  • BRISTOL BABCOCK APPLICATION NOTE

    TeleFlow/AATM Page 1

    Wiring TeleFlow (3530-XXX)To

    Invensys Auto-Adjust Turbo-Meter

    Table of Contents

    Section 1 - FORWARD ..............................................................................................................2

    Section 2 - DEFINITIONS ........................................................................................................2

    Section 3 - WIRING...................................................................................................................3

    Section 4 - SOFTWARE CONFIGURATION..........................................................................13

  • BRISTOL BABCOCK APPLICATION NOTE

    Page 2 TeleFlow/AATM

    Section 1 - Forward

    This document provides technical information on wiring the Bristol Babcock line ofTeleFlow series products to an Invensys Auto-Adjust Turbo-Meter.

    TeleFlow series (3530) units listed in Table 1-1 can be interconnected to an Invensys Auto-Adjust Turbo-Meter. Interface requirements dictate the 3530 be equipped with at least twoPulse (Counter) Inputs. The TeleFlow Plus (Model 3530-20B) is equipped with a TeleFlowCPU Board and will require the use of a BBI Low Power I/O Expansion Board since theCPU Board has only one Pulse Input. Units equipped with the TeleRTU CPU Board dontrequire an additional Low Power I/O Expansion Board (unless an additional Pulse Input isdictated) since the TeleRTU CPU Board is equipped with two Pulse Inputs.

    Table 1-1 3530-XXX Organizational Overview & I/O Requirements

    Model NumberProduct Name

    Expansion I/ORequired?

    Notes

    3530-15B - TeleRTU NO Expansion Bd. Not Accommodated3530-20B - TeleFlow Plus YES Expansion Bd. Accommodated3530-25B - TeleRTU Plus NO Expansion Bd. Accommodated3530-35B - TeleRTU Module NO Expansion Bd. Accommodated3539-45B - TeleRecorder NO Expansion Bd. Not Accommodated

    This documents provides illustrations that show the recommended connections betweenBBI Series 3530s and the Invensys Auto-Adjust Tubo-Meter in a Class I, Division 2environment.

    Section 2 - Definitions

    The Auto-Adjust Turbo-Meter (AAT) meter referenced herein is manufactured by InvensysEnergy Metering, 805 Liberty Blvd. DuBois, PA 15801.

    Control Amplifiers shown in the illustrations provided herein are manufactured byPepperl+Fuchs.

    Abbreviations used within this document (text and illustrations) are provided below:

    AAT Auto-Adjust Turbo-MeterBTS Blade Tip SensorCPU Central Processing UnitEXC Excitation (+12Vdc) from 3530-XXX CPU Bd.MR AAT Main RotorSR AAT Sensor RotorSS Slot Sensor

  • BRISTOL BABCOCK APPLICATION NOTE

    TeleFlow/AATM Page 3

    Section 3 - Wiring

    Recommended wiring is shown for connection of a Bristol Babcock Series 3530-XXX unit toan AAT. Figures 2 through 5 are provided for 3530s equipped with a TeleFlow CPU Board,i.e., 3530-10B, -20B and 50B. These units require the use of a Low Power I/O ExpansionBoard. The Low Power I/O Expansion Board provides a second counter input for the SensorRotor. Figures 6 through 9 are provided for 3530s that utilize the TeleRTU CPU Board, i.e.,3530-15B, -25B, -35B and -45B. Figure 1 shows and edge view of the BBI 3530-XXX circuitboards utilized to interface to an AAT.

    Figure 1 - BBI CPUs and Low Power I/O Expansion Boards

  • BRISTOL BABCOCK APPLICATION NOTE

    Page 4 TeleFlow/AATM

    A control amplifier/barrier is required between the AAT and the 3530-XXX; the amplifiermodel numbers shown (K numbers) in Figures 2 through 9 are for Pepprl+Fuchs devices.

    Wiring diagrams are provided for the following 4 different types of amplifiers:

    24 Vdc with Slot Sensor (SS)24 Vdc with Blade Tip Sensor (BTS)120 Vac with SS120 Vac with BTS

    The Blade tip configuration requires +12 VDC to the AAT sensors through a MTL715+isolator made by MTL Instruments Inc.

    The amplifier outputs are connected in emitter-follower mode i.e., the emitter of theoutput transistor connects to the 3530-XXX counter input which has a 1000 ohm pulldown resistor to circuit common.

    +12 Vdc for the amplifier output stage is supplied from the 3530-XXX CPU Board via anExcitation (EXC) terminal. On the TeleRTU CPU Board, EXC is available from Pin #2 ofconnectors P10, P11, P12 or P13. On the TeleFlow CPU Board, EXC is available from Pin#7 of connector P14.

    Table 3-1 Wiring Diagrams

    CONFIGURATION 3530-XXX CPU Bd. FIGURE PAGE #24 Vdc with Slot Sensor (SS) TeleFlow 2 5120 Vac with Slot Sensor (SS) TeleFlow 3 624 Vdc with Blade Tip Sensor (BTS) TeleFlow 4 7120 Vac with Blade Tip Sensor (BTS) TeleFlow 5 824 Vdc with Slot Sensor (SS TeleRTU 6 9120 Vac with Slot Sensor (SS) TeleRTU 7 1024 Vdc with Blade Tip Sensor (BTS) TeleRTU 8 11120 Vac with Blade Tip Sensor (BTS) TeleRTU 9 12

  • BRISTOL BABCOCK APPLICATION NOTE

    TeleFlow/AATM Page 5

    Figure 2 - Slot Sensor AAT Meter to BBI 3530-20B (via 24 Vdc Control Amplifier)

  • BRISTOL BABCOCK APPLICATION NOTE

    Page 6 TeleFlow/AATM

    Figure 3 - Slot Sensor AAT Meter to BBI 3530-20B (via 120 Vac Control Amplifier)

  • BRISTOL BABCOCK APPLICATION NOTE

    TeleFlow/AATM Page 7

    Figure 4 - Blade Tip Sensor AAT Meter to BBI 3530-20B(via 24 Vdc Control Amplifier)

  • BRISTOL BABCOCK APPLICATION NOTE

    Page 8 TeleFlow/AATM

    Figure 5 - Blade Tip Sensor AAT Meter to BBI 3530-20B(via 120 Vac Control Amplifier)

  • BRISTOL BABCOCK APPLICATION NOTE

    TeleFlow/AATM Page 9

    Figure 6 - Slot Sensor AAT Meter to BBI 3530-XXB (with TeleRTU CPU Bd.)(via 24 Vdc Control Amplifier)

  • BRISTOL BABCOCK APPLICATION NOTE

    Page 10 TeleFlow/AATM

    Figure 7 - Slot Sensor AAT Meter to BBI 3530-XXB (with TeleRTU CPU Bd.)(via 120 Vac Control Amplifier)

  • BRISTOL BABCOCK APPLICATION NOTE

    TeleFlow/AATM Page 11

    Figure 8 - Blade Tip Sensor AAT Meter to BBI 3530-XXB (with TeleRTU CPU Bd.)(via 24 Vdc Control Amplifier)

  • BRISTOL BABCOCK APPLICATION NOTE

    Page 12 TeleFlow/AATM

    Figure 9 - Blade Tip Sensor AAT Meter to BBI 3530-XXB (with TeleRTU CPU Bd.)(via 120 Vac Control Amplifier)

  • BRISTOL BABCOCK APPLICATION NOTE

    TeleFlow/AATM Page 13

    Section 4 - Software Configuration

    In order to access data from the Invensys Auto-Adjust Turbo-Meter, you will need toconfigure the AAT Module in your ACCOL Load. Full details on configuring the AATModule are included in the AAT section of the ACCOL II Reference Manual (documentD4044).