wireless remote controller (mr-ah01/bh01) hq se. on/off control air flow control temperature...
TRANSCRIPT
Wireless Remote Controller(MR-AH01/BH01)
HQ SE
On/Off control
Air flow control
Temperature setting
Filter reset
Louver Control
Simple ON/OFF schedule
Service Mode
- Main/RMC address check
- Communication status check
Features MR-AH01 MR-BH01
Main Difference
MR-AH01 : ON/OFF schedule time Increase only
MR-BH01 : ON/OFF schedule time Increase/Decrease both
For MR-BH01, real time clock is not supported !
Wireless remote controller
Option code setting mode (MR-AH01)
1. Remove one battery from the wireless remote controller.
2. Press + together and put the battery back to enter the option code setting mode.
3. Use the Mode button to toggle the option code page.
4. Press the Set/Cancel button to change the option code.
Toggle option code page
Set option code
Entering option code mode Setting option code
Option code setting mode (MR-BH01)
1. Remove one battery from the wireless remote controller.
2. Press + together and put the battery back to enter the option code setting mode.
3. Use the Mode button to toggle the option code page
4. Press Power button to change the option code.
Toggle option code page
Set option code
Entering option code mode Setting option code
Press together
Option code setting mode (Neo forte R/C)
1. Remove one battery from the wireless remote controller.
2. Press Temp ▲▼ together and put the battery back to enter the option code setting mode.
3. Set option code 2 digits. And press “Mode” and set next 2 digits.
4. Press the On/Off power button to change the option code.
Entering option code mode Setting option code
<Initial display>
<Example : 027402 – 14221A – 200001 - 300000>
4) Then “OFF timer” is displayed.
5) Set next 2 digit.
6) After setting completion, press “On/Off”
※ Only blue colored 20 digits should be set
1) Set 2 digits using Temp ▲▼button
2) Press “Mode” , then will move to down. Set next 2 digit◀
3) After setting 10 digits, press “Mode”
Option code setting mode (Neo forte R/C)
Service mode (MR-AH01)
1. Remote one battery from the wireless remote controller.
2. Press + together and put the battery back to enter the Service Mode.
NOTE : Whenever Mode, Func1 and Func2 are changed, signal wave is transmitted from the wireless
remote controller.
Mode
Func1
Func2
Press Set/Cancel button
Entering service mode Selecting service mode
Service mode (MR-BH01)
1. Remote one battery from the wireless remote controller.
2. Press + together and put the battery back to enter the Service Mode.
NOTE : Whenever Mode, Func1 and Func2 are changed, signal wave is transmitted from the wireless
remote controller.
ModeFunc2
Press Set/Cancel button
Entering service mode
Func1
Selecting service mode
Press together
Service mode
Mode Func1 Func2 Description
0 0 0
COM1 communication status (Blinking display only is valid)
Operation LED Blinking – communication status of all channels
Schedule LED Blinking – Outdoor ↔ Indoor units communication status
Fan LED Blinking – Wired remote controller ↔ Indoor units communication status
Filter LED Blinking – Interface module ↔ Indoor units communication status
0 1 0
COM1 Main Address check
0 2 0LED display test (Rotating display)
Operation LED → Schedule LED → FAN LED → Filter LED → Defrost LED
All On → All Off → All On → All Off ………
MAIN addressOperation
LED
Schedule LED
FAN LED
Filter LED
0 OFF OFF OFF OFF
1 OFF OFF OFF ON
2 OFF OFF ON OFF
… … … … …
15 ON ON ON ON
Mode Func1 Func2 Description
10 x 0
MAIN address assigned by outdoor unit (if in the AUTO addressing mode)
(Read as decimal value)
x : MAIN address of indoor unit
If matched, all LEDs are lit ON.
Ex) For DVM Plus II, MAIN(1) = 1, MAIN(2) =2 MAIN address = 12
11 x 0
RMC Address check. (Read as HEX value)
x : RMC address of indoor unit
If matched, all LEDs are lit ON
Ex) For DVM Plus II, RMC(1)=1, RMC(2)=2 RMC address = 1*16 + 2 = 18
For DVM Plus II, RMC(1)=2, RMC(2)=1 RMC address = 2*16 + 1 = 22
13 x 0
Rotary switch MAIN address check (Read as decimal value)
x : MAIN address of indoor unit
If matched, all LEDs are lit ON
Ex) For DVM Plus II, MAIN(1) = 1, MAIN(2) =2 MAIN address = 12
NOTE : Exit the service mode by pressing any general keys in the Normal mode.
NOTE : Service mode 10,11 and 13 are not allowed for COM1-only indoor units.
NOTE : Applied for Cassette/Duct indoor units (not for Wall-mount indoor units)