping equivalent length (m)
1
0.90
0.80
0.95
0.85
0.75
0.65
0.70
Hea
ting
capa
city
cor
rect
ion
fact
or
0 20 40 60 80 100 120 140 160 180
PQRY-P250, 300YHM-A
Piping equivalent length (m)
1
0.90
0.80
0.95
0.85
0.75
0.65
0.70
Hea
ting
capa
city
cor
rect
ion
fact
or
0 20 40 60 80 100 120 140 160 180
PQRY-P550, 600YSHM-A
1 PQRY-P200YHMEquivalent length = (Actual piping length to the farthest indoor unit) + (0.35 x number of bends in the piping) m
2 PQRY-P250, 300YHMEquivalent length = (Actual piping length to the farthest indoor unit) + (0.42 x number of bends in the piping) m
3 PQRY-P400, 450, 500, 550, 600YSHMEquivalent length = (Actual piping length to the farthest indoor unit) + (0.50 x number of bends in the piping) m
2 - 451
6. CAPACITY TABLES G10 2nd
HEAT SOURCE UNITS
WR
2
6-5. Operation temperature range
30
25
20
15
10
5-20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45 50-4 5 14 23 32 41 50 59 68 77 86 95 104 113 122
-4 5 14 23 32 41 50 59 68 77 86 95 104 113 122
Indo
or te
mpe
ratu
re
Circulating water temperature
30
25
20
15
10
5
86
77
68
59
50
41
86
77
68
59
50
41-20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45 50
Indo
or te
mpe
ratu
re
Circulating water temperature
Water temperature
10 to 45 C (50 to 113 F) 15 to 27 CDB (59 to 81 FDB)
Indoor temperature
Cooling Heating
15 to 24 CWB (59 to 75 FWB)
Combination of cooling/heating operation (Cooling main or Heating main)
• Cooling
• Heating
7. SYSTEM DESIGN GUIDE G10 2nd
HEAT SOURCE UNITS 2 - 452
WR
2
7. SYSTEM DESIGN GUIDE7-1. Designing of water circuit system
E.H
S.T
T T
C.T.P
C.T
P
3-way valve
1) Example of basic water circuit
Example of basic water circuit for water heat source CITY MULTI
The water circuit of the water heat source CITY MULTI connects the heat source unit with the cooling tow-er/auxiliary heat source/heat storage tank/circulation pump with a single system water piping as shown in the figure below. The selector valve automatically controls to circulate water toward the cooling tower in the cooling season, while toward the heat storage tank in the heat-ing season. If the circulation water temperature is kept in a range of 10~45°C[50~113°F]* regardless of the building load, the water heat source CITY MULTI can be operated for either cooling or heating. Therefore in the summer when only cooling load exists, the tempera-ture rise of circulation water will be suppressed by oper-ating the cooling tower. While in the winter when heat-ing load increases, the temperature of circulation water may be dropped below 10°C[50°F]. Under such situa-tion, the circulation water will be heated with the auxili-ary heat source if it drops below a certain temperature.When the thermal balance between cooling and heating operation is in a correct proportion, the operation of the
auxiliary heat source and cooling tower is not required.In order to control the above thermal balance properly and use thermal energy effectively, utilizing of heat stor-age tanks, and night-time discounted electric power as a auxiliary heat source will be economical.Meantime as this system uses plural sets of heat source unit equipped with water heat exchangers, water quality control is important. Therefore it is recommended to use closed type cooling towers as much as possible to pre-vent the circulation water from being contaminated.When open type cooling towers are used, it is essential to provide proper maintenance control such as that to install water treatment system to prevent troubles caused by contaminated circulation water.
S.T : Heating tank (Heat storage tank)C.T : Cooling towerC.T.P : Cooling water pumpP : Circulation water pumpT : Thermostat for waterE.H : Electric heater : Heat source unit for cooling operation : Heat source unit for heating operation
The indoor unit and refrigerant piping system are excluded in this figure.
2 - 453
7. SYSTEM DESIGN GUIDE G10 2nd
HEAT SOURCE UNITS
WR
2
2) Cooling tower a) Types of cooling tower
Types of cooling towersThe cooling towers presently used include the open type cooling tower, open type cooling tower + heat ex-changer, closed type cooling tower, and air-cooled type cooling tower. However, as the quality control of circula-tion water is essential when units are installed in decen-tralized state inside a building, the closed type cooling tower is generally employed in such case.Although the circulation water will not be contaminated by atmospheric air, it is recommended to periodically blow water inside the system and replenish fresh water instead.In a district where the coil may be frozen in the winter, it is necessary to apply antifreeze solution to the circula-tion water, or take freeze protection measures such as to automatically discharge water inside the cooling coil at the stopping of the pump.When the open type cooling tower is used, be sure to install a water quality control device in addition to the freeze protection measures, as the water may be deter-iorated by atmospheric contaminants entered into the cooling tower and dissolved into the circulation water.
Closed type
Air-cooled type
b) Calculation method of cooling tower capacityAll units of the water heat source CITY MULTI may pos-sibly be in cooling operation temporarily (at pulling down) in the summer, however, it is not necessary to determine the capacity according to the total cooling ca-pacity of all CITY MULTI units as this system has a wide operating water temperature range.
It is determined in accordance with the value obtained by adding the maximum cooling load of an actual build-ing, the input heat equivalent value of all CITY MULTI units, and the cooling load of the circulating pumps. Please check for the values of the cooling water volume and circulation water volume.
Cooling tower capacity = (Refrigeration ton)
Qc : Maximum cooling load under actual state (kcal/h)Qw : Total input of water heat source CITY MULTI at simultaneous operation under
maximum state (kW)Pw : Shaft power of circulation pumps (kW)
Qc + 860 x (ΣQw + Pw)3,900
Cooling tower capacity = (Refrigeration ton)
Qc : Maximum cooling load under actual state (BTU/h)Qw : Total input of water heat source CITY MULTI at simultaneous operation under
maximum state (kW)Pw : Shaft power of circulation pumps (kW)
* 1 Refrigerant ton of cooling tower capacity ≈ US refrigerant ton x (1+0.3) = 3,900 kcal/h = 15,500 BTU/h
Qc + 3,412 x (ΣQw + Pw)15,500
7. SYSTEM DESIGN GUIDE G10 2nd
HEAT SOURCE UNITS 2 - 454
WR
2
Determining the auxiliary heat source capacity
When heat storage tank is not used
For the CITY MULTI water heat source system, a heat storage tank is recommended to use. When employ-ment of the heat storage tank is difficult, the warming up operation should be arranged to cover the starting up heating load. Since the holding water inside the piping circuit owns heat capacity and the warming up opera-tion can be assumed for about one hour except that in a cold region, the heat storage tank capacity is required to
be that at the maximum daily heating load including the warming up load at the next morning of the holiday. However the auxiliary heat source capacity should be determined by the daily heating load including warming up load on the week day.For the load at the next morning of the holiday, heat storage is required by operating the auxiliary heat source even outside of the ordinary working hour.
3) Auxiliary heat source and heat storage tankWhen the heating load is larger than the cooling load, the circulation water temperature lowers in accordance with the heat balance of the system. It should be heated by the auxiliary heat source in order to keep the inlet wa-ter temperature within the operating range of the water heat source CITY MULTI.Further in order to operate the water heat source CITY MULTI effectively, it is recommended to utilize the heat storage tank to cover the warming up load in the morn-ing and the insufficient heat amount.Effective heat utilization can be expected to cover insuffi-cient heat at the warming up in the next morning or peak load time by storing heat by installing a heat stor-age tank or operating a low load auxiliary heat source at the stopping of the water heat source CITY MULTI. As it can also be possible to reduce the running cost through the heat storage by using the discounted night-time elec-tric power, using both auxiliary heat source and heat storage tank together is recommended.
The effective temperature difference of an ordinary heat storage tank shows about 5deg. even with the storing temperature at 45°C[113°F].However with the water heat source CITY MULTI, it can be utilized as heating heat source up to 15°C[59°F] with an effective temperature of a high 30deg°C[54deg°F]. approximately, thus the capacity of the heat storage tank can be minimized.
a) Auxiliary heat sourceThe following can be used as the auxiliary heat source.
• Boiler (Heavy oil, kerosine, gas, electricity)• Electric heat (Insertion of electric heater into heat stor-
age tank)• Outdoor air (Air-heat source heat pump chiller)• Warm discharge water (Exhaust water heat from ma-
chines inside building and hot water supply)• Utilization of night-time lighting• Solar heat
Please note that the auxiliary heat source should be se-lected after studying your operating environment and economical feasibility.
QH = HCT ( 1 - ) - 1000 x Vw x ΔT - 860 x Pw
QH : Auxiliary heat source capacity (kcal/h)HCT : Total heating capacity of each water heat source CITY MULTI (kcal/h)COPH : COP of water heat source CITY MULTI at heatingVW : Holding water volume inside piping (m3)ΔT : Allowable water temperature drop = TWH - TWL (°C)TWH : Heat source water temperature at high temperature side (°C)TWL : Heat source water temperature at low temperature side (°C)PW : Heat source water pump shaft power (kW)
1COPh
QH = HCT ( 1 - ) - 8.343 x Vw x ΔT - 3412 x Pw
QH : Auxiliary heat source capacity (BTU/h)HCT : Total heating capacity of each water heat source CITY MULTI (BTU/h)COPH : COP of water heat source CITY MULTI at heatingVW : Holding water volume inside piping (G)ΔT : Allowable water temperature drop = TWH - TWL (°F)TWH : Heat source water temperature at high temperature side (°F)TWL : Heat source water temperature at low temperature side (°F)PW : Heat source water pump shaft power (kW)
1COPh
2 - 455
7. SYSTEM DESIGN GUIDE G10 2nd
HEAT SOURCE UNITS
WR
2
When heat storage tank is not used
HQ1T • ( 1 - ) - 860 x Pw x T2
QH = x K (kcal) T1
QH1T : Total of heating load on weekday including warming up (kcal/day)T1 : Operating hour of auxiliary heat source (h)T2 : Operating hour of heat source water pump (h)K : Allowance factor (Heat storage tank, piping loss, etc.) 1.05~1.10
HQ1T is calculated from the result of steady state load calculation similarly by using the equation below.HQ1T = 1.15 x (ΣQ'a + ΣQ'b + ΣQ'c + ΣQ'd + ΣQ'f) T2 - ψ (ΣQe1 + ΣQe2 + ΣQe3) (T2 - 1)
Q'a : Thermal load from external wall/roof in each zone (kcal/h)Q'b : Thermal load from glass window in each zone (kcal/h)Q'c : Thermal load from partition/ceiling/floor in each zone (kcal/h)Q'd : Thermal load by infiltration in each zone (kcal/h)Q'f : Fresh outdoor air load in each zone (kcal/h)Q'e1 : Thermal load from human body in each zone (kcal/h)Q'e2 : Thermal load from lighting fixture in each zone (kcal/h)Q'e3 : Thermal load from equipment in each zone (kcal/h)ψ : Radiation load rate 0.6~0.8T2 : Air conditioning hour
1COPh
HQ1T • ( 1 - ) - 3,412 x Pw x T2
QH = x K (BTU) T1
QH1T : Total of heating load on weekday including warming up (BTU/day)T1 : Operating hour of auxiliary heat source (h)T2 : Operating hour of heat source water pump (h)K : Allowance factor (Heat storage tank, piping loss, etc.) 1.05~1.10
HQ1T is calculated from the result of steady state load calculation similarly by using the equation below.HQ1T = 1.15 x (ΣQ'a + ΣQ'b + ΣQ'c + ΣQ'd + ΣQ'f) T2 - ψ (ΣQe1 + ΣQe2 + ΣQe3) (T2 - 1)
Q'a : Thermal load from external wall/roof in each zone (BTU/h)Q'b : Thermal load from glass window in each zone (BTU/h)Q'c : Thermal load from partition/ceiling/floor in each zone (BTU/h)Q'd : Thermal load by infiltration in each zone (BTU/h)Q'f : Fresh outdoor air load in each zone (BTU/h)Q'e1 : Thermal load from human body in each zone (BTU/h)Q'e2 : Thermal load from lighting fixture in each zone (BTU/h)Q'e3 : Thermal load from equipment in each zone (BTU/h)ψ : Radiation load rate 0.6~0.8T2 : Air conditioning hour
1COPh
7. SYSTEM DESIGN GUIDE G10 2nd
HEAT SOURCE UNITS 2 - 456
WR
2
b) Heat storage tankHeat storage tank can be classified by types into the open type heat storage tank exposed to atmosphere, and the closed type heat storage tank with structure separated from atmosphere. Although the size of the tank and its installation place should be taken into ac-count, the closed type tank is being usually employed
by considering corrosion problems.The capacity of heat storage tanks is determined in ac-cordance with the daily maximum heating load that in-cludes warming up load to be applied for the day after the holiday.
HQ2T ( 1 - ) - 860 x Pw x T2 - QH x T2
V = (ton) ΔT x 1,000 x ηV
1COPh
HQ2T ( 1 - ) - 3,412 x Pw x T2 - QH x T2
V = (Ibs) ΔT x ηV
1COPh
When auxiliary heat source is operated during operation and even after stopping of water heat source CITY MULTI unit
HQ2T ( 1 - ) - 860 x Pw x T2
V = (ton) ΔT x 1,000 x ηV
HQ2T : Maximum heating load including load required for the day after the holiday (kcal/day)ΔT : Temperature difference utilized by heat storage tank (deg°C)ηV : Heat storage tank efficiency
HQ2T : 1.3 x (ΣQ'a + ΣQ'c + ΣQ'd + ΣQ'f) T2 - ψ(ΣQe2 + ΣQe3) (T2 - 1)
1COPh
HQ2T ( 1 - ) - 3,412 x Pw x T2
V = (Ibs) ΔT x ηV
HQ2T : Maximum heating load including load required for the day after the holiday (BTU/day)ΔT : Temperature difference utilized by heat storage tank (deg°F)ηV : Heat storage tank efficiency
HQ2T : 1.3 x (ΣQ'a + ΣQ'c + ΣQ'd + ΣQ'f) T2 - ψ(ΣQe2 + ΣQe3) (T2 - 1)
1COPh
HQ2T : Maximum heating load including load required for the day after the holiday (kcal/day)ΔT : Temperature difference utilized by heat storage tank (deg°C)ηV : Heat storage tank efficiency
HQ2T : 1.3 x (ΣQ'a + ΣQ'c + ΣQ'd + ΣQ'f) T2 - ψ(ΣQe2 + ΣQe3) (T2 - 1)
HQ2T : Maximum heating load including load required for the day after the holiday (BTU/day)ΔT : Temperature difference utilized by heat storage tank (deg°F)ηV : Heat storage tank efficiency
HQ2T : 1.3 x (ΣQ'a + ΣQ'c + ΣQ'd + ΣQ'f) T2 - ψ(ΣQe2 + ΣQe3) (T2 - 1)
When auxiliary heat source is operated after stopping of water heat source CITY MULTI unit
2 - 457
7. SYSTEM DESIGN GUIDE G10 2nd
HEAT SOURCE UNITS
WR
2
4) Piping system
System example of water circuit
The following items should be kept in your mind in planning / designing water circuits.
a) All units should be constituted in a single circuit in principle.
b) When plural numbers of the water heat source CITY MULTI unit are installed, the rated circulating water flow rate should be kept by making the piping resistance to each unit almost same value. As an example, the reverse return system as shown below may be employed.
c) Depending on the structure of a building, the water circuit may be prefabricated by making the layout uniform.
d) When a closed type piping circuit is constructed, install an expansion tank usable commonly for a make-up water tank to absorb the expansion/contraction of water caused
by temperature fluctuation.
e) If the operating temperature range of circulation water stays within the temperature near the normal temperature (summer : 29.4°C[85°F], winter : 21.1°C[70°F]), thermal insulation or anti-sweating work is not required for the piping inside buildings.
In case of the conditions below, however, thermal insulation is required.
• When well water is used for heat source water.• When piped to outdoor or a place where freezing may
be caused.• When vapor condensation may be generated on piping
due to an increase in dry bulb temperature caused by the entry of fresh outdoor air.
Heatsource
unit
BC controller
Backflow prevention valvePump Strainer
3-way valve
3-way valve
Cooling tower Heating tank
Flexible joint
Refrigerant piping
Refrigerant piping
To indoor unit
ValveJoint
Drain
Y-shape strainer
Heatsource
unit
BC controller
Heatsource
unit
BC controller
Heatsource
unit
BC controller
7. SYSTEM DESIGN GUIDE G10 2nd
HEAT SOURCE UNITS 2 - 458
WR
2
5) Practical System Examples and Circulation Water Control
Example-1 Combination of closed type cooling tower and hot water heat storage tank (using underground hollow slab)
Since the water heat source CITY MULTI is of water heat source system, versatile systems can be constitut-ed by combining it with various heat sources.The practical system examples are given below.Either cooling or heating operation can be performed if the circulation water temperature of the water heat source CITY MULTI stays within a range of 15~45°C
[59~113°F]. However, the circulation water temperature near 32°C[90°F] for cooling and 20°C[68°F] for heating is recommended by taking the life, power consumption and capacity of the air conditioning units into considera-tion. The detail of the control is also shown below.
By detecting the circulation water temperature of the water heat source CITY MULTI system with T1 (around 32°C[90°F]) and T2 (around 20°C[68°F]), the temperature will be controlled by opening/closing V1 in the summer and V2 in the winter.In the summer, as the circulation water temperature rises exceeding the set temperature of T1, the bypass port of V1 will open to lower the circulation water temperature. While in the winter, as the circulation water temperature drops, V2 will open following the command of T2 to rise the circulation water temperature.The water inside the heat storage tank will be heated by the auxiliary heat source by V3 being opened with timer op-eration in the night-time. The electric heater of the auxiliary heat source will be controlled by T3 and the timer. The start/stop control of the fan and pump of the closed type cooling tower is applied with the step control of the fan and pump following the command of the auxiliary switch XS of V1, that operates only the fan at the light load while the fan and pump at the maximum load thus controlling water temperature and saving motor power.
Heatsource
unit
Heat exchanger
Heat storagetank pump
T1~T4 : ThermostatV1~V2 : Proportional type motor-driven 3-way valveV3 : Motor-driven 3-way valveXS : Auxiliary switchMG : Magnetic switchEH : Electric heater
Heat storage tank
Auxiliaryheat source
T2
V2
EH
T4
MG
V3
T3
Cooling water pumpClosed typecooling tower
Expansion tank
Circulation water pump
V1
T1XS
2 - 459
7. SYSTEM DESIGN GUIDE G10 2nd
HEAT SOURCE UNITS
WR
2
Example-2 Combination of closed type cooling tower and hot water heat storage tank
In the summer, as the circulation water temperature rises exceeding the set temperature of T1, the bypass port of V1 will open to lower the circulation water temperature. In the winter, if the circulation water temperature stays below 25°C[77°F], V2 will open/close by the command of T2 to keep the circulation water temperature constant.The temperature of the hot water inside the heat storage tank will be controlled through the step control of the electric heater by step controller operation following the command of T3.During the stopping of the heat source water pump, the bypass port of V2 will be closed fully by interlocking thus pre-venting the high temperature water from entering into the system at the starting of the pump.The start/stop control of the fan and pump of the closed type cooling tower is applied with the step control of the fan and pump following the command of the auxiliary switch XS of V1, that operates only the fan at the light load while the fan and pump at the maximum load thus controlling water temperature and saving motor power.
Heatsource
unit
Closed typecooling tower
T1 : Proportional type, insertion system thermostatT2 : Proportional type, insertion system thermostatT3 : Proportional type, insertion system thermostatV1 : Proportional type, motor-driven 3-way valveV2 : Proportional type, motor-driven 3-way valveXS : Auxiliary switch (Duplex switch type)SC : Step controllerR : RelayMG : Magnetic
SC MG
T3
CV
V1
XS
R
V2
T2
Hot water heatstorage tank
Heat sourcewater pumpPump interlock
7. SYSTEM DESIGN GUIDE G10 2nd
HEAT SOURCE UNITS 2 - 460
WR
2
Example-3 Combination of closed type cooling tower and boiler
In the summer, as the circulation water temperature rises exceeding the set temperature of T1, the bypass port of V1 will close to lower the circulation water temperature. In the winter, if the circulation water temperature drops below 25°C[77°F], V2 will conduct water temperature control to keep the circulation water temperature constant.During the stopping of the heat source water pump, the bypass port of V2 will be closed fully by interlocking.The start/stop control of the fan and pump of the closed type cooling tower is applied with the step control following the command of the auxiliary switch XS of V1, thus controlling water temperature and saving motor power.
Heatsource
unit
Closed typecooling tower
T1 : Proportional type, insertion system thermostatT2 : Proportional type, insertion system thermostatT3 : Proportional type, insertion system thermostatV1 : Proportional type, motor-driven 3-way valveS : Selector switchR : RelayXS : Auxiliary switch (Duplex switch type)
Relay board
Boiler
XSV1
T1
V2
R
T2
Heat sourcewater pump
Pump interlock
2 - 461
7. SYSTEM DESIGN GUIDE G10 2nd
HEAT SOURCE UNITS
WR
2
Example-4 Combination of closed type cooling tower and heat exchanger (of other heat source)
In the summer, as the circulation water temperature rises exceeding the set temperature of T1, the bypass port of V1 will close to lower the circulation water temperature. In the winter, if the circulation water temperature drops below 26°C[79°F], V2 will conduct water temperature control to keep the circulation water temperature constant.During the stopping of the heat source water pump, the bypass port of V2 will be closed fully by interlocking.The start/stop control of the fan and pump of the closed type cooling tower is applied with the step control following the command of the auxiliary switch XS of V1, thus controlling water temperature and saving motor power.
Heatsource
unit
Closed typecooling tower
T1 : Proportional type, insertion system thermostatT2 : Proportional type, insertion system thermostatV1 : Proportional type, motor-driven 3-way valveV2 : Proportional type, motor-driven 3-way valveS : Selector switchR : RelayXS : Auxiliary switch (Duplex switch type)
Relay board
XSV1
T1
V2
T2
Heat sourcewater pump
Heat exchanger
Other heat source water
7. SYSTEM DESIGN GUIDE G10 2nd
HEAT SOURCE UNITS 2 - 462
WR
2
Indoorunit
Heat sourceequipment
Watercircuit
Heat sourcewater pump
(MP)
Site control panel
Refrigerant piping
Transmission lineBC controller
Remote controllerRoom-A
Indoorunit
Room-B
Room-E
Indoorunit
Room-C
Indoorunit
Room-D
Room-F(Remote controller
operation at two spot)Room-G
6) Pump interlock circuit
TM1
TM2
1TB8
Heat source equipment
Heat source equipment
To next equipment
2
3
4
1TB8
2
3
4
52P
MP
Site control panel ~ / N 240/230/220V
X : RelayTM1, 2 : Timer relay (closes after elapsing the set time when it is powered, while opens promptly when it is not powered)52P : Magnetic contactor for heat source water pumpMP : Heat source water pumpMCB : Circuit breaker
*Remove the short circuit wire between 3 and 4 when wiring to TB8.
52P
TM1
MCB
TM2
• Plural indoor units (8HP:15sets, 16HP:16sets maximum) being connected to a single refrigerant system can be controlled individually.• The transmission line is of a jumper wiring system using non-polar 2 wires.
This circuit uses the “Terminal block for pump interlock (TB8)“ inside the electrical parts box of the heat source equipment.This circuit is for interlocking of the heat source equipment operation and the heat source water pump.
Wiring diagram
L1 N
2 - 463
7. SYSTEM DESIGN GUIDE G10 2nd
HEAT SOURCE UNITS
WR
2
Operation ON signal
Pump Interlock
Terminal No.
Output
Operation
TB8-1, 2
Relay contacts output Rated voltage : L1 - N : 220 ~ 240VRated load : 1A
• When Dip switch 2-7 is OFFThe relay closes during compressor operation.
• When DIP switch 2-7 is ON.The relay closes during reception of cooling or the heating operation signal from the controller.(Note : It is output even if the thermostat is OFF (when the compressor is stopped).)
Terminal No.
Input
Operation
TB8-3, 4
Level signal
If the circuit between TB8-3 and TB8-4 is open, compressor operation is prohibited.
7. SYSTEM DESIGN GUIDE G10 2nd
HEAT SOURCE UNITS 2 - 464
WR
2
7-2. Water piping work
Installation example of heat source unit
Although the water piping for the CITY MULTI WR2 system does not differ from that for ordinary air conditioning systems, pay special attention to the items below in conducting the piping work.
1) Items to be observed on installation work• In order to equalize piping resistance for each unit, adapt
the reverse return system.• Mount a joint and a valve onto the water outlet/inlet of the
unit to allow for maintenance, inspection and replacement work. Be sure to mount a strainer at the water inlet piping of the unit. (The strainer is required at the circulation water inlet to protect the heat source unit.)
* The installation example of the heat source unit is shown right.
• Be sure to provide an air relief opening on the water piping properly, and purge air after feeding water to the piping system.
• Condensate will generate at the low temperature part inside the heat source equipment. Connect drain piping to the drain piping connection located at the bottom of the heat source equipment to discharge it outside the equip-ment.
• At the center of the header of the heat exchanger water inlet inside the unit, a plug for water discharge is being provided.Use it for maintenance work or the like.
• Mount a backflow prevention valve and a flexible joint for vibration control onto the pump.
• Provide a sleeve to the penetrating parts of the wall to prevent the piping.
• Fasten the piping with metal fitting, arrange the piping not to expose to cutting or bending force, and pay sufficient care for possible vibration.
• Be careful not to erroneously judge the position of the inlet and outlet of water.(Lower position : Inlet, Upper position : Outlet)
• When connecting heat source unit water piping and water piping on site, apply liquid sealing material for water piping over the sealing tape before connection. (for Maximum water pressure above 1.0MPa)
• Wrap the sealing tape as follows.Wrap the joint with sealing tape in the direction of the threads (clockwise), and do not let the tape run over the edge.Overlap the sealing tape by two-thirds to three-fourths of its width on each turn. Press the tape with your fingers so that it is pressed firmly against each thread.Leave the 1.5th through 2nd farthest threads away from the pipe end unwrapped.
• Hold the pipe on the unit side in place with a spanner when installing the pipes or strainer. Tighten screws to a torque of 150N·m.
2) Thermal insulation workThermal insulation or anti sweating work is not required for the piping inside buildings in the case of the CITY MULTI WR2 system if the operating temperature range of circulation water stays within the temperature near the normal (summer : 29.4°C[85°F], winter : 21.1°C[70°F]).In case of the conditions below, however, thermal insula-tion is required.
• Use of well water for heat source water• Outdoor piping portions• Indoor piping portions where freezing may be caused in
winter• A place where vapor condensation may be generated on
piping due to an increase in dry bulb temperature inside the ceiling caused by the entry of fresh outdoor air
• Drain piping portions
3) Water treatment and water quality controlFor the circulation water cooling tower of the CITY MULTI WR2 system, employment of the closed type is recom-mended to keep water quality. However, in the case that an open type cooling tower is employed or the circulating water quality is inferior, scale will adhere onto the water heat exchanger leading to the decreased heat exchange capacity or the corrosion of the heat exchanger. Be sufficiently careful for water quality control and water treatment at the installation of the circulation water system
• Removal of impurities inside pipingBe careful not to allow impurities such as welding fragment, remaining sealing material and rust from mixing into the piping during installation work.
• Water treatmentThe water quality standards have been established by the industry (Japan Refrigeration, Air Conditioning Industry Association, in case of Japan) for water treatment to be applied.
1
2
3
pH (25°C[77°F])Electric conductivity
Chloride ion (mg Cl-/ )Sulfate ion (mg SO4 2-/ )Acid consumption (pH4.8)
(mg CaCO3/ )Total hardness (mg CaCO3/ )Calcium hardness (mg CaCO3/ )Ionic silica (mg SiO2/ )Iron (mg Fe/ )Copper (mg Cu/ )
Sulfide ion (mg S2-/ )
Ammonium ion (mg NH4+/ )
Residual chlorine (mg Cl/ )Free carbon dioxide (mg CO2/ )Ryzner stability index
Standarditems
Refer-enceitems
Items
Lower mid-rangetemperature water system
7.0 ~ 8.030 or less
[300 or less]50 or less50 or less
50 or less
70 or less50 or less30 or less1.0 or less1.0 or lessnot to bedetected
0.3 or less0.25 or less0.4 or less
–
7.0 ~ 8.030 or less
[300 or less]50 or less50 or less
50 or less
70 or less50 or less30 or less0.3 or less0.1 or lessnot to bedetected
0.1 or less0.3 or less4.0 or less
–
TendencyRecirculating
water
[68<T<140°F][20<T<60°C]
Make-upwater
Corrosive Scale-forming
Reference : Guideline of Water Quality for Refrigeration and Air ConditioningEquipment. (JRA GL02E-1994)
(mS/m) (25°C[77°F])(μS/cm) (25°C[77°F])
Main circulatingwater pipe
Shutoff valve
Y-type strainer
Shutoffvalve
Refrigerant pipes
Drain pipe
Water outlet (lower)
Water inlet (upper)
2 - 465
7. SYSTEM DESIGN GUIDE G10 2nd
HEAT SOURCE UNITS
WR
2
In order to keep the water quality within such standards, you are kindly requested to conduct bleeding-off by overflow and periodical water quality tests, and use inhibitors to suppress condensation or corrosion. Since piping may be corroded by some kinds of inhibitor, consult an appropriate water treatment expert for proper water treatment.
4) Pump interlockOperating the heat source unit without circulation water inside the water piping can cause a trouble. Be sure to provide interlocking for the unit operation and water circuit. Since the terminal block is being provided inside the unit, use it as required.
8. OPTIONAL PARTS G10 2nd
HEAT SOURCE UNITS 2 - 466
WR
2
8. OPTIONAL PARTS8-1. JOINTCITY MULTI units can be easily connected by using Joint sets and Header sets provided by Mitsubishi Electric. Three kinds of Joint sets are available for use. Refer to section 3 in "System Design" or the Installation Manual that comes with the Joint set for how to install the Joint set.
For Gas pipe:
*Pipe diameter is indicated by inside diameter.
CMY-Y102SS-G2<Deformed pipe(Accessory)>
ø15.88
ø19.05ø19.05
30
58 (2 Pcs.)
(Outside diameter)
(Outside diameter)
(Outside diameter)
ø19.05
ø19.05
ø12.7ø15.88
ø15.88
ø12.7
28
30
37
36
18
ø9.52
ø9.52
ø9.52(Outside diameter)
ø9.52
(2 Pcs.)
ø6.35
20
For Liquid pipe:mm
<Deformed pipe(Accessory)>
For Gas pipe: For Liquid pipe:
*Pipe diameter is indicated by inside diameter.
mmCMY-Y102LS-G2
<Deformed pipe(Accessory)>
<Deformed pipe(Accessory)>
ø25.4 ø25.4
ø19.05
76
39
(2 Pcs.)
(2 Pcs.)
(2 Pcs.)
(Outside diameter)
(Outside diameter)
(Outside diameter)
(Outside diameter)
(Outside diameter)
(Outside diameter)
(Outside diameter)
54
41
45
42
54
30
37
ø22.2ø25.4
ø25.4 ø28.58
ø19.05ø25.4
ø15.88ø25.4ø19.05
ø19.05
ø12.7ø19.05
ø15.88
ø22.2ø9.52
ø12.7 ø12.7
40
20
(2 Pcs.)
(Outside diameter)
(Outside diameter)
ø12.7
ø9.52
23
20
ø9.52
ø6.35
For Gas pipe:
*Pipe diameter is indicated by inside diameter.
mmCMY-Y202S-G2
<Deformed pipe(Accessory)>
<Deformed pipe(Accessory)>
ø15.88(Outside diameter)
ø12.7(Outside diameter)
(Outside diameter)
(Outside diameter)
ø12.7
ø15.88
28
23
28
23
ø9.52
ø6.35
ø9.52
ø12.7
ø12.7ø15.88 ø15.88
49
23
ø25.4 ø25.4ø19.05
76
39
(3 Pcs.)
(Outside diameter)
(Outside diameter)
(Outside diameter)
(Outside diameter)
(Outside diameter)
(Outside diameter)
54
54
42
54
30
37
ø22.2ø25.4
ø25.4 ø28.58
ø25.4ø19.05
ø19.05
ø19.05
ø12.7ø19.05
ø15.88
ø22.2
For Liquid pipe:
2 - 467
8. OPTIONAL PARTS G10 2nd
HEAT SOURCE UNITS
WR
2
8-2. OUTDOOR TWINNING KITThe following optional Outdoor Twinning Kit is needed to use to combine multiple refrigerant pipes. Refer to the chapter entitled System Design Section for the details of selecting a proper twinning kit.
High-pressure twinning pipe
Low-pressure pipe twinning kitCMY-Q100VBK
<Deformed pipe(Accessory)>
<Pipe for routing through the front (Accessory)>
(Outside diameter)
61
15454
41
35
80
62
<Pipe for routing through the front (Accessory)>
<Elbow pipe(Accessory)>
(Outside diameter)
(Outside diameter) 95
132
2846
23108
23122432
160
50
50
36
36
The angle of the branch pipe for hign pressure is within against the horizontal plane. 2. Use the attached pipe to braze the port-opening of the distributer.3. Pipe diameter is indicated by inside diameter.
Note 1. Reference the attitude angle of the branch pipe below the fig.
Distributer
15
15
8. OPTIONAL PARTS G10 2nd
HEAT SOURCE UNITS 2 - 468
WR
2
8-3. JOINT KIT "CMY-R160-J1" FOR BC CONTROLLER
Ref.: WT05840X01_01
2 Joint pipe (for liquid side) 3 Joint pipe (for gas side) mm(in.)
PQRY-P-Y(S)HM-A
Joint kitCMY-R160-J1
CMY-Y102SS-G2Joint BC controller
Fig.1. CMY-R160-J1 applying scheme
IU IU IU
IU IU IU IU
Group1Total Indoor Capacity<=P80
Group2Total Indoor CapacityP81 to P250
Group3Indoor CapacityP100 to P250
Ref.: WT05840X01_02
Piping to indoor unit(Non-oxidized brazing)
Joint pipe (for liquid side)2
Joint pipe(for gas side)3
Fig.2. Connecting CMY-R160-J1 Ref.: WT05840X01_03
1. Designing CMY-R160-J1 to a PQRY-P-Y(S)HM-A systemThe maximum down-stream Indoor capacity for 1 port of BCcontroller is P80. When the down-stream Indoor capacity isabove P80, Joint kit CMY-R160-J1 is needed to combined 2ports of BC controller to enlarge the capacity, like Group 2 and3 in Fig. 1.Maximum 3 Indoor units are allowed to connect to 1 port of BCcontroller or 2 combined ports of BC controller using CMY-R160-J1.When connecting Indoor units to 1 port of BC controller or 2combined ports of BC controller using CMY-R160-J1 or CMY-Y102SS-G2 is applicable, like Group 1 and 2 in Fig. 1
Caution: Mixed cooling and heating mode at the same time forIndoor units connecting to 1 port or 2 combined ports is notavailable.
2. Piping at the installation siteThe connection of CMY-R160-J1 to BC controller and pipe leading to Indoor units is referable to Fig. 2. Non-oxidized brazing isnecessary. All piping must be careful to avoid foreign material getting inside.After piping and air-tight testing, insulation work to the Joint and pipe should be done. Details is available at the Installation Manual.
Joint kit "CMY-R160-J1" for BC controller is used to combine 2 ports of the BC controller at a PQRY-P-Y(S)HM-A system so as to enable down-stream Indoor capacity above P80 as shown in Fig. 1.
Ref: CMY_R160_J_DOC_EUDB
ø15.88(5/8")ø9.52(3/8")
ø19.
05(3
/4")
ø9.5
2(3/
8")
ø15.88(5/8")ø9.52(3/8")
226(8-29/32")226(8-29/32")
60(2
-3/8
")
60(2
-3/8
")
Instruction
This sheet
Please prepare the following items in the field. Tape for insulation material sealing Extension pipe for refrigerant circuit1pc 1pc 1pc 1pc for gas side 1pc for Iiquid side 8pcs 1pc 1pc2pcs
Cover 1 Cover 2 Cover 3 Band Reducer 2Joint pipe(Small) Joint pipe(Large) 7 9Reducer 1865432
2
1
1
OD19.05-ID22.2 OD19.05-ID15.88
The Joint kit include following items:
Cutting point
Have pipe expansion of indoor unit connecting port by cutting the piping at the cutting point.Remove burr after cutting the piping to prevent entering the piping.Check that there is no crack at the pipe expansion part.
3 - 1
CITY MULTI
G10 2nd
CONTROLLER
3. CONTROLLER
1. MITSUBISHI ELECTRIC's Air-conditioner Network System. (MELANS) ........................................................ 3 - 21-1.Function table of controllers ...................................................................................................................... 3 - 3
2. Local remote controller .................................................................................................................................... 3 - 42-1.MA remote controller [PAR-31MAA].......................................................................................................... 3 - 42-2.Smart ME Controller [PAR-U02MEDA] ..................................................................................................... 3 - 52-3.Simple MA remote controller [PAC-YT52CRA] ......................................................................................... 3 - 62-4.Wireless remote controller [PAR-FL32MA / PAR-FA32MA / PAR-SA9FA / PAR-SL94B-E] ..................... 3 - 72-5.LOSSNAY remote controller [PZ-52SF] .................................................................................................... 3 - 82-6.LOSSNAY remote controller for LGH-RX5-E [PZ-60DR-E]....................................................................... 3 - 9
3. System remote controller................................................................................................................................. 3 - 103-1.ON/OFF remote controller [PAC-YT40ANRA]........................................................................................... 3 - 103-2.Advanced touch controller [AT-50B].......................................................................................................... 3 - 123-3.Centralized controller [AG-150A]............................................................................................................... 3 - 203-4.Centralized controller [EB-50GU-J] ........................................................................................................... 3 - 293-5.Centralized controller [GB-50ADA-J]......................................................................................................... 3 - 373-6.Power supply unit [PAC-SC51KUA] .......................................................................................................... 3 - 443-7.Expansion Controller [PAC-YG50ECA] ..................................................................................................... 3 - 463-8.Integrated centralized control software [TG-2000A] .................................................................................. 3 - 493-9.Electric amount count software [PAC-YG11CDA] ..................................................................................... 3 - 543-10.PLC software for general equipment [PAC-YG21CDA]........................................................................... 3 - 553-11.BACnet® interface [BAC-HD150] ............................................................................................................ 3 - 563-12.PLC software for demand input [PAC-YG41CDA]................................................................................... 3 - 583-13.LONWORKS® interface [LMAP04-E].......................................................................................................... 3 - 603-14.Transmission booster [PAC-SF46EPA]................................................................................................... 3 - 633-15.AHC ADAPTER [PAC-IF01AHC-J].......................................................................................................... 3 - 643-16.PI controller [PAC-YG60MCA]................................................................................................................. 3 - 693-17.DIDO controller [PAC-YG66DCA] ........................................................................................................... 3 - 753-18.AI controller [PAC-YG63MCA]................................................................................................................. 3 - 85
4. System component .......................................................................................................................................... 3 - 944-1.S, Y, HP, R2 series.................................................................................................................................... 3 - 944-2.Outdoor unit input/output connector .......................................................................................................... 3 - 964-3.WY, WR2 series ........................................................................................................................................ 3 - 984-4.Heat source unit input/output connector.................................................................................................... 3 - 1004-5.Indoor unit "-E" type input/output connector .............................................................................................. 3 - 101